36
Description Vacuum type tube heaters are negative pressure gas- fired infrared heaters designed to provide comfort heat. They consist of four (4) main components: a burner control box, radiant tube, reflector assembly, and vacuum exhauster. The heaters are typically suspended from the ceiling by chains and controlled by a thermostat. They can be installed either vented or unvented, and may use outside air for combustion if necessary. The radiant tube may be installed in different configurations depending on the heating requirements. These heaters use infrared energy to heat spaces. When heat is required, the burner control box ignites a gas/air mixture and the vacuum pulls the hot gases into the radiant tube. As the gases pass through the assembly, the tubing is heated and emits infrared, which is then directed toward the floor by reflectors. This is known as primary infrared and is absorbed by the floor, objects and people in the space, raising their temperatures. They in turn reradiate this heat, known as secondary infrared, to create a comfort zone at the floor level. This is how tube heaters can heat large spaces without having to provide primary infrared for every square foot of area. However, if the goal is to spot heat a small area within a large space, only the primary infrared makes this possible. Vacuum tube heaters are design certified for use in industrial and commercial buildings, such as warehouses, manufacturing plants, aircraft hangars and vehicle maintenance shops. No heater may be used in a class 1 or class 2 explosive environment. Unless otherwise indicated, they are not certified for residential use or where flammable gases or vapors are generally present, such as spray booths. Printed in U.S.A. © Detroit Radiant Products Co. 21400 Hoover Rd., Warren, MI 48089 T. (586) 756-0950 F. (586) 756-2626 http://www.reverberray.com Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vincinity of this or any other appliances. FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department. HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez pas aux interrupteurs électriques. 3. éteingnez toute flamme nue. 4. Contactez immédiatement votre compagnie de gaz. Il est interdit d’utiliser des liquides inflammables ou dégageant des vapeurs inflammables, á proximité de tout appareil fonctionnant au gaz. WARNING: This heater must be installed and serviced by trained gas installation and service personnel only! Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. Protect yourself and others by observing all safety information. Retain instructions for future reference. ! WARNING! In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or in the absence of such thermostats in a conspicuous location. !

HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

DescriptionVacuum type tube heaters are negative pressure gas-fired infrared heaters designed to provide comfortheat. They consist of four (4) main components: aburner control box, radiant tube, reflector assembly,and vacuum exhauster. The heaters are typicallysuspended from the ceiling by chains and controlledby a thermostat. They can be installed either ventedor unvented, and may use outside air for combustionif necessary. The radiant tube may be installed indifferent configurations depending on the heatingrequirements.

These heaters use infrared energy to heat spaces.When heat is required, the burner control box ignitesa gas/air mixture and the vacuum pulls the hot gasesinto the radiant tube. As the gases pass through theassembly, the tubing is heated and emits infrared,which is then directed toward the floor by reflectors.This is known as primary infrared and is absorbedby the floor, objects and people in the space, raisingtheir temperatures. They in turn reradiate this heat,known as secondary infrared, to create a comfort zoneat the floor level. This is how tube heaters can heatlarge spaces without having to provide primaryinfrared for every square foot of area. However, ifthe goal is to spot heat a small area within a largespace, only the primary infrared makes this possible.Vacuum tube heaters are design certified for use inindustrial and commercial buildings, such aswarehouses, manufacturing plants, aircraft hangarsand vehicle maintenance shops. No heater may beused in a class 1 or class 2 explosive environment.Unless otherwise indicated, they are not certified forresidential use or where flammable gases or vaporsare generally present, such as spray booths.

Printed in U.S.A.© Detroit Radiant Products Co.

21400 Hoover Rd., Warren, MI 48089T. (586) 756-0950 F. (586) 756-2626

http://www.reverberray.com

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

FOR YOUR SAFETYDo not store or use gasoline or other flammablevapors and liquids in the vincinity of this or any otherappliances.

FOR YOUR SAFETYWhat to do if you smell gas:

• Do not try to light any appliance.• Do not touch any electrical switch; do not

use any phone in your building.• Immediately call your gas supplier from

a neighbor’s phone. Follow the gassupplier’s instructions.

• If you cannot reach your gas supplier,call the fire department.

HLV SERIESTUBE HEATERVACUUM SYSTEM

LIOHLV- 1M-11/02 (MWG)

CONSIGNES DE SÉCURITÉ

Sivous sentez une odeur de gaz:

1. Ouvrez les fenêtres.2. Ne touchez pas aux interrupteurs électriques.3. éteingnez toute flamme nue.4. Contactez immédiatement votre compagnie de gaz.

Il est interdit d’utiliser des liquides inflammables oudégageant des vapeurs inflammables, á proximité

de tout appareil fonctionnant au gaz.

WARNING: This heater must be installed and serviced by trained gas installation and service personnel only!Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.Protect yourself and others by observing all safety information. Retain instructions for future reference.

!

WARNING!In locations used for the storage of combustiblematerials, signs must be posted to specify the maximumpermissible stacking height to maintain the requiredclearances from the heater to the combustibles. Signsmust either be posted adjacent to the heater thermostatsor in the absence of such thermostats in a conspicuouslocation.

!

Page 2: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

WARNING!

This is not an explosion-proof heater. Where thereis the possibility of exposure to flammable vapors,consult the local fire marshal, the fire insurancecarrier and other authorities for approval of theproposed installation.

WARNING!

NOT FOR RESIDENTIAL USE!

Do not use in the home, sleeping quarters,attached garages, etc.

2

WARNING!Do not operate heater with any part bypassed,with any part failed or in any scenario that maycompromise safety.

Warnings

Maintain all clearances to combustibles at all times!See page 5 for clearance to combustibles guidelines.

This infrared heater is designed for use in industrial and commercial buildings such as warehouses,manufacturing plants, aircraft hangars, service garages, etc.

Detroit Radiant Products Company cannot anticipate every use which may be made of their heaters.Check with your local fire safety authority if you have questions about local regulations.

This heater must be installed and serviced bytrained gas installation and service personnel only.Read and understand these instructions thoroughlybefore attempting to install, operate or service thisheater. Failure to comply could result in personalinjury, asphyxiation, death, fire, and/or propertydamage. Retain these instructions for futurereference.

WARNING!

Tube Heater Vacuum System

Any alteration of the system or of factory-authorized components specified in this manualor by Detroit Radiant Products Company voidsall certification and warranties.

IMPORTANT!

Page 3: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

3

Table of Contents and Certifications

1. SAFETY INFORMATION .............................................................................................. 4

2. DESIGN ......................................................................................................................... 62.1 Pre-Design .................................................................................................................... 62.2 Design for Non-Condensing System .............................................................................. 72.3 Design for Condensing Systems ................................................................................... 82.4 Definitions ..................................................................................................................... 102.5 Vacuum Pump Application ............................................................................................ 112.6 Damper Application ....................................................................................................... 12

3. INSTALLATION ............................................................................................................. 133.1 Pre-Installation .............................................................................................................. 133.2 Vacuum Pump Assembly & Mounting ........................................................................... 153.3 Tube & Burner Box Mounting ........................................................................................ 153.4 Baffle Assembly ............................................................................................................ 173.5 Reflector Assembly ....................................................................................................... 183.6 Reflector Accessories ................................................................................................... 193.7 Flue Venting for Non-Condensing Systems ................................................................... 203.8 Flue Venting for Condensing Systems .......................................................................... 213.9 Combustion Air Intake ................................................................................................... 223.10 Gas Supply ................................................................................................................... 23

4. OPERATION ...................................................................................................... 254.1 Electrical Requirements ................................................................................................ 254.2 Lighting Instructions ...................................................................................................... 254.3 Shutdown Instructions ................................................................................................... 254.4 Theory of Operation ....................................................................................................... 254.5 System Start-Up & Damper Setting .............................................................................. 29

5. MAINTENANCE .................................................................................................. 305.1 Troubleshooting Chart ................................................................................................... 315.2 Troubleshooting Flowchart ............................................................................................ 325.3 HLV Parts List .............................................................................................................. 34

6. LIMITED WARRANTY .......................................................................................... 36

Approval Standards and CertficationsDetroit Radiant Products units comply with or are certified by the following organizations or standards:

American National Standards (ANSI Z83.6 and Z83.20)Occupational Safety and Health Act (OSHA)CSA International (CSA)National Standards of Canada

Page 4: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Detroit Radiant Products Company21400 Hoover Road, Warren, MI 48089

T. (586) 756-0950 F. (586) 756-2626http://www.reverberray.com

4

Check the CSA rating label on the heaterto verify the proper gas to be used.

Check the other labels on the heater to verify proper mountingand clearance to combustibles.

The installation of this heater must conform with local buildingcodes or, in the absence of local codes, with the NationalFuel Gas Code, ANSI Z223.1 (NFPA 544) (latest edition).Applications in Canada must conform to CAN/CGA B149.1and 2 codes and Canadian Electrical Code C22.1 (latestedition).

GARAGES

The installation of this heater in public garages must conformwith the Standard for Parking Structures, ANSI/NFPA 88A(latest edition), or the Standard for Repair Garages, ANSI/NFPA 88B (latest edition), and must be at least 8 ft. abovethe floor (see page 5 for Clearances to Combustibles).Applications in Canada must conform to the Canadian ElectricCode C22.1 (latest edition) when an external electrical sourceis used.

! CAUTION

1. SAFETY INFORMATIONHANGARS

The installation of this heater in aircraft hangars must conformwith the Standard for Aircraft Hangars, ANSI/NFPA 409 (latestedition). The heater must be installed at least 10 ft. above theupper wing surfaces and engine enclosures of the highestaircraft which might be stored in the hangar. In areas adjoiningthe aircraft storage area, the heaters must be installed atleast 8 ft. above the floor. The heaters must be located inareas where they will not be subject to damage by aircraft,cranes, movable scaffolding or other objects.

