T Hazardous areas guide Dust groups IIIA Combustible flyings IIIB Non-conductive dust IIIC Conductive dust Gas groups IIA e.g. Propane IIB e.g. Etyhlene IIC e.g. Hydrogen ZONE 1 ZONE 2 ZONE 0 ZONE 1 ZONE 0 PETROLEUM ZONE 21 ZONE 22 ZONE 20 Equipment group acc. to directive 2014/34/EU Equipment category acc. to directive 2014/34/EU Classification of hazardous areas acc. to directive 1999/92/EG Group acc. to IEC/EN60079-0 Combustible materials Equipment protection level (EPL acc. to IEC/EN 60079-0) I Mining M1 very high level of protection; remain functional at occurrence of Ex-atmosphere I Methane, Carbon dust Ma I M2 high level of protection; de-energized at occurrence of Ex-atmosphere I Mb II Other industries (except mining) 1 very high level of protection; save even in an event of rare incidents 0 II Gases, Vapours, Mists (G) Ga II 2 high level of protection; save even in an event of predictable failures 1 II Gb II 3 normal level of protection; save during normal operation 2 II Gc II Other industries (except mining) 1 very high level of protection; save even in an event of rare incidents 20 III Dust (D) Da II 2 high level of protection; save even in an event of predictable failures 21 III Db II 3 normal level of protection; save during normal operation 22 III Dc Area classification Types of protection for electrical equipment in explosive gas atmospheres Type of protection Symbol Main application Norm increased safety eb junction boxes, control stations for installing Ex-components (with a different type of protection), squirrel-cage motors, light fittings IEC 60079-7 EN 60079-7 ISA 60079-7 flameproof enclosures db switchgears, control stations, indicating equipment, control systems, motors, transformers, heating equipment, light fittings IEC 60079-1 EN 60079-1 ISA 60079-1 pressurized enclosures pxb pyb pzc switchgear and control cabinets, analysers, large motors IEC 60079-2 EN 60079-2 ISA 60079-2 intrinsic safety ia ib ic instrumentation technology, fieldbus technology, sensors, actuators [Ex ib] = associated electrical apparatus – installation in the safe area IEC 60079-11 EN 60079-11 ISA 60079-11 intrinsically safe systems IEC 60079-25 EN 60079-25 FISCO: fieldbus intrinsically-safe concept IEC 60079-27 EN 60079-27 ISA 60079-27 oil immersion ob transformers, starting resistors IEC 60079-6 EN 60079-6 ISA 60079-6 powder filling qb sensors, display units, electronic ballasts, transmitters IEC 60079-5 EN 60079-5 ISA 60079-5 encapsulation ma mb mc switchgear with small capacity, control and signalling units, display units, sensors IEC 60079-18 EN 60079-18 ISA 60079-18 type of protection “n” nAc nCc nRc all electrical equipment for Zone 2 nA = non-sparking device nC = sparking devices and components nL = energy limited apparatus nR = restricted breathing enclosures IEC 60079-15 EN 60079-15 ISA 60079-15 optical radiation op_a op_b op_c op is = inherently safe optical radiation op pr = protected optical radiation op sh = optical radiation interlock IEC 60079-28 EN 60079-28 Types of Protection Types of protection for electrical equipment in explosive dust atmospheres Type of protection Symbol Main application Norm protection by enclosures ta tb tc switchgear, control stations, junction boxes, control boxes, motors, light fittings IEC 60079-31 EN 60079-31 ISA 60079-31 pressurization pb pc switchgear and control cabinets, motors IEC 60079-2 EN 60079-2 ISA 60079-2 intrinsic safety ia ib ic instrumentation technology, fieldbus technology, sensors, actuators [Ex ib] = associated electrical apparatus – installation in the safe area IEC 60079-11 EN 60079-11 ISA 60079-11 encapsulation ma mb mc switchgear with small capacity, control and signalling units, display units, sensors IEC 60079-18 EN 60079-18 ISA 60079-18 \ T è ê é í Certifications worldwide Protection against ingress of external particle matter (1st digit) Digit 0 No protection 1 Protection against ingress of large solid bodies with diameter > 50 mm. (Protection to prevent dangerous parts being touched with the back of the hand.) 2 Protection against ingress of large solid bodies with diameter > 12.5 mm. (Protection to prevent dangerous parts being touched with the fingers.) 3 Protection against ingress of large solid bodies with diameter > 2.5 mm. (Protection to prevent dangerous parts being touched with a tool.) 4 Protection against ingress of large solid bodies with diameter > 1 mm. (Protection to prevent dangerous parts being touched with a piece of wire.) 5 Protection against harmful deposits of dust, which cannot enter in an amount sufficient to interfere with satisfactory operation. 6 Complete protection against ingress of dust. The class of protection is indicated by a code consisting of the two letters IP and two digits representing the class of protection according to IEC/EN 60529 IP class of protection to (IEC/EN 60529) Example: IP66 2nd digit: protection from liquids 1st digit: protection from solid bod Protection against penetration of liquids (2nd digit) Digit 0 No protection 1 Protection against drops of condensed water falling vertically. 