  • CONTENTS

    Chapter 1 Outline of GM8 Series 3

    Chapter 2

    Improvements through spur with long accumulation 13

    Chapter 3 Technology specications 23

    Chapter 4 Accessories 63

    Chapter 5 Overall and mounting dimensions 75

    Chapter 6 Purchase terms and conditions 86

  • Chapter 1 Outline of GM8 Series

    Data table for quick selection of GM8 series moulded case circuit-

    breaker 4

    Type explanation of GM8 series moulded case circuit-breaker 6

    Six types optional release 8

    Tripping indication module T1 11

    Function indicating diagram of control panel 12

  • 4Chapter 1 Outline of GM8 Series1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Type GM8-125 GM8-250 GM8-400 GM8-630 GM8-800

    Frame size Inm A 125 250 400 630 800

    Rated current InThermomagnetic type A 101620253240506380100125 125140160180200225250 250315350400 400500630 400500630700800

    Electronic type Intelligent type A 3216~326332~6312563~125 250125~250 400200~400 630315~630 800400~800

    Pole number P 34 34 34 34 34

    Rated insulation voltage Ui ACV 800 800 800 800 800

    Rated operational voltage Ue ACV 400690 400690 400690 400690 400690

    Rated impulse withstand voltage Uimp kV 8 8 8 8 8

    Short-time withstand current Icw kA /0.8s 5 7.6 9.6

    Utilization category A A AB AB AB

    Short-circuit

    breaking capacity

    Code M H R G M H R G M H R G M H R G M H R G

    Rated ultimate short-circuit breaking capacity Icu

    AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100

    AC 690V kA 25 25 25 25 25

    Rated service short-circuit breaking capacity Ics

    AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75

    AC 690V kA 10 10 15 15 15

    Release type

    Thermomagnetic type TM Note

    Electromagnetic type X

    Electronic type E

    Intelligent type(Internal controller Zn

    Intelligent type(External controller Zs

    Arc distance mm 0 0 0 2 0 2 0

    Prospective-maximization

    maintenance durability Mechanical/Electrical440VIn/2 time 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500

    Test durability Mechanical/Electrical time 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000

    Overall dimensions

    Wmm 90 105 140 140 210

    L mm 174 184 284 284 302

    H mm 68 86 68 86 103 103 103

    Mounting type Fixed type front : none, rear: B ), plug-in type (C) Fixed type front : none, rear: B ), plug-in type

    (C)Fixed type front : none, rear: B ), plug-in type (C)withdrawable

    type(C2)Fixed type front : none, rear: B ), plug-in type (C)

    withdrawable type(C2)Fixed type front : none, rear: B ), plug-in type (C)

    withdrawable type(C2)

    Internal accessories

    (Cassette accessories)

    Auxiliary contact AX

    Alarm contact AL

    Shunt release SHT

    Under-voltage release UVT

    External accessories

    Power-driven operating device P

    Turning handle operating device Z

    Connecting bar L

    Tripping indication module TI

    Mechanical interlocking MI

    Note 1 TMNon-adjustable thermomagnetic distribution protection TMF: Non-adjustable thermomagnetic generator protection TMB: Non-adjustable thermomagnetic transformer protection TMD Non-adjustable thermomagnetic motor protection; TMU: Non-adjustable thermomagnetic mine-used circuit-breaker. 2 When the protective cover 9.5mm in height of GM8-125 and GM8-250 is removed, the arc distance50mm; When the protective cover 13.5mm in height of GM8-400 GM8-630 and GM8-800 is removed, the arc distance100mm; All 4P products are short ashover. 3 Only suitable for GM8-Zs intelligent circuit-breaker. 4 means this function is provided means without this function. 5 Ano articial time-delay when a short-circuit occurs; B: articial time-delay when a short-circuit occurs.

    Data table for quick selection of GM8 series moulded case circuit-breaker

  • 5Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Type GM8-125 GM8-250 GM8-400 GM8-630 GM8-800

    Frame size Inm A 125 250 400 630 800

    Rated current InThermomagnetic type A 101620253240506380100125 125140160180200225250 250315350400 400500630 400500630700800

    Electronic type Intelligent type A 3216~326332~6312563~125 250125~250 400200~400 630315~630 800400~800

    Pole number P 34 34 34 34 34

    Rated insulation voltage Ui ACV 800 800 800 800 800

    Rated operational voltage Ue ACV 400690 400690 400690 400690 400690

    Rated impulse withstand voltage Uimp kV 8 8 8 8 8

    Short-time withstand current Icw kA /0.8s 5 7.6 9.6

    Utilization category A A AB AB AB

    Short-circuit

    breaking capacity

    Code M H R G M H R G M H R G M H R G M H R G

    Rated ultimate short-circuit breaking capacity Icu

    AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100

    AC 690V kA 25 25 25 25 25

    Rated service short-circuit breaking capacity Ics

    AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75

    AC 690V kA 10 10 15 15 15

    Release type

    Thermomagnetic type TM Note

    Electromagnetic type X

    Electronic type E

    Intelligent type(Internal controller Zn

    Intelligent type(External controller Zs

    Arc distance mm 0 0 0 2 0 2 0

    Prospective-maximization

    maintenance durability Mechanical/Electrical440VIn/2 time 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500

    Test durability Mechanical/Electrical time 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000

    Overall dimensions

    Wmm 90 105 140 140 210

    L mm 174 184 284 284 302

    H mm 68 86 68 86 103 103 103

    Mounting type Fixed type front : none, rear: B ), plug-in type (C) Fixed type front : none, rear: B ), plug-in type

    (C)Fixed type front : none, rear: B ), plug-in type (C)withdrawable

    type(C2)Fixed type front : none, rear: B ), plug-in type (C)

    withdrawable type(C2)Fixed type front : none, rear: B ), plug-in type (C)

    withdrawable type(C2)

    Internal accessories

    (Cassette accessories)

    Auxiliary contact AX

    Alarm contact AL

    Shunt release SHT

    Under-voltage release UVT

    External accessories

    Power-driven operating device P

    Turning handle operating device Z

    Connecting bar L

    Tripping indication module TI

    Mechanical interlocking MI

  • 6Chapter 1 Outline of GM8 Series1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    The 8th series

    moulded

    case circuit-

    breaker of

    the brand of

    SECURELUCKY

    Type explanation of GM8 series moulded case circuit-breaker

    Frame size

    Inm=125

    Inm=250

    Inm=400

    Inm=630

    Inm=800

    Short-circuit breaking capacity code

    M ypical type 35kANote

    H Higher type50kA

    R High type70kA

    G Highest type85~100kA

    Omit Zero ashover

    G Short ashover

    Connection mode code

    Omit Front

    B Rear

    C Plug-in

    C2 Withdrawable Note

    GM8 125 H 3 TM G B

    Tripping type code

    Distribution protection Transformer protection Generator protection Motor protection Mine-used circuit-breaker

    TM Thermomagnetic release TMB Thermomagnetic release TMFThermomagnetic

    release TMDThermomagnetic

    release TMUThermomagnetic

    release

    E Electronic release MD Electromagnetic release EU Electronic release

    Zn Intelligent internal controller ZUn Intelligent internal controller

    Zs Intelligent external controller ZUs Intelligent external controller

    Tn Communication internal controller XU Electromagnetic release

    Ts Communication external controller

    X Electromagnetic release

    Examples:

    GM8-125M/3TM In=80A

    Meaning: GM8 series circuit-breaker, frame size is 125A, breaking capacity is 35A, 3P, with thermomagnetic release, rated

    current is 80A.

    GM8-400H/3Zs SHT+AX TIs In=400A

    Meaning: GM8 series circuit-breaker, frame size is 400A, breaking capacity is 50A, 3P , with intelligent internal controller,

    auxiliary switch and shunt release, tripping indication module can be optional orded, rated current is 400A.

    Note:Eg products can be used for ground protection.

    Pole number

    3:Three-pole

    4A Note:Four-pole

    4B:Four-pole

    4C:Four-pole

    4D:Four-pole

  • 7Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Rated current

    P AC230V 230VSHT+ALAX MIL TIs 80AIn=

    TIs Tripping indication module of external controller (separated installation) Note

    Note: 1 Type Zn, Zs and E without M-type breaking capacity

    2 Only suitable for the circuit-breaker which frame size400 A.

    3 Only GM8-Zs could equip with optional module.

    4 Classication according to the type of neutral pole (pole N):

    Type A: Pole N is non-equipped with over-current tripping device, which is making always and do not closing or opening with other

    three poles.

    Type B: Pole N is non-equipped with over-current tripping device, which always closing or opening with other three poles (contact

    rstly and then opening).

    Type C: Pole N is equipped with over-current tripping device, which always closing or opening with other three poles (contact rstly

    and then opening).

    Type D: Pole N is equipped with over-current tripping device, which is making always and do not closing or opening with other three

    poles.

    Over-current tripping value of pole N needs to be provided by the users.

