FX-350 Series Analog/Addressable Fire Alarm Panels LT-959 Rev. 3.1 March 2012 Installation and Operation Manual SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM SIGNAL SILENCE BUZZER SILENCE LAMP TEST SPARE AC ON 1 2 ABC 3 5 6 7 8 9 * 0 # 4 X M ? DEF GHI JK L MNO PRS TUV WX Y QZ COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM NORMAL DEC 03, 2009 10:25AM FX-350 SERIES Fire Alarm Control Panel COMMON ALARM COMMON SUPV COMMON TROUBLE CPU FAULT GROUND FAULT SYSTEM RESET FIRE DRILL ALARM ACKNOWLEDGE GENERAL ALARM SIGNAL SILENCE BUZZER SILENCE LAMP TEST SPARE AC ON 1 2 ABC 3 DEF 5 JKL 6 MNO 7 8 TUV 9 WXY * 0 QZ # 4 GHI PRS X M ? SYSTEM NORMAL DEC 03, 2010 02:41PM FX-350 SERIES Fire Alarm Control Panel

FX-350 Installation Manual - Phoenix Fire and Security...FX-350 Series Analog/Addressable Fire Alarm Panels LT-959 Rev. 3.1 Installation and Operation Manual March 2012 Advanced Life

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

  • Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113

    � Mircom 2002Printed in CanadaSubject to change without prior notice

    www.mircom.com

    FX-350 SeriesAnalog/Addressable Fire Alarm Panels

    LT-959 Rev. 3.1March 2012Installation and Operation Manual

    Advanced Life Safety Solutions

    U.S.A. 60 Industrial Parkway Cheektowaga, NY 14227 Tel: 1-888-660-4655 Fax: 1-888-660-4113

    SYSTEMRESET

    FIREDRILL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNALSILENCE

    BUZZERSILENCE

    LAM PTEST

    SPARE

    AC ON1 2

    A B C3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    DE F

    GHI JK L MNO

    P RS T UV WX Y

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    SYSTEM NORMAL

    DEC 03, 2009 10:25AM

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    FX-350 SERIESFire Alarm Control Panel

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    FIREDRILL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNALSILENCE

    BUZZERSILENCE

    LAMPTEST

    SPARE

    AC ON1 2

    ABC3

    DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?

    SYSTEM NORMAL

    DEC 03, 2010 02:41PM

    FX-350 SERIESFire Alarm Control Panel

  • FX-350 Series Installation and Operation Manual

    Table of Contents

    Industry Canada and FCC Notice ........................................................................................... 7Introduction .............................................................................................................................. 8

    Features................................................................................................................................ 8Conventions ............................................................................................................................ 9

    Circuits ................................................................................................................................. 9Zone/Group........................................................................................................................... 9Display Points ...................................................................................................................... 9Wiring Styles ........................................................................................................................ 9

    System Components .............................................................................................................. 10Panel Models ........................................................................................................................ 10Output Class A converter: four circuits ................................................................................. 11Polarity reversal/city tie ......................................................................................................... 11Remote Annunciator ............................................................................................................. 12Smart Relay Module ............................................................................................................. 12RAM-216 Remote Annunciator ............................................................................................. 12Panel Components and System Accessories ....................................................................... 13Analog/Addressable Devices ................................................................................................ 14

    Mechanical Installation............................................................................................................ 15Installing the Enclosures ....................................................................................................... 15

    Installing Adder Modules ........................................................................................................ 18Cable and Jumper Connections for Main Board and Adder Modules .................................. 19OCAC-304 Output Class A Converter Adder Module .......................................................... 21Polarity Reversal and City Tie Module (Model PR-300) ...................................................... 22RAX-332 Display Adder Module ........................................................................................... 22

    Circuits and Devices................................................................................................................ 23Addressable/Analog Devices ................................................................................................ 23Analog Devices ..................................................................................................................... 23Contact Inputs....................................................................................................................... 24 Contact Outputs ................................................................................................................... 24

    Field Wiring .............................................................................................................................. 25Main Fire Alarm Board Field Wiring ..................................................................................... 25Loop Isolators ....................................................................................................................... 25Loop Operation ..................................................................................................................... 26Indicating (Powered Output) Circuits .................................................................................... 27Indicating Circuit Wiring ....................................................................................................... 27Dialer Wiring ......................................................................................................................... 29Polarity Reversal and City Tie Module (PR-300) Wiring ...................................................... 30Auxiliary Power Supplies ...................................................................................................... 31Power Supply Connections................................................................................................... 32

    System Checkout .................................................................................................................... 33Before turning the power “ON” ............................................................................................. 33Power-up procedure ............................................................................................................ 33

    Troubleshooting ...................................................................................................................... 33Indicators, Controls and Operations ..................................................................................... 34

    Common Indicators............................................................................................................... 35Common Controls ................................................................................................................. 36Single Stage Operation......................................................................................................... 37Two-Stage Operation............................................................................................................ 38Positive Alarm Sequence...................................................................................................... 39Enabling or Disabling the Positive Alarm Sequence............................................................. 39Input Types ........................................................................................................................... 40Output Types ........................................................................................................................ 42Evacuation Codes................................................................................................................. 43

    iii

  • Table of Contents

    Remote Annunciator Operation ............................................................................................. 46Dialer Operation ...................................................................................................................... 47Appendix A: Compatible Receivers....................................................................................... 47Appendix B: Reporting .......................................................................................................... 48

    Ademco Contact-ID ............................................................................................................. 48Security Industries Association SIA-DCS ............................................................................ 49

    Appendix C: Specifications................................................................................................... 50Appendix D: Power Supply and Battery Calculations ......................................................... 51 Warranty & Warning Information .......................................................................................... 53

    Warning Please Read Carefully ........................................................................................... 53Limited Warranty .................................................................................................................. 55Warranty Procedure ............................................................................................................. 55Disclaimer of Warranties ...................................................................................................... 55Out of Warranty Repairs ...................................................................................................... 56

    iv

  • FX-350 Series Installation and Operation Manual

    List of Figures & Tables

    Figure 1: Wallbox Dimensions / Mounting the FX-350 – Surface /Flush .............................. 15Figure 2: Mounting the FX-350 - Flush ................................................................................ 16Figure 3: Flush Trim Detail.................................................................................................... 16Figure 4: Wallbox Dimensions / Mounting the FX-351/FX-353 – Surface /Flush ................. 17Figure 5: Installation of Adder Modules ............................................................................... 18Figure 6: Main Fire Alarm Board Cable Connectors and Jumper Locations......................... 19Figure 7: Main Board (3 loop model) Cable Connectors and Jumper Locations .................. 20Figure 8: OCAC-304 Output Class A Converter Adder Modules .......................................... 21Figure 9: Polarity Reversal and City Tie Module .................................................................. 22Figure 10: Addressable Loop Wiring - Class B or Style 4..................................................... 25Figure 11: Addressable Loop Wiring -Class A or Style 6...................................................... 26Figure 12: Indicating Circuit – Class B or Style Y Wiring ...................................................... 28Figure 13: Indicating Circuit –Class A or Style Z Wiring ....................................................... 28Figure 14: Dialer Wiring ....................................................................................................... 29Figure 15: Polarity Reversal and City Tie Module Terminal Connection ............................. 30Figure 16: Supervision Of Auxiliary Supplies........................................................................ 31Figure 17: Main Power Supply Connections......................................................................... 32Figure 18: LCD Display, LED indicators and control buttons ............................................... 34Figure 19: Evacuation and Alert Codes ................................................................................ 43

    Table 1: Connectors and Jumpers on the Main Fire Alarm Board ....................................... 21Table 2: PR-300 Cable and Jumper Settings ...................................................................... 22Table 3: Loop Wiring Table .................................................................................................. 25Table 4: Indicating Circuit Wiring ......................................................................................... 27

    v

  • List of Figures & Tables

    vi

  • FX-350 Series Installation and Operation Manual

    Industry Canada and FCC Notice

    Notice for all FX-350 Series Built-In UDACTs Sold in CanadaMircom's FX-350 SERIES BUILT-IN UDACT Communicator described in this manual is listed by Underwriters Laboratories Canada (ULC)for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units forFire Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems and Services). These Communicatorsshould be installed in accordance with this manual; the Canadian / Provincial / Local Electrical Code; and/or the local Authority HavingJurisdiction (AHJ).

    Industry Canada NoticeRepairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs oralteration made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request theuser to disconnect the equipment. Users should ensure for their own protection that the Earth Ground connections of the power utility,telephone lines and internal metallic water pipe system, if present, are connected together. This is necessary both for proper operation and

    for protection.

    Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A.

    Mircom's FX-350 SERIES BUILT-IN UDACT Digital Communicator described in this manual is listed by Underwriters Laboratories Inc.(ULI) for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire ProtectiveSignalling Systems). These Communicators comply with the National Fire Protection Association (NFPA) performance requirements forUDACTs and should be installed in accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These Communicatorsshould be installed in accordance with this manual; the National Electrical Code (NFPA 70); and/or the local Authority Having Jurisdiction(AHJ).

