CONTENTS
Chapter 1 Outline of GM8 Series 3
Chapter 2
Improvements through spur with long accumulation 13
Chapter 3 Technology specications 23
Chapter 4 Accessories 63
Chapter 5 Overall and mounting dimensions 75
Chapter 6 Purchase terms and conditions 86
Chapter 1 Outline of GM8 Series
Data table for quick selection of GM8 series moulded case circuit-
breaker 4
Type explanation of GM8 series moulded case circuit-breaker 6
Six types optional release 8
Tripping indication module T1 11
Function indicating diagram of control panel 12
4Chapter 1 Outline of GM8 Series1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Type GM8-125 GM8-250 GM8-400 GM8-630 GM8-800
Frame size Inm A 125 250 400 630 800
Rated current InThermomagnetic type A 101620253240506380100125 125140160180200225250 250315350400 400500630 400500630700800
Electronic type Intelligent type A 3216~326332~6312563~125 250125~250 400200~400 630315~630 800400~800
Pole number P 34 34 34 34 34
Rated insulation voltage Ui ACV 800 800 800 800 800
Rated operational voltage Ue ACV 400690 400690 400690 400690 400690
Rated impulse withstand voltage Uimp kV 8 8 8 8 8
Short-time withstand current Icw kA /0.8s 5 7.6 9.6
Utilization category A A AB AB AB
Short-circuit
breaking capacity
Code M H R G M H R G M H R G M H R G M H R G
Rated ultimate short-circuit breaking capacity Icu
AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100
AC 690V kA 25 25 25 25 25
Rated service short-circuit breaking capacity Ics
AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75
AC 690V kA 10 10 15 15 15
Release type
Thermomagnetic type TM Note
Electromagnetic type X
Electronic type E
Intelligent type(Internal controller Zn
Intelligent type(External controller Zs
Arc distance mm 0 0 0 2 0 2 0
Prospective-maximization
maintenance durability Mechanical/Electrical440VIn/2 time 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500
Test durability Mechanical/Electrical time 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000
Overall dimensions
Wmm 90 105 140 140 210
L mm 174 184 284 284 302
H mm 68 86 68 86 103 103 103
Mounting type Fixed type front : none, rear: B ), plug-in type (C) Fixed type front : none, rear: B ), plug-in type
(C)Fixed type front : none, rear: B ), plug-in type (C)withdrawable
type(C2)Fixed type front : none, rear: B ), plug-in type (C)
withdrawable type(C2)Fixed type front : none, rear: B ), plug-in type (C)
withdrawable type(C2)
Internal accessories
(Cassette accessories)
Auxiliary contact AX
Alarm contact AL
Shunt release SHT
Under-voltage release UVT
External accessories
Power-driven operating device P
Turning handle operating device Z
Connecting bar L
Tripping indication module TI
Mechanical interlocking MI
Note 1 TMNon-adjustable thermomagnetic distribution protection TMF: Non-adjustable thermomagnetic generator protection TMB: Non-adjustable thermomagnetic transformer protection TMD Non-adjustable thermomagnetic motor protection; TMU: Non-adjustable thermomagnetic mine-used circuit-breaker. 2 When the protective cover 9.5mm in height of GM8-125 and GM8-250 is removed, the arc distance50mm; When the protective cover 13.5mm in height of GM8-400 GM8-630 and GM8-800 is removed, the arc distance100mm; All 4P products are short ashover. 3 Only suitable for GM8-Zs intelligent circuit-breaker. 4 means this function is provided means without this function. 5 Ano articial time-delay when a short-circuit occurs; B: articial time-delay when a short-circuit occurs.
Data table for quick selection of GM8 series moulded case circuit-breaker
5Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Type GM8-125 GM8-250 GM8-400 GM8-630 GM8-800
Frame size Inm A 125 250 400 630 800
Rated current InThermomagnetic type A 101620253240506380100125 125140160180200225250 250315350400 400500630 400500630700800
Electronic type Intelligent type A 3216~326332~6312563~125 250125~250 400200~400 630315~630 800400~800
Pole number P 34 34 34 34 34
Rated insulation voltage Ui ACV 800 800 800 800 800
Rated operational voltage Ue ACV 400690 400690 400690 400690 400690
Rated impulse withstand voltage Uimp kV 8 8 8 8 8
Short-time withstand current Icw kA /0.8s 5 7.6 9.6
Utilization category A A AB AB AB
Short-circuit
breaking capacity
Code M H R G M H R G M H R G M H R G M H R G
Rated ultimate short-circuit breaking capacity Icu
AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100
AC 690V kA 25 25 25 25 25
Rated service short-circuit breaking capacity Ics
AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75
AC 690V kA 10 10 15 15 15
Release type
Thermomagnetic type TM Note
Electromagnetic type X
Electronic type E
Intelligent type(Internal controller Zn
Intelligent type(External controller Zs
Arc distance mm 0 0 0 2 0 2 0
Prospective-maximization
maintenance durability Mechanical/Electrical440VIn/2 time 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500
Test durability Mechanical/Electrical time 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000
Overall dimensions
Wmm 90 105 140 140 210
L mm 174 184 284 284 302
H mm 68 86 68 86 103 103 103
Mounting type Fixed type front : none, rear: B ), plug-in type (C) Fixed type front : none, rear: B ), plug-in type
(C)Fixed type front : none, rear: B ), plug-in type (C)withdrawable
type(C2)Fixed type front : none, rear: B ), plug-in type (C)
withdrawable type(C2)Fixed type front : none, rear: B ), plug-in type (C)
withdrawable type(C2)
Internal accessories
(Cassette accessories)
Auxiliary contact AX
Alarm contact AL
Shunt release SHT
Under-voltage release UVT
External accessories
Power-driven operating device P
Turning handle operating device Z
Connecting bar L
Tripping indication module TI
Mechanical interlocking MI
6Chapter 1 Outline of GM8 Series1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
The 8th series
moulded
case circuit-
breaker of
the brand of
SECURELUCKY
Type explanation of GM8 series moulded case circuit-breaker
Frame size
Inm=125
Inm=250
Inm=400
Inm=630
Inm=800
Short-circuit breaking capacity code
M ypical type 35kANote
H Higher type50kA
R High type70kA
G Highest type85~100kA
Omit Zero ashover
G Short ashover
Connection mode code
Omit Front
B Rear
C Plug-in
C2 Withdrawable Note
GM8 125 H 3 TM G B
Tripping type code
Distribution protection Transformer protection Generator protection Motor protection Mine-used circuit-breaker
TM Thermomagnetic release TMB Thermomagnetic release TMFThermomagnetic
release TMDThermomagnetic
release TMUThermomagnetic
release
E Electronic release MD Electromagnetic release EU Electronic release
Zn Intelligent internal controller ZUn Intelligent internal controller
Zs Intelligent external controller ZUs Intelligent external controller
Tn Communication internal controller XU Electromagnetic release
Ts Communication external controller
X Electromagnetic release
Examples:
GM8-125M/3TM In=80A
Meaning: GM8 series circuit-breaker, frame size is 125A, breaking capacity is 35A, 3P, with thermomagnetic release, rated
current is 80A.
GM8-400H/3Zs SHT+AX TIs In=400A
Meaning: GM8 series circuit-breaker, frame size is 400A, breaking capacity is 50A, 3P , with intelligent internal controller,
auxiliary switch and shunt release, tripping indication module can be optional orded, rated current is 400A.
Note:Eg products can be used for ground protection.
Pole number
3:Three-pole
4A Note:Four-pole
4B:Four-pole
4C:Four-pole
4D:Four-pole
7Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Rated current
P AC230V 230VSHT+ALAX MIL TIs 80AIn=
TIs Tripping indication module of external controller (separated installation) Note
Note: 1 Type Zn, Zs and E without M-type breaking capacity
2 Only suitable for the circuit-breaker which frame size400 A.
3 Only GM8-Zs could equip with optional module.
4 Classication according to the type of neutral pole (pole N):
Type A: Pole N is non-equipped with over-current tripping device, which is making always and do not closing or opening with other
three poles.
Type B: Pole N is non-equipped with over-current tripping device, which always closing or opening with other three poles (contact
rstly and then opening).
Type C: Pole N is equipped with over-current tripping device, which always closing or opening with other three poles (contact rstly
and then opening).
Type D: Pole N is equipped with over-current tripping device, which is making always and do not closing or opening with other three
poles.
Over-current tripping value of pole N needs to be provided by the users.