    Operational type Operational voltage

    Omit Body Omit

    Z Manual Omit

    P Motor-driven AC 110V

    AC 230V

    AC 400V

    DC 24V

    DC 110V

    DC 220V

    Internal accessories Operational voltage

    AL Alarm switch Omit

    AX Auxiliary switch Omit

    SHT Shunt release AC230VAC400VDC24VDC110VDC220V

    UVT Under-voltage release AC230VAC400V

    External accessories

    L Connecting bar

    External accessories

    M Mechanical interlocking

  • 8Chapter 1 Outline of GM8 Series1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Not

    e:

    3:

    thre

    e-po

    le; 4

    :four

    -pol

    e st

    anda

    rd ty

    pe; 4

    A:fo

    ur-p

    ole

    A ty

    pe;

    N

    one:

    dist

    ribut

    ion

    prot

    ectio

    n; D

    : mot

    or p

    rote

    ctio

    n;

    N

    one:

    adj

    usta

    ble

    oper

    atio

    n ty

    pe;

    SD

    : adj

    usta

    ble

    alar

    m ty

    pe;

    O

    mit

    front

    con

    nect

    ion

    B

    rear

    con

    nect

    ion

    C1

    plug

    -in c

    onne

    ctio

    nC

    2w

    ithdr

    awab

    le

    rate

    d cu

    rren

    t40

    0A

    ;

    O

    pera

    tiona

    l typ

    eO

    mit

    body

    Z

    man

    ual

    P

    mot

    or-d

    riven

    . O

    ptio

    nal o

    pera

    tiona

    l vol

    tage

    of m

    otor

    -driv

    e:A

    C11

    0V

    AC

    230V

    DC

    24V

    D

    C11

    0V

    DC

    220V

    ;

    A

    Lal

    arm

    con

    tact

    A

    X

    auxi

    liary

    con

    tact

    S

    HT

    shun

    t rel

    ease

    LE

    Ele

    ctro

    nic

    resi

    dual

    cu

    rren

    t op

    erat

    ed

    circ

    uit-

    brea

    ker

    100

    Fram

    e si

    ze

    D

    Pro

    tect

    ion

    type

    SD

    Res

    idua

    l

    curr

    ent

    oper

    ated

    type

    B

    Con

    nect

    ion

    type

    P A

    C23

    0

    Ope

    ratio

    n ty

    pe

    SH

    T+A

    LAX

    230

    V

    Opt

    iona

    l in

    tern

    al

    acce

    ssor

    ies

    In=8

    0A

    Rat

    ed

    curr

    ent

    4 Pole

    num

    ber

    The

    8th

    serie

    s m

    ould

    edca

    se c

    ircui

    t-br

    eake

    r of

    the

    bran

    d of

    S

    EC

    UR

    ELU

    CK

    Y

    GM

    8

    Type

    exp

    lana

    tion

    of G

    M8L

    E s

    erie

    s le

    akag

    e pr

    otec

    tion

    circ

    uit-b

    reak

    er

    TM

    Ther

    mom

    agne

    tic

    rele

    ase

  • 9Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Six types optional release

    1Rated current of thermomagnetic release GM8-TM:10~800A

    Tripping types Release code Protection function Acting curve

    Thermomagnetic type

    release

    Distribution

    protection:TM,M

    Transformer

    protection:TMB

    Generator

    protection:TMF

    Motor

    protection:TMD,MD

    Mine-used circuit-

    breaker:TMU

    Over-load long time-delay

    protection

    (thermal) ( internal xed )

    Short-circuit instantaneous

    protection(electromagnetic)

    (internal xed )

    2Rated current of electromagnetic release GM8-X (distribution protection): 10~800A

    Tripping types Release code Protection function Acting curve

    Electromagnetic

    release

    Distribution protection:XMine-used circuit-

    breaker:XU

    Short-circuit back-upprotection (electromagnetic)

    (built-in xed)

    3Rated current of electronic release GM8-E (distribution protection): 16~800A

    Tripping types Release code Protection function Acting curve

    Electronic releaseDistribution protection:E

    Mine-used circuit-breaker:EU

    Over-load long time-delay protection(electronic)

    ( adjustable )

    Short-circuit short time-delay protection

    (electronic)(adjustable with Ii)

    Short-circuit instantaneousprotection(electronic)

    (adjustable )Short-circuit back-up

    protection(electromagnetic) 20Inm20%

    PAL pre-alarm(for indication)(adjustable )

    t

    I

    TM

    t

    I

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    I

    t

    I

    M

  • 10

    Chapter 1 Outline of GM8 Series1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    4Rated current of intelligent release GM8-Zn (distribution protection): 16~800A

    Tripping types Release code Protection function Acting curve

    Intelligent

    release(internal)

    Distribution

    protection:Zn

    Mine-used circuit-

    breaker:ZUn

    Over-load long time-delay protection(intelligent) (

    adjustable )Short-circuit short time-delay

    protection (intelligent) ( adjustable )

    Short-circuit instantaneousprotection (intelligent) (

    adjustable )Short-circuit back-up

    protection(electromagnetic)

    PAL pre-alarm(for indication)(adjustable )

    5Rated current of GM8-Zs intelligent release(distribution protection): 16~800A

    Tripping types Release code Protection function Acting curve

    Intelligent

    release(internal)

    Distribution

    protection:Zs

    Mine-used circuit-

    breaker:ZUs

    Over-load long time-delay protection

    (intelligent) ( adjustable )Short-circuit short time-delay

    protection (intelligent) ( adjustable )

    Short-circuit instantaneousprotection (intelligent) (

    adjustable )Short-circuit back-up

    protection(electromagnetic)

    PAL pre-alarm(for indication)(adjustable )

    6Rated current of GM8-Tn/Ts intelligent communicative release: 16~800A

    Tripping types Release code Protection function Acting curve

    Intelligent

    communicative release

    Distribution

    protection:T

    Over-load long time-delay protection

    (electronic) ( adjustable )Short-circuit short time-delay

    protection (electronic) ( adjustable )

    Short-circuit instantaneousprotection (electronic) (

    adjustable )Short-circuit back-up

    protection(electromagnetic)

    PAL pre-alarm(for indication)(adjustable )

    Net communications based on the

    MODBUS protocol

    t Ir

    IiTsd

    Tsd=OFFIsdTr

    I

    t Ir

    IiTsd

    Tsd=OFFIsdTr

    I

    t Ir

    IiTsd

    Tsd=OFFIsdTr

    I

  • 11

    Chapter 1 Outline of GM8 Series Chapter 1 Outline of GM8 Series 1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Tripping indication module Ti

    1Outline

    TIs

    For GM8-Zs series circuit-breaker, we could equip tripping indication

    module. Main function:

    (1) Offering tripping signal node output (automatic reset);

    (2) Fullling the fault type indication with external controller.

    2Function and combination explanation

    L : O v e r - l o a d

    l ong t ime-de lay

    protection

    S : Sho r t - c i r cu i t

    short time-

    delay protection

    I: Short-circuit

    i n s t a n t a n e o u s

    protection

    PAL : PAL p re -

    alarm

    indication

    Offering tr ipping signal

    node output

    Local display fault tripping

    category

    consistently (manual reset)

    Function

    When module TIs is mounted on

    the circuit-breaker,power supply

    and signal could be provided after

    circuit-breaker tr ipping and fault

    tripping category could be displayed

    consistently on external controller.

    The module TIs is specially designed,

    and can be separately mounted to

    adapt to the compact installation

    space.

    GM8-Zs circuit-breaker should be used co-ordination with module Tls

    parameter adjustment

    of L,S,I,Ip

    Three phase current

    circularly display

    L,S,I fault tr ipping

    indication

    (should be supported by

    module TI)

    Note: TIs module need external AC220V power supply connected by users. If the voltage of power supply is not AC220V, please mark it in ordering.

    + =

  • 12

    Chapter 1 Outline of GM8 Series1

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    10 12 510

    58

    12

    I sd=I i2 I sdOFF 0.8 0.9

    0.7 1.0

    I n=250AGER23E

    160180

    200225

    125

    140

    250t sd=0.08s I iI rI rA I pI rFunction indicating diagram of controller panel1Function sketch map of GM8-E electronic controller Over-load (long time-delay ) current setting IrShort-circuit instantaneous current setting IiPre-alarm current setting Ip

    2Function sketch map of GM8-Zn/Tn intelligent internal controller

    Over-load (long time-delay ) current setting IrOver-load (long time-delay ) time setting TrShort-circuit (short time-delay ) current setting IsdShort-circuit (short time-delay ) time setting TsdShort-circuitinstantaneouscurrent setting IiPre-alarm current setting Ip

    3Function sketch map of GM8-Zs/Ts intelligent external controller

    Over-load (long-time delay )fault tripping indicationShort-circuit (short-time delay) fault tripping indicationShort-circuit (instantaneous) fault tripping indicationResetting button

    0.7Ir Indicated lumpPre-alarm indicated lumpOver-load indicated lumpTest terminalSafety lock hole

    Liquid crystal display screen

    Use co-ordination with Ti module

    "Cancel" buttonDown buttonUp buttonSet/Enter"button

    150

    60

    30

    90

    16

    120.8

    .7

    .9

    1.0

    8

    3

    5

    1012

    14

    OFF

    4

    2

    3

    58

    12 .06

    .1

    .2.3

    OFF

    10

    160

    125

    140

    180200

    250

    225

    Ir(A) Tr(s) Tsd(s) Ii(Ir)Isd(Ir) Ip(Ir)

  • Chapter 1 Outline of GM8 Series

    Performance improvement 14

    Advanced and safe arc spray outward-oriented design 14

    Zero-ashover 15

    Degree of protection IP30 15

    New contact system 15

    Ics=100% Icu 15

    The novel external controller 16

    Suitable for isolation 17

    Back-up electromagnetic protection 17

    Mounting, operation and maintenance

    Cassette accessories 17

    Safety operating device 18

    Safe and reliable connection type 18

    Compact size 18

    Standardization aperture 19

    Customized design 19

    Advanced technical theory 20

    Modulization communication function 21

    Chapter 2 Improvements through spur with long accumulation

  • 14

    Chapter 2 Improvements through spur with long accumulation2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Performance improvementAdvanced and safe arc spray outward-oriented design

    Circuit-breaker is a kind of protective electrical installation,

    which protects lines and equipment from damage due to short-

    circuit, especially from personal injure, so it must meet high safety

    design standard. In former applications, people often injured

    by flashover because of the unreasonable arc spray outward-

    oriented design. In order to avoid these accidents, GM8 series

    circuit-breakers adopt the advanced patent technique of arc spray

    outward-oriented design to provide a reliable protection for users.

