36
Project No. 07ME07257 File E320934 Page Page 1 of 36 LABORATORY DATA PACKAGE Date ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 1 Form Revised: 2006-05-03 Form Copyright ã 2004 Underwriters Laboratories Inc. Only those products bearing the UL Mark should be considered as being covered by UL. Number of pages in this package _42_ TEST LOCATION: [x]UL or Affiliate []WTDP []CTDP []OTHER Company Name UL Melville Address CLIENT INFORMATION Company Name General Protecht Group Inc Address 555 Daxing Rd West Liushi, Yueqing, Zhejiang Province China. AUDIT INFORMATION: Description of Tests Per Standard No. UL 943 Edition 4th [] Tests Conducted by + Printed name Signature Reviewer at client facility (CTDP only) Printed name Signature Reviewed and accepted by Responsible Engineer Frederick Reyes S Billings Fred Reyes Printed Name Signature TESTS TO BE CONDUCTED: Test No. Done Test Name [] Comments/Parameters []Tests Conducted by ++ 1 6/5/07 Drop Test James J. Cavanagh 2 5/29/07 6/5/07 Humidity Conditioning & Leakage Currents Please condition 2 samples James J.Cavanagh 3 6/5/07 Unwanted Tripping Test (Ring Wave) E.Bochan 4 6/5/07 Surge Immunity Tests (Combination Wave) E.Bochan 5 6/6/07 6/8/07 Automated High Resistance Ground Fault and False Tripping Sequence. James J. Cavanagh 6 6/8/07 Dielectric Withstand Test James J. Cavanagh 7 6/4/07 Overload Test James J. Cavanagh 8 6/4/07 Low Resistance Ground Fault Test James J. Cavanagh 9 6/11/07 Endurance James J. Cavanagh UnRegistered

GFCI E320934 TestRecord Ul943

Embed Size (px)

DESCRIPTION

reporte de laborario segun norma ul 943

Citation preview

Page 1: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 1 of 36

LABORATORY DATA PACKAGE Date

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 1 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Number of pages in this package _42_ TEST LOCATION:

[x]UL or Affiliate []WTDP []CTDP []OTHER

Company Name UL Melville

Address

CLIENT INFORMATION

Company Name General Protecht Group Inc

Address 555 Daxing Rd West Liushi, Yueqing, Zhejiang Province China.

AUDIT INFORMATION:

Description of Tests Per Standard No. UL 943 Edition 4th

[] Tests Conducted by +

Printed name Signature

Reviewer at client facility (CTDP only)

Printed name Signature

Reviewed and accepted by Responsible Engineer

Frederick Reyes S Billings

Fred Reyes

Printed Name Signature

TESTS TO BE CONDUCTED: Test No. Done Test Name

[] Comments/Parameters []Tests Conducted by ++

1 6/5/07 Drop Test James J. Cavanagh

2 5/29/07

6/5/07

Humidity Conditioning & Leakage Currents

Please condition 2 samples

James J.Cavanagh

3 6/5/07 Unwanted Tripping Test (Ring Wave)

E.Bochan

4 6/5/07 Surge Immunity Tests (Combination Wave)

E.Bochan

5 6/6/07

6/8/07

Automated High Resistance Ground Fault and False Tripping Sequence.

James J. Cavanagh

6 6/8/07 Dielectric Withstand Test James J. Cavanagh

7 6/4/07 Overload Test James J. Cavanagh

8 6/4/07 Low Resistance Ground Fault Test

James J. Cavanagh

9 6/11/07 Endurance James J. Cavanagh

UnReg

ister

ed

Page 2: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 2 of 36

LABORATORY DATA PACKAGE Date

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 2 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

TESTS TO BE CONDUCTED: Test No. Done Test Name

[] Comments/Parameters []Tests Conducted by ++

6/13/07

10 6/6/07 Extra Low resistance Ground Fault Test

James J. Cavanagh

11 6/6/07 Short Circuit Test James J. Cavanagh

12 6/15/07 Normal Temperature James J. Cavanagh

Test Equipment- See "TEST EQUIPMENT INFORMATION" Samples – See "TEST SAMPLE IDENTIFICATION"

Instructions - + - When all tests are conducted by one person, printed name and signature can be inserted here instead of including printed name and signature on each page containing data. Must indicate number of pages in the data package. ++ - When test conducted by more than one person, printed name and signature of person conducting the test can be inserted next to the test name instead of including printed name and signature on each page containing data. Must indicate number of pages in the data package.