2 Protection against drops of liquid falling at an angle of 15° with respect to the vertical. 3 Protection against drops of liquid falling at an angle of 60° with respect to the vertical. 4 Protection against liquids splashed from any direction. 5 Protection against water jets projected by a nozzle from any direction. 6 Protection against strong jets of water 7 1 m Protection against immersion in water under defined conditions of pressure and time. 8 Protection against indefinite immersion in water under defined conditions of pressure (which must be agreed between manufacturer and user and must be more adverse than number 7). 9K Protected against close-range high pressure, high temperature spray downs. Smaller specimens rotate slowly on a turntable, from 4 specific angles. Larger specimens are mounted upright, no turntable required, and are tested freehand for at least 3 minutes at distance of 0.15–0.2 m. There are specific requirements for the nozzle used for the testing. Definition of the protection degrees according to NEMA/UL Type 1 Enclosure predominately for indoor use. Protection against penetration by solid foreign bodies. 2 Enclosure predominately for indoor use. Protection against penetration by solid foreign bodies and water. 3 Enclosure predominately for indoor use. Protection against penetration by rainfall and dust as well as damage due to ice formation. 3R Enclosure predominately for indoor use. Protection against rain and snow as damage due to ice-formation. 3S Enclosure predominately for indoor use. Protection against rain, snow and foreign bodies. External mechanisms can be operated despite ice accumulation. 4 Enclosure for indoor or outdoor use. Protection against rain, foreign bodies, splashing water and hose water as well as damage due to ice-formation on the outside of the enclosure. 4X Enclosure for indoor or outdoor use. Protection against corrosion, rain, foreign bodies, splashing water and hose water as well as damage due to ice-formation on the outside of the enclosure. 6 Enclosure for indoor or outdoor use. Protection against hose water as well as against penetration by water during immersion; protection damage due to ice formation on the outside of the enclosure. 12 Enclosure for indoor use. Protection against dust accumulation, foreign bodies and non-corrosive drops of liquids. 13 Enclosure for indoor use. Protection against dust build- up, splashing water, oil, and non-corrosive coolants. Protection degree NEMA/UL Protection degree IEC/EN ç [V] [A] [mm²] 20 °C ... + 55 °C IP 66 600 21 4 Klingenbergstr. 16 – D 32758 Detmold _____________________________________________________ 4x T amb: - Cable size: Weidmüller Interface GmbH & Co. KG Type: P/N: S/N: Year of Construction: W A R N I N G - DO NOT OPEN WHEN ENERGIZED Klippon TB MH 303020 NEMA TYPE: 9876543219 2018 Class I Zone 1 AEx e IIC T4 Gb E223792 Rated voltage: Rated current: XA-DE-A-0000 Juncition Box for HAZ. LOC. Hexagon Ex for ATEX Group Mining or Not Mining Equipment Group G = Gas D=Dust Ex = Explosion Protection Kind of protection Protection Level Gas/Dust Group T-Class / Max. Surface temperature Dust T-Class No. G=Gas D=Dust EPL Equipment Protection Lavel application T II 2 G Ex i a IIC T 4 G b T II 1 D Ex t a IIIC 135 °C D a W A R N I N G - DO NOT OPEN WHEN ENERGIZED Weidmüller Interface GmbH & Co. KG Klingenbergstr. 16 – D 32758 Detmold % 0344 Type: Klippon TB MH 303020 P/N: 9876543219 S/N: XA-DE-A-0000 Year of Construction: 2018 IP 66 Rated voltage: 600 [V] Rated current: 21 [A] Cable size: 4 [mm²] T amb: - 20 °C ... + 55 °C IBExU14ATEX1050 II 2G Ex eb IIC T4 Gb IECEx IBE 14.0013 Ex eb IIC T4 Gb _____________________________________________________ Certification conditions and logo Part designation Name and address of manufacturer Year of Contruction IP ingress protection class Ambient temperature Part No. Serial number Ex marking Approval number Approval number Weidmüller Interface GmbH & Co. KG Klingenbergstraße 16 32758 Detmold, Germany T +49 5231 14-0 F +49 5231 14-292083 www.weidmueller.com Personal support can be found on our website: www.weidmueller.com/contact Type label for enclosure assemblies Classification of the maximum surface temperatures into temperature classes for eletrical equipment of group II Temperature class ATEX/IECEx Temperature class NEC/UL (AEx) Maximum surface temperature T1 T1 450 °C 842 °F T2 T2 300 °C 572 °F T2A 280 °C 536 °F T2B 260 °C 500 °F T2C 230 °C 446 °F T2D 215 °C 419 °F T3 T3 200 °C 392 °F T3A 180 °C 356 °F T3B 165 °C 329 °F T3C 160 °C 320 °F T4 T4 135 °C 275 °F T4A 120 °C 248 °F T5 T5 100 °C 212 °F T6 T6 85 °C 185 °F IEC/DIN EN 60079-0 NEC500ff °C °F Temperature class Made in Germany Order number: 2654330000/01/2019/SMB