ELECTRICAL

The heater, when installed, must be electrically grounded inaccordance with the National Electrical Code ANSI/NFPA 70(latest edition).

Under no circumstance is either the gas supply line or theelectrical supply line to the heater to provide any assistancein the suspension of the heater.

The weight of the heater must be entirely suspended from apermanent part of the building structure having adequate loadcharacteristics.

Neither the gas supply line, electrical supply line nor sprinklerheads shall be located within the minimum clearances tocombustibles as shown in the Clearances to CombustiblesChart on page 5.

Signs should be posted in storage areas to specify maximumstacking height allowed in order to maintain clearances tocombustibles. DRP part #PLQ warning plaques arerecommended.

IMPORTANT NOTE

Unless otherwise indicated on the AGA label (Chart 2 (C2)or Chart 3 (C3)), this infra-red heater is designed to operateon standard BTU gas (either 1000 BTU ft3 for natural gas or2500 BTU ft3 for propane gas) at elevations 0 to 4000 feetMSL (Sea Level).

Tube Heater Vacuum SystemThe following must be reviewed before installing this heater.

Page 5: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

0 MOUNTING ANGLE

TOP

45 MOUNTING ANGLE

BELOW

FRONT BEHIND

TOP

BELOW

SIDE SIDE

0 W/1 SIDE SHIELDTOP

0 W/2 SIDE SHIELDS

BELOW

SIDE SIDE

BELOW

TOP

FRONT BEHIND

NOTE: Infra-red heaters can cause discomfort to buildingoccupants if the heaters are mounted too low. Therefore, aminimum mounting height must be observed, based uponthe clearance to combustibles and the specified minimummounting height. Also, a maximum mounting height for eachheater should be observed for effective radiant heating.

NOTE: See HLV Design Guide for Determination of PublishedClearances to Combustibles.

5

For the safe installation of this unit, consult the clearance tocombustibles chart. It contains clearances that must bemaintained.

! WARNING This heater should beinstalled so that the minimum

clearances to combustibles, as marked on theheater, will be maintained from vehicles parkedbelow. If vehicle lifts are present, ensure thatthese clearances will be maintained from thehighest raised vehicle.

Safety Clearance InformationClearances to Combustibles

Clearances listed in the following table apply to individualburners located in the HLV system. Inspect each burner ratinglabel to ensure that clearances are maintained

WARNING!In locations used for the storage of combustiblematerials, signs must be posted to specify themaximum permissible stacking height to maintain therequired clearances from the heater to thecombustibles. Signs must either be posted adjacentto the heater thermostats or in the absence of suchthermostats in a conspicuous location.

!

! WARNINGFailure to comply with the stated clearances tocombustibles could result in personal injury,death and/or property damage.

FRONT BEHINDHLV 50 (N,P) 0º 9 9 4 47

45º 39 8 10 47W/1 side shield 0º 29 8 4 47W/2 side shields 0º 9 9 4 4720 ft from burner 0º 7 7 4 30

HLV 60 - HLV 75 (N,P) 0º 9 9 4 4845º 39 8 10 48

W/1 side shield 0º 29 8 4 48W/2 side shields 0º 9 9 4 4820 ft from burner 0º 7 7 4 30

HLV 80 (N,P) 0º 11 11 4 4845º 39 8 10 48

W/1 side shield 0º 29 8 4 48W/2 side shields 0º 16 16 4 4820 ft from burner 0º 7 7 4 30

HLV 90 (N,P) 0º 12 12 4 5445º 39 8 10 54

W/1 side shield 0º 29 8 4 54W/2 side shields 0º 16 16 4 5420 ft from burner 0º 7 7 4 30HLV 100 (N,P) 0º 14 14 4 66

45º 39 8 10 66W/1 side shield 0º 29 8 4 66W/2 side shields 0º 16 16 4 6620 ft from burner 0º 7 7 4 30

HLV 110 - 125 (N,P) 0º 18 18 4 7245º 58 8 10 72

W/1 side shield 0º 42 8 4 72W/2 side shields 0º 20 20 4 7220 ft from burner 0º 7 7 4 30

HLV 140 - HLV 150 (N,P) 0º 24 24 6 8145º 58 8 10 81

W/1 side shield 0º 42 8 6 81W/2 side shields 0º 30 30 6 8120 ft from burner 0º 11 11 6 44

HLV 170 - HLV 175 (N,P) 0º 34 34 6 9245º 63 8 10 92

W/1 side shield 0º 50 8 6 92W/2 side shields 0º 30 30 6 9220 ft from burner 0º 11 11 6 44

HLV 180 - HLV 200 (N,P) 0º 41 41 6 9445º 63 8 10 94

W/1 side shield 0º 54 8 6 94W/2 side shields 0º 30 30 6 9421 ft from burner 0º 11 11 6 44

CLEARANCES TO COMBUSTIBLES (IN.)MODEL NO. MOUNTING

ANGLESIDE

TOP BELOW

Page 6: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

1) The HLV can be a Non-condensing system or acondensing system. After the pre-design section is read,go to the appropriate section for the desired system. If itis uncertain what type of system is to be used, start offby going to the condensing section (2.3) and if thecompleted design does not require condensing pipe, thenby default, the system will be a non-condensing system.

2) All non-condensing systems must be on a singletemperature zone. If two temperature zones are required,the system will be a condensing system thus continue tosection 2.3.

3) Determine the heat load required for the building.

4) Mounting height and coverage are the two critical variablesin selecting the proper size burners and the number ofburners for a layout.

a) The mounting height of the system will determine thelargest size burner that can be used. Refer to the charton page 6 of the HLV Design Guide for recommendedmounting height information.

b) During the design phase it may be discovered thatthe number of burners is not enough to achieve propercoverage, it may be necessary to use a larger number ofsmaller burners.

5) When determining the location of the system, keep inmind clearances to combustible materials, lights, sprinklerheads, overhead doors, storage areas with stackedmaterials, gas and electrical lines, parked vehicles, cranesand any other possible obstructions or hazards. Adequateclearance around air openings leading into the combustionchamber and accessibility for service must be provided.Refer to the Warnings, Cautions and the Clearances toCombustibles Chart on the previous page and on the heaterto verify that a safe installation condition exists.

6) Section 2.4 lists the ‘System Design Parameter’definitions. These definitions will need to be referencedfor system design.

2. DESIGN

2.1 Pre-Design for Condensing and Non-Condensing Systems

6

Tube Heater Vacuum System

Page 7: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

7

Design

2.2 Design for Non-Condensing Systems

1) The best approach to designing a system is to start offby actually laying out a design without concerning oneselfwith the system design parameters. In using this approachit is ideal to place the burners where desired and thevacuum pump where desired. Referring to the ‘TypicalLayouts’ section of the HLV Design Guide may be helpful.

2) Now that there is a tentative layout for the system, makesure that each run in the system meets the ‘calculatedminimum run’ criteria. Calculated minimum run isfigured by adding the total ‘single flow’ plus one-half ofthe common clow (refer to section 2.4 for illustrationsand definitions). If the system does not meet theCalculated Minimum Run, add length to the run to makesure all burners meet calculated minimum run.

3) Refer to the chart below for “Non-condensing systemdesign parameters” and check the ‘calculated maximumrun’ for every burner. It will be necessary to make thesystem a condensing system or shorten a run if thecalculated maximum run is exceeded. Refer to section2.4 for examples to determine ‘calculated maximum run’.

4) Check to make sure the following applies for non-condensing systems only.

a) A maximum of two elbows per run is allowed in asystem.

b) A maximum of three intersections (tees or crosses)are allowed in a system (per vacuum pump).

c) A reflector over an elbow or intersection is required if20 feet or less from the burner.

The system tube lengths are determined by the gas input (BTU/H). The chart below indicates the system design parameters foreach burner model used in a system. Elbows and tees have already been accounted for, therefore do not add them whencalculating tube lengths.

Designing a non-condensing system can be quite simple if the following four steps are read carefully. Along with these foursteps, an understanding of the design definitions is critical. Refer to section 2.4 for definitions and illustrations.

HLV Burner Model

Minimum Distance from Burner to first

Elbow or Intersection (feet)

Calculated Minimum Run

(feet)

Calculated Maximum Run

(Distance is of Actual Radint Pipe) (feet)

50, 60 10 30 4575, 80 10 35 50

90, 100 10 40 55110, 125 10 45 60140, 150 15 50 65

170, 175, 180 15 55 70200 20 60 75

Design Parameters for Non-Condensing Systems(Refer to Section 2.4 For Chart Definitions)

Page 8: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

8

Tube Heater Vacuum System

2.3 Design for Condensing Systems

1) The best approach to designing a system is to start off byactually laying out a design with out concerning oneselfwith the system design parameters. In unsing this approachit is ideal to place the burners where desired and the vacuumpump where desired. Referring to the Typical Layoutssection 3.2 may be helpful.

2) Now that there is a tentative layout for the system, makesure that each run in the system meets the ‘CalculatedMinimum Run’ criteria. Calculated minimum run isfigured by adding the total ‘Single Flow’ plus one-half ofthe Common Flow (refer to section 2.4 for illustrations anddefinitions). If the system does not meet the calculatedminimum run, add length to the run to make sure allburners meet calculated minimum run.

3) Determine the calculated starting point of thecondensing run. Look up each burner size on the chartto determine at what point in the ‘calculated run’ wherecondensing pipe must begin. Once the condensing pipebegins in a run, all intersections and elbows thereafter mustbe condensing pipe as well. Do this for each individual run.If none of the runs are long enough to use condensing pipethen the system is regarded as a ‘non-condensing’ system.

3a) Alternate approach to step 3 if simulating an in-line design.If doing an in-line system, the tie-in burners must be at theminimum distance to elbow (no more, no less). Referencethe Maximum Actual Distance between Tie-Ins to makesure the tie-in distance is not exceeded. Reference theStarting Point of Condensing for ‘Similated In-Line’ systemsand determine when the condensing pipe starts after thelast tie-in. When using this approach, step 4 does not apply.

