Upload
sandeepbabu28
View
233
Download
2
Embed Size (px)
Citation preview
7/30/2019 HVDC Valvesppt ABB
1/20
HVDC Valves---ABB
Basic Requirement:
1.shall be able to carry current only in
forward direction.
2. Non conducting valve shall be able to
sustain a forward and reverse blocking
voltage. The valve is designed for a max
blocking voltage about three times the rated
direct voltage of the 6-pulse converter bridge.
7/30/2019 HVDC Valvesppt ABB
2/20
HVDC Valves
3. transition from the blocking condition to the conductingcondition takes place when the valve is given a controlpulse(firing pulse)It remains in the conducting state untilthe current through the valve is reduced to zero.
4. the valve is also designed for over current condition .themaximum over current occurs for a direct short circuitacross a valve an the amplitude is mainly determined bythe reactance of the converter transformer.
In addition it should have;
High reliability Low losses
Minimum installation and maintenance costs.
7/30/2019 HVDC Valvesppt ABB
3/20
HVDC Converter
HVDC converter normally built with two 6-pulseconverter bridges in cascade.
Transformers feeding 6-p bridges are star-star andstar-delta (YY and YD) respectively ,introducing a
phase shift of 30o between two bridges. a12-pulse converter with thyristor valves is normally
built with three physical units , quadruple valves,
Quadruple valve is air insulated and water cooled
Each single valve is protected with a valve arresterwhich is mounted on one side of the quadruplevalve.
7/30/2019 HVDC Valvesppt ABB
4/20
The Thyristor
cvvcv
Cathode
Anode
Gate
v
v
v
v
7/30/2019 HVDC Valvesppt ABB
5/20
Hvdc valves
Ref power semiconductor devices
and circuits edited by Andre A Jacklin
7/30/2019 HVDC Valvesppt ABB
6/20
The AC/Dc converter is subjected to very high voltagesand each valve in the converter bridge must be able towithstand several hundred kV. The line current isnormally in the range of 1000 to 4000 A.
The modern HVDC valves are based on thyristors.
The voltage capability of the single thyristors is limitedto less than 10 kV and a large number of thyristorsmust therefore be connected in series to support this
voltage.
The thyristor string is often organized in thyristormodules with current limiting inductors in between.
7/30/2019 HVDC Valvesppt ABB
7/20
Most thyristors are located at a high electric
potential, making certain demands on the valve
designs.
The necessary means for firing and protection of
thyristors must be energized by valve current at
each particular thyristor level.
Triggering signals between the firing andprotection means and controls system at ground
potential must be transmitted optically.
7/30/2019 HVDC Valvesppt ABB
8/20
The LTT should be self protected against voltage
triggering i.e.
1. the thyristor must not be damaged by spurious
triggering due to an excessively high off statevoltage (leakage current),
2. excessively fast dVo/dt ( displacement current)
or3. an unintended forward blocking voltage during
the reverse recovery period (stored charge)
7/30/2019 HVDC Valvesppt ABB
9/20
HVDC valve requirement
HVDC valve design is installation specific .themain aspects are ;
i) converter must be able to operate at steady
state under specified condition within ratherwide current and voltage ranges.
ii) uninterrupted operation must continue
during transitory AC fault and disturbances .iii)Lightning strikes and earth faults must notdamage the converter valves.
7/30/2019 HVDC Valvesppt ABB
10/20
Features of Full size self protected
LTTs
The main data for a 45 cm2 LTTs
Off state voltage 7000 V
Line current 1600 A
On state voltage 1.7 V at 1600 A
Minimum optical triggering power 10 mw at=940 nm for LED and 5mw at 840 nm for LD.
dVo/dt capability 4000 V/ s to 7000 V/ s
dI/dt , single pulse capability 3000 A/ s dI/dt , 50 Hz capability 800 A/ s
Max operating temp 80o
7/30/2019 HVDC Valvesppt ABB
11/20
Valve firing
current
voltage
Indicating
pulse
Control
pulse
Firing pulse
7/30/2019 HVDC Valvesppt ABB
12/20
Optical indicating pulse is generated at each
thyristor level as soon as the anode cathode
voltage across the thyristor has reached an
appropriate level for safe turn on.
When the converter control system generates
the control (CP) the valve control system will
send optical firing pulses to all thyristor levelsof the string.
7/30/2019 HVDC Valvesppt ABB
13/20
Triggering of ETT
In ETT(Electricallytriggeredthyristor) case
FP triggers theTCU (Thyristorcontrol unit) torelease gate
pulse from aprechargedcapacitor.
TCU
FP
IP
ETT
R R
C
7/30/2019 HVDC Valvesppt ABB
14/20
ETT Triggering
TCU
FP
IP
ETT
R R
C
LTT
FP triggers the LTT
(light Triggered Thyristor)
And supplies gate pulse
to ETT
7/30/2019 HVDC Valvesppt ABB
15/20
LTT Triggering
TCU
FP
IP
LTT
R R
C
A new 45 cm 2 7 kV self
protected LTT was
developed in 1987. For
short turnon delay a
high optical power ( > 30
mw, =940 nm) results in
td ,< 4 s.
A
7/30/2019 HVDC Valvesppt ABB
16/20
Optical firing systems
One LED per LTT carrying 3.5 A and generate
45 mw for 10 sOR
One LD (Laser diode) per two LTT carrying 1.5A supplying 70 mw for 100 s
7/30/2019 HVDC Valvesppt ABB
17/20
Optical firing systems
When using direct light triggering a new principle forgenerating firing pulses from the valve control electronics.
A high frequency indicating pulses are generated by TMU (Thyristor monitoring unit) as long as LTT voltage exceeds110 volts . The optical firing signal (FP) starts at thebeginning of the control pulse command and will last aslong as IP is generated.
The FP signal is then cut off as soon as all the thyristors inthe valve have turned on , thus reducing the stress on thelight sources. The firing pulse length will normally be about20 sec but operating at low delay angle or low ac voltagewill require longer pulses. The maximum pulse length islimited to 100 sec.
7/30/2019 HVDC Valvesppt ABB
18/20
7/30/2019 HVDC Valvesppt ABB
19/20
Improved LTT firing system
Improved LTT firing system based oncommercially available 50 mw continuouslaser diode (originally intended for office
automation products) are used as light source.No light reserve redundancy is needed as thethyristor will operate by self triggering in caseof missing regular pulse. The light pulses are
cut off by TMU (thyristor Monitoring Unit)signals when thyristor have turned on in orderto save LD life time.
7/30/2019 HVDC Valvesppt ABB
20/20
Voltageacross
thyristor
110V
Safer firing voltage
IP
CP
FP
t
TMU
LTT
LD
FP
50mw
IP
Improved LTT Triggering System