    FCC NoticeThis equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the telco transformer of thisequipment is a label that contains, among other information, a product identifier in the format US:1M8AL02BFX350. If requested, thisnumber must be provided to the telephone company. This equipment is capable of seizing the line. This capability is provided in thehardware.Type of Service: The Communicator is designed to be used on standard device telephone lines. It connects to the telephone line bymeans of a standard jack called the USOC RJ-11C (or USOC FJ45S). Connection to telephone company provided coin service (centraloffice implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.Telephone Company Procedures: The goal of the telephone company is to provide you with the best service it can. In order to do this, itmay occasionally be necessary for them to make changes in their equipment, operations or procedures. If these changes might affect yourservice or the operation of your equipment, the telephone company will give you notice, in writing, to allow you to make any changesnecessary to maintain uninterrupted service.In certain circumstances, it may be necessary for the telephone company to request information from you concerning the equipment whichyou have connected to your telephone line. Upon request of the telephone company, provide the FCC registration number and the ringerequivalence number (REN); both of these items are listed on the equipment label. The sum of all of the REN’s on your telephone linesshould be less than five in order to assure proper service from the telephone company. In some cases, a sum of five may not be usable ona given line.If Problems Arise: If any of your telephone equipment is not operating properly, you should immediately remove it from your telephone line,as it may cause harm to the telephone network. If the telephone company notes a problem, they may temporarily discontinue service. Whenpractical, they will notify you in advance of this disconnection. If advance notice is not feasible, you will be notified as soon as possible.When you are notified, you will be given the opportunity to correct the problem and informed of your right to file a complaint with the FCC.Contact your telephone company if you have any questions about your phone line. In the event repairs are ever needed on theCommunicator, they should be performed by Mircom Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. Forinformation contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page of this document.

    CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate

    Note: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5.The Label Identification Number for this product is US:1M8AL02BFX350. The 02B represents the REN without a decimal point (e.g., 02B is a REN of 0.2B). For earlier products, the REN is separately shown on the label.

    7

  • Introduction

    Introduction

    Mircom’s FX-350 Series Analog/Addressable Fire Alarm Control Panel provides a loop for 60,126 or three loops for378 input and output devices, four supervised Class B or A (Style Y or Z) indicating circuits, a full range of auxiliarypower supplies, and extensive common control features via its integrated LCD display and push button console.Many of its features are fully configurable utilizing the built-in configuration capability via the front panel display andswitches. The panels are available with or without an optional, integrated dialer/modem (except the FX-353 versionwhich always includes the dialer/modem), and is available (FX-351 and FX-353 - in a larger enclosure) with aninternal LED display for up to 64 points (32 standard). Optional modules include Polarity Reversal and City Tie,RAX-332 LED Display Adder, and Class A Converter for indicating circuits. Semi-flush or surface mountableenclosures can be used for retrofits and on new installations. This manual covers the following panels:

    FX-350-60-DR 60 pt addressable FACP(w/ dialer)

    FX-351-LW 126 pt addressable FACP(w/ one 32 point LED display)

    FX-351-LDW 126 pt addressable FACP(w/ dialer and one 32 point LED display)

    FX-351-LDR 126 pt addressable FACP(w/ dialer)

    FX-353-LW 378 pt addressable FACP without LED strip(w/ dual loop adder and one 32 point LED display)

    FX-353-LDR 378 pt addressable FACP without LED strip(w/ dialer and dual loop adder)

    Features• The FX-350 panels support a loop of 60 or 126 analog devices and up to 3 loops of 378 analog devices, including

    thermal, ion, photo detectors, and contact input and output devices. Drift compensation and Auto Test features are provided for analog devices.

    • Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be configured as Class A (Style Z) using an output Class A converter adder module. Each indicating circuit may be configured as silenceable signal, non-silenceable signal, silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be Steady, Temporal Code, California Code, or March Time. The system provides the necessary protocols to sync strobes from major manufacturers.

    • Two-stage, alarm verification, and waterflow retard operations available.

    • Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and One-Man Walk Test.

    • Subsequent Alarm, Supervisory, and Trouble operation.

    • provides a regulated, supervised 21.1VDC auxiliary power supply @ 500mA max.; unfiltered, unsupervised 24V FWR power supply @ 1.7 A max and a resettable auxiliary power supply @ 300mA max.

    • Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all non-disconnectable and Auxiliary Alarm Relay (disconnectable).

    • Output for remote trouble indicator and Buzzer (RTI).

    • RS-485 Interface for RAM-300LCD Annunciators, RA-1000 Series Remote Annunciators and SRM-312 Smart Relay Modules (max total of 7 remote annunciators).

    • Optional Module for City Tie and Polarity Reversal Signaling.

    • Extensive transient protection

    • With or without built-in UDACT (Digital Alarm Communicator Transmitter)

    • Extensive and easy configuration of the panel via the integrated LCD display and keypad

    • Remote dial up (with built-in UDACT version) for event log checking and/or configuration changing

    Note: Installation of the FX-350 Series Fire Alarm Control panel should be in accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final acceptance subject to the Local Authority Having Jurisdiction (AHJ).

    8

  • FX-350 Series Installation and Operation Manual

    Conventions

    Circuits Refers to a physical electrical interface for the analog loop, indicating signals or relays, and common alarm,supervisory, and trouble relay outputs.

    Zone/GroupIs a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit. Groups are usedextensively in the FX-350 to facilitate annunciation of multiple input and output points on the 32 (up to 64) LEDdisplay and to facilitate bypassing of inputs and outputs.

    Display Points The FX-350 provides an LCD display to annunciate the status of the system and connected devices. The FX-351and FX-353 also provides up to 64 LED display points on the panel front in addition to the LCD display. Displaypoints may be assigned to LEDs during configuration to groups of inputs or outputs. There are two LEDs for everydisplay point: one single color (amber) and one dual color (red/amber).

    Wiring Styles The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations. Changing the indicatingcircuits to Class A requires an OCAC-304 adder board which will convert four indicating zones from Class B (StyleY) circuits to Class A (Style Z). This is done without reducing the number of circuits.

    Note: The Model FX-350-60-R and FX-350-60DR panels DO NOT recognize any devices with addresses higher than 60.

    9

  • System Components

    System Components

    Panel Models

    All FX-350 Series Panels have the following features:

    • Multi-zone fire alarm control panel with 2 x 20 LCD display.

    • Style Y or Style D analog loop(s).

    • Four Power Limited Class B (Style Y) indicating circuits (max 1.7 Amps each - 5 Amps total).

    • Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.

    • Additional RAX-332 Display Adders can be added to provide 64 annunciation points per added.

    • An optional OCAC-304 Class A converter module may be used to convert the indicating circuits to Class A (Style Z).

    • Additional outputs include connections for a RTI remote trouble indicator, PR-300 Reverse Polarity Module, an RS-485 bus for connection of up to seven RAM-300LCDs, SRM-312s and RA-1000 Series annunciators.

    • Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC filtered and regulated, and resettable auxiliary power supply.

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    FIREDRILL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNALSILENCE

    BUZZERSILENCE

    LAMPTEST

    SPARE

    AC ON1 2

    ABC3

    DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?

    SYSTEM NORMAL

    DEC 03, 2010 02:41PM

    FX-350 SERIESFire Alarm Control Panel

    SYSTEMRESET

    FIREDRILL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNALSILENCE

    BUZZERSILENCE

    LAM PTEST

    SPARE

    AC ON1 2

    A B C3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    DE F

    GHI JK L MNO

    P RS T UV WX Y

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    SYSTEM NORMAL

    DEC 03, 2009 10:25AM

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E -1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    ZO N E - 1

    FX-350 SERIESFire Alarm Control Panel

    SYSTEMRESET

    FIREDRILL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNALSILENCE

    BUZZERSILENCE

    LAM PTEST

    SPARE

    AC ON1 2

    A B C3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    DE F

    GHI JK L MNO

    P RS T UV WX Y

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    SYSTEM NORMAL

    DEC 3, 2009 3:25AM

    FX-350 SERIESFire Alarm Control Panel

    FX-350-60DR FX-351-LDRFX-353-LDR

    FX-351-LWFX-351-LDWFX-353-LW

    10

  • FX-350 Series Installation and Operation Manual

    See the table below for the specifics of each panel.

    Some models may not be available in all markets. Verify with your local distributor.