The system tube lengths are determined by the gas input (BTU/H). The chart below indicates the system design parameter foreach burner model used in a system. Elbows and tees have already been accounted for, therefore do not add them whencalculating tube lengths.

Designing a condensing system can be quite simple if the following six steps are read carefully. Along with these six steps, anunderstanding of the design definitions is critical. Refer to section 3.6 for definitions and illustrations.

HLV Burner Model

Minimum Distance from Burner to first

Elbow or Intersection (feet)

Calculated Minimum Run (feet)

Calculated Starting Point of Condensing Run

(feet)

Calculated Maximum Run

(Including Condensing Pipe)

(feet)

Maximum Actual Distance between

Tie-Ins for 'Simulated In-Line' systems

(feet)

Starting Point of Condensing for

'Simulated In-Line' systems

50, 60 10 30 45 85 35 30 ft After Last Tie-in75, 80 10 35 50 95 40 30 ft After Last Tie-in

90, 100 10 40 55 105 45 30 ft After Last Tie-in110, 125 10 45 60 110 50 40 ft After Last Tie-in140, 150 15 50 65 120 55 40 ft After Last Tie-in

170, 175, 180 15 55 70 130 55 40 ft After Last Tie-in200 20 60 75 140 55 40 ft After Last Tie-in

Design Parameters for Condensing Systems(Refer to Section 2.4 For Chart Definitions)

Simulated in-line Systems

Page 9: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Figure 2-1

9

Design

T

T

Condensing pipe

Points where zone1 & 2 share commontubing. Condensingpipe must beginhere.

Zone 1

Zone 2

6) Check to make sure the following applies for condensingsystems only. If these items are exceeded, contact thefactory for approval.

a) A maximum of three elbows per run is allowed in asystem.

b) A maximum of six intersections (tees or crosses) areallowed in a system (per vacuum pump).

c) A reflector over an elbow or intersection is required if20 feet or less from the burner.

4) Check the calculated maximum run for every burner. It isusually recommended to shorten a run if the calculatedmaximum run is exceeded. Refer to section 2.4 forexamples to determine ‘calculated maximum run’.

5) If two different temperature zones are going to be used ona system, where some burners will be on one thermostatand the remainder of the burners will be on a secondthermostat, the following guidelines must be met.

a) At the point where the two different zones will haveburners that share common tubing, condensing pipe mustbe used. The condensing pipe will start at this point andcontinue through to the pump. See figure 2-1 for anexample.

Page 10: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

10

2.4 Definitions

Run – The total actual length of radiant pipe from the individualburner box to the exhauster.

Minimum Distance to Elbow or Intersection – Theminimum allowable distance from the burner box to the firstelbow or intersection.

Single Flow – The radiant pipe in a run from the burner boxto the first intersection (tee or cross). Refer to figure 2-2.

Common Flow – The radiant pipe in a run between thefirst intersection (tee or cross) and the exhauster. ‘CommonFlow’ begins at the point where two (2) or more burners sharea common exchanger. Refer to figure 2-2.

(Please read this important definition carefully!)Calculated Run – Calculated run is determined byadding the total ‘single flow’ plus one half of the ‘commonflow’ of Pipe. For Example, if an actual run, has 30 feetof ‘single flow’ and 20 feet of ‘common flow’, this equals40 feet (30 ft. + one half of 20 ft.) of Calculated Run.Refer to figure 2-2.

Calculated Minimum Run – The minimum allowable‘calculated run’.

Calculated Starting Point of Condensing Run – The pointin the ‘calculated run’ where condensing pipe must begin.Refer to figure 2-3 for an example.

Calculated Maximum Run –The longest allowable ‘calculatedrun’ from the burner to the exhauster including the condensingpipe.

In figure 2-3, a model HLV-75 starts it’s condensing pipe at 50cacluated feet (40 feet plus one-half of 20 feet). The amountof condensing pipe in this particular example is 20 ft.

Figure 2-2

ISOLATION BOOT VACUUM PUMP

PRIMARY DAMPER

HLV-75HLV-75

20 FT

30 FT30 FT

Figure 2-3

40 FT 40 FT

HLV-75HLV-7540 FT

20 FT

20 FT

VACUUM PUMP

Start point ofcondensing

Definitions

Tube Heater Vacuum System

Com

mon

Flow

SingleFlow

SingleFlow

Page 11: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Pump Application

11

2.5 Vacuum Pump Application

The following table indicates which vacuum pump should beused for a system based on the specific BTU/H input.

* NC-7 IS FOR NON-CONDENSING SYSTEMS ONLY.

A system containing a HLV-150 burner and two HLV-100burners would have a total system input of 350,000 BTU/H.Therefore, this system requires a PB-9 vacuum pump asindicated the table.

The vacuum pump exhaust venting length must be between 2feet and 25 feet. The maximum number of elbows in theexhaust vent is two.

Isolation boots provided with the system must be installedbefore the vacuum pump on all systems.

VACUUM PUMP

MODEL NO.

TOTAL SYSTEM INPUT RANGE

(BTU/H)

MAXIMUM BURNERS ON PUMP

NC-7 * 50,000 - 150,000 2PB-8 50,000 - 275,000 5PB-9 280,000 - 545,000 6PB-10A 550,000 - 750,000 6

Use appropriate hardwareto attach to structure

Tube & Reflector Hangerw/ Chain Hanging Set

Primary DamperIsolation Boot

Support Plate

Vibration Isolators

4" Vent

Threaded Rod

Vacuum Pump Control Box

Design

Figure 2-4

Page 12: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

12

2.6 Damper Application

All systems are provided with a primary damper which is placed before the vacuum pump. Due to variations in gas input andradiant tube length, secondary dampers should be placed at various points as necessary to balance the system’s exhaust flow.A maximum of six dampers per system is allowed. The following are three typical examples of damper placement:

Example #3 - Figure 2-7A system containing two HLV-75 burners with unequal lengthsof radiant tube running to the vacuum pump from each burner.This system requires a primary damper at the vacuum pumpand a secondary damper before the tee (HLV-T) on the shortertube length as shown in Figure 2-7.

Figure 2-6

HLV-75

SECONDARY DAMPER

SECONDARY DAMPER

ISOLATION BOOT

VACUUM PUMP

HLV-T

PRIMARY DAMPER

HLV-100

20 FT.

40 FT. 40 FT.

Tube Heater Vacuum System

Example #2 - Figure 2-6Figure 2-6 shows a system containing a HLV-75 burner (gasinput of 75 MBTU/H) and a HLV-100 burner (gas input of 100MBTU/H) with equal lengths of radiant tube running to thevacuum pump from each burner. This system required aprimary damper at the vacuum pump and a secondary damperbefore the tee (HLV-T) serving the lower MBTU/H heater.

Example #1 - Figure 2-5A system containing two HLV-75 burners with equal lengthsof radiant tube running to the vacuum pump from each burner.This system required only a primary damper as shown inFigure 2-5.

Figure 2-5

30 FT.30 FT.

20 FT.

HLV-75HLV-75

PRIMARY DAMPER

VACUUM PUMPISOLATION BOOT

Figure 2-7

VACUUM PUMP

PRIMARY DAMPER

ISOLATION BOOT

SECONDARY DAMPER

HLV-75 HLV-75

20 FT.

40 FT. 30 FT.

HLV-T

SECONDARY DAMPER

Page 13: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

First Tube (Alum-Ti) downstream of the burner

box - Referred to as the Combustion Chamber

Welded seam must be positioned downward

175,000 - 225,000 models require a

stainless steel tube clamp between the

first and second 10 foot radiant tubes.

13

Installation

3. INSTALLATION

3.1 Pre-Installation

1) Verify that all parts have been received by checking themagainst the packing list. If anything is missing, notify theRe-Verber-Ray representative or Detroit Radiant Products.

2) Check the AGA rating label on the burner to verify themodel number, the gas to be used and that the clearancesto combustibles will be met.

3) Check the AGA rating label on the vacuum pump to verifythat it is adequate for the gas input (BTU/H) of the system.

4) Identify the Alumi-Ti 10 ft. tube(s), and ensure that oneexists for each burner.

5) Following a layout drawing, determine the location of thesuspension points for the system in relation to the buildingstructure. Ensure that the finished installation will conformto the design requirements listed in the foreword, andthe Clearances to Combustibles Chart on page 5.

6) Each system is supplied with the necessary wire hangersfor suspending the burner, radiant tubing and reflectors(see Figure 3-1).

7) Use of 12 gauge, size #1, double-loop chain (THCS) isrecommended when hanging the system. Quantity 3 perburner, 1 per tube.

8) Mounting chains must hang perpendicular to the system.

9) The first 10 ft. of tube downstream from a burner must betitanium alloy aluminized steel tube (Alumi-Ti). Identifythis tube and make sure it is installed with welded seamdown (see Figure 3-1).

Figure 3-1

Page 14: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

14

INSTALLATION NOTES

IMPORTANT: Mount burner control box and chain sets levelto the ground. Do not rotate control box assembly.

IMPORTANT: 175,000 through 225,000 BTU/H models mustbe installed with a stainless steel tube clamp at the secondjoint of the exchanger between the first and second radianttubes.

IMPORTANT: Mount all tubes with welded seam facingdownward (see figure 3-3). Be sure to have swaged endspointed towards the exhaust end of the heater.

NOTE: If windy conditions exist in the space around theheater, it may be necessary to rigidly mount the heater toprevent swaying. It is recommended that threaded rod beused for the two hanging points at the burner control box (seeFigure 3-2). The remaining hanging points should use chainsto allow for heater expansion.