Operational type Operational voltage
Omit Body Omit
Z Manual Omit
P Motor-driven AC 110V
AC 230V
AC 400V
DC 24V
DC 110V
DC 220V
Internal accessories Operational voltage
AL Alarm switch Omit
AX Auxiliary switch Omit
SHT Shunt release AC230VAC400VDC24VDC110VDC220V
UVT Under-voltage release AC230VAC400V
External accessories
L Connecting bar
External accessories
M Mechanical interlocking
8Chapter 1 Outline of GM8 Series1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Not
e:
3:
thre
e-po
le; 4
:four
-pol
e st
anda
rd ty
pe; 4
A:fo
ur-p
ole
A ty
pe;
N
one:
dist
ribut
ion
prot
ectio
n; D
: mot
or p
rote
ctio
n;
N
one:
adj
usta
ble
oper
atio
n ty
pe;
SD
: adj
usta
ble
alar
m ty
pe;
O
mit
front
con
nect
ion
B
rear
con
nect
ion
C1
plug
-in c
onne
ctio
nC
2w
ithdr
awab
le
rate
d cu
rren
t40
0A
;
O
pera
tiona
l typ
eO
mit
body
Z
man
ual
P
mot
or-d
riven
. O
ptio
nal o
pera
tiona
l vol
tage
of m
otor
-driv
e:A
C11
0V
AC
230V
DC
24V
D
C11
0V
DC
220V
;
A
Lal
arm
con
tact
A
X
auxi
liary
con
tact
S
HT
shun
t rel
ease
LE
Ele
ctro
nic
resi
dual
cu
rren
t op
erat
ed
circ
uit-
brea
ker
100
Fram
e si
ze
D
Pro
tect
ion
type
SD
Res
idua
l
curr
ent
oper
ated
type
B
Con
nect
ion
type
P A
C23
0
Ope
ratio
n ty
pe
SH
T+A
LAX
230
V
Opt
iona
l in
tern
al
acce
ssor
ies
In=8
0A
Rat
ed
curr
ent
4 Pole
num
ber
The
8th
serie
s m
ould
edca
se c
ircui
t-br
eake
r of
the
bran
d of
S
EC
UR
ELU
CK
Y
GM
8
Type
exp
lana
tion
of G
M8L
E s
erie
s le
akag
e pr
otec
tion
circ
uit-b
reak
er
TM
Ther
mom
agne
tic
rele
ase
9Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Six types optional release
1Rated current of thermomagnetic release GM8-TM:10~800A
Tripping types Release code Protection function Acting curve
Thermomagnetic type
release
Distribution
protection:TM,M
Transformer
protection:TMB
Generator
protection:TMF
Motor
protection:TMD,MD
Mine-used circuit-
breaker:TMU
Over-load long time-delay
protection
(thermal) ( internal xed )
Short-circuit instantaneous
protection(electromagnetic)
(internal xed )
2Rated current of electromagnetic release GM8-X (distribution protection): 10~800A
Tripping types Release code Protection function Acting curve
Electromagnetic
release
Distribution protection:XMine-used circuit-
breaker:XU
Short-circuit back-upprotection (electromagnetic)
(built-in xed)
3Rated current of electronic release GM8-E (distribution protection): 16~800A
Tripping types Release code Protection function Acting curve
Electronic releaseDistribution protection:E
Mine-used circuit-breaker:EU
Over-load long time-delay protection(electronic)
( adjustable )
Short-circuit short time-delay protection
(electronic)(adjustable with Ii)
Short-circuit instantaneousprotection(electronic)
(adjustable )Short-circuit back-up
protection(electromagnetic) 20Inm20%
PAL pre-alarm(for indication)(adjustable )
t
I
TM
t
I
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
I
t
I
M
10
Chapter 1 Outline of GM8 Series1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
4Rated current of intelligent release GM8-Zn (distribution protection): 16~800A
Tripping types Release code Protection function Acting curve
Intelligent
release(internal)
Distribution
protection:Zn
Mine-used circuit-
breaker:ZUn
Over-load long time-delay protection(intelligent) (
adjustable )Short-circuit short time-delay
protection (intelligent) ( adjustable )
Short-circuit instantaneousprotection (intelligent) (
adjustable )Short-circuit back-up
protection(electromagnetic)
PAL pre-alarm(for indication)(adjustable )
5Rated current of GM8-Zs intelligent release(distribution protection): 16~800A
Tripping types Release code Protection function Acting curve
Intelligent
release(internal)
Distribution
protection:Zs
Mine-used circuit-
breaker:ZUs
Over-load long time-delay protection
(intelligent) ( adjustable )Short-circuit short time-delay
protection (intelligent) ( adjustable )
Short-circuit instantaneousprotection (intelligent) (
adjustable )Short-circuit back-up
protection(electromagnetic)
PAL pre-alarm(for indication)(adjustable )
6Rated current of GM8-Tn/Ts intelligent communicative release: 16~800A
Tripping types Release code Protection function Acting curve
Intelligent
communicative release
Distribution
protection:T
Over-load long time-delay protection
(electronic) ( adjustable )Short-circuit short time-delay
protection (electronic) ( adjustable )
Short-circuit instantaneousprotection (electronic) (
adjustable )Short-circuit back-up
protection(electromagnetic)
PAL pre-alarm(for indication)(adjustable )
Net communications based on the
MODBUS protocol
t Ir
IiTsd
Tsd=OFFIsdTr
I
t Ir
IiTsd
Tsd=OFFIsdTr
I
t Ir
IiTsd
Tsd=OFFIsdTr
I
11
Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Tripping indication module Ti
1Outline
TIs
For GM8-Zs series circuit-breaker, we could equip tripping indication
module. Main function:
(1) Offering tripping signal node output (automatic reset);
(2) Fullling the fault type indication with external controller.
2Function and combination explanation
L : O v e r - l o a d
l ong t ime-de lay
protection
S : Sho r t - c i r cu i t
short time-
delay protection
I: Short-circuit
i n s t a n t a n e o u s
protection
PAL : PAL p re -
alarm
indication
Offering tr ipping signal
node output
Local display fault tripping
category
consistently (manual reset)
Function
When module TIs is mounted on
the circuit-breaker,power supply
and signal could be provided after
circuit-breaker tr ipping and fault
tripping category could be displayed
consistently on external controller.
The module TIs is specially designed,
and can be separately mounted to
adapt to the compact installation
space.
GM8-Zs circuit-breaker should be used co-ordination with module Tls
parameter adjustment
of L,S,I,Ip
Three phase current
circularly display
L,S,I fault tr ipping
indication
(should be supported by
module TI)
Note: TIs module need external AC220V power supply connected by users. If the voltage of power supply is not AC220V, please mark it in ordering.
+ =
12
Chapter 1 Outline of GM8 Series1
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
10 12 510
58
12
I sd=I i2 I sdOFF 0.8 0.9
0.7 1.0
I n=250AGER23E
160180
200225
125
140
250t sd=0.08s I iI rI rA I pI rFunction indicating diagram of controller panel1Function sketch map of GM8-E electronic controller Over-load (long time-delay ) current setting IrShort-circuit instantaneous current setting IiPre-alarm current setting Ip
2Function sketch map of GM8-Zn/Tn intelligent internal controller
Over-load (long time-delay ) current setting IrOver-load (long time-delay ) time setting TrShort-circuit (short time-delay ) current setting IsdShort-circuit (short time-delay ) time setting TsdShort-circuitinstantaneouscurrent setting IiPre-alarm current setting Ip
3Function sketch map of GM8-Zs/Ts intelligent external controller
Over-load (long-time delay )fault tripping indicationShort-circuit (short-time delay) fault tripping indicationShort-circuit (instantaneous) fault tripping indicationResetting button
0.7Ir Indicated lumpPre-alarm indicated lumpOver-load indicated lumpTest terminalSafety lock hole
Liquid crystal display screen
Use co-ordination with Ti module
"Cancel" buttonDown buttonUp buttonSet/Enter"button
150
60
30
90
16
120.8
.7
.9
1.0
8
3
5
1012
14
OFF
4
2
3
58
12 .06
.1
.2.3
OFF
10
160
125
140
180200
250
225
Ir(A) Tr(s) Tsd(s) Ii(Ir)Isd(Ir) Ip(Ir)
Chapter 1 Outline of GM8 Series
Performance improvement 14
Advanced and safe arc spray outward-oriented design 14
Zero-ashover 15
Degree of protection IP30 15
New contact system 15
Ics=100% Icu 15
The novel external controller 16
Suitable for isolation 17
Back-up electromagnetic protection 17
Mounting, operation and maintenance
Cassette accessories 17
Safety operating device 18
Safe and reliable connection type 18
Compact size 18
Standardization aperture 19
Customized design 19
Advanced technical theory 20
Modulization communication function 21
Chapter 2 Improvements through spur with long accumulation
14
Chapter 2 Improvements through spur with long accumulation2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Performance improvementAdvanced and safe arc spray outward-oriented design
Circuit-breaker is a kind of protective electrical installation,
which protects lines and equipment from damage due to short-
circuit, especially from personal injure, so it must meet high safety
design standard. In former applications, people often injured
by flashover because of the unreasonable arc spray outward-
oriented design. In order to avoid these accidents, GM8 series
circuit-breakers adopt the advanced patent technique of arc spray
outward-oriented design to provide a reliable protection for users.
