Upload
hamayoun-murtaza
View
218
Download
0
Embed Size (px)
Citation preview
7/27/2019 High Impedance Sformer Differential
1/6
HIGH IMPEDANCE BUS DIFFERENTIAL VS BIASED TRANSFORMER
DIFFERENTIAL
Operating times for diff protection, excluding breaker tripping time are generally of thefollowing order:
Transformer diff - 10 cycles
Busbar diff - 4 cyclesFeeder diff - 5 cycles
Modern relays act even faster
These operating times are practically independent of magnitude of fault current. Trip time
for transformer diff is a little longer to ensure that the relays do not operate incorrectlydue to initial transients.
LOW IMPEDANCE DIFF SCHEMES HIGH IMPEDANCE DIFF SCHEMES
Low impedance system (bias or unbias) -
current operated
High impedance system - voltage operated
CTs are much cheaper (Compare prices ofa 10P10 CT and a Class X CT).
low impedance refers to biased / percentage
differential relay.
high impedance utilizes a series resistor
with the overcurrent differential element
Main disadvantage of circulating current
protection using low impedance relays isthrough fault instability due to CT
saturation.
and the low cost, if used on asimple bus system. However withthe introduction of numerical
relays and their low CT burden aswell as their ability of measuringseveral feeder currents, a lowimpedance bus differentialprincipal could be applied onsimple busses also
High impedance bus differential relays are
used on most of the busses in North
America. The popularity can be explained
by the good performance of this scheme inrelation to CT saturation and the low cost,
if used on a simple bus system
Common advantages of all
7/27/2019 High Impedance Sformer Differential
2/6
low impedance bus protectionschemes are the ability to be able to use
CT's of different ratios on respectivebranch inputs and the fact that the same CT
used for the bus protection can be shared
with the feeder protection relay
The metrosil is there to prevent very high voltages occuring under heavy fault
conditions. These voltages would otherwise damage the CT, the relay, and the wiring.
The stabilising resistor in principle converts the current operated relay into a voltageoperated relay.
Highly recommended.
http://www.areva-td.com/servlet/ContentServer?page...
For older type of schemes:
Transformators: Low impedance diff (bias or unbias) over
the windings and high impedance diff (REF-protection) over
the windings and the neutral CT. REF stands for restricted
earth fault protection.
Busbars: High impedance diff in all the zones which include
different incomers and feeders. A typical zone can consist
out of an incomer and 4 feeders (15 CTs), which make a low
impedance diff circuit difficult.
http://www.areva-td.com/servlet/ContentServer?pagename=OpenMarket/Xcelerate/Render&c=AGF_Product&cid=1056536208199&rid=1018348589697&norid=truehttp://www.areva-td.com/servlet/ContentServer?pagename=OpenMarket/Xcelerate/Render&c=AGF_Product&cid=1056536208199&rid=1018348589697&norid=true7/27/2019 High Impedance Sformer Differential
3/6
Q: Where to use High & Low impedance differential protection? I want to know,
where should we use high impedance differential protection and where low
impedance should be used?What are the advantages & disadvantages of both schemes?
Ans: Please see thread 238-216247: High Impedance Differential protection
High Impedance:
Since it is having greater stability (during CT sat)for out of zone faults than lowimpedance version. Mainly used in Bus protection and Transformer (resistance grounded)
REF protection schemes. Low cost, simple design, easy testing, needs accurate CT and
wiring data to set the voltage setting. , there everything should be identical starting fromturns ratio. knee point voltage, winding resistance and exciting current. Hi Z is
traditionally used where there are numerous CT inputs to deal with, such as bus
differential. Ct's designed for HI protection will have higher knee point voltage whencompared to LI protection which will increase the cost of CT production. In my opinion
for new substation where CTs are identical High Impedance 87B, is the best solution.
However, in case of expansion or having different CTs low impedance should be use.Configuration, setup, and testing is much simpler with the Hi Z bus diff relaying.
High impedance relay use for 87B, 87REF, 87 shunt reactor, etc.
High impedance relays are much cheaper, simple design, and have been in service 10's ofyears.
All other relays are Low impedance type. Diff low impedance is used for 87T.
Low impedance:
Low stability for out of zone faults.
Mainly used in Bus Protection, Transformer, Generator and Motor Differential protection
schemes. Also with present day microprocessor based relays, Transformer REF schemescan have low impedance version too. In LI we can use different ratio Ct's but not in HI
Low Z was normally used for differential zones with two or three sets of CRTs, such as
transformers, generators and motors.I don't think any problem in using LI protection scheme for bus bar, For multiple bus
configuration we must go for LI protection, if we use HI protection, we have to switch
the CT circuit, which may lead to mal operation of protection if there is any failure in
switching, IF we use LI, only we have to give isolator input for bus selection, central unit
7/27/2019 High Impedance Sformer Differential
4/6
of BB protection will do the rest.
I don't agree with the others who are saying that HI will be stable during external faults
but not LI to counter this one we are using biased differential protection, how transformerbiased differential protection works, it has to be stable for external faults, same way LI
for bus bars also.
A good reference on the principles of busbar protection can also be found at
http://pm.geindustrial.com/FAQ/Documents/B30/GER-3984.pdf
Creepage Distance-Is it a Reliable Design Parameter?Thomas Johansson, Robert Axelsson, Sven Nord Ceram GroupIntroductionCreepage Distance(CD) has many advantages. It is easy to understand, visualise,
calculate and measure. A disadvantage is that it does not accurately predicting the
electrical performance of Insulators of various diameters. Even following IECstandards, the accuracy of the calculations are limited. The poorer performance,
under polluted conditions, of lager diameter versus smaller diameter Insulators,both designed in accordance with IEC standards, similar profiles and located in the
same position, indicates the need for more accurate design parameters than those
offered by CD.
7/27/2019 High Impedance Sformer Differential
5/6
3.11. Creepage DistanceThe shortest distance, or the sum of the shortest distances, along the contours of the externalsurfaces of the insulating parts of the insulator between those parts which normally have theoperating voltage between them.3.12. Specific Creepage Distance
The overall creepage distance of an insulator divided by the highest operating voltage acrossthe insulator. It is generally expressed in mm/kV.CE to check3.13. Dry Arcing DistanceThe shortest distance in air external to the insulator between those parts which normally have
the operating voltage between them.
7/27/2019 High Impedance Sformer Differential
6/6