NOTE: The tube clamps provided with the heater are pre-assembled at the factory. If a clamp is dismantled, it isimportant that upon reassembly the spacer is properly inserted(see Figure 3-7). The spacer’s concave surface must facethe radiant tube. Incorrect spacer placement will result inshearing of the bolt when torqued to the recommendedspecifications (40-60-lb. ft.).

Figure 3-2

MOUNT BURNER BOX LEVEL

Figure 3-3

Tube Heater Vacuum System

NOTE: When positioning heaters, keep in mind the clearanceto combustible materials, lights, sprinkler heads, overheaddoors, storage areas with stacked materials, gas and electricallines, parked vehicles, cranes and any other possibleobstructions or hazards. Refer to the Warnings, Cautionsand the Clearance to Combustibles chart in the SafetyInformation Section and on the heater to verify that a safeinstallation condition exists.

- IMPORTANT -

• Do not exceed the maximum vent length for exhaustingthe heater. Consult sections 3.7 & 3.8 for guidelines.

Consult Combustion Air Requirements section on page 22.

• Do not exceed the maximum duct length for fresh airintake. Consult Air Intake Duct Chart on page 22.

• Do not draw fresh air into the heater from an attic space.There is no guarantee that adequate air will be supplied.

• All unvented heaters must use Part No. WVE-GALV ventwith flapper.

Once all of the safety precautions and design criteria are met,the actual installation of the heater may begin.

Page 15: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Beam Clamp

Turnbuckle

S-Hook

Bar Joist Clip

Anchor

Washers

Wood BeamLocknut

3.3 Tube & Burner Box Mounting

1) Installation will begin at the vacuum pump. Condensingpipe has to be sloped downward at 1/4” per 10 feet as itapproaches the pump (which is upward at 1/4” per 10 feetgoing from the pump). The standard radiant pipe will bemounted level. Refer to figure 3-6 on the following page.

2) It may be easiest to start by mounting the first tube withtwo (2) hangers spaced approximately 8 to 9 feet apart.Every 10 foot tube thereafter should only need one (1)hanger spaced at approximately 8 to 9 feet apart. Referto figure 3-13 on page 18 for an example of hangerplacement.

3) It is critical that the tube mounting starts with therun having the greatest amount of condensing pipe.If there is no condensing pipe in the system, startwith the longest run.

4) Clamps must be placed directly over the tube seams.Refer to figure 3-7.

5) After the first run is completely installed with all tubes,dampers, elbows, intersections, etc., install the run withnext greatest amount of condensing pipe, and so on andso on, until all runs are complete.

6) For ease of installation, it is recommended that reflectorsbe mounted with each tube as it is installed (seeinstructions on reflector assembly.

7) Make sure all dampers have been properly placed in thesystem and temporarily set each damper to half-closed.

8) Adjust suspension hardware so that the tubes are in lineand straight. Adjust chain lengths until standard radiantpipe is level and the condensing pipe is at the properpitch. It is recommended that the condensing pipe isinstalled with turnbuckles (Part# V-TB) for ease of slopingthe tube(s). One V-TB needed per suspension point.

9) Heater must be independently supported. It must notrely on the gas or electrical lines for any of its support.

10) Mount burner control box level and be sure that theburner sight glass is visible from the floor.

3.2 Vacuum Pump Assembly and Mounting

1. Before mounting vacuum pump make sure that thebuilding structure and support brackets have adequateload characteristics to support the pump. See chart below.

2 Install vacuum pump as shown on plan drawing. Makesure pump is properly aligned with system. Allow an 8"to 12" space for the isolation boot between the primarydamper and the vacuum pump inlet adapter. Refer tofigure 3-6.

3. Mount the inlet and outlet adapters to the vacuum pumpusing self-tapping sheet metal screws, and seal the jointswith high temperature sealant.(The NC-7 does not require an inlet adapter or isolationboots. See figure 3-5 for illustration).

4. Install isolation boot with clamps provided.See figure 3-6.

NOTE: The average sound level of the PB series vacuumpumps is between 60 and 63 DBA. If the applicationrequires a lower sound level, relocation of the vacuumpump or a sound-deadening enclosure may be used.Consult factory.

15

Vacuum Pump Model No.

Vacuum Pump Weight (lbs.)

NC-7 20PB-8 60PB-9 67PB-10A 73

Installation

Figure 3-4

Turnbuckle (Part# V-TB) is recommended on all condensingpipe suspension points for ease of slope adjustments.

Page 16: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Isolation Boot

Primary Damper

Vacuum Pump Control Box Vibration Isolators

All Condensing pipe must be installed on 1/4" per 10 foot downward slope toward exhauster.

Tube & Reflector Hangerw/ Chain Hanging Set

Support Plate

CONDENSING PIPE 1/4" per 10ft

All standard exchanger pipe must be installed level.

Turnbuckle Part# V-TB is recommended for all condensing tube suspension points for ease

of slope adjustment.Inlet Adapter

STANDARD PIPE AL-TI

16

Tube Heater Vacuum System

SAFETY CHAIN

SEAM

EXHAUSTER ASSEMBLY

POWER BOX

EXHAUST DISCHARGE

Primary Damper

Tube & Reflector Hangerw/ Chain Hanging Set

Use appropriate hardwareto attach to structure

NOTE: Isolation boots are not needed between the damper and exhauster

assembly when using the NC-7 model exhauster on

an HLV system

Figure 3-6

Right Wrong

Swaged Tube

Seam

Clamp

Tube Clamp

Figure 3-7

Figure 3-5

Correct Incorrect

Page 17: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Installation

17

1. All systems include 99” of baffle. Baffle must be installedas close to the pump as possibe in the section of tubingthat allows insertion of the entire length of baffle. Refer tofigure 3-8.

2. As shown in figure 3-9, assemble the baffle to the properlength. Baffle assembly may be done on the ground orassembled in increments of 33” while being fed into thetube.

Place male side (tab fittings) against femaleside (keyhole) at a 90-degree angle.

Center tabs. Repeat process asnecessary to complete entire baffle.

With tabs centered, rotate baffle90-degrees to complete assembly.

Place opposite tab throughkeyhole and slide baffle backtowards the center position.

Insert one tab into keyholeand slide fully to one side.

Place complete baffle into radiant tubes.Install baffle in the horizontal position.

Figure 3-9

3.4 Baffle Assembly & Installation Instructions

NOTE: Install assembled baffle so that the key hole is insertedfirst. All baffles must be placed vertically in the radianttube/heat exchanger.

Installed Baffle

Baffle Assembly

Figure 3-8

Page 18: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Reflector Expansion Joints

Reflector Expansion Joints

First installed tube(s) can be mounted using two hangers.

All tube(s) installed after the first tube typically require only one hanger.

18

3.5 Reflector Assembly

1. Mount reflector center support (RCS) at halfway pointbetween hangers (see figure 3-10).

2. Slide reflectors through wire hangers and overlap matingreflector ends four inches for support (see figure 3-11).Install sheet metal screws as shown.

3. Install elbow and tee reflector assemblies if used.

4. Install elbow and tee reflector end-caps at any exposedends of the reflectors using four clips per end cap (seefigure 3-12).

Note: Leave an expansion joint in eachrun of reflector, the preferred locationis between reflector one and two.

Figure 3-13

Tube Heater Vacuum System

ANTI-RATTLE SPRING

REFLECTOR Secure reflectors with sheet metal screws at all non-expansion joints.

Figure 3-11

CLIPS

ANTI-RATTLE SPRING

REFLECTOR ENDCAP

Figure 3-12Figure 3-10

Page 19: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Reflector Elbows (Part No. RE) are designed to fit atop anelbow tube fitting (see figure 3-16).

“U” Reflectors (Part No. RU) cover TF1B “U” Fittings. Theyattach to standard reflectors covering the end of a “U”configuration (see figure 3-17). Reflectors cannot be rotatedafter installation of this accessory.

Protective Guards. (Part No. PG) Designed to attach to thestandard reflector. They are typically used to prevent debrisor objects from becoming lodged between the radiant tubeand reflector.

Aluminum Egg Crate. (Part No. EC) is designed to fit into astandard 2’ x 4’ ceiling tile opening. Drop ceiling side panels(Part No. DCSP) are needed for complete installation of eggcrate. The side panels are used to direct infra-red rays awayfrom ceiling tiles.

Protective Heat Shields (Part No. PHS) attach below reflectorto shield heat sensitive areas. Can only be used on 00

mounted reflectors.

Stainless Steel Reflectors (Part No. SSR or SSRAO) arealso available for applications in harsh environments.

See the Accessory Guide for product specific information.

0 W/2 SIDE SHIELDS

TOP

BELOW

SIDE SIDE

0 W/1 SIDE SHIELD

TOP

BELOW

FRONT BEHIND

Figure 3-14

Installation

19

3.6 Reflector Accessories

Different applications will require the use of reflectoraccessories. Available options include side shield extensions,protective guards, elbow or U shields, stainless steel reflectorsand drop ceiling panels. Consult the Detroit Radiant ProductsAccessory Guide for detailed product information.

Side Shield Extensions. (Part No. SSE) Designed to directinfra-red rays downward, away from sidewalls andcombustibles. This includes stored combustible containers,heating between two large vehicles, crane rail motors, wiringand other applications that require protection. Figure 3-14details a side shield assembly installation. Figure 3-15 showswhere to measure the new clearances from. Data for theseclearances is available in the product insert for each series ofheaters.

Figure 3-15

Figure 3-16 Figure 3-17

Page 20: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

20

3.7 Flue Venting for Non-Condensing Systems

• Check all applicable codes prior to installing any exhaustvent. Local codes may vary. In the absence of local codessee the National Fuel Code ANSI Z223.1 (NFPA 54) latestedition. This system is designed to operate with a 4”diameter exhaust vent.