Arc spray outward-oriented: it is known that the high dense
high-temperature ion and electron would spread into the low
density and low-temperature medium. So, in the period of arc
generate to extinguished, after it passed arc extinguish chamber
and continues to spray out of circuit-breaker, this time, the oriented
structure can give an out-spray direction to it.
Arc temperature: the temperature of the arc can up to
5000~8000
The backward arc-oriented design and its harm
In figure1, a insulating paper (Nomex) be mounted above
the arc extinguish chamber of circuit-breaker. At the usual time,
the elastic insulating paper can protect against foreign body drop
into circuit-breaker. But when short-circuit occurs, the paper will be
bounced outward because of the spraying high temperature and
pressure gas generated by flashover, and the arc will be spray
forward out of circuit-breaker along the paper surface. At this
time, if somebody is closed to the handle or the jet orice is near
the mental cabinet, burn accident or another short-circuit will be
happened.
Why the arc-oriented structures are designed spraying
forward instead of upward in some factories? The long tripping
breaking time, bad current-limiting capacity and long out-
spray(upward) distance are the main reasons for these products.
Due to the ashover distance requirement of above circuit-breaker
can not exceed 50~100mm in IEC60947-2, they design the
ashover forward, but backward and unsafe.
The harmfulness of ashover spraying forward are:
1. Result in that the arcs connect together and misoperation
of upper stage (as gure1)
Usually, there aren't interphase barriers at the front of circuit-
breaker (the plane), if a short-circuit fault happened, ashover out
of each pole is spraying forward, the arc from two adjoining poles
will connect together and lead to a short-circuit at lead-in side,
cause a misoperation of the upper stage, result in an expanding
fault; Meanwhile, It can burn the cabinet and cause a human injury
accident.
2. Circuit-breakers mounted in an open cabinet
If a short-circuit has been exit in circuit, operators will be
injured by ashover sprayed to them when they close to the circuit-
breaker. Because the circuit-breaker will trip due to short-circuit
and spray ashover outward, however, the ashover will be spray
to operator because of the oriented effect of Nomex insulating
paper.(as gure2)
3. Circuit-breakers mounted in a closed cabinet
When there is a short-circuit current in system, the moveable
and static contacts breaking, and arcs generated in each pole
spray forward and connect together by mental cabinet will lead to
an interphase short-circuit, at last, cause a false action of upper
stage circuit-breaker. The arcs spraying to mental enclosure will
generate high temperature to melt down the mental cabinet, and
someone stands front of it will be hurt and cause a safety accident.
4. Circuit-breakers equip with manual or motor-driven
operation device
The four mounting feet of manual or motor-driven operation
device are mounted in the middle of three-phase lead-in side. The
arcs which spray forward and pass the mental mounting feet will
cause a interphase short-circuit again at the lead-in side and lead
to a false action of upper stage circuit-breaker. Arcs spraying to
manual operation device will generate high temperature to melt
down the enclosure of drawer, someone will be shock if his hand
or body contacts the cabinet.
GM8 advanced arc spray outward-oriented design
The arc spraying direction of our advanced circuit-breaker is
designed upward but not forward, it avoids the above safety risk
of those backward circuit-breakers. More details see GM8 series
circuit-breaker.
15
Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
The elastic Nomex insulating paper where the arc sprays to operator or to the mental enclosure of distribution cabinet.
Spraying forward causes an interphase short-circuit
Figure1 The moulded case circuit-breakers
structure of usual domestic manufacturers
Figure2 Operate the circuit-breaker directly by
operator Circuit-breaker
Cabinet
FIrure3 The mounting of circuit-breaker in closed
x cabinet
Mounting board
Flashover forward causing interphase short-circuit
Mounting foot
FIrure4 The mounting of circuit-breaker in drawer
Flashover direction -- upward
FIrure5 Arc spray outward-oriented design of
GM8 series circuit-breaker
16
Chapter 2 Improvements through spur with long accumulation2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Repulsed position of moving contact
Conductor on static contact
Repulsed position of static contact
Flexible connection
Ia current
Ia current
Conductor on static contact
Moving contact
Static contactFlexible connection
Zero-ashoverGM8 series circuit-breaker adopts an innovative arc
control system,so it can quench arc effectively and realize
the zero-ashover easily.
Protection degree IP30Special protective cover can stop any objects with
the diameter of 2.5 mm into the internal of enclosure, the
protection degree could up to IP 30.
Novel contact systemGM8 series circuit-breaker adopts a special designed contact system, which possesses
some merits such as strong repulsion and long open range.
When the circuit-breaker is making:
Movable contact bear a tension and a repulsion as well, named FIac and FIbc
respectively.
Static contact bears two repulsions, named FIab and FIbc respectively.
When the short-circuit current reaches the acting value of the instantaneous release, the
above-mentioned forces will accelerate the speed of moving /static contact arc, increase the
arc length and make the arc quenching easier.
The innovative design of the bidirectional repelling system breakthrough the limitations
of traditional design, that is moving contact upward moving and static contact xed. Then the
opening range between moving contact and static contact is increased greatly.
By adopting this contact system, which has big repulsion and long opening range, GM8
series circuit-breaker is more easily to quench the arc, so it has a higher current-limit ability
and short-circuit breaking capacity.
Protective cover
Protection degree IP30
Contact construction of four repulsion
Ics=100% Icu Thanks to its super current limiting ability, outstanding arc control system and the moving and static contact have superior withstand
arcing ability, GM8 series circuit-breaker has an excellent performance: Ics=100%Icu.
According to Standards GB14048.2 (IEC 60947-2), the test procedures of rated ultimate short-circuit breaking capacity (Icu) and rated service short-circuit breaking capacity (Ics) as follows:
Rated ultimate
short-circuit
breaking
capacity Icu
Verication of overload release Reference temperature/ 2 times setting current/ acting within the longest time in 2 times setting current
Rated ultimate short-circuit breaking capacity test
Operation procedure: O-t-CONote: O-One time opening operation; t-interval; CO-One automatic opening right after one closing operation
Verication of dielectric withstand capacity Take the larger one between 2Ue and 1000V, the leakage current shall not exceed 6mA (Isolation)
Verication of overload release Reference temperature/ 2.5 times setting current/ acting within the longest time in 2 times setting current
Rated service
short-circuit
breaking
capacity Ics
Rated service short-circuit breaking capacity test Operation procedure: O-t-CO-t-CO
Verication of operational performance capability 5% of the electrical durability
Verication of dielectric withstand capacity
Take the larger one between 2Ue and 1000V, the leakage current shall not exceed 2mA (Isolation)
Verication of temperature-rise The temperature of terminals don t exceed 80K
Verication of overload release Reference temperature/ 1.45 times setting current/ acting in 2(1) hour
According to the standards GB14048.2 (IEC947-2), Ics could be 25%, 50%, 75% or 100% of Icu.GM8 series circuit-breaker strictly follows the above-mentioned test procedures, achieves Ics=100%Icu reliably.
Bidirectional repulsion of the moving/static contactGM8-125M/H/R/GGM8-250R/G
17
Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
The novel external controller
The traditional systemWhen the customers have a higher requirement of
maintainability and safety to the low voltage distribution systems, they will spend extra money to purchase the intelligent circuit-breaker installed in the distribution
cabinet. One of their main purposes is: adjust the acting parameters by the adjustment button on the panel of intelligent circuit-breaker.
Whereas, according to investigations, we found that the adjustment acting parameters is very difcult to realize. The reason lies in the external operating device (manual or motor-driven), an accessory which is widely used in the low voltage distribution cabinet.
The handle is installed in the drawer of the circuit-breaker. As a result, the customers cant reach the adjustment panel, so the adjustment function is no-way to achieve.