Hazardous areas guide - Weidmüller

  • Upload
    others

  • View
    4

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Hazardous areas guide - Weidmüller

T Hazardous areas guide

Dust groups

IIIA Combustible flyings

IIIB Non-conductivedust

IIIC Conductive dust

Gas groups

IIA e.g. Propane

IIB e.g. Etyhlene

IIC e.g. Hydrogen

ZONE 1

ZONE 2

ZONE 0

ZONE 1

ZONE 0PETROLEUM

ZONE 21

ZONE 22

ZONE 20

Equi

pmen

t gro

upac

c. to

dire

ctiv

e 20

14/3

4/EU

Equi

pmen

t cat

egor

yac

c. to

dire

ctiv

e 20

14/3

4/EU

Clas

sific

atio

n of

haz

ardo

us

area

s ac

c. to

dire

ctiv

e 19

99/9

2/EG

Gro

upac

c. to

IEC/

EN60

079-

0

Com

bust

ible

mat

eria

ls

Equi

pmen

t pro

tect

ion

leve

l (E

PL a

cc. t

o IE

C/EN

600

79-0

)

I

Mining

M1very high level of protection; remainfunctional at occurrence ofEx-atmosphere

IMethane,Carbon dust

Ma

I M2 high level of protection; de-energizedat occurrence of Ex-atmosphere I Mb

II

Otherindustries(exceptmining)

1 very high level of protection; saveeven in an event of rare incidents 0 II

Gases,Vapours,Mists(G)

Ga

II 2 high level of protection; save even inan event of predictable failures 1 II Gb

II 3 normal level of protection; saveduring normal operation 2 II Gc

II

Otherindustries(exceptmining)

1very high level of protection;save even in an event of rareincidents

20 III

Dust(D)

Da

II 2high level of protection;save even in an event of predictablefailures

21 III Db

II 3 normal level of protection;save during normal operation 22 III Dc

Area classificationTypes of protection for electrical equipmentin explosive gas atmospheres

Type ofprotection

Symbol Main application Norm

increasedsafety

eb junction boxes, control stations for installing Ex-components (with a different type of protection), squirrel-cage motors, light fittings

IEC 60079-7EN 60079-7ISA 60079-7

flameproofenclosures

db switchgears, control stations, indicating equipment, control systems, motors, transformers, heating equipment, light fittings

IEC 60079-1EN 60079-1ISA 60079-1

pressurizedenclosures

pxbpybpzc

switchgear and control cabinets, analysers, large motors

IEC 60079-2EN 60079-2ISA 60079-2

intrinsic safety iaibic

instrumentation technology, fieldbus technology, sensors, actuators [Ex ib] = associated electrical apparatus – installation in the safe area

IEC 60079-11EN 60079-11ISA 60079-11

intrinsically safe systems IEC 60079-25EN 60079-25

FISCO: fieldbus intrinsically-safe concept IEC 60079-27EN 60079-27ISA 60079-27

oil immersion ob transformers, starting resistors IEC 60079-6EN 60079-6ISA 60079-6

powder filling qb sensors, display units, electronic ballasts,transmitters

IEC 60079-5EN 60079-5ISA 60079-5

encapsulation mambmc

switchgear with small capacity, control andsignalling units, display units, sensors

IEC 60079-18EN 60079-18ISA 60079-18

type of protection“n”

nAcnCcnRc

all electrical equipment for Zone 2nA = non-sparking devicenC = sparking devices and componentsnL = energy limited apparatusnR = restricted breathing enclosures