    Output Class A converter: four circuits

    Polarity reversal/city tie

    Model # of devices

    # of analog loops

    2 line UDACT Digital Communicator

    (y/n)

    DoorColor

    # of 32 point LED

    Displays

    Max # of LED Displays

    Dual Loop Adder (y/n)

    FX-350-60-DR 60 1 y red n/a n/a n

    FX-351-LW 126 1 n white 1 2 n

    FX-351-LDW 126 1 y white 1 2 n

    FX-351-LDR 126 1 y red 0 2 n

    FX-353-LW 378 3 n white 1 2 y

    FX-353-LDR 378 3 y red 0 2 y

    Model Description

    OCAC-304Output Class A converter module (four circuits)

    Model Description

    PR-300Polarity Reversal and/or City Tie Module

    - SI

    G1

    OU

    T+-

    SIG

    2 O

    UT+

    - SI

    G1

    RET

    +-

    SIG

    2 R

    ET+

    BLK

    RED

    BLK

    RED

    - SI

    G3

    OU

    T+-

    SIG

    4 O

    UT+

    - SI

    G3

    RET

    +-

    SIG

    4 R

    ET+

    BLK

    RED

    BLK

    RED

    POLAR

    ITYREVER

    SALALAR

    M

    POLAR

    ITYREVER

    SALSU

    PV

    CITYTIE

    + | -+ | -

    + | -

    JW4

    P1 P2

    Mounting hole for#6-32 screws

    Mounting hole for#6-32 screws

    11

  • System Components

    Remote Annunciator

    Smart Relay Module

    RAM-216 Remote Annunciator

    Model Description

    RAM-300LCDWRemote Annunciator module, LCD display, white painted box

    RAM-300LCDR Remote Annunciator Module, LCD display, red painted box

    Model Description

    SRM-312WSmart Relay Module (12 relays) with white enclosure

    SRM-312RSmart Relay Module (12 relays) with red enclosure

    Model Description

    RAM-216 16 Zone remote annunciator

    FA-300 SERIESRemote Annunciator

    SYSTEMRESET

    SIGNALSILENCE

    FIREDRILL

    BUZZERSILENCE

    LAMPTEST

    1

    4

    7

    *

    2

    5

    8

    0

    3

    6

    9

    #

    ENTER

    MENU

    CANCEL

    INFO

    ABC DEF

    GHI JKL MNO

    PRS TUV WXY

    QZ

    A.C. ON ALARM SUPV TRBL CPU FAIL

    SYSTE M NORMA L

    18 :01 MO N 2003- 04-05

    Advanced Life Safety Solutions

    REMOTE RELAY

    Advanced Life Safety Solutions

    FA-300 SERIES

    A.C.ON

    COMMONTROUBLE

    SIGNALSILEBCE

    BUZZERSILENCE

    SIGNALSILENCE

    LAMPTEST

    SYSTEMRESET

    SWITCHENABLE

    FIRE ALARMANNUNCIATOR

    12

  • FX-350 Series Installation and Operation Manual

    Panel Components and System Accessories

    MODEL NO. DESCRIPTIONS

    ALC-252 252 Point Dual Loop Addressable Adder

    RAX-332 32 Zone Internal Display Adder (for FX-351 and FX-353 only)

    RAM-208/R 8 LED Remote Annunciator

    RAM-1016/TZ Remote Annunciator with 16 bi-colored (red and yellow) LEDs. TZ version has 32 yellow LEDs for trouble indication.

    RAM-1032/TZ Remote Annunciator with 32 bi-colored (red and yellow) LEDs. TZ version has 32 yellow LEDs for trouble indication.

    RAX-1048/TZ Remote Annunciator with 48 bi-colored (red and yellow) LEDs. TZ version has 48 yellow LEDs for trouble indication.

    MGD-32 Graphic Annunciator

    AGD-048 Graphic Annunciator Adder Driver Board

    RTI-1 Remote Trouble Indicator, Buzzer and LED

    FA-300-TRB Trim Ring For Small Enclosure (Black)

    FA-UNIV-TRB Universal Trim Ring For Big Enclosure (Black)

    BB-1001(R) Enclosure for one annunciator, white. R version is red.

    BB-1002(R) Enclosure for two annunciators, white. R version is red.

    BB-1003(R) Enclosure for three annunciators, white. R version is red.

    BB-1008(R) Enclosure for eight annunciators, white. R version is red.

    BB-1012(R) Enclosure for twelve annunciators, white. R version is red.

    MP-300 End-of-line resistor plate, 3.9K ohm

    BC-160 External Battery Cabinet

    13

  • System Components

    Analog/Addressable Devices

    DESCRIPTION Mircom Model

    Ionization Smoke Detector (U.S. Model Only) MIX-3000

    Photoelectric Smoke Detector MIX-3100

    * Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor) MIX-3200Heat Detector MIX-3300

    BASES

    4 inch Standard Base MIX-2000

    6 inch E-Z Fit Base MIX-2001

    6 inch Base with Relay MIX-2001R

    6 inch Base with Sounder MIX-2001H

    6 inch Base with Temporal Tone Sounder MIX-2001HT

    ANCILLARY MODULES

    Priority Monitor Module MIX-100P

    Mini Priority Monitor Module MIX-101P

    Single Relay Output Module (1 Form C Contacts, 2 Gang Mount) 55000-820

    Supervised Control Module MIX-100S

    Isolator c/w Mounting Base

    MIX-100X (Kit)

    100XH (Isolator)

    100XB (Base)

    ADDRESSABLE DUCT DETECTORS

    Ionization Duct Smoke Detector (UL Listed) MIX-DH3000

    Photoelectric Duct Smoke Detector (UL Listed) MIX-DH3100

    Ionization Duct Smoke Detector with relay (UL Listed) MIX-DH3000R

    Photoelectric Duct Smoke Detector with relay (UL Listed) MIX-DH-3100R

    ADDRESSABLE PULL STATIONS

    Addressable Single Stage Pull Station MS-401ID(U)

    Addressable Two Stage Pull Station (Canadian Model Only) MS-402ID

    Addressable Single Stage Single Action Pull Station MS-701ID(U)

    Addressable Two Stage Single Action Pull Station MS-702ID(U)

    Addressable Single Stage Dual Action Pull Station MS-710ID(U)

    * Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the product data sheet for detailed functionality, operation and application.

    Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO CONFIG.

    14

  • FX-350 Series Installation and Operation Manual

    Mechanical Installation

    Installing the EnclosuresInstall the FX-350 Series Fire Alarm Panel enclosure as shown below. Mount the enclosure using the four mounting holes and the screws provided.

    Figure 1: Wallbox Dimensions / Mounting the FX-350 – Surface

    11"

    14.5"

    1.5"

    14.5"

    5.4"

    4.5"

    20"

    Mounting Hole

    Mounting Hole

    Mounting Hole

    Mounting Hole

    15

  • Mechanical Installation

    Figure 2: Mounting the FX-350 - Flush

    The figure below shows a cross-section of the semi-flush mounted backbox and the trim ring. Make sure to allow a minimum depth of 1” above the wall surface for proper door opening.

    Figure 3: Flush Trim Detail

    17"

    22.5"

    PLACE FA-300TRB TRIM RING OVER BACKBOX

    14.5"

    3.5"

    1"

    4.5"

    11"

    20.0"

    1.5"

    4"

    14.5"

    3.5" is the maximum depthfor semi-flush mountingusing the flush trim ring

    1" is the minimum depthabove the wall requiredfor semi-flush mountingusing the flush trim ring

    4 MountingHoles forSurface

    Mounting

    Adhere trim ring towall surface aroundFX-350 backbox

    Back box

    Trim ring

    Wall

    Wood stud

    16

  • FX-350 Series Installation and Operation Manual

    Figure 4: Wallbox Dimensions / Mounting the FX-351/FX-353 – Surface /Flush

    Note: See Figure 3 for Flush Trim Details for mounting the trim ring.

    17"

    28.5"

    PLACE FA-UNIV-TRB TRIM RING OVER BACKBOX

    14.5"

    3.5"

    1"

    4.5"

    11"

    26"

    1.5"

    4"

    20.5"

    3.5" is the maximum depthfor semi-flush mountingusing the flush trim ring

    1" is the minimum depthabove the wall requiredfor semi-flush mountingusing the flush trim ring

    4 MountingHoles forSurface

    Mounting

    Adhere trim ring towall surface aroundFX-351 backbox

    17

  • Installing Adder Modules

    Installing Adder Modules

    The FX-350 Series Fire Alarm panels come pre-assembled with all components and boards except for Adder Modules. Module installation locations are shown below. Refer to Figure 6 and 6A on the next page for Jumper or DIP Switch settings and see Wiring Tables and Information for wiring specifications.

    Figure 5: Installation of Adder Modules

    CLASS- A converterboard for indicating

    circuits OCAC-304(4 circuits)