The price of intelligent circuit-breaker is 2 or 3 times higher than the normal thermomagnetic circuit-breaker which parameters are nonadjustable. It is absolutely a huge waste if the adjustment function cant work.
The new system adopting external controllerIn order to solve the mentioned problem above,
the intelligent controller of GM8-Zs series (belonging to GM8-Z) is external of the circuit-breaker, and connects with circuit-breaker by date lines.
The ex terna l cont ro l le r adopts the same dimensions as the panel amperemeter, it can display the three phase current. So the clients could adjust the parameters on the drawer panel conveniently.
The external control ler doesn t need any additional power supply and any auxiliaries, it can realize the following functions:
Adjust all the acting parameters real time during the application process;
Display the three phase current;Display the tripping type continually (TI module
is needed).
External controller
External controller
Intelligent circuit-breaker
Amperemeter
Amperemeter
Circuit-breaker
18
Chapter 2 Improvements through spur with long accumulation2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Suitable for isolation
By increasing the opening range between moving contact and static contact and enhancing the performance of the insulating material
between the conductive parts, GM8 series circuit-breaker has isolation function.
Back-up electromagnetic protectionBoth the electronic and intelligent circuit-breaker are equipped with a back-up protection release
in a magnetic yoke type, its rated acting current is 20Inm (where Inm is frame size). The back-up
protection release plays important roles in the following two aspects:
(1) The back-up protection release will acting before the electronic release when the short-circuit
current of distribution circuit exceeded 20Inm. Consequently, it can increase the acting sensitivity
and maximum guarantee the safety of the power supply lines.
(2) When the electronic release broke down, the back-up release will act a back-up protection
function, providing double protection for the safety of the power supply lines.Back-up protection release of
magnetic yoke type
Installation, Operation and Maintenance
Cassette Accessories
The false action or failure action
problem often occurs for moulded case
circuit-breakers field use. Therefore,
Beijing People's Electric Plant Co., Ltd.
organized experts to analyze and they
found that many problems were related
to the error installation of accessories
or foreign matters drop into the circuit-
breakers after accessories installation.
Because o f a l l these accessor ies '
installation process is:
Step 1: Press down the button "Trip"
to make circuit-breaker tripping;
Step 2: Twist off all big screws on the
cover of circuit-breaker (In general, there
are 8-12 big screws, so we need spend
more time and bigger torque to do it.);
Step 3: Open the cover of circuit-
breaker (At this time, all parts in circuit-
breaker are exposed and arc extinguishers
always drop out.);
Step 4: Install the accessories (During
installing, some important parts of circuit-
breakers, like tripping device and bimetal
element, maybe touched unexpected, so
their position will be changed and then
affect the operation characteristic of circuit-
breakers, sometimes operator's arms also
be hurt and foreign matters easily drop
into circuit-breaker, such as cable head);
Step 5: Close the cover of circuit-
breaker (in order to make sure the cover
and body of circuit-breaker matched well,
the accessories and internal parts must be
at the correct position.);
Step 6: Turn all the screws on cover
tight (All screws must be tighten, otherwise
it will affect the safety of circuit-breaker.
When there is a short-circuit current, the
high temperature and high pressure arc
gas generated by movable and static
contacts breaking may push off the cover
and cause safety accidents.)
On the whole, we can clearly find
that above installation method not only
inf luences the safety and operation
characteristics of circuit-breaker, but also
inconvenient to operation. At the same
time, the normal functions of accessories
will be affected if they are installed at an
incorrect position or match with the circuit-
breaker body not very well.
Step 1 Step 2 Step 3 Step 4 Step 5
19
Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Safety operating device
GM8 adopts a double layer insulation handle to guarantee the absolute
safety of the operators.
The first insulation protection: The handle is molded with high insulting
property engineering plastics, which makes the handle has super-strong insulating
property.
The second insulation protection: As the well insulating design, the metal
operating device connected with handle is isolated from the internal conductors.
The adoption of the double insulation handle ensures the circuit-breaker is
much safer and reliable even when the handle is damaged.
Safety and reliable connection type
Connection type of other manufacturers Improved connection type
Tap on the static contact connector; screw it together with the external
connector.This kind of connection is less reliable and easy to loosen.
Adopting the iron nut to screw the connectors together with static contact, so
it is more stable and reliable.
Compact sizeThanks to the new conductive and arc control system scheme, GM8 circuit-breaker acts more stable and short-circuit breaking
capacity is improved widely, what s more, the size is reduced substantially.
GM8-630 shares the same case dimensions with GM8-400, which means GM8-630 is smaller, and the performance is much better
than the primary version (the original width: 182mm, the original breaking capacity: 65kA; the present width: 140mm, the present breaking
capacity: 100kA).
182m
m
140m
m
GM8-630A/3P
Breaking capacity 100kA
Other domestic product 630A/3P
Breaking capacity 65kA
Imported product 630A/3P
Breaking capacity:70kA
External connecting board
Connecting board self-fastening
Static contact connecting board
External connecting board
Tightening with iron nut
Static contact connecting board
Insulating tube
Movable contact
Handle
20
Chapter 2 Improvements through spur with long accumulation2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
GM8-125A was improved and the thickness is reduced to 68 mm at the minimum.
86m
m
68m
m
Standardization aperture
GM8-125A/3P
Breaking capacity 50kA
Other domestic product 125A/3P
Breaking capacity 50kA
Imported product 125A/3P
Breaking capacity:50kA
Adopting novel design theory, the mounting dimensions of GW8 were modied into two types to make the manufacture process of
complete equipment is much simpler.
60 90
125/250 Type 125/250 Type
Customized design
There are use indication windows on the panel
of the circuit-breaker, so the purpose of circuit
could be labeled on the circuit-breaker directly.
The circuit label could be served with the
circuit-breakers, but the users should explain the
purpose of circuit-breaker when ordering.
When the accessory is installed, it is very
convenient to lead out its signal lines to the
corresponding terminals along the lateral lead slot.
Due to this merit, GM8 series circuit-breakers can
be mounted next to each other, leaving the mount
size more compact.
21
Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Advanced technical theory
1.High reliability and safety of the circuit
GM8 series circuit-breaker processes with the virtual effective value; it can fundamentally prevent
the false tripping of the intelligent circuit-breakers to realize the accurate protection. The circuit
analysis plan as the following graph:
2.Pre-alarm indication function
Both the electronic and intelligent circuit-breaker have a pre-warning function. They
can indicate the over load condition before circuit-breaker tripping. When the load current
exceeded the setting value, the micro processor will output a pre-alarm signal through the
solid-state relay to light the PAL pre-alarm indicated lump.
CT
CT
CT
CT *OQVU0VUQVUI
CV
PSS
WDT
CPU
SSW
LSW
PSW
A/D 0WFSMPBEDVSSFOUJOEJDBUFEMVNQ1SFBMBSNJOEJDBUFEMVNQ Pre-alarm output
**OTUBOUBOFPVTDJSDVJU$77PMUBHFTUBCJMJ[JOHDJSDVJU1441IBTFDIPPTJOHTBNQMFDJSDVJU8%5$MPDLEPHUJNJOHDJSDVJU4484IPSUUJNFEFMBZTPGUXBSF-48-POHUJNFEFMBZTPGUXBSF1481SFBMBSNTPGUXBSFThe terminals of power supply Breaker-circuit operational device Customized integration apparatus
The terminal of load Load current indicated lump70%
Test input Characteristics setting
Converter
Tripping coil
Micro processor
Trigger circuit
Rectification apparatus
4BNQMJOHBOE"%DPOWFSTJPO$BMDVMBUJPOPGUIFFGGFDUJWFWBMVF$IBSBDUFSJTUJDTPGQSPDFTTJOHUIFMPOHUJNFEFMBZQSFBMBSN
22
Chapter 2 Improvements through spur with long accumulation2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Modulization of communication functions
GM8-T series (also belonging to GM series circuit-breaker) is a communicative product. The communication accessories includes: external communication module, RS485 interface extended plate, communication controller and series of conguration software. The external communication module is connected to the circuit-breaker. The clients can conveniently build the communication net consistent with the MODBUS protocol, the schematic diagram as follows
23
Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Communication protocol
Field-bus protocol MODBUS-RTU is comply with the international standard IEC61158. The physical layer electrical interface is the serial RS485, which consistent with the international standard TIA/EIA-485-A. The date frame format is 1 start bit, 8 date bits, 2 stop bits, none verification (Including odd and even verifying). The report format is address code (1 bit), function code (1 bit), date domain (maximum 252 bits), CRC verication (2 bits).