IEC 60079-15EN 60079-15ISA 60079-15

optical radiation op_aop_bop_c

op is = inherently safe optical radiationop pr = protected optical radiationop sh = optical radiation interlock

IEC 60079-28EN 60079-28

Types of Protection Types of protection for electrical equipment in explosive dust atmospheres

Type ofprotection

Symbol Main application Norm

protection byenclosures

tatbtc

switchgear, control stations, junction boxes,control boxes, motors, light fittings

IEC 60079-31EN 60079-31ISA 60079-31

pressurization pbpc

switchgear and control cabinets, motors IEC 60079-2EN 60079-2ISA 60079-2

intrinsic safety iaibic

instrumentation technology,fieldbus technology, sensors, actuators[Ex ib] = associated electrical apparatus– installation in the safe area

IEC 60079-11EN 60079-11ISA 60079-11

encapsulation mambmc

switchgear with small capacity, control andsignalling units, display units, sensors

IEC 60079-18EN 60079-18ISA 60079-18

\ T è ê

é í

Certifications worldwide

Protection against ingress of external particle matter (1st digit)

Digit0 No protection

1 Protection against ingress of large solid bodies with diameter > 50 mm. (Protection to prevent dangerous parts being touched with the back of the hand.)

2 Protection against ingress of large solid bodies with diameter > 12.5 mm. (Protection to prevent dangerous parts being touched with the fingers.)

3 Protection against ingress of large solid bodies with diameter > 2.5 mm. (Protection to prevent dangerous parts being touched with a tool.)

4 Protection against ingress of large solid bodies with diameter > 1 mm. (Protection to prevent dangerous parts being touched with a piece of wire.)

5 Protection against harmful deposits of dust, which cannot enter in an amount sufficient to interfere with satisfactory operation.

6 Complete protection against ingress of dust.

The class of protection is indicated bya code consisting of the two letters IPand two digits representing the class ofprotection according to IEC/EN 60529

IP class of protection to (IEC/EN 60529)Example:

IP66 2nd digit: protection from liquids 1st digit: protection from solid bod

Protection against penetration of liquids (2nd digit)

Digit0 No protection

1 Protection against drops of condensed water falling vertically.

2 Protection against drops of liquid falling at an angle of 15° with respect to the vertical.

3 Protection against drops of liquid falling at an angle of 60° with respect to the vertical.

4 Protection against liquids splashed from any direction.

5 Protection against water jets projected by a nozzle from any direction.

6 Protection against strong jets of water

7

1 m

Protection against immersion in water under defined conditions of pressure and time.

8 Protection against indefinite immersion in water under defined conditions of pressure (which must be agreed between manufacturer and user and must be more adverse than number 7).

9K Protected against close-range high pressure, high temperature spray downs. Smaller specimens rotate slowly on a turntable, from 4 specific angles. Larger specimens are mounted upright, no turntable required, and are tested freehand for at least 3 minutes at distance of 0.15–0.2 m. There are specific requirements for the nozzle used for the testing.

Definition of the protection degrees according to NEMA/UL

Type1 Enclosure predominately for indoor use. Protection

against penetration by solid foreign bodies.

2 Enclosure predominately for indoor use. Protection against penetration by solid foreign bodies and water.

3 Enclosure predominately for indoor use. Protection against penetration by rainfall and dust as well as damage due to ice formation.

3R Enclosure predominately for indoor use. Protection against rain and snow as damage due to ice-formation.

3S Enclosure predominately for indoor use. Protection against rain, snow and foreign bodies. External mechanisms can be operated despite ice accumulation.

4 Enclosure for indoor or outdoor use. Protection against rain, foreign bodies, splashing water and hose water as well as damage due to ice-formation on the outside of the enclosure.

4X Enclosure for indoor or outdoor use. Protection against corrosion, rain, foreign bodies, splashing water and hose water as well as damage due to ice-formation on the outside of the enclosure.

6 Enclosure for indoor or outdoor use. Protection against hose water as well as against penetration by water during immersion; protection damage due to ice formation on the outside of the enclosure.