• It is recommended that single-wall vent material be used.The portion of the vent which goes through combustiblematerial in the building wall or roof must pass through adual insulated vent sleeve with an approved 1 inch clearancethimble (see Figure 3-18 and 3-19).

• Vertical vents which exit through the roof should be at least2 ft. higher than any portion of the building within ahorizontal radius of 10 ft. of where it passes through theroof of the building (see Figure 3-18). A standard rain capmay be used to shield the vent.

• The vent tube length allowed must be between 2 ft. and 25ft. Do not use more than two 90° elbows in the vent (allmodels).

• Horizontal venting must be terminated using a vent capwith flapper (HLV-WVE) and have a 1 inch clearance fromcombustible walls (see Figure 3-19). Through the wallventing shall not terminate over public walkways and mustbe at least 4 ft. below, 4 ft. horizontally from, or 1 ft. aboveany door, window or gravity air inlet into any building.

• All vent tubes must be sealed to prevent leakage of fluegas into building.

• Single-wall vent tube that is exposed to cold air must beinsulated to prevent condensation.

• Vent cap must be protected from blockage by snow.• The building must be protected from damage by flue gases.• Single wall aluminum flue pipe – minimum 26 ga.

Typical Vertical Venting for Non-Condensing Systems Typical Horizontal Venting for Non-Condensing Systems

Figure 3-18 Figure 3-19

Tube Heater Vacuum System

The following guidelines must be observed to ensure proper system performance and safety.

Page 21: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Extend at least 24" past building to avoid potential

building discoloration

Horizontal venting must slope downward 1" per foot

Adhere to local codes for condensate disposal

Isolation Boot

Condensate Trap Assembly not required on horizontal venting unless local codes require such.

Storm collar is recommended to prevent drippage

back flow.

3.8 Flue Venting for Condensing Systems

• A condensate trap is required on the discharge side ifthere is a vertical rise in the discharge line (figure 3-20).On a horizontal discharge the condensate trap can beeliminated if the discharge is pitched down one inch perfoot (figure 3-21). Check with local codes for propercondensate disposal.

• For ease of installation and condensate disposal, horizontalventing is recommended and preferred.

• For horizontal venting, extend the vent a minimum of twofeet past the building exterior in order to minimize potentialbuilding discoloration from condensate drippage.

Vent Recommendations in order of preferred use:• Stainless Steel condensing tube 4” O.D.

-part # 10SST for 10 ft. sections.-part # SST-60 for 5 ft. sections.

• Single wall aluminum flue pipe – minimum 26ga.

21

Installation

Flue Venting

Figure 3-21

Isolation Boot

Condensate Trap AssemblyPart No. V-CDT

Adhere to local codes for condensate disposal.

Figure 3-20

For condensing systems all of the non-condensing rules apply as well as the following.

Page 22: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

22

MODEL AIR INTAKE DUCT SIZE (IN.)

MAX. INTAKE LENGTH (FT.)

4 305 456 75

AIR INTAKE DUCT CHART

ALL MODELS

Flexible Air Inlet Boot 16"

Duct to Outside

Hook-up4" Air

Proper use of flexible air inlet boot & hook-up

(Part # AIRH)

3.9 Combustion Air Requirements

Combustion air intake has a factory preset air orifice. If indoorcombustion air is to be supplied for a tightly closed room, onesquare inch of free air opening should be provided for each1,000 BTU/H of heater input.

Non-contaminated air for combustion must be ducted to theheater if chlorinated or fluorinated contaminants are presentin the area where the heater is installed, or if the building hasa negative pressure. Typical sources of these contaminantsare refrigerants, solvents, adhesives, degreasers, paintremovers, paints, lubricants, pesticides, etc.

Outside combustion air may be provided by an accessory airduct, and directly attached over the air orifice. A WIV wallinlet cap must be used with horizontal outside air intake ducts.The use of flexible 4” hose, connecting the air intake pipe tothe heater is recommended to allow flexibility for expansion.See figure 3-22.

For limitation of length and size, see the Air Intake Duct-Chart below. The maximum number of 90° elbows allowed istwo.

Keep intake opening at least 4 ft. from any exhaust ventopenings. On rooftop penetrations, always place the ventstack higher than the air intake stack.

The air intake cap must be installed to prevent blockage.Locate WIV air intake by an area that dirt, steam, snow, etc.will not contaminate or clog the 1/2” intake screen.

NOTE: In humid applications use insulated duct or PVC pipeto prevent condensation on outer surface of the intake pipe.

NOTE: Sidewall air intake is preferred over roof air intake.

Figure 3-23

Figure 3-22

Tube Heater Vacuum System

Page 23: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Drip Leg/Sediment Trap

Side View

AGA Ball Valve/Gas Cock

AGA Stainless Flexible Gas Connector

End View

23

3.10 Gas Supply

CAUTION!

CORRECT INLET PRESSURES ARE VITAL FOR EFFICIENTOPERATION OF HEATER. REFER TO AGA/CGA(CSA)RATING PLATE AND, IF NECESSARY, CONSULT GASCOMPANY.

If all or a portion of the gas supply line consists of used pipe,it must be cleaned and then inspected to determine itsequivalency to new pipe. Test all main supply lines accordingto local codes. (Isolate heater gas valve and suppliedgas cock during test.)

Excessive torque on manifold may misalign orifice. Alwaysuse two wrenches when tightening mating pipe connections.

WARNING!Never use a match or any other flame to test for gas leaks. Usea soap and water solution to check for leaks.

If any portion of the gas supply line is located in an area thatcould cause an abnormal amount of condensate to occur inthe pipe, a sediment trap should be installed (see figure3-24).

Figure 3-24

NOTE: For high pressure gas above 14 in. W.C.P. (WaterColumn Pressure), a high pressure regulator and gas cockmust be used. If compressed air is used to detect leaks inthe gas supply line, disconnect and cap shutoff cock to avoiddamage to regulator and gas valve.

A typical gas supply line connection is illustrated in figure3-24. The method shown will decrease the possibility of anyloose scale or dirt in the supply line entering the heater’scontrol system and causing a malfunction. Provide a 1/8 in.(3.2mm) NPT, plugged tapping accessible for test gaugeconnection immediately up stream of gas connection to heater.The gas supply line must be of sufficient size to provide therequired capacity and inlet pressure to the heater (consultgas company) as follows.

NOTE: Manifold pressure should be checked at the tap onthe gas valve. Readings will be above atmospheric pressure.

• Natural Gas

To obtain the required manifold pressure of 3.5 in. W.C.P.,a minimum inlet pressure of 5.0 in. W.C.P. is necessaryfor purposes of input adjustment. A maximum inletpressure of 14.0 in. W.C.P. is allowed for all units.

• Liquefied Petroleum Gas

To obtain the required manifold pressure of 10.0 in. W.C.P.,a minimum of 11.0 in. W.C.P. for purposes of inputadjustment to a maximum of 14.0 in. W.C.P. must beprovided ahead of the control system on each heater. Donot exceed a manifold operating pressure of 10.0 in. W.C.P.

Use only a pipe joint compound that is resistant to liquefiedpetroleum gases.

• Pressure Equivalents

1 in. W.C.P. equals 0.58 oz/sq. in. or 2.49 millibars.

Installation

Gas Supply

Page 24: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

• Allowance for Expansion

Allowances must be made for the system to expand. Astainless steel, flexible gas connector is recommended.If, however, local codes require rigid piping to the heater,a swing joint can be used.

• Gas Line Connection

a. The gas outlet shall be in the same room as theappliance and the connector must not be concealedwithin or run through any wall, floor or partition.

b. The connector shall be of adequate length.

c. The final assembly shall be tested for leaks.CAUTION: Matches, candles, open flame or othersources of ignition shall not be used for this purpose.Leak test solutions may cause corrosion. Waterrinse after test.

d. Contact with foreign objects or substances should beavoided.

e. The connector should not be kinked, twisted or torqued.

f. Connectors are not designed for movement afterinstallation. Bending, flexing or vibration must be avoided.

Connectors are for use only on piping systems having fuelgas pressures not in excess of ½ pound per square inch.

CAUTION!

CONNECTOR NUTS MUST NOT BE CONNECTED DIRECTLYTO PIPE THREADS. THIS CONNECTOR MUST BEINSTALLED WITH ADAPTORS PROVIDED. DO NOTREUSE.

*See kit content chart on page 12 of product insert to determine if above piece(s) should be supplied.

24

Tube Heater Vacuum System

Page 25: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

4. OPERATION

4.1 Electrical Requirements

1. The system operates on 120V, 60 Hz.

2. The system must be grounded in accordance with theNational Electrical Code NFPA 70 latest edition.

3. The system must be installed in accordance with thetypical wiring diagrams (see Figures 4-1 & 4-2).

4. Figure 4-3 illustrates the wiring of a PB series pumpassembly.

5. All systems are two-stage heat systems and will beoperated by a two-stage controller.

6. Check vacuum pump (PB Series) to ensure wiring iscorrect for proper fan wheel rotation. Check directionalarrow on pump housing for proper wheel rotation (excludesNC-7 Series).

7. The amperage draws for the individual HLV componentsare as follows. The circuit(s) must be sufficient to handlethe starting current of the buner control boxes and therunning amperage of the pump.

4.2 Burner Lighting Instructions

1. Purge main gas supply line.

2. Rotate burner’s manual gas valve knob to the “ON”position.

3. Close electrical circuit.

4. If burner fails to light, turn off gas and wait five minutesbefore repeating the above procedure.

4.3 Burner Shutdown Instructions

1. Open electrical circuit.

2. Rotate burner’s manual gas valve to the “OFF” position.

25

Operation

HLV VACUUM PUMPS

RUNNING CIRCUIT

(amp)

NC-7 2.2PB-8 7.6PB-9 9.6

PB-10A 11.4

STARTING RUNNING

0.7 0.2

HLV BURNER CONTROL BOX CIRCUIT (amp)

4.4 Theory of Operation

Starting Circuit (Figures 4.1 and 4.2)

There is constant line voltage sitting at both the vacuum pumpand burner(s). When the thermostat closes it sends power torelays at both the vacuum pump and burner(s).