Network characteristics
The communication medium is double-wiring shielded line. Each communication line can connect with 32 devices at the maximum and with 1000 meters at its longest distance. A repeater is needed if the distance is exceeded than 1000 meters, and a brancher has to be adopted if there is a branch.The standard band rate is 19200bps (could be set to 9600bps or 38400bps). Besides, all the devices connected to the same bus must share the same band rate and parity check, and the address of the slave station cant repeat.When there are too many devices connected to the bus, a RS485 adapter is needed to connect more devices. The devices in one slave station cant exceed 247 in the MODBUS communication system.
Communication controller
The communication controller is connected with the circuit-breaker by special communication lines. The controller can set the parameters (slave-station address, communication bond rate, current parameter, tripping parameter), display the parameters, electric switching control, display warning (overload, short-circuit fault) and communication (local and remote communication). The communication controller doesnt need external power supply and consequently is very convenient to be installed in the distribution cabinet. The controller will automatically scan the circumscribed devices when turned on and build a dynamic address list. The limitation is no more than 32 devices. The controller can achieve remote communication by connecting it to the remote monitoring computer.
Remote communication
By connecting the circuit-breaker and monitoring computer with double-wiring shielded line and RS485 converter. To set, display and communicate locally and remotely, we should connect the controller with the circuit-breaker before it was connected to the remote monitoring computer.
I f the circui t-breaker adopts electr ic operating device, the remote control can achieve. If adopt network instruments, remote measurement of the electrical parameters can achieve.Due to adopting the standard protocol MODBUS-RTU, the controller can be further interfaced with the industrial Ethernet.
Conguration software
The moni tor ing computer can adopt c o n f i g u r a t i o n s o f t w a r e t o a c h i e v e t h e management of power and distribution systems.The conguration software is usually customized mode. The inter face is beaut i fu l , v isual , friendly, various and convenient for the device management.Integration network solutions are also ready for our clients.
Chapter 3 Technical Specications
GM8-TM thermomagnetic moulded case circuit-breaker 24
GM8-E electronic moulded case circuit-breaker for distribution
protection 31
GM8-Z intelligent moulded case circuit-breaker for distribution
protection 45
GM8-X electromagnetic moulded case circuit-breaker for distribution
protection 57
GM8-TM SeriesThermomagne t i c mou lded case circuit-breaker
Over-load long-time delay protection
Short-circuit instantaneous protection
26
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Application range
GM8-TM se r i es mou lded case
c i rcu i tbreakers are one of the new
type circuit-breakers which have been
developed using international advanced
design and manufacturing technology,
menwhile, the circuit-breaker complies
with the demands of the new international
standards. The rated insulation voltage
of the circuit-breakers is 800V, which
could be used in the circuit of AC 50Hz,
rated operational voltage 400V or 690V
and rated operational current 10A-800A,
where the circuit-breakers take the role of
infrequent closing/opening and infrequent
motor starting-up. The circuit-breakers are
feature with over-current, short-circuit and
under-voltage protection functions, so it
can protect the distribution circuit and the
power equipment from damage.
Design
According to rated ultimate short-
circuit breaking capacity, GM8-TM series
circuit-breakers can be classied into four
categories: M typical type (35KA); H higher
type (50KA); R high type (70KA);G highest
type (80 100KA). The circuit-breaker is
feature with compact size, high breaking
capacity, zero-flashover and vibration
resistance.
The c i r cu i t - b reake rs can be
installed vertically (upright) or horizontally
(transverse).
Wired adversely is forbidden for the
circuit-breakers, so 1,3 and 5 can only
be connected with power line:2,4 and 6
can only be connected with load line.
The circuit-breaker has isolation
function and corresponding symbol is
shown as
The circuit-breaker can be used at
ambient air temperature below 40 and do
not need lowering capacity.
Circuit-breaker and over-current
release are integrated and provided as an
equipments. There are four kinds internal
accessories: auxiliary switch, alarm switch,
shunt release and under-voltage release.
Internal accessories is easy to mount
by adopting a cassette type, so that the
accessories can be installed directly in eld
or in the factory.
Standard
IEC60947-1 and GB14048.1-2000
General rules
IEC60947-2 and GB14048.2-2001
Lowvoltage circuit-breakers
IEC60947-4 and GB14048.4-2003
Contactor and motor starter
IEC60947-5-1 and GB14048.5-
2001Electromechanical control circuit
devices.
Normal serv ice and mounting conditions
The altitude of the site of installation
does not exceed 2000m;
The ambient air temperature
dose not exceed +40 and the lower limit
of the ambient air temperature is -5 ,
meanwhile, its average over a periods of
24h does not exceed +35 .
The relative humidity of he air
does not exceed 50% at a maximum
temperature of +40 . Higher relative
humidities may be permitted at lower
temperature e.g. 90% at +20 . Special
measures may be necessary in cases of
occasional condensation due to variations
in temperature;
Pollution degree: 3;
Mounting categories: The mounting
category of main circuit, under-voltage
release is and other auxiliary and control
circuits is ;
The circuit-breaker could not be
mounted in the place with the explosive
possibility, and there must be not any
gas which would corrode metal or any
conducting dust which would destroy the
insulation.
The circuit-breaker should be
mounted in the place protect against
splashing spraying water.
Circuit-breakers should be mounted
in accordance with instructions.
The protection degree of circuit-
breakers could be up to IP30 (comply with
the demands of IEC60947-1), and the
protection degree is IP20 without protective
cover up and down.
Main characteristic
GM8-TM thermomagnetic moulded
case circuit-breakers have over-load long-
time delay and short-circuit instantaneous
two-levels protection function.
GM8-TM series circuit-breakers
can be equipped with internal cassette
accessories.
GM8-TM series circuit-breakers are
zeroashover.
Category o f 4 -po le circuit-breakers
Classication according to the type of
neutral pole (pole N):
Type A: Pole N is non-equipped
with overcurrent tripping device, which
is making always and do not closing or
opening with other three poles.
Type B: Pole N is non-equipped with
overcurrent tripping device, which always
closing or opening with other three poles
contact rstly and then opening .
Type C: Pole N is equipped with
over-current tripping device, which always
27
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Protective characteristics
Distribution protection
Over-load long-time
delay protection
Distribution protectionTM
Generator protectionTMF
Transformer protectionTMB
Mine-used circuit-breakerTMU
1.05InCold state 2h Not actingIn63A1hNot acting
1.3InHeat state 2h ActingIn63A1h Acting
InInternal xed
Short-circuitinstantaneous
protection
Distribution protectionTMM 10In20%
Generator protectionTMF 3In20%
Transformer protectionTMB 5In20%
Mine-used circuit-breakerTMU 10In20%
Motor protection
Over-load long-timedelay protection
Motor protectionTMD
1.0InCold state 2h Not acting
1.2InHeat state 2h Acting
1.5InHeat state 8min ActingIn225A4min Acting
7.2InCold state 6sTp20s ActingIn225A4sTp10s Acting
Short-circuitinstantaneous
protectionMotor protectionTMDMD 12In20%
Note: the code explanation of thermomagnetic release
TThermal release MMagnetic release BTransformer protection
FGenerator protection DMotor protection UMine-used circuit-breaker
closing or opening with other three poles
(contact rstly and then opening ).
Type D: Pole N is equipped with over-
current tripping device, which is making
always and do not closing or opening with
other three poles.
Over-current tripping value of pole N
needs to be provided by the users.
28
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Technical specications
Type GM8-125/TM GM8-250/TM GM8-400/TM GM8-630/TM GM8-800/TM
Frame size Inm A 125 250 400 630 800
Rated current InA12510080
6350403225201610
250225200180160140
125
400350315250
630500400800700
630500400
Short-circuit instantaneous acting current Ii ADistribution protectionTM10In20%Generator protectionTMF3In20%Mine-used protectionTMU10In20% Transformer protectionTMB5In20%Motor protectionTMD12In20%
The code of rated short-circuit breaking capacity M H R G M H R G M H R G M H R G M H R G
Rated ultimate short-circuit breaking capacity Icu
AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100
AC 690V kA 25 25 25 25 25
Rated service short-circuit breaking capacity
Ics
AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75
AC 690V kA 10 10 15 15 15
Pole number P 34
Rate insulation voltage Ui ACV 800
Rate impulse withstand voltage Uimp V 8000
Rate operational voltage Ue ACV 400690
Arc distance mm 0 Note
Uitilization category A
Prospective-maximization maintenance durability
Mechanical/Electrical440VIn/2times 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500
Test durability Mechanical/Electrical times 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000
Overall
dimensions
mm 90 105 140 140 210
L mm 174 184 284 284 302
H mm 68 86 68 86 103 103 103
Mounting type Fixed front : none, rear: B , plug-in type (C), withdrawable type(C2)
Internal accessories
Cassette
accessories
Auxiliary switch AX Note
Alarm switch AL
Shunt release SHT
Under-voltage release
UVT
External
accessories
Motor-driven operational
device P
Turning handle operational
mechanism Z
Connecting bar L
Mechanical interlocking
MI
Note When the protective cover of GM8-125 and GM8-250 is removed 9.5mm in height, the arc distance50mm;
When the protective cover of GM8-400 GM8-630 and GM8-800 is removed 13.5mm in height , the arc distance 100mm;
All 4P products are short ashover.
means this function is provided;means without this function.