    Arc spray outward-oriented: it is known that the high dense

    high-temperature ion and electron would spread into the low

    density and low-temperature medium. So, in the period of arc

    generate to extinguished, after it passed arc extinguish chamber

    and continues to spray out of circuit-breaker, this time, the oriented

    structure can give an out-spray direction to it.

    Arc temperature: the temperature of the arc can up to

    5000~8000

    The backward arc-oriented design and its harm

    In figure1, a insulating paper (Nomex) be mounted above

    the arc extinguish chamber of circuit-breaker. At the usual time,

    the elastic insulating paper can protect against foreign body drop

    into circuit-breaker. But when short-circuit occurs, the paper will be

    bounced outward because of the spraying high temperature and

    pressure gas generated by flashover, and the arc will be spray

    forward out of circuit-breaker along the paper surface. At this

    time, if somebody is closed to the handle or the jet orice is near

    the mental cabinet, burn accident or another short-circuit will be

    happened.

    Why the arc-oriented structures are designed spraying

    forward instead of upward in some factories? The long tripping

    breaking time, bad current-limiting capacity and long out-

    spray(upward) distance are the main reasons for these products.

    Due to the ashover distance requirement of above circuit-breaker

    can not exceed 50~100mm in IEC60947-2, they design the

    ashover forward, but backward and unsafe.

    The harmfulness of ashover spraying forward are:

    1. Result in that the arcs connect together and misoperation

    of upper stage (as gure1)

    Usually, there aren't interphase barriers at the front of circuit-

    breaker (the plane), if a short-circuit fault happened, ashover out

    of each pole is spraying forward, the arc from two adjoining poles

    will connect together and lead to a short-circuit at lead-in side,

    cause a misoperation of the upper stage, result in an expanding

    fault; Meanwhile, It can burn the cabinet and cause a human injury

    accident.

    2. Circuit-breakers mounted in an open cabinet

    If a short-circuit has been exit in circuit, operators will be

    injured by ashover sprayed to them when they close to the circuit-

    breaker. Because the circuit-breaker will trip due to short-circuit

    and spray ashover outward, however, the ashover will be spray

    to operator because of the oriented effect of Nomex insulating

    paper.(as gure2)

    3. Circuit-breakers mounted in a closed cabinet

    When there is a short-circuit current in system, the moveable

    and static contacts breaking, and arcs generated in each pole

    spray forward and connect together by mental cabinet will lead to

    an interphase short-circuit, at last, cause a false action of upper

    stage circuit-breaker. The arcs spraying to mental enclosure will

    generate high temperature to melt down the mental cabinet, and

    someone stands front of it will be hurt and cause a safety accident.

    4. Circuit-breakers equip with manual or motor-driven

    operation device

    The four mounting feet of manual or motor-driven operation

    device are mounted in the middle of three-phase lead-in side. The

    arcs which spray forward and pass the mental mounting feet will

    cause a interphase short-circuit again at the lead-in side and lead

    to a false action of upper stage circuit-breaker. Arcs spraying to

    manual operation device will generate high temperature to melt

    down the enclosure of drawer, someone will be shock if his hand

    or body contacts the cabinet.

    GM8 advanced arc spray outward-oriented design

    The arc spraying direction of our advanced circuit-breaker is

    designed upward but not forward, it avoids the above safety risk

    of those backward circuit-breakers. More details see GM8 series

    circuit-breaker.

  • 15

    Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    The elastic Nomex insulating paper where the arc sprays to operator or to the mental enclosure of distribution cabinet.

    Spraying forward causes an interphase short-circuit

    Figure1 The moulded case circuit-breakers

    structure of usual domestic manufacturers

    Figure2 Operate the circuit-breaker directly by

    operator Circuit-breaker

    Cabinet

    FIrure3 The mounting of circuit-breaker in closed

    x cabinet

    Mounting board

    Flashover forward causing interphase short-circuit

    Mounting foot

    FIrure4 The mounting of circuit-breaker in drawer

    Flashover direction -- upward

    FIrure5 Arc spray outward-oriented design of

    GM8 series circuit-breaker

  • 16

    Chapter 2 Improvements through spur with long accumulation2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Repulsed position of moving contact

    Conductor on static contact

    Repulsed position of static contact

    Flexible connection

    Ia current

    Ia current

    Conductor on static contact

    Moving contact

    Static contactFlexible connection

    Zero-ashoverGM8 series circuit-breaker adopts an innovative arc

    control system,so it can quench arc effectively and realize

    the zero-ashover easily.

    Protection degree IP30Special protective cover can stop any objects with

    the diameter of 2.5 mm into the internal of enclosure, the

    protection degree could up to IP 30.

    Novel contact systemGM8 series circuit-breaker adopts a special designed contact system, which possesses

    some merits such as strong repulsion and long open range.

    When the circuit-breaker is making:

    Movable contact bear a tension and a repulsion as well, named FIac and FIbc

    respectively.

    Static contact bears two repulsions, named FIab and FIbc respectively.

    When the short-circuit current reaches the acting value of the instantaneous release, the

    above-mentioned forces will accelerate the speed of moving /static contact arc, increase the

    arc length and make the arc quenching easier.

    The innovative design of the bidirectional repelling system breakthrough the limitations

    of traditional design, that is moving contact upward moving and static contact xed. Then the

    opening range between moving contact and static contact is increased greatly.

    By adopting this contact system, which has big repulsion and long opening range, GM8

    series circuit-breaker is more easily to quench the arc, so it has a higher current-limit ability

    and short-circuit breaking capacity.

    Protective cover

    Protection degree IP30

    Contact construction of four repulsion

    Ics=100% Icu Thanks to its super current limiting ability, outstanding arc control system and the moving and static contact have superior withstand

    arcing ability, GM8 series circuit-breaker has an excellent performance: Ics=100%Icu.

    According to Standards GB14048.2 (IEC 60947-2), the test procedures of rated ultimate short-circuit breaking capacity (Icu) and rated service short-circuit breaking capacity (Ics) as follows:

    Rated ultimate

    short-circuit

    breaking

    capacity Icu

    Verication of overload release Reference temperature/ 2 times setting current/ acting within the longest time in 2 times setting current

    Rated ultimate short-circuit breaking capacity test

    Operation procedure: O-t-CONote: O-One time opening operation; t-interval; CO-One automatic opening right after one closing operation

    Verication of dielectric withstand capacity Take the larger one between 2Ue and 1000V, the leakage current shall not exceed 6mA (Isolation)

    Verication of overload release Reference temperature/ 2.5 times setting current/ acting within the longest time in 2 times setting current

    Rated service

    short-circuit

    breaking

    capacity Ics

    Rated service short-circuit breaking capacity test Operation procedure: O-t-CO-t-CO

    Verication of operational performance capability 5% of the electrical durability

    Verication of dielectric withstand capacity

    Take the larger one between 2Ue and 1000V, the leakage current shall not exceed 2mA (Isolation)

    Verication of temperature-rise The temperature of terminals don t exceed 80K

    Verication of overload release Reference temperature/ 1.45 times setting current/ acting in 2(1) hour

    According to the standards GB14048.2 (IEC947-2), Ics could be 25%, 50%, 75% or 100% of Icu.GM8 series circuit-breaker strictly follows the above-mentioned test procedures, achieves Ics=100%Icu reliably.

    Bidirectional repulsion of the moving/static contactGM8-125M/H/R/GGM8-250R/G

  • 17

    Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    The novel external controller

    The traditional systemWhen the customers have a higher requirement of

    maintainability and safety to the low voltage distribution systems, they will spend extra money to purchase the intelligent circuit-breaker installed in the distribution

    cabinet. One of their main purposes is: adjust the acting parameters by the adjustment button on the panel of intelligent circuit-breaker.

    Whereas, according to investigations, we found that the adjustment acting parameters is very difcult to realize. The reason lies in the external operating device (manual or motor-driven), an accessory which is widely used in the low voltage distribution cabinet.

    The handle is installed in the drawer of the circuit-breaker. As a result, the customers cant reach the adjustment panel, so the adjustment function is no-way to achieve.