At the vacuum pump, the relay closes to allow a completedcircuit across L1 and L2.

At the burner control box negative air pressure generated bythe vacuum pump will cause the normally open differentialswitch to close. A low voltage circuit is completed from thesecondary side of the transformer through the relay andpressure switch to the control module. The hot surface igniteris now immediately powered. After the ignitor has beenpowered for 4-5 seconds, the control causes the gas valve toopen and then initiates a 15 second ignition trial.

Running Circuit

After ignition, the flame rod monitors the flame. As long as aflame is present, the valve is held open. If proof of flame is notestablished within 15 seconds, the unit will attempt ignitiontwo more times and then lock out. If lockout occurs, thecontrol can be reset by briefly interrupting the power source.

If the flame is established for a period of time and then lost,the control acts to close the valve within one second, and anew trial sequence identical to that at start-up is initiated.

Page 26: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

W MV1 GND

LIGHT

BK

C

BKLIGHT

R

O

HI M

BK

R

T-STAT TERMINAL

L1

W

RELAY BOARD

OY

BL

120V-240V AC

PRESSURE SWITCH

TRITON 2465HIGNITION MODULE

S1 L1 L2 S2FC1 FC2

BK

BL24V

Y

120V

LIGHT

P

W

BK

G

IGNITOR

BK

ROD

BK

W

FLAME

BK

BK

L2

T'STATTERMINAL

120VAC

TRITON 2465HIGNITION MODULE

S1 L1 L2 S2

W

120-240 / 24VTRANSFORMER

L2

L1

W

BK

BK

RELAY BOARD

Y R

O

120-240V

W

Y

24V

Y

Y

R

PRESSURE SWITCH

BL

A B

C D

BL

TERMINALBLOCK

INDICATOR LIGHTS

Y

O

G

Y

Y Y

FC1 FC2

ON

GAS VALVE

HI

PM C

GY

C

PH

IM

OFF

BURNERFLAME

W MV1 GND

BK

ROD

WBK

IGNITOR

Figure 4-1 Block Wiring Diagram

Figure 4-2 Ladder Wiring Diagram

26

Tube Heater Vacuum SystemInternal Wiring for Burner Control Box

Page 27: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

GYO

R

BL BL

BLBL

BL

4

3

2

NO

NC

COM24V COIL

COM

NO

NC

24V COIL

R

1

BL

FUSE

L1

L2 120V/230V

R

G

W

G

Y 24V

TRA

NSF

OR

MER

120V

/230

V

W

G

R

O

GY

24V INPUT FOR ZONE #1

24V INPUT FOR ZONE #2 IF USED

NCNO24V

COIL

COM

27

Internal Wiring for Pump & Panel Assembly

Installation

Figure 4-3

Note: In North America, pumpand panel are pre-wired at thefactory for 120V. If alternatevoltage will be used consultfactory.

Page 28: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

VACUUM PUMP CONTROL BOX

(MOUNTED TO PUMP)

120

V

24V

24V IN

L2COMMON

A COMMON WIRE IS REQUIRED FOR THERMOSTATS THAT

REQUIRE CONSTANT POWER

-

24V OUT - STAGE 2 (HIGH FIRE)

24V OUT - STAGE 1 (LOW FIRE)

24V IN

24V TWO-STAGE CONTROLLER

24V

+

L1

120

V

1N 2

N 1 2

A COMMON WIRE IS REQUIRED FOR THERMOSTATS THAT

REQUIRE CONSTANT POWER

COMMON

-

L2

24V INPUT FOR ZONE

#1

N 1 2

2N 1

2N 1

N 1 2

24V TWO-STAGE CONTROLLER

24V OUT - STAGE 2 (HIGH FIRE)

24V OUT - STAGE 1 (LOW FIRE)

21N

N 1 2

+

L1

THIS SHOWS ADDITIONAL WIRING FOR SYSTEMS THAT WILL OPERATE ON TWO

TEMPERATURE ZONESNOTE: DO NOT EXCEED THE TOTAL

NUMBER OF BURNERS ALLOWED PER SYSTEM AS STATED IN THE PUMP

APPLICATION GUIDELINES

N 1 2

24V INPUT FOR ZONE

#2 (IF USED)

EXTERNALTRANSFORMER

(FIELD SUPPLIED)

EXTERNALTRANSFORMER

(FIELD SUPPLIED)

Zone 1 Burner(s)

Zone 2 Burner(s) (if secondheat zone is to be used)

28

Tube Heater Vacuum SystemSystem Field Wiring

Figure 4-4

Page 29: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

4.5 System Start-Up and Damper Setting

1. Recheck installation of gas piping, electrical, etc.

2. Preset primary and secondary dampers to half open.

3. Unassisted outside combustion air ducts (if required) mustbe installed before start-up.

4. Fan assisted outside combustion air ducts (if used) mustnot be connected to control box upon initial start-up.

5. To set the dampers, the system must be run for 20minutes in High Fire Mode. Check to make sure all lightson the burner control are on .

6. All dampers in the system are initially set to half closed.If a burner does not light and stay lit, the damper for thatburner will need to be adjusted to get the burner to lightfor the initial 20 miniute start-up.

29

7. Using a manometer with an adequate range, measurethe vacuum at the burner (Figure 4-5) farthest away fromthe vacuum pump. Adjust the primary damper at thepump until the manometer reaches the specified readingshown in the chart below.

8. If secondary dampers have been installed in the system,connect manometer to the designated burner and setsecondary damper to the specified reading shown in thechart below.

9. All dampers must now be readjusted a second time inthe same order. Lock the dampers in place.

BTU Rating

50,000 - 60,000 +/-.0175,000 - 110,000 +/-.01120,000 - 180,000 +/-.01200,000 - 225,000 +/-.01

-0.22-0.19

Box Pressure (inches W.C.)

-0.51-0.19

Each system damper must be adjustedto obtain the following box pressure.The systems must be operating for aminimum of 20 minutes before adjustingthe dampers to the following setpoints.

Operation

Burner Control Box

Vacuum Port

When measuring box pressure, make certain burner box lid is tightened securely.

Figure 4-5

Page 30: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

30

5. MAINTENANCE

The HLV Series Vacuum System requires basic maintenanceto keep it operating at peak performance. This system requiresno filters to be replaced.

1. Routinely inspect the vent intakes and vent exhausts fordirt and/or obstructions. If dirt becomes a problem,installation of outside air intake ducts for combustion arerecommended.

2. Keep the aluminum reflectors clean using a light soapand water solution. Use a metal polish if reflectors areseverely dirty. Maintenance of the reflectors can varysignificantly depending on the environment.

Tube Heater Vacuum System

3. Annually inspect the exhauster system for abnormalnoise. Consult factory for troubeshooting.

4. Periodically check the integrity of the combustion tubeand heat exchangers. Replace if there are signs ofstructural failure.

Date Maintenance Performed Replacement Components Requied

Page 31: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

31

5.1 Troubleshooting Chart

Maintenance

SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION

1. Blow n fuse. 1. Replace.2. Defective thermostat. 2. Replace.3. Defective vacuum pump relay. 3. Replace.4. Loose or disconnected w ire. 4. Repair as required.5. Defective vacuum pump. 5. Repair or replace.

1. Low vacuum pressure setting. 1. Adjust damper for proper pressure.2. Loose or disconnected w iring. 2. Repair as needed.3. Plugged or restricted exhaust vent and/or air intake

3. Clean.

4. Plugged vacuum pressure sw itch lines. 4. Clean or replace.5. Defective circuit control. 5. Replace.

1. Defective glo-bar. 1. Replace.2. Loose or disconnected w ire. 2. Repair or replace.3. Defective circuit control. 3. Replace.

1. System not grounded. 1. Connect electrical ground.2. Defective circuit control. 2. Replace.3. Vacuum pressure setting incorrect. 3. Adjust.4. Low gas inlet pressure. 4. Provide required gas pressure.5. Restricted air inlet. 5. Clean

1. Low gas inlet 1. Provide required gas pressure.2. Defective vacuum pressure sw itch. 2. Replace.3. Restricted air inlet. 3. Clean.4. Vacuum pressure set incorrectly. 4. Adjust

Thermostat closed. Ignition occurs. Burner cycles off and w ill not recycle.

Thermostat closed. Ignition occurs. Burner cycles off and w ill not recycle.

General Trouble Shooting Chart

Thermostat closed but nothing happens.

Thermostat closed. Vacuum pump operates.

Thermostat closed. Vacuum pump operates. No glo-bar energization.

Page 32: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Turn

up

ther

mos

tat.

Doe

s the

exh

aust

erfa

n tu

rn o

n?

YES

NO

Doe

s the

igni

ter

war

m u

p an

d gl

owor

ange

?

Is th

e in

com

ing

pow

er a

tth

e ex

haus

ter p

anel

asse

mbl

y 120

V/2

40V

?

NOIs

ther

e 120

V/2

40V

goin

g to

the

burn

erco

ntro

l box

?

NO

Find

the

sour

ce o

f the

elec

trica

l pro

blem

.

YES

Is 2

4V b

eing

supp

lied

toth

e ex

haus

ter p

anel

asse

mbl

y fr

om th

eth

erm

osta

t?

NO

Find

the

sour

ce o

f the

elec

trica

l pro

blem

.

YES

Is 2

4V b

eing

supp

lied

from

the

ther

mos

tat t

oth

e te

rmin

al p

lug

on th

eco

ntro

l box

?

YES

NO

Find

the

sour

ce o

f the

elec

trica

l pro

blem

betw

een

the

ther

mos

tat

and

the

cont

rol b

ox.