29
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
GM8-125/Acting characteristics curve and temperature compensating curve
GM8-TM acting characteristics curve and temperature compensating curve
Act
ing
time
x100%Rated current
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
In=63A~125AMax.63~125
Act
ing
time
x100%Rated current
63A~125A
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
30
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
GM8-250/TM Acting characteristics curve and temperature compensating curve
Act
ing
time
x100%Rated current
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
GM8-400/TM Acting characteristics curve and temperature compensating curve
Act
ing
time
x100%Rated current
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
31
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
GM8-630/TM Acting characteristics curve and temperature compensating curve
GM8-800/ Acting characteristics curve and temperature compensating curve
Act
ing
time
x100%Rated current
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
Act
ing
time
x100%Rated current
Temperature compensating curve
Rated ambient air temperature 40 Ambient air temperature ()
Set
ting
curr
ent(%
)
Chapter 3 Technical Specications
Over-load long-time delay protection
Short-circuit short-time delay protection
Short-circuit instantaneous protection
Pre-alarm indicator
GM8-E ElectronicMoulded case c i rcui t -breaker for distribution protection
33
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Application range
GM8-E series moulded case circuit-
breakers are one of the new type circuit-
breakers which have been developed
using international advanced design and
manufacturing technology. Meanwhile, the
circuit-breaker complies with the demands
of the new international standards and
widen the range of stage dif ference
coordination. The rated insulation voltage
of the circuit-breakers is 800V, which could
be used in the circuit of AC 50Hz, rated
operational voltage 400V or 690V and rated
operational current 16A-800A, where the
circuit-breakers take the role of infrequent
turn on/off and infrequent motor starting-
up. The circuit-breaker has over-load long-
time delay, short-circuit short-time delay
and under-voltage protection functions, so
it can protect the distribution circuit and the
power equipment from damage.
Design
According to rated ultimate short-
circuit breaking capacity, GM8-E series
circuit-breakers can be classied into three
categories: H higher type 50KA ; R high
type 70KA ;G highest type 80 100KA . The
circuit-breaker is feature with compact size,
high breaking capacity, zeroashover and
vibration resistance.
The circuit-breakers can be installed
vert ical ly upright or horizontal ly
transverse .
Wired adversely is forbidden for the
circuitbreakers, so 1,3 and 5 can only be
connected with power line:2,4 and 6 can
only be connected with load line.
The circuit-breaker has isolation
function and its corresponding symbol is
shown as .
The protective characteristic of
circuitbreaker is not influenced by the
change of ambient air temperature Circuit-
breaker and over-current release are
integrated and provided as an equipments.
There are four kinds internal accessories:
auxil iary switch, alarm switch, shunt
release and under-voltage release. Internal
accessories is easy to mounting by
adopting a cassette structure, so that the
accessories can be installed directly in eld
or in the factory.
Standard
IEC60947-1 and GB14048.1-2000
General rules.
IEC60947-2 and GB14048.2-2001
Lowvoltage circuit-breakers.
Normal serv ice and mounting conditions
The altitude of the site of installation
does not exceed 2000m;
The ambient air temperature dose
not exceed +40 and the lower limit
of the ambient air temperature is -5 ,
meanwhile, its average over a periods of
24h does not exceed +35 .
The relative humidity of he air
does not exceed 50% at a maximum
temperature of +40 . Higher relative
humidi ty may be permit ted at lower
temperature e.g. 90% at +20 . Special
measures may be necessary in cases of
occasional condensation due to variations
in temperature;
Pollution degree: 3.
Mounting categories: The mounting
category of main circuit, under-voltage
release is and other auxiliary and control
circuits is ;
The circuit-breaker could not be
mounted in the place with the explosive
possibility, and there must be not any
gas which would corrode metal or any
conducting dust which would destroy the
insulation
The circuit-breaker should be
mounted in the place protect against
splashing spraying water.
Circuit-breakers should be mounted
in accordance with instructions.
The protection degree of circuit-
breakers could be up to IP30 (comply with
the demands of IEC60947-1), and the
protection degree is IP20 without protective
cover up and down.
Main performance GM8-E series electronic distribution
protection moulded case circuit-breaker
equipped with electronic release GER23E
which adopted microprocessor technology,
it can ensure the high accuracy of tripping
, high reliable of acting and the accuracy of
acting can not be inuenced by the change
of ambient air temperature. GER23E could
be integrated on the circuit-breaker and
achieve kinds of characteristic protection
of distribution circuit in the condition of
without external power supply. GER23E
has three-levels protective function and
has better selective combining with other
protective device of the circuit.
Three-levels protective function:
Both Ir and Ii could be set or adjusted by
the users according to the requriement of
load current, Isd and Tsd could be adjusted
with Li and can be off; electronic controller
do not need external power supply and
current signal and control power supply
comes from the ring currenttransformer
internal circuit-breakers;
Pre-alarm indicator: when the load
current exceed preinstall current, the LED
PAL on the panel of circuit-breaker turn
yellow;
Over-load indicator: when the load
current exceed setting current, LED
34
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Electronic over-current releaseOver-load indicated lump
Pre-alarm indicated lump
0.7Ir Indicated lump
Test Test Port: Verication the reliability of
controller
The current of pre-alarm IP can be adjusted
The current Ii of short-circuit instantaneous can be adjusted The function of short-circuit short-time delay could be adjusted with Ii, can be offThe current Ir of over-load long-time delay can be adjusted
160
125
140
180200
250
225
0.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A) Ii(Ir)Tsd=0.08s
GER23EIn=250A
Ip(Ir)
Ii2Isd= Isd (OFF)
OVER
PAL
70%
OVER on the panel of circuit-breaker
turn red;
Reliable back-up protection: when
the short-circuit current exceed I20Im,
the back-up electromagnetic tripping
device of circuit-breaker acting;
Provide hand special tester: test
the reliable of electronic controller internal
circuitbreaker.
Ze ro - f l ashove r : mak ing the
distr ibution system more safety and
reliable.
The exper t sys tem cascade
protection: according to the rated current
In of circuit-breaker, the tripping time and
returnability time of shortcircuit short-
time delay have been set, so the cascade
coordination could be simple.
Comply with the EMC requirements of
GB14048.2 annex J.
Category o f 4 -po le circuit-breakers
Classication according to the type of
neutral pole (pole N):
Type A: Pole N is non-equipped
with overcurrent tripping device, which
is making always and do not closing or
opening with other three poles.
Type B: Pole N is non-equipped with
overcurrent tripping device, which always
closing or opening with other three poles
contact rstly and then opening .
Type C: Pole N is equipped with
over-current tripping device, which always
closing or opening with other three poles
contact rstly and then opening .
Type D: Pole N is equipped with over-
current tripping device, which is making
always and do not closing or opening with
other three poles. Over-current tripping
value of pole.
35
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
The diagram of cascade protection expert system for GM8-E series circuit-breaker
GW8 conventional circuit-breaker
The acting time of short-circuit short-time delayprotection
Tsd is set 0.4s
GM8-800 630/E electronic moulded case circuit-breaker
The acting time of short-circuit short-time delay protection
Tsd is set 0.2s
GM8-400/E electronic moulded case circuit-breaker
The acting time of short-circuit short-time delay protection
Tsd is set 0.13s
GGM8-250/E electronic moulded case circuit-breaker
The acting time of short-circuit short-time delay protection
Tsd is set 0.08s
GM8-125/E In=125A electronic moulded case circuit-breaker
The acting time of short-circuit short-time delay protection
Tsd is set 0.05s
GM8-125/E In=63 32A Electronic mouldeed case circuit-breaker
The acting time of short-circuit short-time delay protection
Tsd is set 0.03s
The select ive of
cascade protection time
of GM8-E series circuit-
breaker is obta ined
basing on a great deal
o f exper imenta t ion ,
t h e a c t i n g t i m e o f
upstream larger than
the sum of the acting
t ime of downstream
and the acting time of
operational device. Tsd
is internal xed and can
not be adjusted, which
co-ordination with Isd.