UnReg

ister

ed

Page 3: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 3 of 36

LABORATORY DATA PACKAGE Date

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 3 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

[]The test facility was deemed to have the environment and capabilities necessary to perform the tests included in this data package. (WTDP Only) Special Instructions –

UnReg

ister

ed

Page 4: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E302934 Page Page 4 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 4 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

TEST EQUIPMENT INFORMATION

Inst. ID No.

Instrument Type

Test Number +, Test Title or

Conditioning Function/Range

Last Cal. Date

Next Cal. Date

+ - If Test Number is used, the Test Number must be identified on the data

sheet pages or on the Data Sheet Package cover page. The following additional information is required when using client’s or rented equipment, or when a UL ID Number for an instrument number is not used. The Inst. ID No. below corresponds to the Inst. ID No. above.

Inst. ID No. Make/Model/Serial Number/Asset No.

[x] Test equipment information is recorded on UL’s Laboratory Project Management (LPM)/Laboratory Equipment Management (LEM) database. (This statement may be selected only if datasheets are completed electronically at a UL facility)

UnReg

ister

ed

Page 5: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 5 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 5 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

TEST SAMPLE IDENTIFICATION:

The table below is provided to provide correlation of sample numbers to specific product related information. Refer to this table when a test identifies a test sample by "Sample No." only. Sample Card

No. Date

Received [] Test No.

Sample No. Manufacturer, Product Identification and Ratings

General Protecht Receptacle Cat No. DG15-L GFCI 120 Vac, 20A, 60Hz.

Samples With Engineer

+ - If Test Number is used, the Test Number or Numbers the sample was used in must be identified on the data sheet pages or on the Data Sheet Package cover page.

[] Sampling Procedure -

UnReg

ister

ed

Page 6: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 6 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 6 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

DROP TEST: UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.3.2 and 5.8.1

Method

One sample was dropped 3 times from a height of 3 ft (.91m) onto a concrete floor with different orientations for each drop. Following the three drops, the sample was examined for accessibility of live parts, reduction of spacings, and continuity of grounding The sample was then checked for proper functioning by pressing the “TEST” & “RESET” buttons. The sample was then subjected to the Visual Inspection Test previously described.

Results

Evaluated by Fred Reyes 4/22/2008 There [was no] [was] accessibility of live parts, reduction of spacings(Engineer will determine), or loss of grounding continuity. After the impact, the unit [operated] [did not operate] correctly. There [was no] damage or loosening of insulated conductors or the insulation of splices and joints. (Engineer will determine) All joints and connections [remained] mechanically secure and [did] provide adequate and reliable contact without strain on connections and terminals. (Engineer will determine) Splices and joints not provided with insulation suitable for the temperature, voltage, and intended use of the conductors themselves [continued] to comply with Spacings, Clause 5.12, or Alternate Spacings – Clearances And Creepage Distances, Clause 5.13. (Engineer will determine) [ ] In the portable cord-connected ground-fault circuit-interrupter, wire terminations or splices [did not become] [became] free to bridge supplementary

For Engineering Use: The visual inspection test after the Drop Test is to be performed by the project handler and compliance documented by this data sheet. See clauses 5.8 and 6.22 of UL 1699.

UnReg

ister

ed

Page 7: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 7 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 7 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

or reinforced insulation. There [was no] [was] breakage at the terminations, splices, or at wire binding screws or nuts.

UnReg

ister

ed

Page 8: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 8 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 8 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Lab Use Only Sample # ___1___ Criteria Result Describe if “Yes” Damage to sample? [ ] Yes [x ]

No

Accessibility of live parts? [ ] Yes [x ] No

Reduction of spacings? [ ] Yes [x ] No

(Engineer will determine)

Loss of grounding continuity?

[ ] Yes [x ] No

Failure to operate? [ ] Yes [x ] No

Evaluated by Fred Reyes 4/22/2008 Lab. Conditions: 20°c 65%RH 6/5/07 Engineering Use Only: Visual Inspection Test conducted by __Fred Reyes______________________ Typed Name Date Criteria Result Describe if “Yes” Damage to insulated conductors or splice insulation?

[ ] Yes [x] No

Loosening of insulated conductors or splice insulation?

[ ] Yes [x ] No

Joints and connections not secure or strain on connections or terminals?

[ ] Yes [x ] No

Noncompliance with applicable spacings requirements?

