Flame Safeguard Equipment Primary Controls Selection Guide 81-00-30-12 1/99 Selection Guide R485B PROTECTORELAY PRIMARY CONTROL Electrical Rathgs (at 120/240V, 60Hz): Pilot Gas Valve --125 VA. Main Gas Valve -- 125 VA. Atternate Rating: 25 VA pilot duty plus 1 or more motorized valves with total rating 400 VA opening, 200 VA holding. Ignition Transformer -- 345 VA. Alarm --125 VA. Accessories Q270A1024 Mounting Subbase --serves as junction box for connecting to external circuits. Contains terminal blocks with coded terminals and screws. S445A1010 Push-button Start-Stop Station. 121708 Flame Simulator (rectifying). W136A1045 Test Meter (includes 196146 Meter Connector Manual start control provides solid state, elec- tronic, flame safeguard protection for semi- automatic single or dual fuel applications. Cuts off both pilot and main fuel and sounds alarm if flame fails. Can be used with flame rods, rectifying photocells, or C7012A, C Purple Peeper Ultraviolet Flame Detectors. For torch-ignited pilot or main burner, used with push-button or any conventional knee- or foot-operated start-stop station. For electrically ignited pilot, used with S445A Pushbutton Start-Stop Station which continues ignition as long as start button is pressed. Mounts on Q270A1024 Subbase (order separately). Ambient Temperature Range: – 20°F to + 125° F [– 29° C to + 52° C). Approximate Dimensions (in- cluding subbase): 5 in. [127 mm] high, 5 in. [127 mm] wide, 4-3/4 in. [120.7 mm] deep. CSA certified: File No. LR1620, Guide No 140-A-2; Factory Mutual approved: Report No. 18301. FLAME FAILURE ORDER VOLTAGE RESPONSE TIME NUMBER (50/60 Hz) (sec) Plug). 132569 Contact Cleaner. 101079 Ignition Transformer 240V, 60Hz 22042 Ignition Transformer 120V, 60Hz Q624A1014 Solid State Ignition Transformer Q652A1007 Solid State Spark Generator Oil 120V, 60Hz Q652B1006 Solid State Spark Generator Gas 120V, 60Hz Q652B1014 Direct Spark Ignition Transformer for gas applications (single electrode) 220V, 50/60 Hz. R1061012 Ignition Cable for ignition installations in high temperature environments; rated at 350°F (177°C) for continuous duty, and up to 500°F (260°C) for intermittent use; tested to 20,000 volts RMS. R1239001 High Tension Ignition Cable; for ignition installations in a contaminating environment; very resistant to severe conditions of oil, heat, and corona. Tested to withstand high voltages up to 25,000 volts RMS in a salt bath for 1 minute without breakdown. Rated at 200°F (93°C) for continuous duty, and up to 350°F (177°C) for intermittent use. R1298020 Cable; for flame detector ("F" Ieadwire) installations in a high temperature environment; rated up to 400°F (204°C) for continuous duty; tested for operation up to 600V and breakdown up to 7500V. R458B1000 120 3 R485B1018 240 3

Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

  • Upload
    ngodan

  • View
    245

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Flame Safeguard Equipment

Primary Controls

Selection Guide81-00-30-121/99

Selection Guide

R485B PROTECTORELAY PRIMARY CONTROL

Electrical Rathgs (at 120/240V, 60Hz):

Pilot Gas Valve --125 VA.Main Gas Valve -- 125 VA.Atternate Rating: 25 VA pilot duty plus 1 or more motorizedvalves with total rating 400 VA opening, 200 VA holding.Ignition Transformer -- 345 VA.Alarm --125 VA.

Accessories

Q270A1024 Mounting Subbase --serves as junction box forconnecting to external circuits. Contains terminal blockswith coded terminals and screws.

S445A1010 Push-button Start-Stop Station.121708 Flame Simulator (rectifying).W136A1045 Test Meter (includes 196146 Meter Connector

Manual start control provides solid state, elec-tronic, flame safeguard protection for semi-automatic single or dual fuel applications.