36
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Technical specicationsType GM8-125/E GM8-250/E GM8-400/E GM8-630/E GM8-800/EFrame size Inm A 125 250 400 630 800Rated current In A 3263125 250 400 630 800The code of short-circuit breaking capacity H R G H R G H R G H R G H R G
Rated ultimate short-circuit breaking capacity Icu
AC 400V kA 50 70 85 50 70 85 50 70 100 50 70 100 50 70 100AC 690V kA 25 25 25 25 25
Rated service short-circuit breaking capacity Ics
AC 400V kA 35 50 70 35 50 70 50 70 75 50 70 75 50 70 75AC 690V kA 10 10 15 15 15
Pole number P 34Rate insulation voltage Ui ACV 800Rate impulse withstand voltage Uimp V 8000Rate operational voltage Ue ACV 400690Short-time withstand current Icw kA/0 .8s 5 7.6 9.6
Over-load long-time delay protective current IrA
In=32A16~32 AdjustableIn=63A32~63 AdjustableIn=125A 63~125 Adjustable
125~250
Adjustable
200~400
Adjustable
315~630
Adjustable
400~800
Adjustable
Acting time of Over-load(long-time delay)protection(at 2Ir)s
100Internal xed
100Internal xed
120Internal xed
120Internal xed
120Internal xed
short-circuit instantaneous protective current IiA
Three-levels protection5-8-10-12Ir Adjustable Two-levels protection5-10-12Ir Adjustable
Short-circuit Short-time delay
protectio
Acting current Isd Isd A 50%Ii (Adjusted with li )or OFF
Acting time Tsd
s
Inverse time-delay IsdI1.5Isd Accord with I
2t=1.5Isd2Tsd
Denite time-delay1.5IsdIIi
In=3263A0.03Internal xedIn=125A0.05Internal xed
0.08Internal xed
0.13Internal xed
0.20Internal xed
0.20Internal xed
Pre-Alarm(for indication) Starting current IpA 0.70.750.80.850.90.951.0IrAdjustable 0.7Ir Indicated lump 0.7Ir10% The indicated lump shall turn on continuous
PAL pre-alarm indicated lump When the current up to Ip, the lump shall be ashing (Interval 1s );
Over-load indicated lump 1.2Ir5%Flashing (Interval 1s ) Arc distance mm 0 Note
Utilization category A B
Prospective-maximizationmaintenance durability
Mechanical/Electrical440V,In/2 times 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500
Test durability Mechanical/Electrical times 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000
Overalldimensions
W mm 90 105 140 140 210L mm 174 184 284 284 302Hmm 68 86 68 86 103 103 103
Mounting typeFixed front : none, rear: B , plug-in type (C), withdrawable type(C2)
(Only suitable for the circuit-breaker of frame size 400A)
Internalaccessories
Cassette accessories
Auxiliary switch AX Note
Alarm switch AL Shunt release SHT U n d e r - v o l t a g e r e l e a s e UVT
Externalaccessories
Motor-driven operational device P
Turning handle operational mechanism Z
Connecting bar L Mechanica l in ter lock ing MI
Note 1 When the protective cover of GM8-125 and GM8-250 is removed 9.5mm in height, the arc distance50mm;When the protective cover of GM8-400 GM8-630 and GM8-800 is removed 13.5mm in height , the arc distance 100mm; All 4P products are short ashover. means this function is provided;means without this function.
37
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
I
Schematic diagram of GM8-E electronic release
1GM8-125/E electronic release
In=32A
In=63A
In=125A
Characteristic curve
2GM8-250/E electronic release
160
125
140
180200
250
225
0.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A) Ii(Ir)Tsd=0.08s
GER23EIn=250A
Ip(Ir)
Ii2Isd= Isd (OFF)
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
ICharacteristic curve
20
16
25
32
0.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A) Ii(Ir)Tsd=0.03s
GER23EIn=32A
Ip(Ir)
Ii2Isd= Isd (OFF)
40
32
5650
63
0.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A) Ii(Ir)Tsd=0.03s
GER23EIn=63A
Ip(Ir)
Ii2Isd= Isd (OFF)
70
63
8090
100
110
125
0.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A) Ii(Ir)Tsd=0.05s
GER23EIn=125A
Ip(Ir)
Ii2Isd= Isd (OFF)
38
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
3GM8-400/E electronic release
4GM8-630/E electronic release
5GM8-800/E electronic release
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
ICharacteristic curve
Characteristic curve
Characteristic curve
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
I
t Ir
IiTsd
Isd=OFFIsd= Ii12
Tr
I
250
200
225
315
400
3500.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A)
Ii(Ir)
Tsd=0.13s
test
GER23EIn=400A
Ip(Ir)
Ii2Isd= Isd (OFF)
450
315
400
500
630
5600.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A)
Ii(Ir)
Tsd=0.2s
test
GER23EIn=630A
Ip(Ir)
Ii2Isd= Isd (OFF)
630
400
500
700
800
7500.8
0.7
0.9
1.0
10
5
8
125
12
10
Ir(A)
Ii(Ir)
Tsd=0.2s
test
GER23EIn=800A
Ip(Ir)
Ii2Isd= Isd (OFF)
39
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
1Inverse time-delay acting characteristic of over-load long-time delay protection as table1
Protective characteristic data of circuit-breaker
Inverse time-delay acting characteristic of over-load long-time delay protection
Current Acting time
Distribution
protection
1.05Ir 2h Not actingIn63A1hNot acting
1.3Ir 2h ActingIn63A1hActing
2Ir Acting time TrsInm=125A250A
Tr=100Internal xed
Inm=400A630A800A
Tr=120Internal xed
Note Inverse time-delay acting time of over-load long-time delay1.2IrIIsdaccords with I2T=2Ir2Tr
Over-load long -time delay acting time: TrTr20%
Time of duration of non-tripping(returnability time)70%Tr
2Acting characteristic of short-circuit short-time delay protection as table
3Acting charactristics of short-circuit (instantaneous protection as table
Acting charactristics of short-circuit (instantaneous protection
Setting current Ii A Three-levels protection581012IrAdjustable Two- levels protection51012IrAdjustable
Max acting time Ti s 0.025
Acting characteristic of short-circuit short-time delay protection
Frame size Inm A 125 250 400 630/800
Acting current Isd A 0.5Ii(Adjust with Ii, can be OFF)
Inverse time-delay acting time TIsdI1.5Isd s Accord with I
2T= 1.5Isd2Tsd
Denite time-delay
acting time
1.5IsdIIi
Setting time Tsd s
In=3263A 0.03Internal-xedIn=125A 0.05Internal-xed
0.08 Internal-xed 0.13Internal-xed 0.20Internal-xed
Returnability time Tdf
s
In=3263A 0.02
In=125A 0.040.06 0.10 0.16
Table1
40
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
4Acting characteristics of pre-alarm for indication as table 4
Acting characteristics of pre-alarm(for indication)
Setting current A 0.70.750.80.850.90.951.0IrAdjustable
5When the users have no special requirement ordering , the parameters of circuit-breaker tripping characteristics shall be installed according to table
Setting value of circuit-breaker factory
Over-load long-time delayprotection
Setting current Ir A In
Time-delay Tr s125A250A 400A630A800A
100sInternal-xed 120sInternal-xed
Short-circuit short-time
delay protection
Setting current Isd A 1/2Ii
T ime -de lay Tsd
s
125 250 400 630/800
In=3263A 0.03Internal-xed
In=125A 0.05Internal-xed
0.08
Internal-xed
0.13
Internal-xed
0.20
Internal-xed
Short-circuit instantaneous
protection
Setting current Ii
A10Ir
PAL Setting current Ip A 0.8Ir
6Power loss as table6
Table of power loss
Type CurrentAPower loss of three phaseVA
Front or rear connection Plug-in connection
GM8-125/E 125 35 40
GM8-250/E 250 62 70
GM8-400/E 400 115 125
GM8-630/E 630 190 210
GM8-800/E 800 262 294
41
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Tripping characteristic curve of GM8-E
Act
ing
time
Adjustable Non-adjustable
Parameters Adjusting range Routinel setting Note
Ir AIn=32 16202532
In
Adjustable
In=63 3240505663
Ii IrIsd ON 581012
10IrIsd OFF 51012
Isd Ir 0.5Iiadjust with Ii or OFF 0.5Ii
Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir
Tr s 1002Ir h 100Internal-xed
Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd
0.03Denite time-delay 0.03
In=32A63ACurrent settingIr
Tripping characteristic curve of GM8-125/E
42
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Parameters Adjusting range Routine setting Note
Ir A In=125 63708090100110125 In
AdjustableI i Ir
Isd ON 58101210Ir
Isd OFF 51012
Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii
Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir
Tr s 1002Ir 100Internal-xed
Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd
0.05Denite time-delay 0.05
Act
ing
time
Adjustable Non-adjustable
In=125ACurrent settingIr
Tripping characteristic curve of GM8-125/E
43
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
In=250ACurrent settingIr
Parameters Adjusting range Routine setting Note
Ir A In=250 125140160180200225250 In