    Reverse polarity and city

    tie module PR -300.Mounted on hex spacer

    with two screws provided

    Transformer

    AC wiring terminal

    -SIG1

    OUT+

    -SIG2OUT

    +

    -SIG1RE

    T+-SIG2RET

    +

    BLK

    RED

    BLK

    RED

    -SIG3

    OUT+

    -SIG4

    OUT+

    -SIG3

    RET+

    -SIG4

    RET

    +

    BLK

    RED

    BLK

    RED

    P3

    BATTERY

    P4

    + -

    P1

    P2

    SEC TX

    POWER

    SUPPLY

    Power supplyboard

    BATTERY

    + -

    BATTERY

    + -

    S-

    +NC

    NO

    CNC

    NO

    CNC

    NO

    CNC

    NO

    CR

    TR

    TR

    TR

    T

    RES

    CO

    RES

    CO

    LINE1

    LINE2

    JW7

    -+

    -+

    -+

    -+

    -+

    -+

    SIG

    1SIG

    2SIG

    3SIG

    4

    TO PR-300 MODULE

    RS-485

    AUX.RELAY

    ALARM

    RELA

    YSUPERVISORY

    REL

    AY

    TROUBLE

    RELAY

    AUX

    SUPPLY

    4-W

    IRE

    SUPPLY

    COM+COM-TRLTRB

    UNFILTERED

    FWR24VDC

    RTI

    PORT

    SYSTEM NORMAL

    OCT 21 , 2005 02:41AM

    Loop

    A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    SYSTEM

    RESET

    F IRE

    DRILL

    ALARM

    ACKNOWLEDGE

    GENERAL

    ALARM

    SIGNAL

    SILENCE

    BUZZER

    SILENCE

    LAMP

    TEST

    SPARE

    AC ON

    1 2ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    D EF

    GH I JKL MN O

    PR S TU V WXY

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    PR- 300 is mounted

    here for FX-351

    JW2

    JW6

    JW5

    For PC programming use UIMA

    Interface module not UL-864 or

    ULC-527 listed. Please refer to

    Document LT-929 for details

    RS-232C PORT

    TO RAX-332

    P12

    P3 P2P8 P4

    18

  • FX-350 Series Installation and Operation Manual

    Cable and Jumper Connections for Main Board and Adder Modules

    Figure 6: Main Fire Alarm Board Cable Connectors and Jumper Locations

    Telephone line #1

    Telephone line #2

    RS-485 for

    annunciators

    Auxiliary Relay

    Alarm Relay

    Supervisory Relay

    Trouble Relay

    Auxiliary

    Supply

    Resettable

    Auxiliary

    Supply

    Unfiltered24V supply

    Connect to PR-300

    Connect toRemote troubleindicator

    Connect to RAX-332

    Addressable

    Loop

    BLK

    RED

    BLK

    RED

    BLK

    RED

    BLK

    RED

    POWER

    SUPPLY

    S-

    +NC

    NO

    CNC

    NO

    CNC

    NO

    CNC

    NO

    CR

    TR

    TR

    TR

    T

    RES

    CO

    RES

    CO

    LIN

    E1

    LINE2

    JW7

    -+

    -+

    -+

    -+

    -+

    -+

    SIG

    1SIG

    2SIG

    3SIG

    4

    RS-485

    AU

    X.RELAY

    ALARM

    RELA

    YSUPERVIS

    ORY

    RELAY

    TR

    OU

    BLE

    RELAY

    AUX

    SUPPLY

    4-W

    IRE

    SUPPLY

    COM +COM -TRLTRB

    UNFILTERED

    FWR 24 VDC

    RTI

    PORT

    SYSTEM NORMAL

    OCT 21 , 2005 02 : 41 AM

    Loop

    A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    SYSTEM

    RESET

    F IRE

    DRILL

    ALARM

    ACKNOWLEDGE

    GENERAL

    ALARM

    SIGNAL

    SILENCE

    BUZZER

    SILENCE

    LAMP

    TEST

    SPARE

    AC ON

    1 2

    ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    D EF

    GH I JKL MN O

    PR S TU V WXY

    QZ

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUND FAULT

    JW2

    JW6

    JW5

    For PC programming use UIMA

    Interface module not UL-864 or

    ULC-527 listed. Please refer to

    Document LT-929 for details

    RS-232C PORTFor PC programming

    P12

    P3 P2P8 P4

    19

  • Installing Adder Modules

    The Figure below shows the main board for the 3 loop addressable model. It is the same as the single loop model with two additional addressable loops.

    Figure 7: Main Board (3 loop model) Cable Connectors and Jumper Locations

    T elephone line #1

    T elephone line #2

    RS-485 forannunciators

    Auxiliary Relay

    Alarm Relay

    Supervisory Relay

    T rouble Relay

    AuxiliarySupply

    ResettableAuxiliarySupply

    Unfil tered24V supply

    Connect to PR-300

    Connect toRemote troubleindicator

    Connect to RAX-332

    Addressable

    1 3 2 Loops

    BL

    K

    RE

    D

    BLK

    RED

    BLK

    RE

    D

    BL

    K

    RE

    D

    PO

    WER

    SUP

    PLY

    S-

    +N

    CN

    OC

    NC

    NO

    CN

    CN

    OC

    NC

    NO

    CR

    TR

    TR

    TR

    T

    RE

    SC

    OR

    ES

    CO

    LIN

    E1LI

    NE

    2

    JW7

    -+

    -+

    -+

    -+

    -+

    -+

    SIG

    1SI

    G2

    SIG

    3SI

    G4

    RS-

    48

    5A

    UX

    .R

    ELA

    YA

    LA

    RM

    RE

    L AY

    SU

    PER

    VIS

    OR

    Y

    RE

    LAY

    TR

    OU

    BLE

    RE

    LAY

    AU

    X

    SU

    PP

    LY

    4-W

    IRE

    SU

    PP

    LY

    CO M +CO M -TRLTRB

    UNF IL TE RE D

    F W R 24 VDC

    RTI

    PO RT

    SYSTEM NORMAL

    OCT 21 , 2005 02 : 41 AM

    Lo

    op A

    +-

    +-

    B

    JW9

    JW1

    JW3

    JW4

    S Y S T E M

    R E S E T

    F IR EDR IL L

    AL AR M

    ACK NOWL E DGE

    GE NE R ALAL AR M

    S IGNAL

    S IL E NC E

    B UZ Z E RS IL E NC E

    L AMP

    T E S T

    S P AR E

    AC ON

    1 2ABC

    3

    5 6

    7 8 9

    * 0 #

    4

    X

    M

    ?

    DEF

    GHI JKL MNO

    PR S TUV WXY

    QZ

    COMMON ALAR M

    COMMON S UP V

    COMMON TR OUB LE

    C P U FAULT

    GR OUND FAULT

    J W2

    JW6

    JW5

    F or PC programming us e U IMAInterface module not UL-864 orULC-527 lis ted. P leas e refer toDocument LT-929 for details

    R S -232C POR TFor PC programming

    P 12

    P 3 P2P 8 P 4

    20

  • FX-350 Series Installation and Operation Manual

    Table 1: Connectors and Jumpers on the Main Fire Alarm Board

    OCAC-304 Output Class A Converter Adder Module

    Figure 8: OCAC-304 Output Class A Converter Adder Modules

    Indicating circuits must be wired from the OCAC-304 to the main Fire Alarm board. For example indicating circuit 1 positive (red wire) and negative (black wire) is wired from the Class A Converter Module to the positive and negative terminals of Indicating circuit 1 on the Main Fire Alarm board.

    The actual indicating zone is wired from the SIGNAL OUT positive and negative to the signaling devices and then wired back to the SIGNAL RET positive and negative.

    P8Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects here. Otherwise not used.

    P4 Cable from connector P1 of the RAX-332 Display Adder Module connects here. Otherwise not used.

    JW1 On the Main Fire Alarm Module, this jumper is not used, open.

    JW2 Remove this jumper if a remote annunciator is used.

    JW3 Not used, open.

    JW4 Not used, open.

    JW5Normally open. Place jumper here and power down (AC and batteries) and power back to restore Master Passcode. After reset, remove jumper and leave normally open.

    JW6Normally open to BLOCK remote configuration via modem. Place jumper here to ALLOW for remote configuration.

    JW7On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity Reversal and City Tie Module is installed.

    JW8, JW9, JW10, JW11, JW12

    Not used, open.-

    SIG

    1 O

    UT+

    -SI

    G2

    OU

    T+

    -SI

    G1

    RET

    +-

    SIG

    2 R

    ET+

    BLK

    RED

    BLK

    RED

    -SI

    G3

    OU

    T+-

    SIG

    4 O

    UT+

    -SI

    G3

    RET

    +-

    SIG

    4 R

    ET+

    BLK

    RED

    BLK

    RED

    OCAC-304

    Mounting hole for #6-32 screw

    Mounting hole for #6-32 screw

    21

  • Installing Adder Modules

    Polarity Reversal and City Tie Module (Model PR-300) Mount the PR-300 on the left side panel of the backbox with the two screws provided, refer to Figure 5.

    Figure 9: Polarity Reversal and City Tie Module

    The following hardware configuration must be performed before installing the PR-300.

    Table 2: PR-300 Cable and Jumper Settings

    The Alarm Transmit signal to the PR-300 can be programmed to turn OFF when signal silence is active. This allows the City Tie Box to be manually reset. On subsequent alarms the silenceable signals will resound and the City Tie Box will be retriggered.

    The Trouble Transmit signal to the PR-300 can be programmed to delay AC power fail 0, 1, 2, or 3 hours if this is the only system trouble.

    RAX-332 Display Adder ModuleThe RAX-332 Display Adder Module is used only with the FX-351 and FX-353 Fire Alarm Panels. No jumpers or other physical configuration steps are required to install this second RAX-332 Display Adder Module. Remove the blank cover plate from the front door and install the RAX-332 with the clear cover in the opening with the hardware provided. Disconnect main and standby power and connect the cable of the second RAX-332 into the open, remaining header of the existing RAX-332. The additional LEDs will be available for configuration as LEDs 33 to 64, when the system power is restored.

    ITEM SETTING

    P1 Cable connects to P8 (bottom left-hand corner) on the Main Fire Alarm Board.

    JW4 Not used. Keep jumper intact.

    POLAR

    ITYREVER

    SALALAR

    M

    POLAR

    ITYREVER

    SALSU

    PV

    CITYTIE

    + | -+ | -

    + | -

    JW4

    P1 P2

    Mounting hole for#6-32 screws

    Mounting hole for#6-32 screws

    22

  • FX-350 Series Installation and Operation Manual

    Circuits and Devices

    Addressable/Analog DevicesThe FX-350 supports up to 3 loops of addressable/analog devices. The device loop can be used to connect up to 60, 126 or 378 analog devices and addressable input or output modules on an unshielded twisted pair (UTP). The devices must be compatible with the Mircom device protocol.