    The price of intelligent circuit-breaker is 2 or 3 times higher than the normal thermomagnetic circuit-breaker which parameters are nonadjustable. It is absolutely a huge waste if the adjustment function cant work.

    The new system adopting external controllerIn order to solve the mentioned problem above,

    the intelligent controller of GM8-Zs series (belonging to GM8-Z) is external of the circuit-breaker, and connects with circuit-breaker by date lines.

    The ex terna l cont ro l le r adopts the same dimensions as the panel amperemeter, it can display the three phase current. So the clients could adjust the parameters on the drawer panel conveniently.

    The external control ler doesn t need any additional power supply and any auxiliaries, it can realize the following functions:

    Adjust all the acting parameters real time during the application process;

    Display the three phase current;Display the tripping type continually (TI module

    is needed).

    External controller

    External controller

    Intelligent circuit-breaker

    Amperemeter

    Amperemeter

    Circuit-breaker

  • 18

    Chapter 2 Improvements through spur with long accumulation2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Suitable for isolation

    By increasing the opening range between moving contact and static contact and enhancing the performance of the insulating material

    between the conductive parts, GM8 series circuit-breaker has isolation function.

    Back-up electromagnetic protectionBoth the electronic and intelligent circuit-breaker are equipped with a back-up protection release

    in a magnetic yoke type, its rated acting current is 20Inm (where Inm is frame size). The back-up

    protection release plays important roles in the following two aspects:

    (1) The back-up protection release will acting before the electronic release when the short-circuit

    current of distribution circuit exceeded 20Inm. Consequently, it can increase the acting sensitivity

    and maximum guarantee the safety of the power supply lines.

    (2) When the electronic release broke down, the back-up release will act a back-up protection

    function, providing double protection for the safety of the power supply lines.Back-up protection release of

    magnetic yoke type

    Installation, Operation and Maintenance

    Cassette Accessories

    The false action or failure action

    problem often occurs for moulded case

    circuit-breakers field use. Therefore,

    Beijing People's Electric Plant Co., Ltd.

    organized experts to analyze and they

    found that many problems were related

    to the error installation of accessories

    or foreign matters drop into the circuit-

    breakers after accessories installation.

    Because o f a l l these accessor ies '

    installation process is:

    Step 1: Press down the button "Trip"

    to make circuit-breaker tripping;

    Step 2: Twist off all big screws on the

    cover of circuit-breaker (In general, there

    are 8-12 big screws, so we need spend

    more time and bigger torque to do it.);

    Step 3: Open the cover of circuit-

    breaker (At this time, all parts in circuit-

    breaker are exposed and arc extinguishers

    always drop out.);

    Step 4: Install the accessories (During

    installing, some important parts of circuit-

    breakers, like tripping device and bimetal

    element, maybe touched unexpected, so

    their position will be changed and then

    affect the operation characteristic of circuit-

    breakers, sometimes operator's arms also

    be hurt and foreign matters easily drop

    into circuit-breaker, such as cable head);

    Step 5: Close the cover of circuit-

    breaker (in order to make sure the cover

    and body of circuit-breaker matched well,

    the accessories and internal parts must be

    at the correct position.);

    Step 6: Turn all the screws on cover

    tight (All screws must be tighten, otherwise

    it will affect the safety of circuit-breaker.

    When there is a short-circuit current, the

    high temperature and high pressure arc

    gas generated by movable and static

    contacts breaking may push off the cover

    and cause safety accidents.)

    On the whole, we can clearly find

    that above installation method not only

    inf luences the safety and operation

    characteristics of circuit-breaker, but also

    inconvenient to operation. At the same

    time, the normal functions of accessories

    will be affected if they are installed at an

    incorrect position or match with the circuit-

    breaker body not very well.

    Step 1 Step 2 Step 3 Step 4 Step 5

  • 19

    Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Safety operating device

    GM8 adopts a double layer insulation handle to guarantee the absolute

    safety of the operators.

    The first insulation protection: The handle is molded with high insulting

    property engineering plastics, which makes the handle has super-strong insulating

    property.

    The second insulation protection: As the well insulating design, the metal

    operating device connected with handle is isolated from the internal conductors.

    The adoption of the double insulation handle ensures the circuit-breaker is

    much safer and reliable even when the handle is damaged.

    Safety and reliable connection type

    Connection type of other manufacturers Improved connection type

    Tap on the static contact connector; screw it together with the external

    connector.This kind of connection is less reliable and easy to loosen.

    Adopting the iron nut to screw the connectors together with static contact, so

    it is more stable and reliable.

    Compact sizeThanks to the new conductive and arc control system scheme, GM8 circuit-breaker acts more stable and short-circuit breaking

    capacity is improved widely, what s more, the size is reduced substantially.

    GM8-630 shares the same case dimensions with GM8-400, which means GM8-630 is smaller, and the performance is much better

    than the primary version (the original width: 182mm, the original breaking capacity: 65kA; the present width: 140mm, the present breaking

    capacity: 100kA).

    182m

    m

    140m

    m

    GM8-630A/3P

    Breaking capacity 100kA

    Other domestic product 630A/3P

    Breaking capacity 65kA

    Imported product 630A/3P

    Breaking capacity:70kA

    External connecting board

    Connecting board self-fastening

    Static contact connecting board

    External connecting board

    Tightening with iron nut

    Static contact connecting board

    Insulating tube

    Movable contact

    Handle

  • 20

    Chapter 2 Improvements through spur with long accumulation2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    GM8-125A was improved and the thickness is reduced to 68 mm at the minimum.

    86m

    m

    68m

    m

    Standardization aperture

    GM8-125A/3P

    Breaking capacity 50kA

    Other domestic product 125A/3P

    Breaking capacity 50kA

    Imported product 125A/3P

    Breaking capacity:50kA

    Adopting novel design theory, the mounting dimensions of GW8 were modied into two types to make the manufacture process of

    complete equipment is much simpler.

    60 90

    125/250 Type 125/250 Type

    Customized design

    There are use indication windows on the panel

    of the circuit-breaker, so the purpose of circuit

    could be labeled on the circuit-breaker directly.

    The circuit label could be served with the

    circuit-breakers, but the users should explain the

    purpose of circuit-breaker when ordering.

    When the accessory is installed, it is very

    convenient to lead out its signal lines to the

    corresponding terminals along the lateral lead slot.

    Due to this merit, GM8 series circuit-breakers can

    be mounted next to each other, leaving the mount

    size more compact.

  • 21

    Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Advanced technical theory

    1.High reliability and safety of the circuit

    GM8 series circuit-breaker processes with the virtual effective value; it can fundamentally prevent

    the false tripping of the intelligent circuit-breakers to realize the accurate protection. The circuit

    analysis plan as the following graph:

    2.Pre-alarm indication function

    Both the electronic and intelligent circuit-breaker have a pre-warning function. They

    can indicate the over load condition before circuit-breaker tripping. When the load current

    exceeded the setting value, the micro processor will output a pre-alarm signal through the

    solid-state relay to light the PAL pre-alarm indicated lump.

    CT

    CT

    CT

    CT *OQVU0VUQVUI

    CV

    PSS

    WDT

    CPU

    SSW

    LSW

    PSW

    A/D 0WFSMPBEDVSSFOUJOEJDBUFEMVNQ1SFBMBSNJOEJDBUFEMVNQ Pre-alarm output

    **OTUBOUBOFPVTDJSDVJU$77PMUBHFTUBCJMJ[JOHDJSDVJU1441IBTFDIPPTJOHTBNQMFDJSDVJU8%5$MPDLEPHUJNJOHDJSDVJU4484IPSUUJNFEFMBZTPGUXBSF-48-POHUJNFEFMBZTPGUXBSF1481SFBMBSNTPGUXBSFThe terminals of power supply Breaker-circuit operational device Customized integration apparatus

    The terminal of load Load current indicated lump70%

    Test input Characteristics setting

    Converter

    Tripping coil

    Micro processor

    Trigger circuit

    Rectification apparatus

    4BNQMJOHBOE"%DPOWFSTJPO$BMDVMBUJPOPGUIFFGGFDUJWFWBMVF$IBSBDUFSJTUJDTPGQSPDFTTJOHUIFMPOHUJNFEFMBZQSFBMBSN

  • 22

    Chapter 2 Improvements through spur with long accumulation2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Modulization of communication functions

    GM8-T series (also belonging to GM series circuit-breaker) is a communicative product. The communication accessories includes: external communication module, RS485 interface extended plate, communication controller and series of conguration software. The external communication module is connected to the circuit-breaker. The clients can conveniently build the communication net consistent with the MODBUS protocol, the schematic diagram as follows

  • 23

    Chapter 2 Improvements through spur with long accumulation Chapter 2 Improvements through spur with long accumulation 2

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Communication protocol

    Field-bus protocol MODBUS-RTU is comply with the international standard IEC61158. The physical layer electrical interface is the serial RS485, which consistent with the international standard TIA/EIA-485-A. The date frame format is 1 start bit, 8 date bits, 2 stop bits, none verification (Including odd and even verifying). The report format is address code (1 bit), function code (1 bit), date domain (maximum 252 bits), CRC verication (2 bits).