[ ] Yes [x ] No

UnReg

ister

ed

Page 9: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 9 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 9 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

HUMIDITY CONDITIONING AND LEAKAGE CURRENT: UL943, 4th Ed./CSA 22.2 No.

144.1-06, Cl. 6.5

Method

The same sample subjected to the [Drop] [Impact] Test was placed in a 30ºC ambient until thermal equilibrium was attained. The sample was then conditioned at 93 ± 2% humidity and 32 ± 2ºC for [168] [48] Hours. Following the conditioning, while still in the chamber or within 60 s after removal from the chamber, the sample was connected to a 132 Vac supply. The leakage current between the neutral supply conductor and accessible metal or a 20 cm x 10 cm piece of metal foil wrapped tightly around the insulating enclosure was then measured. Following the leakage current measurement, the sample was checked for proper functioning by pressing the “TEST” & “RESET” buttons. Please condition 2 samples

Results

The results of this test [were] [were not] acceptable since the leakage current did [not] exceed 0.5 Ma to accessible metal parts or the foil mentioned above [and did [not] exceed 3.5 Ma to inaccessible functionally insulated metal parts.] The unit [operated] [did not operate] correctly after the conditioning. Lab Use Only Sample # ______1____ Conditioning Chamber Parameters: Temp Setting ______32_____°C, Humidity Setting ____93_______%

S1 Open S2 Norm.

S1 Open S2 Rev.

S1 Closed S2 Norm.

S1 Closed S2 Rev.

Leakage mA Less than 0.3mA

Less than 0.3mA

Less than 0.3mA

Less than 0.3mA

UnReg

ister

ed

Page 10: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 10 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 10 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Criteria 1. Leakage current shall be no more than 0.5mA measured to accessible

metal parts or the metal foil mentioned in the Method. 2. Leakage current shall be no more than 3.5mA measured to inaccessible

functionally insulated metal parts. Lab Use Only Sample # _____1A_____ Conditioning Chamber Parameters: Temp Setting _______32____°C, Humidity Setting ____93_______%

Criteria

3. Leakage current shall be no more than 0.5mA measured to accessible metal parts or the metal foil mentioned in the Method.

4. Leakage current shall be no more than 3.5mA measured to inaccessible functionally insulated metal parts.

S1 Open S2 Norm.

S1 Open S2 Rev.

S1 Closed S2 Norm.

S1 Closed S2 Rev.

Leakage mA Less than 0.3mA

Less than 0.3mA

Less than 0.3mA

Less than 0.3mA

UnReg

ister

ed

Page 11: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 11 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 11 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

VOLTAGE SURGE TESTS UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.6

GENERAL The same sample that was subjected to the drop and Leakage Current Tests was subjected to this test. The line side terminals of the Line-Neutral and Line-Line terminals that are protected by the representative ground-fault circuit-interrupter were subjected to the following surge tests: Unwanted Tripping Test, Surge Immunity Test. The ground-fault circuit-interrupter was connected to a supply of rated voltage. The grounding lead or terminal of the ground-fault circuit-interrupter (if provided) was connected to the supply conductor serving as the neutral. The ground-fault circuit interrupter was placed in the “on” condition with no load connected. A GFCI intended only for use in an enclosure was tested in the intended enclosure that was representative of the worst case situation for these tests.

UnReg

ister

ed

Page 12: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 12 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 12 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

UNWANTED TRIPPING TEST (RING WAVE): UL943, 4th Ed./CSA 22.2 No.

144.1-06, Cl. 6.6.2 METHOD

One representative ground-fault circuit interrupter was subjected to ten random applications or three controlled applications of a 3 kV surge applied at 60 second intervals. When three controlled applications were employed, one application was essentially at zero of the supply voltage wave, one at the positive peak, and one at the negative peak. The surge generator had a surge impedance of 50 ohms. The no load waveform of the surge generator was essentially as follows:

a) Initial rise time, 0.5 microseconds between 10 percent and 90 percent of peak amplitude,

b) The period of the following oscillatory wave, 10 microseconds, and

c)Each successive peak, 60 percent of the preceding peak.

Following the application of the surges, the sample was checked for proper functioning by pressing the “TEST” & “RESET” buttons.