Cuts off both pilot and main fuel and sounds alarm if flamefails. Can be used with flame rods, rectifying photocells, orC7012A, C Purple Peeper Ultraviolet Flame Detectors. Fortorch-ignited pilot or main burner, used with push-button orany conventional knee- or foot-operated start-stop station.For electrically ignited pilot, used with S445A PushbuttonStart-Stop Station which continues ignition as long as startbutton is pressed. Mounts on Q270A1024 Subbase (orderseparately). Ambient Temperature Range: – 20°F to+ 125° F [– 29° C to + 52° C). Approximate Dimensions (in-cluding subbase): 5 in. [127 mm] high, 5 in. [127 mm] wide,4-3/4 in. [120.7 mm] deep. CSA certified: File No. LR1620,Guide No 140-A-2; Factory Mutual approved: Report No.18301.

FLAME FAILUREORDER VOLTAGE RESPONSE TIME

NUMBER (50/60 Hz) (sec)

Plug).132569 Contact Cleaner.101079 Ignition Transformer 240V, 60Hz22042 Ignition Transformer 120V, 60HzQ624A1014 Solid State Ignition TransformerQ652A1007 Solid State Spark Generator Oil 120V, 60HzQ652B1006 Solid State Spark Generator Gas 120V, 60HzQ652B1014 Direct Spark Ignition Transformer for gas

applications (single electrode) 220V, 50/60 Hz.R1061012 Ignition Cable for ignition installations in high

temperature environments; rated at 350°F (177°C) forcontinuous duty, and up to 500°F (260°C) for intermittentuse; tested to 20,000 volts RMS.

R1239001 High Tension Ignition Cable; for ignitioninstallations in a contaminating environment; veryresistant to severe conditions of oil, heat, and corona.Tested to withstand high voltages up to 25,000 voltsRMS in a salt bath for 1 minute without breakdown. Ratedat 200°F (93°C) for continuous duty, and up to 350°F(177°C) for intermittent use.

R1298020 Cable; for flame detector ("F" Ieadwire)installations in a high temperature environment; rated upto 400°F (204°C) for continuous duty; tested for operationup to 600V and breakdown up to 7500V.

R458B1000 120 3

R485B1018 240 3

Page 2: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12Page 2

RA890F/RA890G

Ambient Temperature Range:MINI- MAXIMUMMUMb

60 Hz 50 Hz

MODEL F C F C F CWithout alarmb – 20 – 29 125 52 115 46

With alarma –20 – 29 115 46 105 41a See ordering table to see which models have alarm contacts. b RA890F1676 Underwriters Laboratories Inc. and CSA listed for

use at – 40°F [–40°C]

Approximate Dimensions (including sub-base): 5 in [127mm] high, 5 in. [127 mm] wide, 4-3/4 in. [120.7 mm] deep.Approvals: listed by Underwriters Laboratories Inc: File No.MP268, Guide No. MCCZ; Industrial Risk Insurers (formerlyFIA) approvable; CSA certified: File No. LR1620, GuideNos. 140-A-2, 300-1-0-2; Factory Mutual approved: ReportNos. 17678, 19417, 19784 and 22013.

Nonprogramming Primary Control provides solidstate, electronic, flame safeguard protection forindustrial and commercial single or dual fuelburners. See page 2 for accessories and Modelnumbers.Used for interrupted ignition with intermittent pilot on gasburners; interrupted or intermittent ignition on oil burners.

The RA890F uses rectification principle of electronic flamedetection. For use with flame rods, rectifying photocells,and C7012A, C Purple Peeper Ultraviolet Flame Detectors.Directly replaces RA890E in most applications; mounts onsame Q270A1024 Subbase.

Power Ratings:WATT VA

RA890F MAXIMUM STANDBY MAXIMUM STANDBY

60 Hz 6.2 1.7 13.5 8.3

50 Hz 8.0 3.0 17.0 13.6

RA890G60 Hz 9.5 3.0 14.0 12.0

50 Hz 10.0 4.0 18.0 17.0

The RA890G uses C7027, C7035, or C7044 MinipeeperUltraviolet Flame Detector for flame sensing.