    Network characteristics

    The communication medium is double-wiring shielded line. Each communication line can connect with 32 devices at the maximum and with 1000 meters at its longest distance. A repeater is needed if the distance is exceeded than 1000 meters, and a brancher has to be adopted if there is a branch.The standard band rate is 19200bps (could be set to 9600bps or 38400bps). Besides, all the devices connected to the same bus must share the same band rate and parity check, and the address of the slave station cant repeat.When there are too many devices connected to the bus, a RS485 adapter is needed to connect more devices. The devices in one slave station cant exceed 247 in the MODBUS communication system.

    Communication controller

    The communication controller is connected with the circuit-breaker by special communication lines. The controller can set the parameters (slave-station address, communication bond rate, current parameter, tripping parameter), display the parameters, electric switching control, display warning (overload, short-circuit fault) and communication (local and remote communication). The communication controller doesnt need external power supply and consequently is very convenient to be installed in the distribution cabinet. The controller will automatically scan the circumscribed devices when turned on and build a dynamic address list. The limitation is no more than 32 devices. The controller can achieve remote communication by connecting it to the remote monitoring computer.

    Remote communication

    By connecting the circuit-breaker and monitoring computer with double-wiring shielded line and RS485 converter. To set, display and communicate locally and remotely, we should connect the controller with the circuit-breaker before it was connected to the remote monitoring computer.

    I f the circui t-breaker adopts electr ic operating device, the remote control can achieve. If adopt network instruments, remote measurement of the electrical parameters can achieve.Due to adopting the standard protocol MODBUS-RTU, the controller can be further interfaced with the industrial Ethernet.

    Conguration software

    The moni tor ing computer can adopt c o n f i g u r a t i o n s o f t w a r e t o a c h i e v e t h e management of power and distribution systems.The conguration software is usually customized mode. The inter face is beaut i fu l , v isual , friendly, various and convenient for the device management.Integration network solutions are also ready for our clients.

  • Chapter 3 Technical Specications

    GM8-TM thermomagnetic moulded case circuit-breaker 24

    GM8-E electronic moulded case circuit-breaker for distribution

    protection 31

    GM8-Z intelligent moulded case circuit-breaker for distribution

    protection 45

    GM8-X electromagnetic moulded case circuit-breaker for distribution

    protection 57

  • GM8-TM SeriesThermomagne t i c mou lded case circuit-breaker

    Over-load long-time delay protection

    Short-circuit instantaneous protection

  • 26

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Application range

    GM8-TM se r i es mou lded case

    c i rcu i tbreakers are one of the new

    type circuit-breakers which have been

    developed using international advanced

    design and manufacturing technology,

    menwhile, the circuit-breaker complies

    with the demands of the new international

    standards. The rated insulation voltage

    of the circuit-breakers is 800V, which

    could be used in the circuit of AC 50Hz,

    rated operational voltage 400V or 690V

    and rated operational current 10A-800A,

    where the circuit-breakers take the role of

    infrequent closing/opening and infrequent

    motor starting-up. The circuit-breakers are

    feature with over-current, short-circuit and

    under-voltage protection functions, so it

    can protect the distribution circuit and the

    power equipment from damage.

    Design

    According to rated ultimate short-

    circuit breaking capacity, GM8-TM series

    circuit-breakers can be classied into four

    categories: M typical type (35KA); H higher

    type (50KA); R high type (70KA);G highest

    type (80 100KA). The circuit-breaker is

    feature with compact size, high breaking

    capacity, zero-flashover and vibration

    resistance.

    The c i r cu i t - b reake rs can be

    installed vertically (upright) or horizontally

    (transverse).

    Wired adversely is forbidden for the

    circuit-breakers, so 1,3 and 5 can only

    be connected with power line:2,4 and 6

    can only be connected with load line.

    The circuit-breaker has isolation

    function and corresponding symbol is

    shown as

    The circuit-breaker can be used at

    ambient air temperature below 40 and do

    not need lowering capacity.

    Circuit-breaker and over-current

    release are integrated and provided as an

    equipments. There are four kinds internal

    accessories: auxiliary switch, alarm switch,

    shunt release and under-voltage release.

    Internal accessories is easy to mount

    by adopting a cassette type, so that the

    accessories can be installed directly in eld

    or in the factory.

    Standard

    IEC60947-1 and GB14048.1-2000

    General rules

    IEC60947-2 and GB14048.2-2001

    Lowvoltage circuit-breakers

    IEC60947-4 and GB14048.4-2003

    Contactor and motor starter

    IEC60947-5-1 and GB14048.5-

    2001Electromechanical control circuit

    devices.

    Normal serv ice and mounting conditions

    The altitude of the site of installation

    does not exceed 2000m;

    The ambient air temperature

    dose not exceed +40 and the lower limit

    of the ambient air temperature is -5 ,

    meanwhile, its average over a periods of

    24h does not exceed +35 .

    The relative humidity of he air

    does not exceed 50% at a maximum

    temperature of +40 . Higher relative

    humidities may be permitted at lower

    temperature e.g. 90% at +20 . Special

    measures may be necessary in cases of

    occasional condensation due to variations

    in temperature;

    Pollution degree: 3;

    Mounting categories: The mounting

    category of main circuit, under-voltage

    release is and other auxiliary and control

    circuits is ;

    The circuit-breaker could not be

    mounted in the place with the explosive

    possibility, and there must be not any

    gas which would corrode metal or any

    conducting dust which would destroy the

    insulation.

    The circuit-breaker should be

    mounted in the place protect against

    splashing spraying water.

    Circuit-breakers should be mounted

    in accordance with instructions.

    The protection degree of circuit-

    breakers could be up to IP30 (comply with

    the demands of IEC60947-1), and the

    protection degree is IP20 without protective

    cover up and down.

    Main characteristic

    GM8-TM thermomagnetic moulded

    case circuit-breakers have over-load long-

    time delay and short-circuit instantaneous

    two-levels protection function.

    GM8-TM series circuit-breakers

    can be equipped with internal cassette

    accessories.

    GM8-TM series circuit-breakers are

    zeroashover.

    Category o f 4 -po le circuit-breakers

    Classication according to the type of

    neutral pole (pole N):

    Type A: Pole N is non-equipped

    with overcurrent tripping device, which

    is making always and do not closing or

    opening with other three poles.

    Type B: Pole N is non-equipped with

    overcurrent tripping device, which always

    closing or opening with other three poles

    contact rstly and then opening .

    Type C: Pole N is equipped with

    over-current tripping device, which always

  • 27

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Protective characteristics

    Distribution protection

    Over-load long-time

    delay protection

    Distribution protectionTM

    Generator protectionTMF

    Transformer protectionTMB

    Mine-used circuit-breakerTMU

    1.05InCold state 2h Not actingIn63A1hNot acting

    1.3InHeat state 2h ActingIn63A1h Acting

    InInternal xed

    Short-circuitinstantaneous

    protection

    Distribution protectionTMM 10In20%

    Generator protectionTMF 3In20%

    Transformer protectionTMB 5In20%

    Mine-used circuit-breakerTMU 10In20%

    Motor protection

    Over-load long-timedelay protection

    Motor protectionTMD

    1.0InCold state 2h Not acting

    1.2InHeat state 2h Acting

    1.5InHeat state 8min ActingIn225A4min Acting

    7.2InCold state 6sTp20s ActingIn225A4sTp10s Acting

    Short-circuitinstantaneous

    protectionMotor protectionTMDMD 12In20%

    Note: the code explanation of thermomagnetic release

    TThermal release MMagnetic release BTransformer protection

    FGenerator protection DMotor protection UMine-used circuit-breaker

    closing or opening with other three poles

    (contact rstly and then opening ).

    Type D: Pole N is equipped with over-

    current tripping device, which is making

    always and do not closing or opening with

    other three poles.

    Over-current tripping value of pole N

    needs to be provided by the users.

  • 28

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Technical specications

    Type GM8-125/TM GM8-250/TM GM8-400/TM GM8-630/TM GM8-800/TM

    Frame size Inm A 125 250 400 630 800

    Rated current InA12510080

    6350403225201610

    250225200180160140

    125

    400350315250

    630500400800700

    630500400

    Short-circuit instantaneous acting current Ii ADistribution protectionTM10In20%Generator protectionTMF3In20%Mine-used protectionTMU10In20% Transformer protectionTMB5In20%Motor protectionTMD12In20%

    The code of rated short-circuit breaking capacity M H R G M H R G M H R G M H R G M H R G

    Rated ultimate short-circuit breaking capacity Icu

    AC 400V kA 35 50 70 85 35 50 70 85 35 50 70 100 35 50 70 100 35 50 70 100

    AC 690V kA 25 25 25 25 25

    Rated service short-circuit breaking capacity

    Ics

    AC 400V kA 35 35 50 70 35 35 50 70 35 50 70 75 35 50 70 75 35 50 70 75

    AC 690V kA 10 10 15 15 15

    Pole number P 34

    Rate insulation voltage Ui ACV 800

    Rate impulse withstand voltage Uimp V 8000

    Rate operational voltage Ue ACV 400690

    Arc distance mm 0 Note

    Uitilization category A

    Prospective-maximization maintenance durability

    Mechanical/Electrical440VIn/2times 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500

    Test durability Mechanical/Electrical times 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000

    Overall

    dimensions

    mm 90 105 140 140 210

    L mm 174 184 284 284 302

    H mm 68 86 68 86 103 103 103

    Mounting type Fixed front : none, rear: B , plug-in type (C), withdrawable type(C2)

    Internal accessories

    Cassette

    accessories

    Auxiliary switch AX Note

    Alarm switch AL

    Shunt release SHT

    Under-voltage release

    UVT

    External

    accessories

    Motor-driven operational

    device P

    Turning handle operational

    mechanism Z

    Connecting bar L

    Mechanical interlocking

    MI

    Note When the protective cover of GM8-125 and GM8-250 is removed 9.5mm in height, the arc distance50mm;

    When the protective cover of GM8-400 GM8-630 and GM8-800 is removed 13.5mm in height , the arc distance 100mm;

    All 4P products are short ashover.

    means this function is provided;means without this function.