RESULTS

The sample [did not] [did] trip after being subjected to the surges and was functional at the conclusion of the test. Lab Use Only: Sample # _____1 _____ [x]Ten random applications

Trip 1 2 3 4 5 6 7 8 9 10 Total Yes No OK OK OK OK OK OK OK OK OK OK [x]Ten random (3 Controlled) applications

Trip 1 2 3 4 5 6 7 8 9 10 Total Yes No OK OK OK Lab. Conditions: 20°c 65%RH 6/5/07

UnReg

ister

ed

Page 13: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 13 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 13 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

SURGE IMMUNITY TEST (COMBINATION WAVE): UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.6.3

NOTE TO LAB TECHNICIAN: Consult Corporate Laboratory Procedural Guide before testing. All calibration waveforms are to be plotted and attached to the Data Sheet package.

METHOD

The same sample of the GFCI that was subjected to the Unwanted Tripping Test was subjected to the Surge Immunity Test. The sample was placed in the orientation to represent the most severe conditions of normal installation while in an unheated condition. It was then connected to a supply of rated voltage. Surge impulses were applied between the points indicated in the table at the 90 and the 270 degree points of the ac waveform. The test was conducted in accordance with the testing methods described in IEC61000-4-5 Electromagnetic Compatibility (EMC) Part 4-5: Testing and measurements techniques – Surge Immunity Test. Five impulses were applied in the positive direction and five impulses were applied in the negative direction at each point for a total of 20 impulses. If the GFCI tripped as a result of an impulse it was reset prior to the next impulse application. The wave shape specifications for each portion of the combination wave are as follows:

Open Circuit Voltage – 4 kV peak, 1.2 by 50 µs Short Circuit Current – 2 kA peak, 8 by 20 µs

During and after the surge application, the sample was examined for

a) Emission of flame, molten metal, glowing or flaming particles through any openings,(either preexisting or created during the test),

b) Ignition of the Enclosure, or c) Creation of an opening in the enclosure that results in accessibility of

live parts. Following the application of the surges, the sample was checked for proper functioning by pressing the “TEST” & “RESET” buttons.

UnReg

ister

ed

Page 14: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 14 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 14 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

RESULTS

Model No. Sample No.

Application Points

Rated Voltage (V ac)

Emission of flame, molten metal or

particles?

Ignition of

enclosure?

Access to Live

parts?

1 L to N 120 [ ] Yes [x ] No

[ ] Yes [x ] No

[ ] Yes [ x] No

The sample [was] [was not] functional at the conclusion of the test. Engineering and Lab Use Only: Application Points For a single pole device: L – N For a two pole device: L1 – L2 at 240 V; L1 – N at 120 V; L2 – N at 120 V

Total Number of Surge Applications Total Number of Trips During Test 20

4

Lab. Conditions: 20°c 65%RH 6/5/07 AUTOMATED HIGH-RESISTANCE AND FALSE TRIPPING Sequence

UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.7 and 6.8

UnReg

ister

ed

Page 15: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 15 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 15 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

METHOD

The same sample that was subjected to the Voltage Surge Tests was used for this test. Testing was conducted in accordance with UL943, 3rd edition, Sections 24 and 25 using automated test methods. [ ] The tests were performed using the selected automated sequence, including the automated method for determining most-adverse parameters. [ ] The tests were performed using the selected automated sequence with the specified most-adverse parameters. (The Most-Adverse Conditions test lines in the automated sequence were not conducted. Most-Adverse Parameters (User specified)

Volts [ ]85-percent, [ ]100-percent, [ ]110-percent Load [ ]no-load, [ ]rated-load Polarity [ ]forward, [ ]reverse

MAhr

Position [ ]1, [ ]2, [ ]3, [ ]4, [ ]5, [ ]6 Volts [ ]85-percent, [ ]100-percent, [ ]110-percent Load [ ]no-load, [ ]rated-load

MAft

Polarity [ ]forward, [ ]reverse

SAMPLE

Cat. No.

Sample No(s). 1 120vac [ ]13A, [ ]15A, [x]20A, [ ]30A, [ ]40A,

[ ]50A Rating

120/240vac [ ]6.5A, [ ]7.5, [ ]13A, [ ]15A, [ ]20A, [ ]30A, [ ]40A, [ ]50A

Mechanism [ ] Mechanical Latch, Pushbutton-Reset [x] Mechanical Latch, Pushbutton-Reset with Lockout [ ] Mechanical Latch, Toggle-Handle [ ] Electric-Latch, Manual Reset [ ] Electric-Latch, Auto-Reset

Reset-Delay [ ]no-delay (default), [ ]5-seconds, [ ] 10-seconds Comments

UnReg

ister

ed

Page 16: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 16 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 16 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