    The loop interface software continuously supervises the devices on its loop against those found during configuration for the following conditions:

    • device missing

    • unconfigured device responding

    • two or more devices responding to the same address

    • wrong device type

    A communication or addressing error on a device is reported as a trouble on the associated zone LED if configured.

    The addressable loop can be configured for class A or B operation. "T-tapping" is allowed (Refer to device installation documentation for details). A short or open on the loop will activate the common trouble sequence with a latching trouble.

    Devices on the loop have an optional LED which normally flashes when the device is polled and goes ON steady when the device is active (alarm for an input device or active for an output device). The flashing of the LED on polling for sensors can be suppressed during configuration. For input or output modules, the LED always flashes when polling. The software limits the maximum number of the devices which can have their LED turned ON when active to fifteen (15).

    Certain devices are designed to support an optional external LED, which operates when the LED on the device is activated. Remote/external LEDs must NOT be used on this system. The panel can provide up to 350mA of current to the devices on the loop. A maximum line loss of 5 volts is permitted, so the loop distance, wire size, and maximum number of devices are limited by this constraint.

    The devices should be installed using unshielded twisted pair (UTP). The total line drop on the loop must not exceed 5 volts at the last device. The calculations required to determine the maximum permissible loop wiring distance with various combinations of devices is relatively complicated, and when isolators are used, includes a consideration of device inrush currents which must not exceed 20mA for a single isolator. In no case should more that twenty devices be connected to a single isolator. To simplify the calculation process, please utilize the loop calculator program located on the Mircom website at http:/www.mircom.com in order to determine maximum loop lengths, number of devices, and wire sizes etc.

    It is also important to note that the device LEDs present a significant extra load on the loop which must be considered in calculating permissible loop lengths, battery capacities, etc. Please refer to the device Installation Instructions and other documentation provided with the addressable devices, bases, and isolators for further information. The system will automatically limit the maximum number of device LEDs which can be illuminated to 15.

    Analog DevicesThe system supports Mircom MIX-3000 Series photo, ion, multi-sensor and thermal (heat) type analog detectors, as well as contact input and output devices. The detectors may be configured as non-verified or verified alarm inputs. To determine an alarm condition, the system polls the analog device and compares the analog value against stored thresholds for pre-alarm and alarm conditions.

    A range of thresholds is provided for each type of analog device (except for contact devices), corresponding to the agency approved range of threshold for a particular device type. Each device can be individually configured to a value in the range of threshold for “day time” and one for the “night time” or after hours operation; i.e. a device may be configured to a low sensitivity for “day time” and high sensitivity at “night time”. The day time threshold will be used unless the after hours operation is active.

    23

    http://www.apollo-fire.co.uk/prod-serv/loopcalc.htm

  • Circuits and Devices

    Drift CompensationThe FX-350 will automatically adjust for gradually increasing affects of dust and other accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual change in the normal clean air value received. When it can no longer compensate for an increasingly dirty detector, a dirty detector trouble is indicated for that device.

    Auto TestPeriodically each detector is commanded to return an alarm value to test its ability to alarm. If it fails the test, a trouble is indicated on that device. This trouble is latched until system reset.

    Contact InputsContact input modules on the addressable/analog device loop may be configured as any of the following input types:

    • non-verified alarm inputs

    • waterflow inputs

    • non-latching supervisory inputs

    • latching supervisory inputs

    • monitor inputs

    • trouble only inputs

    • remote switch inputs

    Contact OutputsContact output modules on the addressable/analog device loop may be configured as any of the following output types:

    • signals

    • strobes

    • relay outputs

    Analog devices may be installed with relay or sounder bases. The outputs of these bases are activated when the device active LED turns ON steady in response to an alarm. The command to activate the output is separate from the command that activates the LED and they are not subject to the same restrictions as the LED. Output modules configured as signals are not stroked by software at the current signal rate. When the system commands them to be either in alert or in evacuation, the panel will simply activate them continuously. It is possible to provide stroked operation by connecting the signal power to a conventional signal output which is stroking at the correct rate when the device is active. Depending on the device, the system can detect open and short troubles and report it as an output circuit trouble.

    24

  • FX-350 Series Installation and Operation Manual

    Field Wiring

    Main Fire Alarm Board Field Wiring Wire devices to the addressable loop as shown in Figure 9 for Class B (Style 4) or Figure 10 for Class A (Style 6). Refer to the Table 3 for loop wire gauges. Wire devices to addressable loops 2 and 3, if available, in the same manner.

    Figure 10: Addressable Loop Wiring - Class B or Style 4

    Table 3: Loop Wiring Table

    Loop IsolatorsTo limit the number of addressable devices compromised by a short on the addressable loop, isolators (MIX-100X, 100XH, or 100XB) may be used to isolate the affect of the short circuit. If the impact of a short circuit must be limited to only one device, an isolating base must be used for each detector. A maximum of twenty devices can be connected between isolators, or between the panel and the first isolator, as long as the maximum in-rush current for the devices on one segment of the loop does not exceed 20mA. Refer to the installation instructions for addressable devices for additional details.

    UNSHIELDED TWISTED

    PAIR WIRE GAUGE

    LOOP TOTAL (OUT AND IN) WIRE RUN

    AWG FEET METRES

    12 20,000 6098

    14 15,942 4859

    16 9960 3036

    18 6265 1910

    CLASS BWIRING

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR PULL STATION

    Loop A

    +-

    +-

    B

    OUTPUT MODULE

    This Loop Wiring Table is for reference only and should not beused without a detailed loop calculation.

    Maximum Loop Current: 350 mA

    Maximum Loop Resistance: 35 subtract 0.2 Ohms per isolator.

    Maximum Loop Capacitance: 0.5 uF

    Maximum Number of Isolators is 40.

    25

  • Field Wiring

    Figure 11: Addressable Loop Wiring -Class A or Style 6

    Loop OperationWhen there is a short circuit on the Class A loop with isolators installed, the isolators isolate the shorted fault, the panel detects it as an open loop and generates an open loop trouble.

    When a Class A loop is opened there may be a few missing devices reported by the panel which will be restored once the panel has established the Class A connection.

    Note: When there is an "Open loop trouble" look for both open and shorts on the loop. As a guide line the isolators which are activated in response to a short will have their LED ON; look for the short between the two isolators with their LEDs ON.

    CLASS AWIRING

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR INPUT MODULE

    Loop A

    +-

    +-

    B

    OUTPUT MODULE

    26

  • FX-350 Series Installation and Operation Manual

    Indicating (Powered Output) CircuitsPowered output circuits can be configured as signal, strobe or relay outputs. Powered output circuits are supervised while they are not active for both open circuits and shorts. The circuit will not actually be activated if there is a short trouble on the circuit. It will be activated if an open trouble is indicated. A circuit trouble activates the common trouble sequence as a non-latching trouble. Since open circuit supervision does not operate while the circuit is in alarm, if the circuit was in trouble before it was activated, it will still indicate trouble while active. The trouble condition will be re-evaluated when supervision resumes.

    Output circuits configured as strobes can have sync protocol for synchronization if configured. Certain strobe and strobe/horns models of the following manufacturers are supported.

    1. All normal non-sychronized horns

    2. Faraday

    3. System Sensor

    4. Wheelock

    5. Gentex

    6. Mircom

    When configured as normal, the output circuit is ON continuously when activated and does not use any sync protocol. When configured as non-silenceable strobes, the strobes cannot be silenced, but the horn can be silenced by pressing the 'signal silence' button

    If the strobe is configured as silenceable strobe both the horn and the strobe are silenced (stopped) by pressing the 'signal silence' button

    Indicating Circuit Wiring The FX-350 Series Addressable Fire Alarm Panel supports Class B (Style Y) and Class A (Style Z) wiring for its indicating circuits. Each circuit is supervised by a 3.9K End-of-Line resistor. Each indicating circuit provides up to 1.7Amperes, total 5Amperes of current maximum if no auxiliary power is used. Wire indicating circuits as in Figure 11 for Class B (Style y) or as in Figure 12 for Class A (Style Z).

    Table 4: Indicating Circuit Wiring

    Total signal load in

    amperes

    Maximum wiring run to last device Max loop resistance

    in ohms18 AWG 16 AWG 14 AWG 12 AWG

    Feet Meters Feet Meters Feet Meters Feet Meters

    0.06 2350 716 3750 1143 6000 1829 8500 2591 30

    0.12 1180 360 1850 567 3000 915 4250 1296 15

    0.3 470 143 750 229 1200 366 1900 579 6

    0.6 235 71 375 114 600 183 850 259 3

    0.9 156 47 250 76 400 122 570 174 2

    1.2 118 36 185 56 300 91 425 129 1.5

    1.5 94 29 150 46 240 73 343 105 1.2

    1.7 78 24 125 38 200 61 285 87 1.0

    Notes:

    • For Class A wiring the resistance in ohms is multiplied by two.

    • Maximum voltage drop should not exceed 1.8 volts.