  • 29

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    GM8-125/Acting characteristics curve and temperature compensating curve

    GM8-TM acting characteristics curve and temperature compensating curve

    Act

    ing

    time

    x100%Rated current

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

    In=63A~125AMax.63~125

    Act

    ing

    time

    x100%Rated current

    63A~125A

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

  • 30

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    GM8-250/TM Acting characteristics curve and temperature compensating curve

    Act

    ing

    time

    x100%Rated current

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

    GM8-400/TM Acting characteristics curve and temperature compensating curve

    Act

    ing

    time

    x100%Rated current

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

  • 31

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    GM8-630/TM Acting characteristics curve and temperature compensating curve

    GM8-800/ Acting characteristics curve and temperature compensating curve

    Act

    ing

    time

    x100%Rated current

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

    Act

    ing

    time

    x100%Rated current

    Temperature compensating curve

    Rated ambient air temperature 40 Ambient air temperature ()

    Set

    ting

    curr

    ent(%

    )

  • Chapter 3 Technical Specications

    Over-load long-time delay protection

    Short-circuit short-time delay protection

    Short-circuit instantaneous protection

    Pre-alarm indicator

    GM8-E ElectronicMoulded case c i rcui t -breaker for distribution protection

  • 33

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Application range

    GM8-E series moulded case circuit-

    breakers are one of the new type circuit-

    breakers which have been developed

    using international advanced design and

    manufacturing technology. Meanwhile, the

    circuit-breaker complies with the demands

    of the new international standards and

    widen the range of stage dif ference

    coordination. The rated insulation voltage

    of the circuit-breakers is 800V, which could

    be used in the circuit of AC 50Hz, rated

    operational voltage 400V or 690V and rated

    operational current 16A-800A, where the

    circuit-breakers take the role of infrequent

    turn on/off and infrequent motor starting-

    up. The circuit-breaker has over-load long-

    time delay, short-circuit short-time delay

    and under-voltage protection functions, so

    it can protect the distribution circuit and the

    power equipment from damage.

    Design

    According to rated ultimate short-

    circuit breaking capacity, GM8-E series

    circuit-breakers can be classied into three

    categories: H higher type 50KA ; R high

    type 70KA ;G highest type 80 100KA . The

    circuit-breaker is feature with compact size,

    high breaking capacity, zeroashover and

    vibration resistance.

    The circuit-breakers can be installed

    vert ical ly upright or horizontal ly

    transverse .

    Wired adversely is forbidden for the

    circuitbreakers, so 1,3 and 5 can only be

    connected with power line:2,4 and 6 can

    only be connected with load line.

    The circuit-breaker has isolation

    function and its corresponding symbol is

    shown as .

    The protective characteristic of

    circuitbreaker is not influenced by the

    change of ambient air temperature Circuit-

    breaker and over-current release are

    integrated and provided as an equipments.

    There are four kinds internal accessories:

    auxil iary switch, alarm switch, shunt

    release and under-voltage release. Internal

    accessories is easy to mounting by

    adopting a cassette structure, so that the

    accessories can be installed directly in eld

    or in the factory.

    Standard

    IEC60947-1 and GB14048.1-2000

    General rules.

    IEC60947-2 and GB14048.2-2001

    Lowvoltage circuit-breakers.

    Normal serv ice and mounting conditions

    The altitude of the site of installation

    does not exceed 2000m;

    The ambient air temperature dose

    not exceed +40 and the lower limit

    of the ambient air temperature is -5 ,

    meanwhile, its average over a periods of

    24h does not exceed +35 .

    The relative humidity of he air

    does not exceed 50% at a maximum

    temperature of +40 . Higher relative

    humidi ty may be permit ted at lower

    temperature e.g. 90% at +20 . Special

    measures may be necessary in cases of

    occasional condensation due to variations

    in temperature;

    Pollution degree: 3.

    Mounting categories: The mounting

    category of main circuit, under-voltage

    release is and other auxiliary and control

    circuits is ;

    The circuit-breaker could not be

    mounted in the place with the explosive

    possibility, and there must be not any

    gas which would corrode metal or any

    conducting dust which would destroy the

    insulation

    The circuit-breaker should be

    mounted in the place protect against

    splashing spraying water.

    Circuit-breakers should be mounted

    in accordance with instructions.

    The protection degree of circuit-

    breakers could be up to IP30 (comply with

    the demands of IEC60947-1), and the

    protection degree is IP20 without protective

    cover up and down.

    Main performance GM8-E series electronic distribution

    protection moulded case circuit-breaker

    equipped with electronic release GER23E

    which adopted microprocessor technology,

    it can ensure the high accuracy of tripping

    , high reliable of acting and the accuracy of

    acting can not be inuenced by the change

    of ambient air temperature. GER23E could

    be integrated on the circuit-breaker and

    achieve kinds of characteristic protection

    of distribution circuit in the condition of

    without external power supply. GER23E

    has three-levels protective function and

    has better selective combining with other

    protective device of the circuit.

    Three-levels protective function:

    Both Ir and Ii could be set or adjusted by

    the users according to the requriement of

    load current, Isd and Tsd could be adjusted

    with Li and can be off; electronic controller

    do not need external power supply and

    current signal and control power supply

    comes from the ring currenttransformer

    internal circuit-breakers;

    Pre-alarm indicator: when the load

    current exceed preinstall current, the LED

    PAL on the panel of circuit-breaker turn

    yellow;

    Over-load indicator: when the load

    current exceed setting current, LED

  • 34

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Electronic over-current releaseOver-load indicated lump

    Pre-alarm indicated lump

    0.7Ir Indicated lump

    Test Test Port: Verication the reliability of

    controller

    The current of pre-alarm IP can be adjusted

    The current Ii of short-circuit instantaneous can be adjusted The function of short-circuit short-time delay could be adjusted with Ii, can be offThe current Ir of over-load long-time delay can be adjusted

    160

    125

    140

    180200

    250

    225

    0.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A) Ii(Ir)Tsd=0.08s

    GER23EIn=250A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    OVER

    PAL

    70%

    OVER on the panel of circuit-breaker

    turn red;

    Reliable back-up protection: when

    the short-circuit current exceed I20Im,

    the back-up electromagnetic tripping

    device of circuit-breaker acting;

    Provide hand special tester: test

    the reliable of electronic controller internal

    circuitbreaker.

    Ze ro - f l ashove r : mak ing the

    distr ibution system more safety and

    reliable.

    The exper t sys tem cascade

    protection: according to the rated current

    In of circuit-breaker, the tripping time and

    returnability time of shortcircuit short-

    time delay have been set, so the cascade

    coordination could be simple.

    Comply with the EMC requirements of

    GB14048.2 annex J.

    Category o f 4 -po le circuit-breakers

    Classication according to the type of

    neutral pole (pole N):

    Type A: Pole N is non-equipped

    with overcurrent tripping device, which

    is making always and do not closing or

    opening with other three poles.

    Type B: Pole N is non-equipped with

    overcurrent tripping device, which always

    closing or opening with other three poles

    contact rstly and then opening .

    Type C: Pole N is equipped with

    over-current tripping device, which always

    closing or opening with other three poles

    contact rstly and then opening .

    Type D: Pole N is equipped with over-

    current tripping device, which is making

    always and do not closing or opening with

    other three poles. Over-current tripping

    value of pole.

  • 35

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    The diagram of cascade protection expert system for GM8-E series circuit-breaker

    GW8 conventional circuit-breaker

    The acting time of short-circuit short-time delayprotection

    Tsd is set 0.4s

    GM8-800 630/E electronic moulded case circuit-breaker

    The acting time of short-circuit short-time delay protection

    Tsd is set 0.2s

    GM8-400/E electronic moulded case circuit-breaker

    The acting time of short-circuit short-time delay protection

    Tsd is set 0.13s

    GGM8-250/E electronic moulded case circuit-breaker

    The acting time of short-circuit short-time delay protection

    Tsd is set 0.08s

    GM8-125/E In=125A electronic moulded case circuit-breaker

    The acting time of short-circuit short-time delay protection

    Tsd is set 0.05s

    GM8-125/E In=63 32A Electronic mouldeed case circuit-breaker

    The acting time of short-circuit short-time delay protection

    Tsd is set 0.03s

    The select ive of

    cascade protection time

    of GM8-E series circuit-

    breaker is obta ined

    basing on a great deal

    o f exper imenta t ion ,

    t h e a c t i n g t i m e o f

    upstream larger than

    the sum of the acting

    t ime of downstream

    and the acting time of

    operational device. Tsd

    is internal xed and can

    not be adjusted, which

    co-ordination with Isd.