AdjustableIi IrIsd ON 581012
10IrIsd OFF 51012
Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii
Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir
Tr s 1002Ir 100Internal-xed
Tsd sInverse time-delay I2T=1.5Isd2Tsd
0.08Denite time-delay 0.08
Tripping characteristic curve of GM8-250/E
Act
ing
time
Adjustable Non-adjustable
44
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Parameters Adjusting range Routine setting Note
Ir A In=400 200225250315350400 In
AdjustableIi IrIsd ON 581012
10IrIsd OFF 51012
Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii
Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir
Tr s 1202Ir 120
Internal-xedTsd s
Inverse time-delay Accord with I2T=1.5Isd2Tsd0.13
Denite time-delay 0.13
Act
ing
time
Adjustable Non-adjustable
In=400ACurrent settingIr
Tripping characteristic curve of GM8-400/E
45
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Act
ing
time
Adjustable Non-adjustable
In=630/800ACurrent settingIr
Parameters Adjusting range Routine setting Note
Ir AIn=630 315400450500560630
In
Adjustable
In=800 400500630700750800
Ii IrIsd ON 581012
10IrIsd OFF 51012
Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii
Ip A 0.70.750.80.850.90.951.0Ir Adjustable 0.8Ir
Tr s 1202Ir 120Internal-xed
Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd
0.20Denite time-delay 0.20
Tripping characteristic curve of GM8-630 800/E
Chapter 3 Technical Specications
Over-load long-time delay protection
Short-circuit short-time delay protection
Short-circuit instantaneous protection
Pre-alarm indicator
GM8-Z IntelligentMou lded case c i r cu i t - b reake r f o r distribution protection
47
Chapter 3 Technical Specications Chapter 3 Technical Specications 3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Application range
GM8-Z series moulded case circuit-
breakers are one of the new type circuit-
breakers which have been developed
using international advanced design and
manufacturing technology, menwhile, the
circuit-breaker complies with the demands
of the new international standards. The
rated insulation voltage of the circuit-
breakers is 800V, which could be used in
the circuit of AC 50Hz, rated operational
voltage 400V or 690V and rated operational
current 16A-800A, where the circuit-
breakers take the role of infrequent closing/
opening. The circuit-breaker has over-
load long-time delay, short-circuit short-
time delay and under-voltage protection
functions, so it can protect the distribution
circuit and the power equipment from
damage.
Design
According to rated ultimate short-
circuit breaking capacity, GM8-Z series
circuit-breakers can be classied into three
categories: H higher type (50KA) ; R high
type (70KA) ;G highest type (80~100KA) .
The circuit-breaker is feature with compact
size, high breaking capacity, zeroashover
and vibration resistance.
The circuit-breakers can be installed
ve r t i ca l l y (up r igh t ) o r ho r i zon ta l l y
(transverse) .
Wired adversely is forbidden for the
circuitbreakers,so 1,3 and 5 can only be
connected with power line:2,4 and 6 can
only be connected with load line.
The circuit-breaker has isolation
function and its corresponding symbol is
shown as
The protective characterist ic of
circuitbreaker is not influenced by the
change of ambient air temperature.Circuit-
breaker and over-current release are
integrated and provided as an equipments.
There are four kinds internal accessories:
auxil iary switch, alarm switch, shunt
re lease and under-vol tage re lease.
Interna accessories is easy to mounting
by adopting a cassette structure, so that
the accessories can be installed directly
in eld or in the factory.GM8- Z series can
be classified into two category: internal
controller (GM8-Zn) and external controller
(GM8-Zs ).
Standard
IEC60947-1 and GB14048.1-2006
General rules
IEC60947-2 and GB14048.2-2008
Low-voltage circuit-breakers
Normal serv ice and mounting conditions
The altitude of the site of installation
does not exceed 2000m;
The ambient air temperature dose
not exceed +40 and the lower limit of the
ambient air temperature is -5 , meanwhile,
its average over a periods of 24h does not
exceed +35 ;
The relative humidity of he air does
not exceed 50% at a maximum temperature
of +40 . Higher relative humidity may be
permitted at lower temperature e.g. 90% at
+20 . Special measures may be necessary
in cases of occasional condensation due to
variations in temperature;
Pollution degree: 3;
The circuit-breaker could not be
mounted in the place with the explosive
possibility, and there must be not any
gas which would corrode metal or any
conducting dust which would destroy
the insulation.
The circuit-breaker could not be
mounted in the place with the explosive
possibility, and there must be not any
gas which would corrode metal or any
conducting dust which would destroy the
insulation.
The circuit-breaker should be
mounted in the place protect against
splashing spraying water.
Circuit-breakers should be mounted
in accordance with instructions.
The protection degree of circuit-
breakers could be up to IP30 (comply with
the demands of IEC60947-1) , and the
protection degree is IP20 without protective
cover up and down.
Main characteristic
GM8-Zn(intelligent internal controller)
and GM8-Zs external controller series
distribution protection moulded case circuit-
breaker equipped with electronic release
GER53Z and GER53ZS which adopted
microprocessor technology, it can ensure
the high accuracy of tripping , high reliable
of acting and the accuracy of acting can not
be inuenced by the change of ambient air
temperature. GER53Z could be integrated
on the circuit-breaker and achieve kinds
of characteristic protection of distribution
circuit in the condition of without external
power supply. GM8-Z intelligent distribution
protection moulded case circuitbreaker
has three-levels protective function and
has better selective combining with other
protective device of the circuit.
Three-levels protective function:
Both current and time of release could
be installed by users according to the
requriement of load current and system.
Intelligent controller do not need
external power supply and current signal
and control power supply comes from the
ring currenttransformer internal circuit-
breakers.
48
Chapter 3 Technical Specications3
BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.
Function diagram of GM8-Zn controllerOver-load indicated lump
Pre-alarm indicated lump
0.7Ir Indicated lump
Test Port: Verication the reliability of controller
Pre-alarm current adjustable
Short- circuit instantaneous current adjustable
Short- circuit short-time delay time adjustable
Short- circuit short-time delay current adjustable
Over-load long-time delay time adjustable
Over-load long-time delay current adjustable
150
60
30
90
16
120.8
.7
.9
1.0
8
3
5
1012
14
OFF
4
2
3
58
12 .06
.1
.2.3
OFF
10
160
125
140
180200
250
225
Ir(A) Tr(s) Tsd(s) Ii(Ir)Isd(Ir) Ip(Ir)
OVER
PAL
70%
Pre-alarm indicator: when the load
current exceed preinstall current, the LED
PAL on the panel of circuit-breaker turn
yellow.
Over-load indicator: when the load
current exceed setting current, LED OVER
on the panel of circuit-breaker turn red.
LCD liquid crystal panel: GM8-
Zs circuitbreaker equips with liquid crystal
panel.
Reliable back-up protection: when
the short-circuit current exceed 20Im, the
back-up electromagnetic tripping device of
circuit-breaker acting.
Provide hand special tester: test
the reliable of intelligent controller internal
circuitbreaker.
Zero - f lashover : mak ing the
distribution system more safety and
reliable.
Accurate cascade coordination
and could be adjusted: the acting current
and acting time of unstream/downstream
circuir-breakers could be installed by
users. So, it is easy to achieve exact
coordination and selective protection.
Comply with the EMC requirements of
GB14048.2 annex J.
Category of 4-pole circuit-breakers
Classication according to the type of
neutral pole (pole N):
Type A: Pole N is non-equipped
with overcurrent tripping device, which
is making always and do not closing or
opening with other three poles.
Type B: Pole N is non-equipped with
overcurrent tripping device, which always
closing or opening with other three poles
(contact rstly and then opening ).
Type C: Pole N is equipped with
over-current tri