    27

  • Field Wiring

    Figure 12: Indicating Circuit – Class B or Style Y Wiring

    Figure 13: Indicating Circuit –Class A or Style Z Wiring

    - S

    IG 1

    +

    STYLE YWIRING

    STYLE YWIRING

    INDICATING CIRCUIT - 1

    INDICATING CIRCUIT - 2

    BELL STROBE 3.9K 1/2 WATT ELR

    INDICATINGCIRCUIT #1

    INDICATINGCIRCUIT #2

    HORN

    FIRE PANEL MAIN BOARD

    - S

    IG 2

    +

    NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS #1 AND #2

    BELL

    STROBE

    HORN

    +

    -

    STYLE ZWIRING

    STYLE ZWIRING

    INDICATINGCIRCUIT #1

    INDICATINGCIRCUIT #2

    INDICATING CIRCUIT 1

    INDICATING CIRCUIT 2

    2 MORE INDICATING CIRCUITS NOT SHOWN

    OCAC-304 CLASS A CONVERTER MODULE

    FIRE PANEL MAIN BOARD

    BLK

    RED

    BLK

    RED

    -SIG

    1 O

    UT+

    -SI

    G2

    OU

    T+

    -SI

    G1

    RET

    +-

    SIG

    2 R

    ET++

    -

    SIG

    1S

    IG 2

    NOTE: WIRE INDICATING CIRCUITS # 3 AND #4 IN THE SAME WAY AS #1 AND #2

    28

  • FX-350 Series Installation and Operation Manual

    Dialer WiringIf you have Fire Alarm Panel model FX-350-60-DR, FX-350-126-DR, FX-350-378-LDR, FX-351-LDW or FX-353-DR, there is a dialer on board and terminals marked Line 1 and Line 2 must be wired as shown in Figure 13 below. Terminals are located in the top left hand corner of the main fire alarm board, from the top down. Refer to Figure 6 for terminal location.

    Figure 14: Dialer Wiring

    Refer to Dialer Operation Section and Appendix B for more information regarding the built-in dialer.

    TT

    RR

    premise telephoneIF permitted

    TT

    RR

    LINE-1

    LINE-2

    1

    2 3

    4

    8 5

    7 6

    Public switchTelephone company

    wiring

    TIP

    RING

    TIP

    RING

    RJ31X

    GREY

    BROWN

    RED

    GREEN

    CO

    CO

    RE

    SR

    ES

    Line 2 is Wired as shown for Line 1

    FIRE ALARM MAIN BOARD

    29

  • Field Wiring

    Polarity Reversal and City Tie Module (PR-300) Wiring Wire the PR-300 Polarity Reversal and City Tie Module (if used) as shown in Figure 14 below. Power Limited cable type FPL, FPLR or FPLP must be used. For USA installation, the installer must use Atlantic Scientific (Tel: 407-725-8000), Model #24544 Protective Device, or similar UL-Listed QVRG secondary protector, as shown. For use in Canada, the Protective Device is not required but still recommended.

    Figure 15: Polarity Reversal and City Tie Module Terminal Connection

    1

    1

    2

    2

    S

    S

    CITY TIE LOCAL ENERGYRATED - 24VDC FILTEREDTRIP COIL - 14 Ohms, 210mA, 5mV RIPPLE

    POLARITY REVERSAL ALARM24VDC OPEN12VDC AT 3.5mA8mA MAX. SHORT

    POLARITY REVERSAL SUPV .24VDC OPEN12VDC AT 3.5mA8mA MAX. SHORT

    PROTECTOR1

    1

    2

    2

    S

    S

    1

    1

    2

    2

    S

    S

    PROTECTOR1

    1

    2

    2

    S

    S

    USE A SHORTING WIRE WHEN THE CITY TIE IS NOT USED

    +

    +

    +

    -

    -

    -

    +

    +

    +

    -

    -

    -

    CONFORMS TO NEMA STANDARD SB3-1969 INTENDED FOR CONNECTION TO POLARITY REVERSAL CIRCUIT OF A REMOTE STATION RECEIVING UNIT HAVING COMPATIBLE RATINGS

    DIN RAIL CONNECTION TO EARTH GROUND

    DIN RAIL CONNECTION TO EARTH GROUND

    NOT POWER LIMITED

    POWER LIMITED

    POWER LIMITED

    PR-300

    PRO

    TECT

    EDPR

    OTE

    CTED

    UN

    PRO

    TECT

    EDUN

    PRO

    TECT

    ED

    NOTES:1. Plug PR-300 ribbon cable P1 into connector P8 of the Main Fire Alarm board.2. Cut Jumper JW1 on the PR-300 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Alarm terminals to the monitoring station.3. Cut Jumper JW2 on the PR-300 Polarity Reversal and City Tie Module in order to transmit a trouble condition from the Polarity Reversal Supervisory terminals to the monitoring station.4. Remove jumper plug from JW7 on the Main Fire Alarm board.5. For USA installation, the installer must use an Atlantic Scientific (Tel. 407-725-8000), Model #24544 Protective Device or similar UL-Listed QVRG secondary protector.6. The Polarity Reversal interface is Power Limited and must use power limited cable type FPL, FPLR or FPLP from the PR-300 to the Protectors.

    EITHER THE CITY TIE or POLARITY REVERSAL INTERFACE MAY BE USED, NOT BOTH.

    30

  • FX-350 Series Installation and Operation Manual

    Auxiliary Power Supplies

    Aux 2 Resettable Auxiliary Power (supervised, regulated)The AUX 2 resettable auxiliary power supply is supervised for shorts, therefore a short will disconnect the power until the “RESET” button is pressed. A trouble signal will be generated if there is a short. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 as shown in Figure 15. This supply is rated at 21.1VDC regulated/300mA max/1V voltage drop maximum.

    Auxiliary Supply (supervised, regulated) Supervised auxiliary power is used to power the remote annunciators and smart relay modules. This filtered circuit is supervised for shorts, therefore a short will disconnect the power until the “RESET” button is pressed. A trouble signal will be generated if there is a short. The circuit must be supervised for opens utilizing the End of Line Relay Model PAM-3 as shown in Figure 15. This supply is rated at 21.1VDC regulated/500mA max/1V voltage drop maximum.

    Unfiltered Supply (unsupervised, unregulated) This unregulated supply is not supervised. When required, it is recommended that the circuit be supervised for opens utilizing the (UL listed - S3403) End of Line Relay Model PAM-3 as shown in Figure 15. This supply is rated at 24VDC/1.7A max. If there is a short on this circuit, the auxiliary power does not recover automatically when the short is removed. The main power and the battery must be disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply.

    Figure 16: Supervision Of Auxiliary Supplies

    14

    23

    56DETECTOR POWER SUPPLY22VDC, 200mAMAX. CURRENT - 300mAMAX. RIPPLE VOL. 5mV(POWER LIMITED)

    END OF LINE RELAY

    +

    -RESETTABLE AUXILIARY POWER OR AUXILIARY SUPPLY ORUNFILTERED SUPPLY

    FIRE ALARM MAIN BOARD

    E.O.L.47K Ohms

    ION SMOKE DETECTOR

    PHOTO SMOKE DETECTOR

    HEAT DETECTOR

    +-

    +-

    B

    LEGEND

    Class B (Style B) WIRING

    Loop

    A

    MIX-101PViolet

    White

    Red

    RedBlack

    Black

    Supervision for Auxiliary Supplies

    MINI MONITOR MODULE

    AUX 2

    Connect auxiliary devices here*

    * Use this supervision set-up only if auxiliary devices are used.

    MIX-101P

    31

  • Field Wiring

    Power Supply ConnectionsThe power supply is located directly behind and below the main board. The ratings are:

    Figure 17: Main Power Supply Connections

    TYPE RATING

    Electrical Input rating 120 VAC, 60Hz, 1.73A / 240VAC, 50Hz, 0.864A

    Battery fuse on Main module 10A, slow blow micro fuse (not replaceable)

    Caution: The main AC branch circuit connection for the Fire Alarm Control Unit must provide a dedicated continuous power without any disconnect devices. Use #12 AWG wire with 600-volt insulation and proper over-current circuit protection that complies with the local codes. Refer to Appendix C for specifications.

    Note: Ensure that the AC supply is disconnected before wiring the power to the panel. Wire the AC power to the AC wiring terminals as shown in Figure 16 using the proper wire gauge. Fire alarm systems must be installed in compliance with local codes and standards and with the Authority Having Jurisdiction (AHJ)

    Note: The FX-350 panel is capable of being wired for 120 VAC or 240 VAC 50/60 Hz as shown above. A good ground connection to the “Ground" terminal is essential to electrical safety, ensure proper operation, and specified noise immunity.

    P3

    BATTERY

    P4

    + -

    P1

    P2

    SEC TX

    P6

    P5

    PO

    WE

    R S

    UP

    PLY

    TRANSFORMER

    AC WIRING TERMINALS

    POWER SUPPLY BOARD

    BATTERY

    + -

    JW7

    TO PR-300 MODULECOM+COM-TRLTRB

    UNFILTEREDFWR 24VDC

    RTI PORT

    BATTERY

    + -

    Yellow

    Red

    Black

    Green

    240VAC 50Hz

    120VAC 60Hz

    N

    Ground

    P3 P2

    RIBBON CABLE

    POWER CONNECTOR

    BLACKRED

    RED

    32

  • FX-350 Series Installation and Operation Manual

    System Checkout

    Before turning the power “ON” To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the main AC supply.