  • 36

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Technical specicationsType GM8-125/E GM8-250/E GM8-400/E GM8-630/E GM8-800/EFrame size Inm A 125 250 400 630 800Rated current In A 3263125 250 400 630 800The code of short-circuit breaking capacity H R G H R G H R G H R G H R G

    Rated ultimate short-circuit breaking capacity Icu

    AC 400V kA 50 70 85 50 70 85 50 70 100 50 70 100 50 70 100AC 690V kA 25 25 25 25 25

    Rated service short-circuit breaking capacity Ics

    AC 400V kA 35 50 70 35 50 70 50 70 75 50 70 75 50 70 75AC 690V kA 10 10 15 15 15

    Pole number P 34Rate insulation voltage Ui ACV 800Rate impulse withstand voltage Uimp V 8000Rate operational voltage Ue ACV 400690Short-time withstand current Icw kA/0 .8s 5 7.6 9.6

    Over-load long-time delay protective current IrA

    In=32A16~32 AdjustableIn=63A32~63 AdjustableIn=125A 63~125 Adjustable

    125~250

    Adjustable

    200~400

    Adjustable

    315~630

    Adjustable

    400~800

    Adjustable

    Acting time of Over-load(long-time delay)protection(at 2Ir)s

    100Internal xed

    100Internal xed

    120Internal xed

    120Internal xed

    120Internal xed

    short-circuit instantaneous protective current IiA

    Three-levels protection5-8-10-12Ir Adjustable Two-levels protection5-10-12Ir Adjustable

    Short-circuit Short-time delay

    protectio

    Acting current Isd Isd A 50%Ii (Adjusted with li )or OFF

    Acting time Tsd

    s

    Inverse time-delay IsdI1.5Isd Accord with I

    2t=1.5Isd2Tsd

    Denite time-delay1.5IsdIIi

    In=3263A0.03Internal xedIn=125A0.05Internal xed

    0.08Internal xed

    0.13Internal xed

    0.20Internal xed

    0.20Internal xed

    Pre-Alarm(for indication) Starting current IpA 0.70.750.80.850.90.951.0IrAdjustable 0.7Ir Indicated lump 0.7Ir10% The indicated lump shall turn on continuous

    PAL pre-alarm indicated lump When the current up to Ip, the lump shall be ashing (Interval 1s );

    Over-load indicated lump 1.2Ir5%Flashing (Interval 1s ) Arc distance mm 0 Note

    Utilization category A B

    Prospective-maximizationmaintenance durability

    Mechanical/Electrical440V,In/2 times 15000/12000 15000/12000 15000/12000 15000/8000 15000/7500

    Test durability Mechanical/Electrical times 8500/6000 7000/3000 4000/2000 4000/1500 2500/1000

    Overalldimensions

    W mm 90 105 140 140 210L mm 174 184 284 284 302Hmm 68 86 68 86 103 103 103

    Mounting typeFixed front : none, rear: B , plug-in type (C), withdrawable type(C2)

    (Only suitable for the circuit-breaker of frame size 400A)

    Internalaccessories

    Cassette accessories

    Auxiliary switch AX Note

    Alarm switch AL Shunt release SHT U n d e r - v o l t a g e r e l e a s e UVT

    Externalaccessories

    Motor-driven operational device P

    Turning handle operational mechanism Z

    Connecting bar L Mechanica l in ter lock ing MI

    Note 1 When the protective cover of GM8-125 and GM8-250 is removed 9.5mm in height, the arc distance50mm;When the protective cover of GM8-400 GM8-630 and GM8-800 is removed 13.5mm in height , the arc distance 100mm; All 4P products are short ashover. means this function is provided;means without this function.

  • 37

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    I

    Schematic diagram of GM8-E electronic release

    1GM8-125/E electronic release

    In=32A

    In=63A

    In=125A

    Characteristic curve

    2GM8-250/E electronic release

    160

    125

    140

    180200

    250

    225

    0.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A) Ii(Ir)Tsd=0.08s

    GER23EIn=250A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    ICharacteristic curve

    20

    16

    25

    32

    0.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A) Ii(Ir)Tsd=0.03s

    GER23EIn=32A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    40

    32

    5650

    63

    0.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A) Ii(Ir)Tsd=0.03s

    GER23EIn=63A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    70

    63

    8090

    100

    110

    125

    0.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A) Ii(Ir)Tsd=0.05s

    GER23EIn=125A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

  • 38

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    3GM8-400/E electronic release

    4GM8-630/E electronic release

    5GM8-800/E electronic release

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    ICharacteristic curve

    Characteristic curve

    Characteristic curve

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    I

    t Ir

    IiTsd

    Isd=OFFIsd= Ii12

    Tr

    I

    250

    200

    225

    315

    400

    3500.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A)

    Ii(Ir)

    Tsd=0.13s

    test

    GER23EIn=400A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    450

    315

    400

    500

    630

    5600.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A)

    Ii(Ir)

    Tsd=0.2s

    test

    GER23EIn=630A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

    630

    400

    500

    700

    800

    7500.8

    0.7

    0.9

    1.0

    10

    5

    8

    125

    12

    10

    Ir(A)

    Ii(Ir)

    Tsd=0.2s

    test

    GER23EIn=800A

    Ip(Ir)

    Ii2Isd= Isd (OFF)

  • 39

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    1Inverse time-delay acting characteristic of over-load long-time delay protection as table1

    Protective characteristic data of circuit-breaker

    Inverse time-delay acting characteristic of over-load long-time delay protection

    Current Acting time

    Distribution

    protection

    1.05Ir 2h Not actingIn63A1hNot acting

    1.3Ir 2h ActingIn63A1hActing

    2Ir Acting time TrsInm=125A250A

    Tr=100Internal xed

    Inm=400A630A800A

    Tr=120Internal xed

    Note Inverse time-delay acting time of over-load long-time delay1.2IrIIsdaccords with I2T=2Ir2Tr

    Over-load long -time delay acting time: TrTr20%

    Time of duration of non-tripping(returnability time)70%Tr

    2Acting characteristic of short-circuit short-time delay protection as table

    3Acting charactristics of short-circuit (instantaneous protection as table

    Acting charactristics of short-circuit (instantaneous protection

    Setting current Ii A Three-levels protection581012IrAdjustable Two- levels protection51012IrAdjustable

    Max acting time Ti s 0.025

    Acting characteristic of short-circuit short-time delay protection

    Frame size Inm A 125 250 400 630/800

    Acting current Isd A 0.5Ii(Adjust with Ii, can be OFF)

    Inverse time-delay acting time TIsdI1.5Isd s Accord with I

    2T= 1.5Isd2Tsd

    Denite time-delay

    acting time

    1.5IsdIIi

    Setting time Tsd s

    In=3263A 0.03Internal-xedIn=125A 0.05Internal-xed

    0.08 Internal-xed 0.13Internal-xed 0.20Internal-xed

    Returnability time Tdf

    s

    In=3263A 0.02

    In=125A 0.040.06 0.10 0.16

    Table1

  • 40

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    4Acting characteristics of pre-alarm for indication as table 4

    Acting characteristics of pre-alarm(for indication)

    Setting current A 0.70.750.80.850.90.951.0IrAdjustable

    5When the users have no special requirement ordering , the parameters of circuit-breaker tripping characteristics shall be installed according to table

    Setting value of circuit-breaker factory

    Over-load long-time delayprotection

    Setting current Ir A In

    Time-delay Tr s125A250A 400A630A800A

    100sInternal-xed 120sInternal-xed

    Short-circuit short-time

    delay protection

    Setting current Isd A 1/2Ii

    T ime -de lay Tsd

    s

    125 250 400 630/800

    In=3263A 0.03Internal-xed

    In=125A 0.05Internal-xed

    0.08

    Internal-xed

    0.13

    Internal-xed

    0.20

    Internal-xed

    Short-circuit instantaneous

    protection

    Setting current Ii

    A10Ir

    PAL Setting current Ip A 0.8Ir

    6Power loss as table6

    Table of power loss

    Type CurrentAPower loss of three phaseVA

    Front or rear connection Plug-in connection

    GM8-125/E 125 35 40

    GM8-250/E 250 62 70

    GM8-400/E 400 115 125

    GM8-630/E 630 190 210

    GM8-800/E 800 262 294

  • 41

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Tripping characteristic curve of GM8-E

    Act

    ing

    time

    Adjustable Non-adjustable

    Parameters Adjusting range Routinel setting Note

    Ir AIn=32 16202532

    In

    Adjustable

    In=63 3240505663

    Ii IrIsd ON 581012

    10IrIsd OFF 51012

    Isd Ir 0.5Iiadjust with Ii or OFF 0.5Ii

    Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir

    Tr s 1002Ir h 100Internal-xed

    Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd

    0.03Denite time-delay 0.03

    In=32A63ACurrent settingIr

    Tripping characteristic curve of GM8-125/E

  • 42

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Parameters Adjusting range Routine setting Note