12 Enclosure for indoor use. Protection against dust accumulation, foreign bodies and non-corrosive drops of liquids.

13 Enclosure for indoor use. Protection against dust build-up, splashing water, oil, and non-corrosive coolants.

Protection degree NEMA/UL Protection degree IEC/EN

ç

[V][A]

[mm²]20 °C ... + 55 °C

IP 66

60021

4

Klingenbergstr. 16 – D 32758 Detmold

_____________________________________________________

4x

T amb: -Cable size:

Weidmüller Interface GmbH & Co. KG

Type:P/N:S/N:

Year of Construction:

W A R N I N G - DO NOT OPEN WHEN ENERGIZED

Klippon TB MH 303020

NEMA TYPE:

9876543219

2018

Class I Zone 1 AEx e IIC T4 Gb

E223792

Rated voltage:Rated current:

XA-DE-A-0000

Juncition Box for HAZ. LOC.

Hex

agon

Ex

for A

TEX

Gro

up M

inin

g or

Not

Min

ing

Equi

pmen

t Gro

up

G =

Gas

D=D

ust

Ex =

Exp

losi

on P

rote

ctio

n

Kind

of p

rote

ctio

n

Prot

ectio

n Le

vel

Gas

/Dus

t Gro

up

T-Cl

ass

/ Max

. Sur

face

tem

pera

ture

Dus

t

T-Cl

ass

No.

G=G

as D

=Dus

t

EPL

Equi

pmen

t Pro

tect

ion

Lave

l app

licat

ion

T II 2 G Ex i a IIC T 4 G bT II 1 D Ex t a IIIC 135 °C D a

W A R N I N G - DO NOT OPEN WHEN ENERGIZED

Weidmüller Interface GmbH & Co. KGKlingenbergstr. 16 – D 32758 Detmold

%0344

Type: Klippon TB MH 303020P/N: 9876543219S/N: XA-DE-A-0000Year of Construction: 2018

IP 66

Rated voltage: 600 [V]

Rated current: 21 [A]Cable size: 4 [mm²]

T amb: - 20 °C ... + 55 °C

IBExU14ATEX1050II 2G Ex eb IIC T4 Gb

IECEx IBE 14.0013Ex eb IIC T4 Gb _____________________________________________________

Certification conditions and logo

Part designation

Name and address of manufacturer

Year of Contruction

IP ingress protection class

Ambient temperature

Part No.Serial number

Ex marking

Approval number

Approval number

Weidmüller Interface GmbH & Co. KGKlingenbergstraße 1632758 Detmold, GermanyT +49 5231 14-0F +49 5231 14-292083www.weidmueller.com

Personal support canbe found on our website:www.weidmueller.com/contact

Type label for enclosure assemblies

Classification of the maximum surface temperatures into temperature classes for eletrical equipment of group IITemperature class ATEX/IECEx

Temperature classNEC/UL (AEx)

Maximum surface temperature

T1 T1 450 °C 842 °FT2 T2 300 °C 572 °F

T2A 280 °C 536 °FT2B 260 °C 500 °FT2C 230 °C 446 °FT2D 215 °C 419 °F

T3 T3 200 °C 392 °FT3A 180 °C 356 °FT3B 165 °C 329 °FT3C 160 °C 320 °F

T4 T4 135 °C 275 °FT4A 120 °C 248 °F

T5 T5 100 °C 212 °FT6 T6 85 °C 185 °FIEC/DIN EN 60079-0 NEC500ff °C °F

Temperature class

Made in Germany

Order number: 2654330000/01/2019/SMB

Page 2: Hazardous areas guide - Weidmüller

T Leitfaden für explosionsgefährdete Bereiche

Bedingungen in explosionsgefährdeten Bereichen Zündschutzarten für elektrische Geräte in gasexplosionsgefährdeten Bereichen

Schutzart Symbol Hauptanwendung Norm

erhöhte Sicherheit

eb Klemmen und Anschlusskästen, Steuerkästen zum Einbau von Ex-Bauteilen (die in einer anderen Zündschutzart geschützt sind), Käfigläufermotoren, Leuchten

IEC 60079-7EN 60079-7ISA 60079-7

druckfeste Kapselung

db Schaltgeräte und Schaltanlagen, Befehlsund Anzeigegeräte, Steuerungen, Motoren, Transformatoren, Heizgeräte, Leuchten

IEC 60079-1EN 60079-1ISA 60079-1

Überdruck-kapselung

pxbpybpzc

Schalt- und Steuerschränke, Analysegeräte, große Motoren

IEC 60079-2EN 60079-2ISA 60079-2

Eigensicherheit iaibic

Mess- und Regeltechnik, Feldbustechnik, Sensoren, Aktoren [Ex ib] = zugehöriges elektrisches Betriebsmittel – Installation im sicheren Bereich