    1. Check that all adder modules are installed in the proper location with the proper connections.

    2. Check all field (external) wiring for opens, shorts, and ground.

    3. Check that all interconnection cables are secure, and that all connectors are plugged in properly.

    4. Check all jumpers and switches for proper setting.

    5. Check the AC power wiring for proper connection.

    6. Check that the chassis is connected to earth ground (cold water pipe).

    7. Make sure to close the front cover plate before powering the system from main AC supply.

    The best way to set up a panel for the first time is to avoid connecting any field wiring at first. To begin set up, power up the panel with end of line resistors connected where appropriate, then connect the battery. The panel will show “System Restart Active”. Press System Reset button to reset the panel. If the panel is free of trouble, connect one circuit at a time, checking for troubles each time. If a trouble occurs at any point during the set-up, correct the fault, then continue connecting the field wiring.

    Power-up procedure After completing the system checkout procedures outlined above,

    8. Power up the panel. The "AC-ON" green LED and the “Common Trouble” LED should illuminate, and the buzzer should sound. Press the “System Reset” button. Since the batteries are not connected, the trouble buzzer should sound intermittently and the common trouble LED should flash.

    9. Connect the batteries while observing correct polarity: the red wire is positive (+) and black wire is negative(-). All indicators should be OFF except for normal power "AC ON" green LED.

    10.Configure the Fire Alarm Control Panel as described in the System Configuration section.

    Troubleshooting

    Symptoms Possible Cause

    Circuit Trouble

    Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated, as well as the common trouble indicator and trouble buzzer. To correct the fault, check for open wiring on that particular circuit loop or that the Circuit Disconnect Switch is in the ON or CLOSED position. Note: Disconnecting a Circuit will cause a system trouble (off-normal position).

    Remote TroubleRemote Trouble will be indicated on the main panel display for any failure reported by, or failure to communicate with a remote annunciator or other remote device.

    Ground FaultThis panel has a common ground fault detector. To correct the fault, check for any external wiring touching the chassis or other Earth Ground connection.

    Battery Trouble Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will cause a battery trouble. If battery trouble condition persists, replace batteries as soon as possible.

    Walk Test Mode If the Walk Test LED is illuminated steadily, the system is in Walk Test Mode.

    Common Trouble

    If only a common trouble is indicated on the main panel and none of the above confirming trouble indicators are ON, check the following for possible fault:

    • Check for any missing interconnection wiring.

    • Check for any Module missing that was part of the Configuration.

    • Check for improperly secured cabling.

    33

  • Indicators, Controls and Operations

    Indicators, Controls and Operations

    Figure 17 below shows the common display panel for both the FX-350, FX-351 and the FX-353 Fire Alarm Control Panels.

    Figure 18: LCD Display, LED indicators and control buttons

    The display panel on the FX-350/FX-351/353 main fire alarm control board consists of:

    • a two line by twenty character LCD display

    • a sixteen button keypad

    • common LED Indicators

    • common control buttons

    FX-351 and FX-353 models are equipped with one RAX-332 LED display adder (32 zone annunciation), with provision for a second optional adder (see page 14 for further explanation) for another 32 zone annunciation for a total of 64 zone annunciation. Each LED zone has a red/amber alarm/supervisory LED and an amber trouble LED.

    LED Indicators may be amber, red, or green, and may illuminate continuously, or at one of following Flash Rates:

    • Steady (Alarm) - ON continuously.

    • Fast Flash (Supervisory) - 120 flashes per minute, 50% duty cycle.

    • Trouble Flash (Trouble) - 20 flashes per minute, 50% duty cycle.

    Red indicators are used for Alarm, amber indicators for Trouble or Supervisory and green for power ON.

    Note that each RAX-332 display is supplied with blank paper labels (#NP-681) for sliding into the plastic label template on the display.

    COMMON ALARM

    COMMON SUPV

    TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    FIREDRI LL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNAL

    BUZZERSILENCE

    LAMPTEST

    BATTERY/CHARGER

    AC ON1 2

    ABC3

    DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?

    SYSTEM NORMAL

    DEC 03, 2009 02:41AM

    COMMON

    SILENCE

    TROUBLE

    34

  • FX-350 Series Installation and Operation Manual

    Common Indicators

    BuzzerThe Buzzer is activated by any of the following:

    • Fire Alarm: Steady

    • Supervisory Alarm: Fast flash rate

    • Trouble: trouble flash rate

    • Monitor: Configurable to sound at trouble flash rate

    If the buzzer turns ON in response to a non-latching trouble or supervisory, it will turn OFF if the condition causing it goes away and there is no other reason for it to be ON.

    AC On LEDThe AC On LED illuminates steady green while the main AC power is within acceptable levels. It turns off when the power level falls below the power-fail threshold and the panel switches to standby (battery) power.

    Common Alarm LEDThe Common Alarm LED illuminates steady red whenever the panel is in alarm. An alarm results from any alarm on any point or input programmed as alarm or activation of the manual General Alarm button (if the panel is set for two stage operation). Since all alarms are latched until the alarm conditions are cleared and the panel is reset, the LED will remain ON until then.

    Common Supervisory LEDThe Common Supervisory LED flashes amber at the Supervisory or Fast Flash rate when there is a supervisory alarm in the panel resulting from any un-bypassed latching or non-latching supervisory circuit. The LED turns OFF if all non-latching Supervisory Circuits are restored and there are no active latching supervisory circuits. Latching supervisory alarms remain active until the panel is reset.

    Common Trouble LEDThe Common Trouble LED flashes amber at the Trouble Flash rate when the panel detects any trouble condition in the system. The LED turns OFF once all non-latching troubles are cleared.

    CPU Fault LEDThe CPU Fault LED flashes amber at the Trouble Flash rate when the panel detects a fault on the CPU. It is turned OFF when the CPU fault is corrected.

    Ground Fault LEDThe Ground Fault LED flashes amber at the trouble flash rate when the Ground Fault Detector detects a ground fault on any field wiring. It turns off immediately after the ground fault is cleared.

    System Reset LEDThe amber System Reset LED will illuminate steadily after the system reset button has been pressed and the system is resetting.

    Signal Silence LEDThe Signal Silence LED flashes amber at the Trouble Flash rate after indicating circuits are silenced either by the Signal Silence button, or by the Auto Signal Silence Timer. It turns OFF after the signals are re-sounded by a subsequent alarm.

    Fire Drill LEDThe Fire Drill LED turns ON steady amber while Fire Drill is active.

    COMMON ALARM

    COMMON SUPV

    COMMON TROUBLE

    CPU FAULT

    GROUNDFAULT

    SYSTEMRESET

    AC ON

    SYSTEMRESET

    FIREDRI LL

    ALARMACKNOWLEDGE

    GENERALALARM

    SIGNAL

    BUZZERSILENCE

    LAMPTEST

    BATTERY/CHARGER

    S ILENCE

    TROUBLE

    35

  • Indicators, Controls and Operations

    Buzzer Silence LEDThe Buzzer Silence LED flashes amber at the Trouble Flash rate when the Buzzer Silence button is pressed. Any new alarm, supervisory or trouble events will resound the buzzer and will cause the Buzzer Silence LEd to turn off.

    Acknowledge LEDIf the panel is configured as a two stage system, the Acknowledge LED flashes amber at the Fast Flash rate while the General Alarm timer is timing. It turns ON steady amber after the Auto General Alarm Timer is cancelled by the activation of the Acknowledge or Signal Silence buttons. If the Auto General Alarm Timer times-out and puts the panel into General Alarm, the Acknowledge LED turns OFF. If the panel is configured as Positive Alarm Sequence (PAS), the Acknowledge LED flashes amber at the Fast Flash rate while a timer counts down 15 seconds to common alarm.

    General Alarm LEDIn two stage operation only, the red General Alarm LED illuminates steadily after the General Alarm button is pressed, or after the Auto General Alarm Timer times out. Once the General Alarm LED turns ON it will stay active until the panel is reset.

    Lamp Test LEDThe amber Lamp Test LED will illuminate steadily after the Lamp Test button is pressed and while system is in Lamp Test mode.

    Battery/Charger Trouble LEDIn a ULI application the amber Battery/Charger Trouble LED flashes at the Trouble Flash rate when any Battery/Charger Trouble occurs.

    In a ULC application the amber Battery/Charger Trouble LED illuminates steady when any Battery/Charger Trouble occurs.

    LEDs 1 to 32 for FX-351 and FX-353 Series OnlyPoints labelled 1 to 32 are available for alarm, supervisory, and monitor annunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

    RAX-332 LEDs 33 to 64 for FX-351 and FX-353 Series OnlyPoints labelled 33 to 64 are available for alarm, supervisory, and monitor annunciation (bi-coloured red/amber LEDs) and trouble annunciation (amber LEDs).

    Common Controls

    LCD DisplayThe display is a two line, 20 character back-lit alphanumeric LCD. It displays information regarding the panel, its circuits, and devices. An on-screen cursor is controlled by the cursor buttons (located to the right of the display) for menu selection and control. Report information provided by the LCD display includes Alarm, Event Log, Current Levels, Verification, and Maintenance reports.

    Cursor ButtonsLocated at key number 2, 8, 6 and 4. The cursor buttons Up (next), Down (previous), Right, and Left allow you to select items on the LCD display. The Up and Down buttons scroll through lists in a continuous loop.

    Enter Button

    Use this button to select a displayed item on the LCD display.

    Cancel Button

    Use this button to cancel an operation or exit a menu.

