GFCI Presentation

Embed Size (px)

Citation preview

  • 8/12/2019 GFCI Presentation

    1/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-1

    Ground Fault

    CircuitInterrupters

  • 8/12/2019 GFCI Presentation

    2/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-2

    A GFCI will open the circuit when the current to ground

    exceeds some predetermined value (such as 5 milliamperes).

    They can be found as part of a circuit breaker in a

    distribution box or in a load center.

    They can be found as part of a duplex receptacle.

    Or, they can be found as part of an assembly at the

    end of a line cord.

    TEST

    RESET

    TEST

  • 8/12/2019 GFCI Presentation

    3/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-3

    LO

    A

    D

    Hot

    Neutral

    Start with a toroid core.

    Add hot and neutral windings.

    Adding a load will cause current

    to flow and magnetic flux in the core.

    Note that the flux created by the neutral

    wire opposes the flux from the hot wire.

  • 8/12/2019 GFCI Presentation

    4/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-4

    LO

    A

    D

    Hot

    Neutral

    The flux cancels.

    No flux means no output

    from the sense winding.

  • 8/12/2019 GFCI Presentation

    5/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-5

    LO

    A

    D

    Hot

    Neutral

    Lets add a ground fault.

    The fault current flows in the

    hot wire but not in the neutral.

  • 8/12/2019 GFCI Presentation

    6/12

    2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-6

    LO

    A

    D

    Hot

    Neutral

    The hot wire current is larger

    and its flux is greater.

    The net flux produces an

    output at the sense winding.

    (to service panel ground)

  • 8/12/2019 GFCI Presentation

    7/12 2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-7

    Hot

    Neutral

    LineLoad

    LM1851

    MOV

    SCR

    Bridge rectifier

    Circuit breaker

    GFCI schematic

    A ground fault induces an output from the sense transformer

    which is amplified and causes the SCR to trigger. The SCR

    then activates the circuit breaker to disconnect the load circuit.

    SenseDrive

  • 8/12/2019 GFCI Presentation

    8/12 2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-8

    Hot

    Neutral

    Line

    LM1851

    Sense

    60 Hz

    1. Ground fault

    2. More current in hot wire

    3. 60 Hz signal at sense winding

    4. SCR fires

    5. Circuit breaker trips

  • 8/12/2019 GFCI Presentation

    9/12 2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-9

    LO

    A

    D

    Hot

    Neutral

    An unwanted low resistance path from ground to neutral

    at the load end can prevent the GFCI from working since

    the currents are no longer unbalanced.

    There is no net flux and no

    output at the sense winding.

    Unwanted ground to neutral path

    As we will see, a second drive coil is used to detect this fault.

  • 8/12/2019 GFCI Presentation

    10/12 2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-10

    Hot

    Neutral

    Panel

    side

    Load

    side

    LM1851

    The bridge injects a 120 Hz signal into the drive coil. When there is

    an unwantedlow-resistance path from the neutral wire to the ground

    wire at the load side, current flows in the neutral via the normal

    connection at the service panel. This current does not flow in the hot

    wire and the imbalance trips the breaker.

    Bridge rectifier

    SenseDrive

    Unwanted 120 Hz

    Normal120 Hz

  • 8/12/2019 GFCI Presentation

    11/12 2013 The McGraw-Hill Companies, Inc. All rights reserved.McGraw-Hill

    1-11

    Hot

    NeutralAmplifier

    Class A GFCIs trip at 5 mA. This sensitivity is achieved by

    amplifying the output of the sense coil. The sensitivity is

    such that nuisance tripping can be experienced with exterior

    outlets during a rain storm. Check the gaskets when thishappens.

    Moisture

  • 8/12/2019 GFCI Presentation

    12/12 2013 The McGraw-Hill Companies, Inc All rights reservedMcGraw-Hill

    1-12

    Hot

    NeutralAmplifier

    The common mode rejection of the amplifier helps prevent

    false tripping. However, large signals can exceed the

    amplifiers common-modelimits. Lightning strikes often

    trip GFCIs.

    A direct hit is not required to trip a GFCI since the wires act

    as antennas. Also, strong radio signals can cause tripping.

    The common-mode rejection usually decreases as frequency

    goes higher.