IEC 60079-11EN 60079-11ISA 60079-11

Eigensichere Systeme IEC 60079-25EN 60079-25

FISCO: Eigensichere Feldbussysteme IEC 60079-27EN 60079-27ISA 60079-27

Ölkapselung ob Transformatoren, Anlasswiderstände IEC 60079-6EN 60079-6ISA 60079-6

Sandkapselung qb Sensoren, Anzeigegeräte, elektronische Vorschaltgeräte, Transmitter

IEC 60079-5EN 60079-5ISA 60079-5

Vergusskapselung mambmc

Schaltgeräte für kleine Leistungen, Befehls- und Meldegeräte, Anzeigegeräte, Sensoren

IEC 60079-18EN 60079-18ISA 60079-18

Zündschutz art „n“ nAcnCcnRc

Alle elektrischen Betriebsmittel für Zone 2nA = nichtfunkende BetriebsmittelnC = funkende Betriebsmittel, in denen

die Kontakte in geeig neter Weise geschützt sind

nL = energiebegrenzte BetriebsmittelnR = schwadensichere Gehäuse

IEC 60079-15EN 60079-15ISA 60079-15

optischeStrahlung

op_aop_bop_c

op is = eigensichere optische Strahlungop pr = geschützte optische Strahlungop sh = Sperrung optischer Strahlung

IEC 60079-28EN 60079-28

Zündschutzarten Zündschutzarten für elektrische Geräte in staubexplosionsgefährdeten Bereichen

Type ofprotection

Symbol Main application Norm

Schutz durch Gehäuse

tatbtc

Schaltgeräte und Schaltanlagen, Steuer-, Anschluss- und Klemmenkästen, Motoren, Leuchten

IEC 60079-31EN 60079-31ISA 60079-31

Überdruck-kapselung

pbpc

Schalt- und Steuerschränke, Motoren IEC 60079-2EN 60079-2ISA 60079-2

Eigensicherheit iaibic

Mess- und Regeltechnik, Feldbustechnik, Sensoren, Aktoren [Ex ib] = zugehöriges elektrisches Betriebs-mittel – Installation im sicheren Bereich

IEC 60079-11EN 60079-11ISA 60079-11

Vergusskapselung mambmc

Schaltgeräte für kleine Leistungen, Befehls- und Meldegeräte, Anzeigegeräte, Sensoren

IEC 60079-18EN 60079-18ISA 60079-18

\ T è ê

é í

Zertifizierungen weltweit

Schutzgrade gegen feste Fremdkörper (1. Ziffer)

Kennziffer0 Nicht geschützt

1 Geschützt gegen feste Fremdkörper 50 mm Durchmesser und größer. Geschützt gegen den Zugang zu gefährlichen Teilen mit dem Handrücken.

2 Geschützt gegen feste Fremd körper 12,5 mm Durchmesser und größer. Geschützt gegen den Zugang zu gefährlichen Teilen mit dem Finger.

3 Geschützt gegen feste Fremdkörper 2,5 mm Durchmesser und größer. Geschützt gegen den Zugang zu gefährlichen Teilen mit einem Werkzeug.

4 Geschützt gegen feste Fremdkörper 1 mm Durchmesser und größer. Geschützt gegen den Zugang zu gefährlichen Teilen mit einem Draht.

5 Staubgeschützt, Eindringen von Staub ist nicht vollständig verhindert, aber Staub darf nicht in einer solchen Menge eindringen, dass das zufrieden stellende Arbeiten des Gerätes oder die Sicherheit beeinträchtigt wird.

6 Staubdicht, kein Eindringen von Staub.

Die Schutzarten werden nach IEC/EN 60529 durch ein Kurz zeichen angegeben, das sich aus zwei stets gleich bleibenden Kennbuchstaben IP und den zwei Kennziffern für den Schutzgrad zusammensetzt.

IP-Schutzarten nach IEC/EN 60529Bespiel:

IP66 2. Ziffer: Schutz gegen Wasser 1. Ziffer: Schutz gegen feste Körper

Schutzgrade gegen Wasser (2. Ziffer)Kennziffer0 Nicht geschützt

1 Senkrecht fallende Tropfen dürfen keine schädliche Wirkung haben.

2 Senkrecht fallende Tropfen dürfen keine schädliche Wirkung haben, wenn das Gehäuse um einen Winkel bis zu 15° beiderseits der Senkrechten geneigt ist.

3 Wasser, das in einem Winkel bis zu 60° beiderseits der Senkrechten gesprüht wird, darf keine schädliche Wirkungen haben.