These Primary Controls Recycle once after flame failure inattempt to re-establish pilot before lockout. Will not start ifFlame-simulating failure occurs in flame detector.

Page 3: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

RA890F/RA890G

Electrical Ratings: R1298020 Cable; for flame detector (“F” Ieadwire)Controller: Use line (120 V) or low (24 V), automatic or installations in a high temperature environment; rated upmanual (such as S446A): to 400°F (204°C) for continuous duty; tested for

operation up to 600V and breakdown up to 7500V.Low Voltage Controller Circuit (T-T): 0.3A.

Terminal Typical Load 120 Vac 240 Vac

3 Burner Full Load 5.2 A 2.6 AMotor Locked Rotor 31.2 A 15.6 A

FLAMEIgn i t ion a , b 3.0 A 1.6 A SAFETY FAILURE SPDT

Pilot Fuel Valveb 25.0 VA 25.0 VASWITCH RESPONSE ALARM

ORDER VOLTAGE TIMING TIME CON-4 Ignition a 3.0 A 1.5 A NUMBER (50/60 Hz) (sec) (sec) TACTS

5 Main gas valve, or sec- 125.0 VA 125.0 VA RA890F1270 120 15 0.8 Yes

ond stage oil valve (if pilot duty pilot duty RA890F1288 120 15 3.0 Yesused) RA890F1296 208 15 3.0 Yes

Alternate Rating: 25 VA pilot duty plus 1 or more RA890F1304 220 15 0.8 Yesmotorized valves with total rating 400 VA opening,200 VA holding. RA890F1320 240 15 3.0 No

RA890F1346 120 30 3.0 YesIsolated Alarm 3.0 A at 24 Vac, or 1.0 A

SPDT Alarm at 120 Vac in suitable RA890F1353 240 30 0.8 Yes

Terminals wiring enclosure. RA890F1361 240 30 3.0 Yes

aIf ignition and motor are connected to terminal 3, terminal 4cannot be used. This is to prevent overloading relay 1K.

RA890F1379 240 15 0.8 Yes

RA890F1387 240 15 3.0 Yes

Accessories

Q270A1024 Mounting Subbase--serves as junction boxfor connecting to external circuits. Contains terminalblocks with coded terminals and screws.

121708 Rectification Flame Simulator for RA890F.123514B Ultraviolet (Minipeeper) Flame Simulator for

RA890G.W136A1045 Test Meter (includes 196146 Meter Connector

Plug).132569 Contact Cleaner.FSP1535 Tester – for operational check of all RA890’s.118702E Remote Reset Cover – 120V, 60Hz.101079 Ignition Transformer 240V, 60Hz22042 Ignition Transformer 120V, 60HzQ624A1014 Solid State Ignition TransformerQ652A1007 Solid State Spark Generator Oil 120V, 60HzQ652B1006 Solid State Spark Generator Gas 120V, 60HzQ652B1014 Direct Spark Ignition Transformer for gas

applications (single electrode) 220V, 50/60 Hz.R1061012 Ignition Cable for ignition installations in high

temperature environments; rated at 350°F (177°C) forcontinuous duty, and up to 500°F (260°C) for intermittentuse; tested to 20,000 volts RMS.

R1239001 High Tension Ignition Cable; for ignitioninstallations in a contaminating environment; veryresistant to severe conditions of oil, heat, and corona.Tested to withstand high voltages up to 25,000 voltsRMS in a salt bath for 1 minute without breakdown.Rated at 200°F (93°C) for continuous duty, and up to350°F(177°C) for intermittent use.

RA890F1429 220 15 3.0 Yes

RA890F1478 120 15 0.8 Yes

RA890G1229 120 15 0.8 Yes

RA890G1245 220 15 0.8 Yes

RA890G1260 120 15 3.0 Yes

RA890G1286 240 15 3.0 Yes

RA890G1294 240 15 0.8 Yes

RA890G1302 220 15 3.0 Yes

Page 4: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12Page 4

R4795A PRIMARY CONTROLS

Electrical Ratings:

Provide solid state, electronic, flame safeguardprotection for commercial and industrial singleor dual fuel burners.