AUTOMATED SEQUENCE

[ ] 01 - Receptacle GFCI - 120V (Full Program) [ ] 01A - Receptacle GFCI - 120V (Standard Program) [ ] 02 - Receptacle GFCI - 120/240V-LN (Full Program) [ ] 02A - Receptacle GFCI - 120/240V-LN (Standard Program) [ ] 03 - Receptacle GFCI - 120/240V+LN (Full Program) [ ] 03A - Receptacle GFCI - 120/240V+LN (Standard Program) [ ] 04 - Circuit Breaker GFCI - 120V (Full Program) [ ] 04A - Circuit Breaker GFCI - 120V (Standard Program) [ ] 05 - Circuit Breaker GFCI - 120/240V (Full Program) [ ] 05A - Circuit Breaker GFCI - 120/240V (Standard Program) [ ] 06 - Auto-Reset GFCI - 120V (Full Program) [ ] 06A - Auto-Reset GFCI - 120V (Standard Program) [ ] 07 - Auto-Reset GFCI - 120V/240V-LN (Full Program) [ ] 07A - Auto-Reset GFCI - 120V/240V-LN (Standard Program) [ ] 08 - Auto-Reset GFCI - 120V/240V+LN (Full Program) [ ] 08A - Auto-Reset GFCI - 120V/240V+LN (Standard Program) [ ] 09 - Manual-Reset GFCI - 120V (Full Program) [ ] 09A - Manual-Reset GFCI - 120V (Standard Program) [ ] 10 - Manual-Reset GFCI - 120V/240V-LN (Full Program [ ] 10A - Manual-Reset GFCI - 120V/240V-LN (Standard Program) [ ] 11 - Manual-Reset GFCI - 120V/240V+LN (Full Program) [ ] 11A - Manual-Reset GFCI - 120V/240V+LN (Standard Program)

[ ] 12 - ALCI Plug - 120V (Standard Program) [ ] 13 - ALCI Plug - 120/240V-LN (Standard Program) [ ] 14 - ALCI Plug - 120/240V+LN (Standard Program) [ ] 15 - Receptacle GFCI+LOF - 120V (Full Program) [x] 15A - Receptacle GFCI+LOF - 120V (Standard Program) [ ] 16 - Receptacle GFCI+LOF - 120/240V-LN (Full Program) [ ] 16A - Receptacle GFCI+LOF - 120/240V-LN (Standard Program) [ ] 17 - Receptacle GFCI+LOF - 120/240V+LN (Full Program) [ ] 17A - Receptacle GFCI+LOF - 120/240V+LN (Standard Program)

UnReg

ister

ed

Page 17: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 17 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 17 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

AUTOMATED HIGH-RESISTANCE AND FALSE TRIPPING TESTS (Cont’d) [ ] 18 - OJ Thermostat - 120V [ ] 18A - OJ Thermostat - 120V - one-position [ ] 19 - OJ Thermostat - 120/240V-LN [ ] 20 - OJ Thermostat - 120/240V+LN

[ ] 21 - Receptacle GFCI+LOF - 120V with Open Neutral Protection

Note:

-LN = no load-neutral +LN = with load-neutral +LOF = with Lockout feature

RESULTS

The results were in that the GFCI [was] capable of interrupting the electric circuit to the load within the required time interval under all required conditions.(Engineer will determine) Evaluated by Fred Reyes 4/22/2008 Lab Use Only:

DIELECTRIC WITHSTAND TEST: UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.11

Method

A 60 Hz essentially sinusoidal potential was gradually increased from zero to the value indicated and then applied for one minute between each of the locations specified in “Results”

Results

Method I

Sample No. 1

UnReg

ister

ed

Page 18: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 18 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 18 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

Note: (FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Lab. Conditions: 20°c 76%RH 6/8/07

OVERLOAD TEST: 3 & 4 UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.12

METHOD I A previously untested sample was connected to a 60 Hz source of supply, at a load current of 120 A (6 x rated), with a closed circuit voltage of (greater than 85% of rated) 102+ V and an open circuit voltage of 120 V (100-105% of rated), at a power factor of 45 – 50%. A 1-A fuse was connected from the grounded supply conductor to the accessible conductive parts of the unit (metal foil). The device was turned “on” for one second and “off” for nine seconds, for a total of 25 operations, at a rate of six cycles per minutes. The load was connected to the LOAD HOT and LOAD Neutral Terminals of the sample.