NO

Find

the

sour

ce o

f the

ele

ctric

al p

robl

em b

etw

een

the

ther

mos

tat a

nd th

e pa

nel a

ssem

bly.

YES

Is th

ere 1

20V

/240

Vle

avin

g th

e pa

nel a

ndgo

ing

to th

e ex

haus

ter?

YES

The

exha

uste

r may

be

faul

tyan

d m

ay n

eed

repl

acin

g.

NOC

heck

the

fuse

in th

epa

nel a

ssem

bly.

Is t

hefu

se b

low

n?

YES

Rep

lace

the

fuse

afte

r che

ckin

g th

atth

ere

is n

o pr

obab

leca

use

such

as

diff

icul

ty in

rota

ting

the f

an w

heel

.

NO Is th

ere 2

4V co

min

g of

f the

seco

ndar

y si

de o

f the

tran

sfor

mer

in th

e pa

nel a

ssem

bly?

YES Re

plac

etra

nsfo

rmer

.

NO

Ther

e may

be a

faul

ty re

lay

in th

epa

nel a

ssem

bly.

Con

sult

fact

ory.

Is th

e ig

nite

r phy

sica

llyda

mag

ed? YE

S

Rep

lace

igni

ter.

NO

Che

ck v

olta

ge a

t ing

nite

r dur

ing

the

igni

tion

sequ

ence

(usu

ally

5se

cond

s af

ter p

ower

to b

urne

rco

ntro

l box

). Is

it 2

4V?

YES

NO

Is th

e re

sist

ance

thro

ugh

the

igni

ter 1

to 6

ohm

s?Is

the

inle

t or t

he o

utle

t of

the

unit

obst

ruct

ed?

Ie.

ice,

bird

’s n

est,

dirt,

etc.

NOYE

S

Repl

ace

Igni

ter.

Rep

lace

faul

tyw

iring

.

YES Re

mov

eob

stru

ctio

n.

NO

Che

ck fo

r loo

se w

iring

or

rest

rictio

ns in

hos

e co

nnec

tions

to th

e pr

essu

re s

witc

h.A

re th

ey o

k?

Repa

ir w

iring

or

hose

con

nect

ions

.

NO YES

The h

eate

r is e

quip

ped

with

a sa

fety

pre

ssur

e sw

itch.

The

switc

h is

a n

orm

ally

ope

n sw

itch

an lo

cate

d in

the

gas

valv

e co

mpa

rtmen

t. T

empo

raril

y pl

ace

aju

mpe

r acr

oss t

he te

rmin

al o

f the

switc

h. B

e sur

e to

rein

stal

l the

cov

er.

Doe

s the

igni

ter g

low

ora

nge?

Che

ck th

e da

mpe

r set

ting

for t

hepr

oper

box

pre

ssur

es a

fter t

hehe

ater

has

run

for 2

0 m

inut

es.

Are

the

setti

ngs

corr

ect?

NOYE

S

Adj

ust d

ampe

rsto

ach

ieve

prop

er b

oxpr

essu

re.

YES

Rep

lace

the s

witc

h af

ter v

erify

ing

the f

ollo

win

g:*

Baf

fle(s

) is i

n th

e pro

per t

ube(

s).

* H

eate

r, fa

n bl

ower

, squ

irrel

cage

, int

ake a

nd ex

haus

t are

kep

t cle

an an

d fr

eefr

om d

irt a

nd o

bstru

ctio

ns.

* Th

ere

is n

ot a

neg

ativ

e pr

essu

re e

xper

ienc

ed a

t the

are

a of

inta

ke (i

e: a

ttic

spac

e, h

igh

win

ds, v

ery

tight

bui

ldin

g).

* Th

e int

ake p

ipe e

xcee

ds th

e the

max

imum

spec

ifica

tions

.

NO

HLV

SER

IES

TRO

UBL

ESH

OO

TIN

G F

LOW

CH

AR

T

YES

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

32

Page 33: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Afte

r the

igni

ter i

sw

arm

ed u

p, d

oes

the

gas

valv

e op

en?

NOYES

Pres

s res

et sw

itch

(if a

ny)

on tr

ansf

orm

er. I

f the

re is

still

no 2

4V si

gnal

, rep

lace

bad

trans

form

er.

Che

ck v

olta

ge o

f int

erna

ltra

nsfo

rmer

of b

urne

r box

.Is

ther

e 24V

com

ing

off t

hese

cond

ary

side

?

Is th

ere a

24V

sign

al ac

ross

L1

and

grou

nd a

t the

circ

uit b

oard

?YE

SR

epla

ce b

adci

rcui

t boa

rd.

Test

for 2

4V at

val

vedu

ring

valv

e op

enin

gpe

riod

(usu

ally

5se

cond

s af

ter p

ower

to th

e he

ater

). Is

ther

e 24V

to v

alve

?

NO

NOPo

ssib

ly, t

he c

ircui

t boa

rd a

nd/o

rw

iring

har

ness

is fa

ulty

. Th

ese

shou

ld b

e re

plac

ed.

YES

Che

ck to

mak

e su

re g

as p

ress

ure

isw

ithin

min

imum

and m

axim

um in

puts,

as in

dica

ted

on A

GA

bur

ner r

atin

gla

bel.

Is g

as p

ress

ure

OK

?

Rep

lace

gas

valv

e.

Corre

ctpr

oble

m.

NOYES

Doe

s th

ebu

rner

ligh

t?

YES

NOIs

the

gas c

ock

in th

e O

N p

ositi

on?

Che

ck to

mak

e su

re g

as p

ress

ure

isw

ithin

min

imum

and m

axim

um in

puts,

as in

dica

ted

on A

GA

bur

ner r

atin

gla

bel.

Is g

as p

ress

ure

OK

?

YES

YES

NO

Mak

e su

re g

aslin

es w

ere

purg

ed o

f air.

Corre

ctpr

oble

m.

YES

Doe

s th

e bu

rner

stay

on?

NOD

oes t

he b

urne

r sta

y on

for a

ppro

x.15

sec

onds

and

then

shu

t off

?YE

SIs

the

heat

er p

rope

rlygr

ound

ed?

Is th

epo

larit

y co

rrec

t? If

NO

, cor

rect

pro

blem

.

YES

Cer

tain

mod

els

have

a s

epar

ate

glo-

bar

igni

ter a

nd fl

ame r

od se

nsor

loca

ted

next

toth

e gl

o-ba

r. O

ther

mod

els

have

a g

lo-b

arig

nite

r onl

y, w

hich

act

s as

bot

h an

igni

ter

and

flam

e se

nsor

. D

oes m

odel

in q

uest

ion

have

glo

-bar

igni

tor o

nly?

YES

Doe

s th

e he

ater

sta

y on

until

cal

l for

hea

t end

s?YE

SNO

* Im

prop

er g

roun

ding

.*

Hig

h w

inds

.*

Taki

ng co

mbu

stio

n ai

rfr

om th

e atti

c.*

Dirt

y en

viro

nmen

t.*

Baf

fle n

ot lo

cate

dpr

oper

ly.

* Fl

uctu

atin

g ga

spr

essu

re.

The

follo

win

g ca

n ca

use

the

heat

er to

shu

t dow

n:

Trou

bles

hoot

ing

ends

.

NO

Exha

ust

pres

sure

sw

itch

may

be f

aulty

or

ther

e is

are

stric

tion

in th

eex

haus

t.

Che

ck to

mak

e su

re th

at th

epr

essu

re is

with

in m

inim

uman

d m

axim

um in

puts

asin

dica

ted

on A

GA

bur

ner

ratin

g la

bel.

Is g

as p

ress

ure

OK

? If

NO

, cor

rect

pro

blem

.

Doe

s th

e bu

rner

com

e on

and

then

turn

off

imm

edia

tely

(1 o

r 2 se

cond

s)?

Sens

ing

rod

is fa

ulty

or f

lam

e is

wea

k. C

heck

to m

ake s

ure h

eate

ris

ope

rati

ng a

t pr

oper

gas

pres

sure

as

indi

cate

d on

AG

Abu

rner

rat

ing

labe

l an

d th

enre

plac

e se

nsin

g ro

d if

need

ed.

Con

sult

fact

ory

for

prop

er p

arts

.

With

amm

eter

, che

ck am

pera

ge at

flam

e rod

.Is

it g

reat

er th

an 7

mic

ro am

ps?

Che

ck to

mak

e sur

efla

me s

enso

r wire

isO

K a

nd th

en re

plac

eci

rcui

t boa

rd.

YES

NO

YES

YES

NOYE

SNO

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

33

Page 34: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

106

212

83

68A

44

31B

122

33B

76

825

828

832

329

1502

1526

70

201

223

208

1541

1540

204

200

31B

303

9

304

125180

156

6

97 217

5

125017

1202

1

56C

NO

PS

218

19B

Emitt

er T

ube(

s)

V24

10

12

V55A V5

6AV2

3

V57A

Com

bust

ion

Cham

ber

220

1254

222

11

26A 12

89

21B

220

26B

1528

4321

1565

1530 24V

FUSE

TRANSFORMER

120V/230V

1526

1566

21B

65I

26A

V302

V301

1216

V303

105

20C

82

832

1527

34

5.3 Parts List

Tube Heater Vacuum SystemTube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

Page 35: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Parts List

35

HLV

SER

IES

PAR

TS L

ISTI

NG

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

TP#

ITEM

TP#

ITEM

TP-1

CO

NTR

OL

BO

X C

OV

ER

TP

-303

RIG

HT

EN

D P

AN

EL

TP-5

FLA

NG

E G

AS

KE

T

TP

-304

CO

NTR

OL

BO

X

TP-9

CO

ND

UIT

CO

UP

LIN

G

TP

-329

1/4"

NE

UTR

AL

TER

MIN

AL

BLO

CK

TP-1

0C

ON

DU

IT 4

" X 1

/2"

TP

-566

VE

NT

LIM

ITIN

G O

RIF

ICE

TP-1

1IG

NIT

OR

BO

X

TP-8

01C

EN

TER

PA

NE

LTP

-12

IGN

ITO

R B

OX

CO

VE

R

TP-8

2524

V IS

OLA

TIO

N R

ELA

Y B

OA

RD

TP-1

7S

IGH

T G

LAS

S K

ITTP

-828

OP

ER

ATI

ON

AL

IND

ICA

TOR

LIG

HTS

TP-1

9B4"

TU

BE

& R

EFL

EC

TOR

HA

NG

ER

W/ S

PR

ING

CLI

PTP

-832

THE

RM

OS

TAT

TER

MIN

AL

STR

IPTP

-20C

120"

RE

FLE

CTO

R

TP

-120

216

'' BU

RN

ER

TU

BE

WIT

H F

LAN

GE

TP-2

1BTU

BE

CLA

MP

TP

-121

6N

C-7

EX

HA

US

TER

PU

MP

TP-2

6A10

FT.