Interchangeable, plug-in amplifiers permit R7495 to beused with rectification or ultraviolet type flame detectors.R4795A recycles once after flame failure in attempt to re-establish pilot before lockout. Power Consumption (at 60Hz): 6.0W maximum for rectification; 8.0W maximum forultraviolet. Safety Switch Timing: 15 see, nominal. Listedby Underwriters Laboratories Inc: 120V models using 30,60 or 90 sec prepurge timers, including -40°F (-40°C)rated models, File No. MP268, Guide No. MCCZ;Underwriters Laboratories Inc. component recognized:120V models using 7 or 10 sec prepurge timers,including -40°F (-40°C) rated models, File No. MP268,Guide No. MCCZ2; Industrial Risk Insurers (formerly FIA)approvable; CSA certified: 120V models only including -40°F (-40°C) rated models, File No. LR1620; FactoryMutual approved: R4795A, 120V models, Report No.18774.

TERMINAL LOAD

3 Pilot ValveIntermittent

Ignition a

4 InterruptedIgnition

5 Main Valve

6-7 Airswitch

8 Fan orBurnerMotor

Isolated AlarmSpdt AlarmTerminals(optional)

RATING

125 VA pilot duty360 VA

360 VA

125 VA pilot duty, or 25 VA pilotduty plus one or more motorizedvalves with total rating up to 400VA opening. 200 VA holding

0.6 A at 30 Vdc

9.8 A full load, 58.8 A lockedrotor (inrush) at 120 Vac, 4.9 Afull load, 29.4 A locked rotor (in-rush) at 220 and 240 Vac.

3.0 A at 24 Vac, or 1.0 A at 120Vac in suitable wiring enclosure.

a If ignition is connected to terminal 3, terminal 4 cannot be used.

Ambient Temperature Range:

MINIMUMa MAXIMUM b

F C F C

50 Hz – 20 – 29 115 46

60 Hz – 20 – 29 125 52

a R4795A1081 has minimum ambient temperature rating of -40°F(40°C) with maximum of 115°F (46°C) at 60 HZ and 105°F (40°C) at50 Hz.

b Subtract 10°F (6°C) if optional alarm contacts are included.

Approximate Dimensions (with cover andsubbase)

HEIGHT WIDTH DEPTH

Model in mm in mm in mm

R4795A 5 127 5 127 4-3/4 120.7

Replacement Parts131891C—Cover Assembly—R4795A.134057B—Cover Assembly—R4795D.

Page 5: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Page 5

Accessories

2270A1024 Mounting Subbase --serves as junction boxfor connecting to external circuits. Contains terminalblocks with coded terminals and screws.

121708 Rectification Flame Simulator for RA890F.1235I4B Ultraviolet (Minipeeper) Flame Simulator for

RA890G.W136A1045 Test Meter (includes 196146 Meter Connector

Plug).132569 Contact Cleaner.FSP1535 Tester -- for operational check of all RA890’s.118702B Remote Reset Cover -- 120V, 60 Hz.101079 Ignition Transformer 240V, 60Hz22042 Ignition Transformer 120V, 60HzQ624A1014 Solid State Ignition TransformerQ652A1007 Solid State Spark Generator Oil 120V, 60HzQ652B1006 Solid State Spark Generator Gas 120V, 60HzQ652B1014 Direct Spark Ignition Transformer for gas

applications (single electrode) 220V, 50/60 Hz.

R1061012 Ignition Cable for ignition installations in hightemperature environments; rated at 350°F (177°C) forcontinuous duty, and up to 500°F (260°C) for intermittentuse; tested to 20,000 volts RMS.

R1239001 High Tension Ignition Cable; for ignitioninstallations in a contaminating environment; veryresistant to severe conditions of oil, heat, and corona.Tested to withstand high voltages up to 25,000 voltsRMS in a salt bath for 1 minute without breakdown.Rated at 200°F (93°C) for continuous duty, and up to350°F (177°C) for intermittent use.