UnReg

ister

ed

Page 19: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 19 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 19 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

RESULTS I [x ] The unit continued to operate without failure or impairment and did not trip during the test. The 1A fuse did not open.

[ ] The unit did not continue to operate without failure or impairment.

[ ] The unit tripped during the test.

[ ] The 1A fuse opened.

[x ] The results (were)/(were not) acceptable

ETHOD II The test of Method I was repeated on the same sample except the load was connected to the GFCI face by means of a suitably rated attachment plug.

RESULTS II

[ x] The unit continued to operate without failure or impairment and did not trip during the test. The 1A fuse did not open.

[ ] The unit did not continue to operate without failure or impairment.

[ ] The unit tripped during the test.

[ ] The 1A fuse opened.

[x ] The results (were)/(were not) acceptable

UnReg

ister

ed

Page 20: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 20 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 20 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

OVERLOAD TEST (Continued):

FOR LAB USE ONLY:

Method I Method II

Sample No. 3 4

Open Circuit V 122 122

Closed Circuit V 120 120

Amperes A 120 120

Power Factor .45 .45

1 A Ground Fuse condition

1 1

No. cycles of Operation

25 25

Lab. Conditions: 20°c 62%RH 6/4/07

UnReg

ister

ed

Page 21: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 21 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 21 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

LOW RESISTANCE GROUND FAULT:5 & 6 UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.13

METHOD I

A previously untested sample was connected to a 60 Hz supply source with an open circuit voltage of 120 V (100-105% rated). A resistor was connected between the ungrounded load terminal and the grounded supply conductor as shown (See Fig. 31.1 of UL 943), simulating a ground fault. The resistance was adjusted to draw a 120 A load (6 x rating). The closed circuit voltage was (greater than 85% of rated) 102+ Vac. The accessible conductive parts (metal foil) was connected to the grounded supply conductor through a 1 A fuse. The test was initiated 25 times by depressing the reset button every ten seconds to complete the circuit. The trip time was measured for each operation.

RESULTS I There was no indication of a hazard or impairment of the device tested. The average trip time was ____18.75___ milliseconds. The maximum trip time was __29.2_____milliseconds. [x ] The 1 A ground fuse remained intact. [ ] The 1A ground fuse opened.

METHOD II The test of Method I was repeated on [a new] [the same] sample except the resistor load was connected to the GFCI face by means of a suitably rated attachment plug.

RESULTS I There was no indication of a hazard or impairment of the device tested. The average trip time was __18.0____ milliseconds. The maximum trip time was 28.8___milliseconds. [ x] The 1 A ground fuse remained intact. [ ] The 1A ground fuse opened.

UnReg

ister

ed

Page 22: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 22 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 22 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

LAB USE ONLY:

Method I Method II

Sample No. 5 6

Open Circuit V 122 122

Closed Circuit V 120 120

Amperes A 120 120

Power Factor N/A N/A

1 A Ground Fuse condition

OK OK

No. cycles of Operation completed

Method I

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

1 20.0 6 19.2 12 19.2 18 19.6 23 21.2

2 23.2 7 21.2 13 22.4 19 22.8 24 18.4

3 20.4 8 19.6 14 19.6 20 19.2 25 18.4

4 18.0 9 20.0 15 19.6 21 29.2 MAX 29.2

5 20.0 10 19.2 16 19.6 22 18.8 AVG 18.75

Method II

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

Trip #

Trip Time (ms)

1 22.8 6 18.4 12 17.6 18 17.6 23 18.0

2 18.4 7 18.8 13 18.8 19 19.6 24 28.8

3 20.4 8 18.0 14 18.0 20 19.6 25 18.8

4 19.2 9 24.8 15 17.2 21 20.4 MAX 18.0

5 18.4 10 19.2 16 18.4 22 19.6 AVG 28.8

UnReg

ister

ed

Page 23: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 23 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 23 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

ENDURANCE:7 & 8 UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.14

METHOD I

A previously untested sample was connected to a 60 Hz source supply, at a load of 20A (rated), with a closed circuit voltage of (97.5% of rated)117+ V and an open circuit voltage of (100-105% of rated) 120 V, at a power factor of 0.75 –0.80 The sample was connected to the supply source using No. 12 AWG wire. A 1 A fuse was connected from the grounded supply conductor to the accessible conductive parts (metal foil). The sample was operated by depressing the ‘reset” button to turn the device “on” and depressing the “test” button to turn the device “off” at a rate of six operations a minute until a total of 3000 operations had been completed. [ ] The sample was operated an additional 3000 times using the manual switching means provided. At the completion of the (3000)\(6000) cycles, the unit was tripped by means of the supervisory circuit and reset, at rated voltage without load, 25 times in as rapid succession as possible. [x]At the conclusion of all of the above cycles of operation, the sample was subjected to the Dielectric Withstand Test

RESULTS I [ x] At the end of the test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [x ] There [was]\[was no]evidence of dielectric breakdown

METHOD II The test of Method I was repeated on the same sample except the load was connected to the GFCI face by means of a suitably rated attachment plug.