    Ir A In=125 63708090100110125 In

    AdjustableI i Ir

    Isd ON 58101210Ir

    Isd OFF 51012

    Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii

    Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir

    Tr s 1002Ir 100Internal-xed

    Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd

    0.05Denite time-delay 0.05

    Act

    ing

    time

    Adjustable Non-adjustable

    In=125ACurrent settingIr

    Tripping characteristic curve of GM8-125/E

  • 43

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    In=250ACurrent settingIr

    Parameters Adjusting range Routine setting Note

    Ir A In=250 125140160180200225250 In

    AdjustableIi IrIsd ON 581012

    10IrIsd OFF 51012

    Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii

    Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir

    Tr s 1002Ir 100Internal-xed

    Tsd sInverse time-delay I2T=1.5Isd2Tsd

    0.08Denite time-delay 0.08

    Tripping characteristic curve of GM8-250/E

    Act

    ing

    time

    Adjustable Non-adjustable

  • 44

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Parameters Adjusting range Routine setting Note

    Ir A In=400 200225250315350400 In

    AdjustableIi IrIsd ON 581012

    10IrIsd OFF 51012

    Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii

    Ip A 0.70.750.80.850.90.951.0IrAdjustable 0.8Ir

    Tr s 1202Ir 120

    Internal-xedTsd s

    Inverse time-delay Accord with I2T=1.5Isd2Tsd0.13

    Denite time-delay 0.13

    Act

    ing

    time

    Adjustable Non-adjustable

    In=400ACurrent settingIr

    Tripping characteristic curve of GM8-400/E

  • 45

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Act

    ing

    time

    Adjustable Non-adjustable

    In=630/800ACurrent settingIr

    Parameters Adjusting range Routine setting Note

    Ir AIn=630 315400450500560630

    In

    Adjustable

    In=800 400500630700750800

    Ii IrIsd ON 581012

    10IrIsd OFF 51012

    Isd Ir 0.5Iiadjust with Iior OFF 0.5Ii

    Ip A 0.70.750.80.850.90.951.0Ir Adjustable 0.8Ir

    Tr s 1202Ir 120Internal-xed

    Tsd sInverse time-delay Accord withI2T=1.5Isd2Tsd

    0.20Denite time-delay 0.20

    Tripping characteristic curve of GM8-630 800/E

  • Chapter 3 Technical Specications

    Over-load long-time delay protection

    Short-circuit short-time delay protection

    Short-circuit instantaneous protection

    Pre-alarm indicator

    GM8-Z IntelligentMou lded case c i r cu i t - b reake r f o r distribution protection

  • 47

    Chapter 3 Technical Specications Chapter 3 Technical Specications 3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Application range

    GM8-Z series moulded case circuit-

    breakers are one of the new type circuit-

    breakers which have been developed

    using international advanced design and

    manufacturing technology, menwhile, the

    circuit-breaker complies with the demands

    of the new international standards. The

    rated insulation voltage of the circuit-

    breakers is 800V, which could be used in

    the circuit of AC 50Hz, rated operational

    voltage 400V or 690V and rated operational

    current 16A-800A, where the circuit-

    breakers take the role of infrequent closing/

    opening. The circuit-breaker has over-

    load long-time delay, short-circuit short-

    time delay and under-voltage protection

    functions, so it can protect the distribution

    circuit and the power equipment from

    damage.

    Design

    According to rated ultimate short-

    circuit breaking capacity, GM8-Z series

    circuit-breakers can be classied into three

    categories: H higher type (50KA) ; R high

    type (70KA) ;G highest type (80~100KA) .

    The circuit-breaker is feature with compact

    size, high breaking capacity, zeroashover

    and vibration resistance.

    The circuit-breakers can be installed

    ve r t i ca l l y (up r igh t ) o r ho r i zon ta l l y

    (transverse) .

    Wired adversely is forbidden for the

    circuitbreakers,so 1,3 and 5 can only be

    connected with power line:2,4 and 6 can

    only be connected with load line.

    The circuit-breaker has isolation

    function and its corresponding symbol is

    shown as

    The protective characterist ic of

    circuitbreaker is not influenced by the

    change of ambient air temperature.Circuit-

    breaker and over-current release are

    integrated and provided as an equipments.

    There are four kinds internal accessories:

    auxil iary switch, alarm switch, shunt

    re lease and under-vol tage re lease.

    Interna accessories is easy to mounting

    by adopting a cassette structure, so that

    the accessories can be installed directly

    in eld or in the factory.GM8- Z series can

    be classified into two category: internal

    controller (GM8-Zn) and external controller

    (GM8-Zs ).

    Standard

    IEC60947-1 and GB14048.1-2006

    General rules

    IEC60947-2 and GB14048.2-2008

    Low-voltage circuit-breakers

    Normal serv ice and mounting conditions

    The altitude of the site of installation

    does not exceed 2000m;

    The ambient air temperature dose

    not exceed +40 and the lower limit of the

    ambient air temperature is -5 , meanwhile,

    its average over a periods of 24h does not

    exceed +35 ;

    The relative humidity of he air does

    not exceed 50% at a maximum temperature

    of +40 . Higher relative humidity may be

    permitted at lower temperature e.g. 90% at

    +20 . Special measures may be necessary

    in cases of occasional condensation due to

    variations in temperature;

    Pollution degree: 3;

    The circuit-breaker could not be

    mounted in the place with the explosive

    possibility, and there must be not any

    gas which would corrode metal or any

    conducting dust which would destroy

    the insulation.

    The circuit-breaker could not be

    mounted in the place with the explosive

    possibility, and there must be not any

    gas which would corrode metal or any

    conducting dust which would destroy the

    insulation.

    The circuit-breaker should be

    mounted in the place protect against

    splashing spraying water.

    Circuit-breakers should be mounted

    in accordance with instructions.

    The protection degree of circuit-

    breakers could be up to IP30 (comply with

    the demands of IEC60947-1) , and the

    protection degree is IP20 without protective

    cover up and down.

    Main characteristic

    GM8-Zn(intelligent internal controller)

    and GM8-Zs external controller series

    distribution protection moulded case circuit-

    breaker equipped with electronic release

    GER53Z and GER53ZS which adopted

    microprocessor technology, it can ensure

    the high accuracy of tripping , high reliable

    of acting and the accuracy of acting can not

    be inuenced by the change of ambient air

    temperature. GER53Z could be integrated

    on the circuit-breaker and achieve kinds

    of characteristic protection of distribution

    circuit in the condition of without external

    power supply. GM8-Z intelligent distribution

    protection moulded case circuitbreaker

    has three-levels protective function and

    has better selective combining with other

    protective device of the circuit.

    Three-levels protective function:

    Both current and time of release could

    be installed by users according to the

    requriement of load current and system.

    Intelligent controller do not need

    external power supply and current signal

    and control power supply comes from the

    ring currenttransformer internal circuit-

    breakers.

  • 48

    Chapter 3 Technical Specications3

    BEIJING PEOPLE'S ELECTRIC PLANT CO., LTD.

    Function diagram of GM8-Zn controllerOver-load indicated lump

    Pre-alarm indicated lump

    0.7Ir Indicated lump

    Test Port: Verication the reliability of controller

    Pre-alarm current adjustable

    Short- circuit instantaneous current adjustable

    Short- circuit short-time delay time adjustable

    Short- circuit short-time delay current adjustable

    Over-load long-time delay time adjustable

    Over-load long-time delay current adjustable

    150

    60

    30

    90

    16

    120.8

    .7

    .9

    1.0

    8

    3

    5

    1012

    14

    OFF

    4

    2

    3

    58

    12 .06

    .1

    .2.3

    OFF

    10

    160

    125

    140

    180200

    250

    225

    Ir(A) Tr(s) Tsd(s) Ii(Ir)Isd(Ir) Ip(Ir)

    OVER

    PAL

    70%

    Pre-alarm indicator: when the load

    current exceed preinstall current, the LED

    PAL on the panel of circuit-breaker turn

    yellow.

    Over-load indicator: when the load

    current exceed setting current, LED OVER

    on the panel of circuit-breaker turn red.

    LCD liquid crystal panel: GM8-

    Zs circuitbreaker equips with liquid crystal

    panel.

    Reliable back-up protection: when

    the short-circuit current exceed 20Im, the

    back-up electromagnetic tripping device of

    circuit-breaker acting.

    Provide hand special tester: test

    the reliable of intelligent controller internal

    circuitbreaker.

    Zero - f lashover : mak ing the

    distribution system more safety and

    reliable.

    Accurate cascade coordination

    and could be adjusted: the acting current

    and acting time of unstream/downstream

    circuir-breakers could be installed by

    users. So, it is easy to achieve exact

    coordination and selective protection.

    Comply with the EMC requirements of

    GB14048.2 annex J.

    Category of 4-pole circuit-breakers

    Classication according to the type of

    neutral pole (pole N):

    Type A: Pole N is non-equipped

    with overcurrent tripping device, which

    is making always and do not closing or

    opening with other three poles.

    Type B: Pole N is non-equipped with

    overcurrent tripping device, which always

    closing or opening with other three poles

    (contact rstly and then opening ).

    Type C: Pole N is equipped with

    over-current tri