R1298020 Cable; for flame detector (“F” leadwire)installations in a high temperature environment; rated upto 400°F (204°C) for continuous duty; tested foroperation up to 600V and breakdown up to 7500V.

REQUIRED COMPONENTS(order separately)

ORDER VOLTAGE SPDT ALARM MOUNTING PLUG-IN PLUG-IN

NUMBER (50/60 Hz) CONTACTS BASE AMPLIFIERa PURGE TIMER

Q270A1024 permits 1, 2, 4, or 5 ST71A1000, 7 sec

R4795A1016 120 Yes recessed or surface 1, 2, 4, or 5 ST71A1042, 10 sec

R4795A1040 220 Yes mounting 1, 2, 4, or 5 STA71018, 30 sec

ST71A1026, 60 sec

ST71A1034, 90 sec

aA number iS listed for each amplifier in table below. These numbers correspond to those listed under “Plug-in Amplifier” above.

FLAME FAILURE

NUMBER ORDER RESPONSE TIME

(see ordering table) NUMBER TYPE (sec) USE WITH

1 R7289A1004 Rectification 3.0 Rectifying photocell flame rod or C7012A, C Pur-(green) ple Peeper Ultraviolet Flame Detector

2 R7289A1012 0.8

3 R7289A1020a 3.0

4 R7290A1001 Ultraviolet 3.0 Use with C7027A, C7035A, or C7044A

(purple) Minipeeper Ultraviolet flame Detector

5 R7290A1019 0.8

6 R7290A1027a 3.0

aMinimum Ambient Temperature Minus 40°F [minus 40°C]

Page 6: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12Page 6

R7795A, B, C, D, E, F, G, H Primary Controls

Provide solid state, electronic, flame safeguardProtection for industrial single or dual fuelburners.

R7795 has 2 field selectable options:1. Recycle or lockout after flame failure (3-sec nominal

flame failure response time).2. 10 or 4 seconds timed trial for pilot flame ignition.

R7795A, C, E, G use the C7027, C7035 or C7044 Mini-peeper Ultraviolet Flame Detector for flame sensing.R7795B, D, F, H use rectification principle of electronicflame detection for use with flame rods, rectifying photo-cells, or C7012A, C Purple Peeper Ultraviolet FlameDetectors. Flame signal amplifiers are built into theR7795 and are color coded; purple for Ultraviolet, greenfor Rectification.

R7795E-H have an airflow switch check. R7795A, B, E, Fprovide ignition cutoff and intermittent pilot. R7795C, D,G, H have interrupted pilot function to provide a10-second main flame establishing period and also havea second main fuel valve terminal. All models require aplug-in prepurge timer of 1.5, 7, 10, 30, 60, 90 seconds.R7795 mounts on a Q795A wiring subbase.

Electrical Ratings:Voltage and Frequency—120 Vac (+ 10, –15%), 50/60Hz.Power Consumption—

R7795A, C—17 VA (maximum).R7795B, D—15 VA (maximum).

TERMINAL LOAD

5 Pilot Valve

18 Ignition

6, 7 Main FuelValve(s)

8 Fan or BurnerMotor

9 Alarm

MAXIMUM RATING AT 120 VAC

125 VA pilot duty

360 VA

125 VA pilot duty or 25 VApilot duty plus one or moremotorized valves with atotal rating of 500 VA open-ing, 250 VA holding

9.8A full load; 58.8A lockedro to r

1.0A

Ambient Temperature Ranges:Operating—minus 40° F (minus 40°C) to plus 135° F (plus57°C).

Flame Failure Response:3 sec. nominal.

Approximate Dimensions:5 x 5 x 5 -1/4in. (127 x 127 x 133.5 mm).

Approvals:R7795A-D

Underwriters Laboratories Inc. listed—File No. MP268,Guide No. MCCZ.

Canadian Standards Association certified—Report No.LR1620-681.

Factory Mutual approved—Report No. J.I.OK389.AF.Industrial Risk Insurers (formerly FIA) approvable.

Approvals pending for R7795E-H.