4 Wasser, das aus jeder Richtung gegen das Gehäuse spritzt, darf keine schädliche Wirkung haben.

5 Wasser, das aus jeder Richtung als Strahl gegen das Gehäuse gerichtet ist, darf keine schädlichen Wirkungen haben.

6 Wasser, das aus jeder Richtung als starker Strahl gegen das Gehäuse gerichtet ist, darf keine schädlichen Wirkungen haben.

7

1 m

Wasser darf nicht in einer Menge eintreten, die schädliche Wirkungen verursacht, wenn das Gehäuse unter genormten Druck- und Zeitbedingungen zeitweilig in Wasser getaucht wird.

8 Wasser darf nicht in einer Menge eintreten, die schädliche Wirkungen verursacht, wenn das Gehäuse dauernd unter Wasser getaucht ist unter Bedingungen, die zwischen Hersteller und Anwender vereinbart werden müssen. Die Bedingungen müssen jedoch schwieriger sein als unter Kennziffer 7.

9K Schutz gegen Eindringen von Wasser bei Hochdruck-/Dampfstrahlreinigung. Kleinere Prüflinge drehen sich langsam auf einem Drehtisch, aus 4 spezifischen Winkeln. Größere Prüflinge werden aufrecht montiert. Hierzu ist kein Drehtisch erforderlich. Die Prüflinge werden dann mindestens 3 Minuten freihändig in einem Abstand von 0,15–0,2 m geprüft. Es gibt spezifische Anforderungen an die Düse, die für die Prüfung verwendet wird.

Definition der Schutzarten nach NEMA/UL

Typ1 Gehäuse zum überwiegenden Einsatz in Innenräumen.

Schutz gegen das Eindringen fester Fremdkörper.

2 Gehäuse zum überwiegenden Einsatz in Innenräumen. Schutz gegen das Eindringen fester Fremdkörper und Wasser.

3 Gehäuse zum überwiegenden Einsatz in Innenräumen. Schutz gegen das Eindringen von Niederschlag und Staub sowie gegen Schäden durch Eisbildung.

3R Gehäuse zum überwiegenden Einsatz in Innenräumen. Schutz gegen Regen und Schnee sowie gegen Schäden durch Eisbildung.

3S Gehäuse zum überwiegenden Einsatz in Innenräumen. Schutz gegen Regen, Schnee und Fremdkörper. Externe Mechanismen können trotz Eisablagerung bedient werden.

4 Gehäuse für Innen- oder Außenräume. Schutz gegen Regen, Fremdkörper, Spritzwasser und Strahlwasser sowie gegen Schäden durch Eisbildung an der Außenseite des Gehäuses.

4X Gehäuse für Innen- oder Außenräume. Schutz gegen Korrosion, Regen, Fremdkörper, Spritzwasser und Strahlwasser sowie gegen Schäden durch Eisbildung an der Außenseite des Gehäuses.

6 Gehäuse für Innen- oder Außenräume. Schutz gegen Strahlwasser sowie gegen das Eindringen von Wasser beim Eintauchen; Schutz gegen Schäden durch Eisbildung an der Außenseite des Gehäuses.

12 Gehäuse für den Einsatz in Innenräumen. Schutz gegen Staubablagerung, Fremdkörper und nichtkorrodierende tropfende Flüssigkeiten.

13 Gehäuse für den Einsatz in Innenräumen. Schutz gegen Staubablagerung, Sprühwasser, Öl und nicht-korrodierende Kühlmittel.

Schutzart NEMA Schutzart IEC/EN

ç

[V][A]

[mm²]20 °C ... + 55 °C

IP 66

60021

4

Klingenbergstr. 16 – D 32758 Detmold

_____________________________________________________

4x

T amb: -Cable size:

Weidmüller Interface GmbH & Co. KG

Type:P/N:S/N:

Year of Construction:

W A R N I N G - DO NOT OPEN WHEN ENERGIZED

Klippon TB MH 303020

NEMA TYPE:

9876543219

2018

Class I Zone 1 AEx e IIC T4 Gb

E223792

Rated voltage:Rated current:

XA-DE-A-0000

Juncition Box for HAZ. LOC.

Hex

agon

Ex

für A

TEX

Gru

ppe

„Ber

gbau

“ ode

r „Ke

in B

ergb

au“

Ger

äteg

rupp

e

G=G

as, D

ämpf

e, N

ebel

/ D

=Stä

ube

Ex =

Exp

losi

onss

chut

z

Schu

tzar

t

Schu

tzgr

ad

Gas

-/Sta

ubgr

uppe

T-Kl

asse

/ M

ax. H

autte

mpe

ratu

r, St

aub

T-Kl

asse

n-N

r.