UnReg

ister

ed

Page 24: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 24 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 24 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

RESULTS II [ x] At the end of the test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [x] There was no]evidence of dielectric breakdown FOR LAB USE ONLY:

Method I Method II

Sample No. 7 8

Open Circuit V 122 122

Closed Circuit V 119 119

Amperes A 20 20

Power Factor .78 .78

1 A Ground Fuse condition

OK OK

No. cycles of Operation

3000 + 25 at no load 3000 + 25 at no load

Lab. Conditions: 20°c 64%RH 6/11/07 (Method I) Lab. Conditions :19°c 68%RH 6/13/07 (Method II)

UnReg

ister

ed

Page 25: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 25 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 25 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Dielectric Results:

Method I

Sample No.7

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

(FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Lab. Conditions:20°c 70%RH 6/12/07

UnReg

ister

ed

Page 26: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 26 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 26 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Method II

Sample No.8

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

(FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Lab. Conditions: 19°c 67%RH 6/13/07 UnR

egist

ered

Page 27: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 27 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 27 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

EXTRA LOW RESISTANCE GROUND FAULT: UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.18, Table 6.18.1, Fig. 6.18.1

METHOD I

A previously untested sample of was connected using two 4-ft lengths of No. 12 AWG wire, to a 60 Hz supply with an open circuit voltage of 120 V(100-105% of rated), capable of producing or 2000 A at a power factor of 90 – 100%, when the supply terminals were short-circuited. The line circuit included a series 20A cartridge fuse. The grounded supply lead was connected to the accessible metal parts and ground pin through a 1 A fuse. Surgical cotton was placed over openings in the device. A 4 ft. length of No. 12AWG wire was connected between the hot load terminal and the grounded line terminal as a simulated ground fault. Current was initiated once by a remote switch in the supply circuit. At the conclusion of the above test, the sample was subjected to the Dielectric Withstand Test The test was repeated on a new sample except that current was initiated once by depressing the reset button to complete the circuit.

RESULTS I Sample 9 and 10 [x ] At the end of each test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [ ] There was no]evidence of dielectric breakdown

METHOD II The test of Method I was repeated on [a new] [the same] sample except the 4 ft. wire was connected to the hot contact of the GFCI face by means of a suitably rated attachment plug.

UnReg

ister

ed

Page 28: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 28 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 28 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

RESULTS II

Sample 11 and 12 [x ] At the end of each test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [x] There [was]\[was no]evidence of dielectric breakdown FOR LAB USE ONLY:

Method I Method II

Remote Switch Reset Remote Switch Reset

Sample No. 9 10 11 12

Open Circuit V 122 122 122 122

Closed Circuit V N/A N/A N/A N/A

Amperes A 2000 2000 2000 2000

Power Factor .90-100 .90-100 .90-100 .90-100

1 A Ground Fuse condition

OK OK OK OK

_20__ A Line fuse condition

Open Open Open Open

Lab. Conditions: 20°c 52%RH 6/6/07 Dielectric Results - Method I:

Method I

Sample No.9 & 10 Remote Switch (9)

Reset (10)

UnReg

ister

ed

Page 29: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 29 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 29 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

(FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Dielectric Results - Method II:

Method II SEE NOTE ABOVE

Sample No.11 & 12 Remote Switch (11)

Reset (12)

UnReg

ister

ed

Page 30: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 30 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 30 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

(FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Lab. Conditions: 20°c 53%RH 6/7/07 UnR

egist

ered

Page 31: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 31 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 31 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

SHORT CIRCUIT: UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.19

METHOD I

A new sample was connected using the circuit described previously in the Extra Low Resistance Ground Fault Test, except that the ground fault was removed. A 20 inch length of No.12 AWG wire was connected between the load terminals. The line circuit included a series 20 A cartridge fuse. The grounded supply lead was connected to the accessible metal parts and ground pin through a 1 A fuse. Surgical cotton was placed over openings in the device. Current was initiated once by a remote switch in the supply circuit. At the conclusion of the above test, the sample was subjected to the Dielectric Withstand Test

RESULTS I [x ] At the end of the test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [ x] There was no]evidence of dielectric breakdown

METHOD II The test of Method I was repeated on [a new] [the same] sample except the 4 ft. wire was connected to the hot contact of the GFCI face by means of a suitably rated attachment plug.