RA

DIA

NT

TUB

E S

TRA

IGH

TTP

-125

024

V IG

NIT

ER

TP

-26B

10 F

T. R

AD

IAN

T TU

BE

STR

AIG

HT

(AL-

TI)

TP-1

251

TRIT

ON

246

5H C

IRC

UIT

BO

AR

DTP

-31B

CO

NTR

OL

BO

X B

RA

CK

ET

TP-1

254

IGN

ITE

R G

AS

KE

TTP

-33B

1/2"

GA

S C

OC

K

TP

-125

5N

C-7

PU

MP

AS

SE

MB

LY W

/ ELE

CTR

ICA

L C

ON

TRO

L P

AN

EL

TP-4

4A

IR O

RIF

ICE

W/S

CR

EE

N -

CO

NS

ULT

FA

CTO

RY

TP-1

289

EX

HA

US

TER

MO

UN

TIN

G T

UB

E F

OR

NC

-7 P

UM

PTP

-56C

1/4"

PR

ES

SU

RE

TU

BE

- C

ON

SU

LT F

AC

TOR

YTP

-150

2H

LV L

EFT

EN

D P

AN

EL

TP-6

5I33

" IN

TER

LOC

KIN

G B

AFF

LETP

-152

675

VA

TR

AN

SFO

RM

ER

W/ F

OO

T M

OU

NTS

TP-6

8AS

TRA

IN R

ELI

EF

BU

SH

ING

TP

-152

724

V S

WIT

CH

ING

CO

NTR

OL

RE

LAY

TP-7

0C

ON

TRO

L B

OX

CO

VE

R G

AS

KE

T (P

ER

FO

OT)

TP-1

528

EX

HA

US

TER

PO

ST

PU

RG

E R

ELA

YTP

-76

RU

BB

ER

GR

OM

ME

T

TP-1

530

FUS

E H

OLD

ER

TP-8

2R

EFL

EC

TOR

CE

NTE

R S

UP

PO

RT

TP-1

540

36E

96-2

24 2

4V N

AT.

GA

S V

ALV

E -

1/2"

(20%

LO

W)

TP-8

3S

TAIN

LES

S S

TEE

L FL

EX

CO

NN

EC

TOR

TP-1

541

36E

96-2

26 2

4V L

P G

AS

VA

LVE

- 1/

2" (2

0% L

OW

)TP

-97

1/4"

X 1

/4" B

RA

SS

INT.

/EX

T. A

TMO

S. B

AR

B F

ITTI

NG

TP-1

565

8" X

8" E

LEC

TRIC

AL

BO

XTP

-105

RE

FLE

CTO

R E

ND

CA

P

TP-1

566

EX

HA

US

TER

CO

NTR

OL

PA

NE

L A

SS

EM

BLY

w/ E

lect

rical

Com

pone

nts

TP-1

06R

EFL

EC

TOR

CLI

P

TP-N

OP

SN

OR

M. O

PE

N D

IFFE

RE

NTI

AL

PR

ES

SU

RE

SW

ITC

HE

STP

-122

GA

SK

ET

FOR

AIR

OR

IFIC

E &

AIR

CO

LLA

R(T

P-6

1B)

N.O

. Diff

eren

tial P

ress

ure

Sw

itch

(50

TO 8

0MB

TU/H

)TP

-200

BU

RN

ER

(50

TO 1

00M

BTU

/H L

P G

AS

)(T

P-6

1E)

N.O

. Diff

eren

tial P

ress

ure

Sw

itch

(90

TO 1

25M

BTU

/H)

TP-2

01B

UR

NE

R (1

25 T

O 2

25 M

BTU

/H N

AT

OR

LP

GA

S)

(TP

-126

1A)

N.O

. Diff

eren

tial P

ress

ure

Sw

itch

(140

TO

180

MB

TU/H

)TP

-204

GA

S O

RIF

ICE

- C

ON

SU

LT F

AC

TOR

Y(T

P-1

061A

) N

.O. D

iffer

entia

l Pre

ssur

e S

witc

h (2

00 T

O 2

25M

BTU

/H)

TP-2

08"Z

" MO

UN

TIN

G B

RA

CK

ET

V

-23

ISO

LATI

ON

BO

OT

TP-2

121/

2" X

3" P

IPE

NIP

PLE

V

-24

WO

RM

GE

AR

CLA

MP

TP-2

17P

RE

SS

UR

E B

AR

B F

ITTI

NG

V-5

5A4"

AD

AP

TER

TP-2

18E

XH

AU

ST

PR

ES

SU

RE

TU

BE

(VIN

YL)

V-5

6A5"

AD

AP

TER

TP-2

20S

TAIN

. STL

. TU

BE

CLA

MP

(175

& 2

25 M

BTU

/H)

V-5

7A6"

AD

AP

TER

TP-2

22FL

AM

E R

OD

V-3

01P

B-8

PU

MP

ON

LYTP

-222

AFL

AM

E R

OD

WIR

EV

-302

PB

-9 P

UM

P O

NLY

TP-2

23G

AS

MA

NIF

OLD

V-3

03P

B-1

0A P

UM

P O

NLY

Page 36: HLV Series - F.J. Evans · HLV SERIES TUBE HEATER VACUUM SYSTEM LIOHLV- 1M-11/02 (MWG) CONSIGNES DE SÉCURITÉ Sivous sentez une odeur de gaz: 1. Ouvrez les fenêtres. 2. Ne touchez

Tube Heater Vacuum System Installation, Operation, Maintenance and Parts Manual

6. Limited Warranty

One-Year Limited Warranty. Radiant Tube Heaters covered in this manual, are warranted by Detroit Radiant ProductsCompany to the original user against defects in workmanship or materials under normal use for one year after date of purchase.Any part which is determined to be defective in material or workmanship and returned to an authorized service location, asDetroit Radiant Products Company designates, shipping costs prepaid, will be, as the exclusive remedy, repaired or replaced atDetroit Radiant Products Company’s option. For limited warranty claim procedures, see PROMPT DISPOSITION below. Thislimited warranty gives purchasers specific legal rights which vary from jurisdiction to jurisdiction.

Additional Limited Warranty. In addition to the above mentioned one-year warranty, Detroit Radiant Products Companywarrants the original purchaser five years on the combustion chamber, five years on aluminized steel radiant tubes (three yearson hot-rolled steel radiant tubes) and ten years on the stainless steel burner.

Limitation of Liability. To the extent allowable under applicable law, Detroit Radiant Products Company’s liability forconsequential and incidental damages is expressly disclaimed. Detroit Radiant Products Company’s liability in all events islimited to and shall not exceed the purchase price paid.

Warranty Disclaimer. Detroit Radiant Products Company has made a diligent effort to provide product information andillustrate the products in this literature accurately; however, such information and illustrations are for the sole purpose ofidentification, and do not express or imply a warranty that the products are merchantable, or fit for a particular purpose, or thatthe products will necessarily conform to the illustrations or descriptions. Except as provided below, no warranty or affirmationof fact, expressed or implied, other than as stated in the “LIMITED WARRANTY” above is made or authorized by Detroit RadiantProducts Company.

Product Suitability. Many jurisdictions have codes and regulations governing sales, construction, installation, and/or use ofproducts for certain purposes, which may vary from those in neighboring areas. While Detroit Radiant Products Companyattempts to assure that its products comply with as many codes, it cannot guarantee compliance, and cannot be responsiblefor how the product is installed or used. Before purchase and use of a product, review the product applications, and allapplicable national and local codes and regulations, and be sure that the product, installation, and use will comply with them.

Certain aspects of disclaimers are not applicable to consumer products: e.g., (a) some jurisdictions do not allow the exclusionor limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you: (b) also, somejurisdictions do not allow a limitation on how long an implied warranty lasts, consequently the above limitation may not apply toyou: and (c) by law, during the period of this limited warranty, any implied warranties of implied merchantability or fitness for aparticular purpose applicable to consumer products purchased by consumers, may not be excluded or otherwise disclaimed.

Prompt Disposition. Detroit Radiant Products Company will make a good faith effort for prompt correction or other adjustmentwith respect to any product which proves to be defective within limited warranty. For any product believed to be defective withinlimited warranty, first write or call dealer from whom the product was purchased. Dealer will give additional directions. If unableto resolve satisfactorily, write to Detroit Radiant Products Company at address below, giving dealer’s name, address, date andnumber of dealer’s invoice, and describe the nature of the defect. Title and risk of loss pass to buyer on delivery to commoncarrier. If product was damaged in transit to you file claim with carrier.

Registration. Register on-line at www.reverberray.com/warranty or mail or fax a completed copy of the manual insert cover.

Detroit Radiant Products Company.21400 Hoover Road Warren, MI 48089 U.S.A.

T. (586) 756-0950 F. (586) 756-2626

36

Limited Warranty