G=G

as, D

ämpf

e, N

ebel

/ D

=Stä

ube

EPL

= G

erät

esch

utzn

ivea

u de

r Anw

endu

ng

T II 2 G Ex i a IIC T 4 G bT II 1 D Ex t a IIIC 135 °C D a

W A R N I N G - DO NOT OPEN WHEN ENERGIZED

Weidmüller Interface GmbH & Co. KGKlingenbergstr. 16 – D 32758 Detmold

%0344

Type: Klippon TB MH 303020P/N: 9876543219S/N: XA-DE-A-0000Year of Construction: 2018

IP 66

Rated voltage: 600 [V]

Rated current: 21 [A]Cable size: 4 [mm²]

T amb: - 20 °C ... + 55 °C

IBExU14ATEX1050II 2G Ex eb IIC T4 Gb

IECEx IBE 14.0013Ex eb IIC T4 Gb _____________________________________________________

Zulassungsumgebung und Logo

Artikelbezeichnung

Name und Anschrift des Herstellers

Baujahr

IP Schutzart

Umgebungstemperatur

ArtikelnummerSeriennummer

Ex Kennzeichnung

Zulassungsnummer

Zulassungsnummer

Weidmüller Interface GmbH & Co. KGKlingenbergstraße 1632758 Detmold, GermanyT +49 5231 14-0F +49 5231 14-292083www.weidmueller.de

Persönlichen Support finden Sie im Internet unter:www.weidmueller.de/kontakt

Made in Germany

Bestellnummer: 2654330000/01/2019/SMB

Typenschild für assemblierte Gehäuse

Einteilung der maximalen Oberflächentemperaturen in Klassen bei elektrischen Geräten der Gruppe IITemperaturklasse ATEX/IECEx

TemperaturklasseNEC/UL (AEx)

Maximale Ober- flächentemperatur

T1 T1 450 °C 842 °FT2 T2 300 °C 572 °F

T2A 280 °C 536 °FT2B 260 °C 500 °FT2C 230 °C 446 °FT2D 215 °C 419 °F

T3 T3 200 °C 392 °FT3A 180 °C 356 °FT3B 165 °C 329 °FT3C 160 °C 320 °F

T4 T4 135 °C 275 °FT4A 120 °C 248 °F

T5 T5 100 °C 212 °FT6 T6 85 °C 185 °FIEC/DIN EN 60079-0 NEC500ff °C °F

Temperaturklasse

Staubgruppen

IIIA z. B. brennbare Flusen

IIIB z. B. nicht leitfähigen Staub

IIIC leitfähigen Staub

Gasgruppen

IIA z. B. Propan

IIB z. B. Etyhlen

IIC z. B. Wasserstoff

ZONE 1

ZONE 2

ZONE 0

ZONE 1

ZONE 0PETROLEUM

ZONE 21

ZONE 22

ZONE 20

Ger

äteg

rupp

ena

ch R

L 20

14/3

4/EU

Ger

ätek

ateg

orie

nach

RL

2014

/34/

EU

Zone

nein

teilu

ng

nach

RL

1999

/92/

EG

Gru

ppe

nach

IEC/

EN60

079-

0

Bre

nnba

re S

toff

e

Ger

ätes

chut

zniv

eau

(E

PL n

ach

IEC/

EN 6

0079

-0)

I

Bergbau

M1Hohes Schutzniveau; Geräte müssen bei vorhandener explosionsfähiger Atmosphäre weiter betrieben werden können

IMethan, Kohlestaub

Ma

I M2Hohes Schutzniveau; beim Auftreten einer explosionsfähigen Atmosphäre müssen die Produkte abgeschaltet werden können

I Mb

II

Andere Industrien (außer Bergbau)

1Sehr hohes Schutzniveau; Geräte gewährleisten bei selten auftretenden Gerätestörungen das erforderliche Maß an Sicherheit

0 II

Gase, Dämpfe, Nebel (G)

Ga

II 2Hohes Schutzniveau; Geräte gewährleisten selbst bei üblicherweise auftretenden Geräte-störungen das erforderliche Maß an Sicherheit

1 II Gb

II 3Normales Schutzniveau; Geräte gewährleisten bei normalem Betrieb das erforderliche Maß an Sicherheit

2 II Gc

II

Andere Industrien (außer Bergbau)