RESULTS II [x ] At the end of the test the unit was still operating normally and no adverse effects had been noted. The 1 A ground fuse was intact. [ ] The unit did not operate after the test and the 1A ground fuse was not intact. [ x] There was no]evidence of dielectric breakdown

UnReg

ister

ed

Page 32: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 32 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 32 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

Lab. Conditions: 20°c 52%RH 6/6/07

UnReg

ister

ed

Page 33: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 33 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 33 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

FOR LAB USE ONLY:

Method I Method II

Sample No. 13 14

Open Circuit V 122 122

Closed Circuit V N/A N/A

Amperes A 2000 2000

Power Factor .90-100 .90-100

1 A Ground Fuse condition

OK OK

_20__ A Line fuse condition

Open Open

Dielectric Results:

Method I Method II

Sample No. 13 14

[x] [x]1240 V [ ] 1000 + (2x Rated V)ac between grounding circuit and ALL live parts GFCI LATCHED

[x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and Face with the GFCI tripped.

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between load terminals and face circuits with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

UnReg

ister

ed

Page 34: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 34 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 34 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

[x] [x]1240 V [ ] 1000 + (2x Rated V) ac between line and load terminals with the GFCI tripped.

[ x] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

[x ] No indication of Breakdown

[ ] Indication of Breakdown at _______ Volts

Note: (FI) = Functional Insulation (SI) = Supplementary Insulation (RI) = Reinforced Insulation Lab. Conditions: 20°c 53%RH 6/7/07

UnReg

ister

ed

Page 35: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 35 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 35 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

TEMPERATURE TEST

SAMPLE 15

UL943, 4th Ed./CSA 22.2 No. 144.1-06, Cl. 6.10

METHOD

The sample was connected as shown in Figure 24.1 of UL 943 using 12AWG wire. The line voltage was set to 120 V, 60 Hz, with the load at 20 A. The value of ground fault current was set to 3.5 mA by adjusting RB. [x] The sample was installed in an outlet box of appropriate size, in normal

orientation (see sketch). Temperatures were recorded by means of thermocouples attached to the points tabulated under “Results” until thermal equilibrium was attained. [ ] Coil temperatures were obtained by the change – in - resistance method. Acceptable Results Evaluated by Fred Reyes 4/22/2008

RESULTS The following temperatures were measured at the indicated locations:

Thermocouple Location Temperature ºC

Ambient Air 20

1. line hot terminal 54-20=34

2. Joint where Line hot busbar meets 62-20=42

3. line hot contact arm 56-20=36

4. Between D1 and PWB 51-20=31

5. Between R4 and PWB 75-20=55

6. Load Hot bus bar closest to Contact 54-20=34

7. Load hot terminal 48-20=28

UnReg

ister

ed

Page 36: GFCI E320934 TestRecord Ul943

Project No. 07ME07257 File E320934 Page Page 36 of 36

Tested by: Date Printed Name Signature

Witnessed by: Date (WTDP Only) Printed Name Signature

ULS-02377-AAAG-DataSheet-0003 Form Issued: 2005-12-19 Form Page 36 Form Revised: 2006-05-03

Form Copyright ã 2004 Underwriters Laboratories Inc.

Only those products bearing the UL Mark should be considered as being covered by UL.

TEMPERATURE TEST (Continued)

FOR LAB USE ONLY: Starting Time_7:00AM____ (Reset Position)

Thermocouple Location Temperature ºC

Temp. Reading # 1 2 3 4 5 6 7 8

Temp Reading Time 1:ooPM 1:15PM 1:30PM

Ambient Air 20 20 20

1. line hot terminal 54 54 54

2. Joint where Line hot busbar meets braid wire

62 62 62

3. line hot contact arm 56 56 56

4. Between D1 and PWB 51 51 51

5. Between R4 and PWB 75 75 75

6. Load Hot bus bar closest to Contact

54 54 54

7. Load Hot Teminal 48 48 48

Lab. Conditions: 20°c 57%RH 6/15/07 TEMPS ARE GOOD> FRED R.

UnReg

ister

ed