    1 2ABC

    3DEF

    5JKL

    6MNO

    7 8TUV

    9WXY

    * 0QZ

    #

    4GHI

    PRS

    X

    M

    ?X

    36

  • FX-350 Series Installation and Operation Manual

    Menu Button

    Use this button to view the Command Menu.

    Info Button

    Push and hold this button to get detailed information about any displayed item.

    Signal Silence ButtonPressing the Signal Silence button after the panel is in alarm turns ON the Signal Silence LED and de-activates any silenceable indicating circuits. Non-silenceable circuits are unaffected. Signals will re-sound upon any subsequent alarm. This button does not function during any configured Signal Silence Inhibit Timer period. It also does not function if indicating circuits are active as the result of a Fire Drill. In a two stage system, if the Auto General Alarm Timer has timed out, the Signal Silence button also performs the same function as the Acknowledge button.

    Fire Drill ButtonThe Fire Drill button activates all programmed and non-disconnected indicating circuits, but does not transmit any Alarms via the city tie or common alarm relay. The Fire Drill is cancelled by pressing the button again (toggle switch), or if the panel goes into a true alarm.

    General Alarm Button (Two Stage Only)If the panel is not configured for two stage operation, this button does nothing. If the panel is configured for two stage operation, activation of the General Alarm button immediately sends the panel into second stage general alarm. It will also re-activate the signals if they have been silenced during general alarm. The General Alarm condition remains active until the panel is reset. Silenceable signals can be silenced using the Signal Silence button.

    System Reset ButtonThe System Reset button resets the panel and all circuits:

    Acknowledge Button (Two Stage or PAS only)If the panel is configured for two stage operation, activation of the Acknowledge button while the Auto General Alarm Timer is timing (e.g. there is an alarm in the panel but it is still in the first stage) cancels the timer and turns the Acknowledge LED ON steady amber. If the panel is configured for Positive Alarm Sequence (PAS), activation of the Acknowledge button within 15 seconds of a PAS alarm will delay a common alarm activation for 60 seconds.

    Lamp Test ButtonPressing and holding the Lamp Test button causes all front panel indicators to illuminate and sounds the buzzer steadily. Bi-coloured LEDs will illuminate twice to show both colors. If lamp test is active for more than ten seconds, the Common Trouble LED activates.

    Single Stage OperationIn a single stage system, all alarm inputs are treated in a similar manner. Alarm inputs include any of the following: non-verified alarm, verified alarm, waterflow alarm, and general alarm circuits. Any of these alarm inputs occurring when the panel is not already in alarm cause the following:

    •Resets all Latching Trouble Conditions •Turns off all Indicating Circuits

    •Resets Aux Resettable Power Supply •Turns off Fire Drill

    •Turns OFF Signal Silence, Ack & GA LEDs •Processes inputs as new events

    •Stops and resets all Timers•Reset cannot be activated until the Signal Silence Inhibit timer has expired

    •Aux Disconnect is not affected•Pressing Reset button after a PAS Acknowledge will reset the system and clear the alarm event.

    ATTENTION: After power-up, press the System Reset button to bring the system to normal and restore the “system power up” trouble.

    M

    ?

    37

  • Indicators, Controls and Operations

    • The buzzer sounds steadily

    • If fire drill is active, it is cancelled

    • The Common Alarm LED turns ON

    • The Common Alarm relay activates if Aux disconnect is not active

    • The Auto Signal Silence timer, if configured, starts

    • The Signal Silence Inhibit timer, if configured, starts

    • All non-disconnected indicating programmed to the input are activated provided that Aux disconnect is not active

    • Non-disconnected strobes associated with the input are activated

    • Non-disconnected signals associated with the input are activated at the evacuation rate

    Subsequent alarms when the panel is already in alarm, cause the following:

    • The alert buzzer sounds steadily

    • If Signals have been silenced, they are resounded, the Signal Silence LED turns OFF, and the Auto Signal Silence timer, if configured, is restarted

    • Any additional non-disconnected strobes associated with the input are activated continuously

    • Any additional non-disconnected signals associated with the new input are activated at the evacuation rate

    Two-Stage OperationIn a Two-Stage system, alarm inputs are either First Stage (alert) inputs or Second Stage (general alarm) inputs. First stage inputs include inputs from the following types of circuits: non-verified alarm, verified alarm, and waterflow alarm. Second stage inputs include alarms on the general alarm circuits, activation of the General Alarm button, or expiration of the Auto General Alarm timer. Any of these alarm inputs occurring when the panel is not already in alarm cause the following:

    • The buzzer sounds steadily.

    • If fire drill is active, it is cancelled.

    • The Common Alarm LED turns ON

    • The Common Alarm relay activates if Aux disconnect is not active.

    • The Auto Signal Silence timer, if configured, starts.

    • The Signal Silence Inhibit timer, if configured, starts.

    • All non-disconnected outputs programmed to the input are activated provided that Aux disconnect is not active.

    If the alarm is a Second Stage alarm,

    • All non-disconnected strobe circuits are activated continuously, if correlated to an alarm input.

    • All non-disconnected signal circuits are activated at the evacuation rate, if correlated to an alarm input.

    • The General Alarm LED turns ON.

    If the alarm is a First Stage alarm,

    • Non-disconnected strobe circuits programmed to that circuit are activated continuously.

    • Non-disconnected signal circuits programmed to that circuit are activated with the alert code (see Output Types on page 42).

    • The Auto General Alarm timer, if configured, starts.

    • The Acknowledge LED starts flashing.

    Subsequent First Stage alarms when the panel is already in alarm, cause the following:

    • The buzzer sounds steadily.

    • If signals have been silenced as a result of the silence button or the Auto signal silence timer, signals are resounded as they were before signal silence, the Signal Silence LED turns OFF, and the Auto Signal Silence timer, if configured, is restarted.

    • If the panel is not already in General Alarm, additional non-disconnected signals programmed to the new input are activated with the Alert Code (see Output Types on page 42).

    38

  • FX-350 Series Installation and Operation Manual

    • If the panel is not already in General Alarm and if the Acknowledge LED is ON steady indicating that the Auto General Alarm timer has been Acknowledged the timer is restarted and the Acknowledge LED is extinguished.

    A second stage alarm (general alarm) when the panel is already in alarm causes the following:

    • The buzzer sounds steadily.

    • All non-disconnected signals are activated at the evacuation rate.

    • If the Signal Silence LED is ON, it turns OFF and the Auto Signal Silence timer, if configured, is restarted.

    • The Acknowledge LED if ON, turns OFF.

    Alarm inputs are latching, they remain active until system reset

    Positive Alarm SequenceIn a Positive Alarm Sequence (PAS) system, only smoke detectors can be dedicated as PAS inputs. PAS Inputs can only be from the following types of circuits: non-verified alarm and verified alarm. Any of these alarm inputs occurring when the panel is not already in alarm cause the following:

    • The buzzer sounds steadily.

    • If fire drill is active, it is cancelled.

    • The Common Alarm LED turns ON

    • The individual zone LED (if programmed) turns ON.

    • The Common Alarm relay does not activate.

    • The PAS timer starts for 15 seconds.

    • All outputs programmed to the input are not activated.

    When the PAS alarm has been acknowledged within 15 seconds, the following sequence occurs:

    • The buzzer is silenced.

    • The Common Alarm LED stays ON.

    • The individual zone LED (if programmed) stays ON.

    • The PAS timer starts for 180 seconds (3 minutes). This is the time allotted to reset the system and avoid any true alarm sequence.

    When the PAS alarm has been acknowledged and the system reset (and there are no new alarms), within the given time limits, the following occurs:

    • The buzzer stays silenced.

    • The Common Alarm LED turns OFF.

    • The individual zone LED (if programmed) turns OFF.

    • The alarm event is cancelled. No log reference.

    • The fire alarm system returns to normal.

    If at any time during the Positive Alarm Sequence a second alarm (PAS or otherwise) is actuated, the fire alarm will go into evacuation mode. In a preconfigured FACP the Positive Alarm Sequence may be enabled or disabled as the user requires.

    Enabling or Disabling the Positive Alarm Sequence• To enable or disable the Positive Alarm Sequence, from the Keypad of the FACP press “M” to enter the Menu

    • Using the Up and Down Arrow buttons, scroll to “Operation” and press the enter key

    • In the Operation Menu scroll to “Positive Alarm” and press enter

    Note: All circuits with process type designated as “signal” are automatically correlated to the “fire drill” and “general alarm” status.

    39

  • Indicators, Controls and Operations

    • You will now see displayed the current status of the Positive Alarm Sequence and will be prompted to change status.

    • If you wish to change the status press the “enter” key.

    • If you do not wish to change the status, press the “cancel” key

    Input TypesThe following is a table of input types available for programming.

    Note: There will be no notification message advising a change of status

    Input Types Description

    Non-Verified Alarm

    When an un-bypassed non-verified alarm input goes into alarm the common alarm sequence is activated. Un-bypassed relay, signal, and strobe outputs are updated according to their programming and alarm zone status indicators associated with the input are activated. Alarm input activations are displayed on the shared display in the common queue with alarm as the highest priority and is displayed first.

    A pre-alarm condition on a device configured as an alarm input is displayed on the shared display and on the alarm zone status indicator. If the pre-alarm condition is restored the status will be cleared. If the input goes from pre-alarm to alarm, the pre-alarm status will be replaced with the alarm status for the input.

    Once an alarm i