Accessories:W136A1045 Test Meter—(includes 196146 MeterConnector Plug).196146 Meter Connector Plug for older W136A TestMeters.123514A Flame Simulator for rectification systems.123514B Flame Simulator for ultraviolet systems.Q624A1014 Solid State Spark Generator. 120Vac, 60HzQ795A Wiring Subbase.ST795A Plug-in Purge Timer—models available with1.5, 7, 10, 30, 60, and 90 sec timings.FSP5004 with tester adapter 198355A for operationalcheck of the R7795.R1061012 Ignition Cable for ignition installations inhigh temperature environments; rated at 350° F(177°C) for continuous duty, and up to 500° F (260°C)for intermittent use; tested to 20,000 volts RMS.R1239001 High Tension Ignition Cable; for ignition in-stallations in a contaminating environment; very resis-tant to severe conditions of oil, heat, and corona.Tested to withstand high voltages up to 25,000 voltsRMS in a salt bath for 1 minute without breakdown.Rated at 200° F (93°C) for continuous duty, and up to350° F (177°C) for intermittent use.R1298020 Cable; for flame detector (“F” leadwire) in-stallations in a high temperature environment; ratedup to 400° F (204°C) for continuous duty; tested foroperation up to 600V and breakdown up to 7500V.198365A Remote Reset Cover; reset the safety

switch on R7795 from a remote location for Series 1.

198365B Remote Reset Cover; reset the safety

switch on R7795 from a remote location for Series 2.

Page 7: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Page 7

TIMER

REQUIRED COMPONENTS(ORDER SEPARATELY)

ORDER VOLTAGE PILOTNUMBER (50/60 HZ) FUNCTION

FLAME DETECTION SYSTEMPLUG-IN PREPURGE

TYPE USE WITH SENSOR NUMBER

R7795A1001 120 Intermittent U.V. C7027A, C7035A, C7044A ST795A1007Minipeeper ST795A1015

ST795A1023R7795B1009 120 Rectifi- Flame rod, rectifying photocells, ST795A1031

cation C7012A, C ST795A1049

R7795C1007 120 Interrupted U.V. C7027A, C7035A, C7044A ST795A1056

Minipeeper

R7795D1005 120 Rectifi- Flame rod, rectifying photocell,cation C7012A, C

SEC

1.57

10306090

MOUNTINGSUBBASE

Q795A1004(4 sides)

Q795A1012(No sides)

Page 8: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

R4140G, L, M FSG AUTOMATIC PROGRAMMING CONTROLS

Provide flameout protection and automaticsequencing for commercial and industrialsingle or dual fuel burners.

Sequence burner motor, firing rate motor (L and G only), ig-nition, pilot valve, and main fuel valve(s). Safe-start check.Safety shutdown on flame failure (lockout). Ten secondpilot flame-establishing period. Flame Failure ResponseTime: 2-4 sec. Lockout Switch Timing: 30 sec. nominal.

lndustrial Risk Insurers (formerly FIA) approvable, andlisted by Underwriters Laboratories Inc.: All R4140 exceptR4140G1114, G1122—File No. MP268, Guide Nos.MCCZ2, MCCZ; CSA certified: File No. LR1620, Guide Nos.140-A-2, 300-1-0-2; Factory Mutual approved: R4140G—Report No. 24180, R4140L—Report No. 24181, R4140M—Report No. 24150.

Electrical RatingsVoltage and Frequency: 120 Vac (102 V to 132V), 50/60 Hz.Power Consumption (with no loads connected to output

terminals):R4140L-18 W max.R4140G, M-13 W max.

Maximum Total Connected Load: 1800VA.

Accessories:W136A1045 Test Meter (includes 196146 Meter Connector

Plug).123514A Flame Simulator (for use with R7247A, B Recti-

fication Amplifiers).123514B Flame Simulator (for use with R7249A Ultraviolet

Amplifier).139695C Cover—with reset button.Q624A1014 Solid State Ignition Transformer—prevents

detection of ignition spark when properly applied withflame detection systems using C7027, C7035, or C7044Minipeeper Ultraviolet Flame Detectors. For use onlywith gas pilots.

22042 Ignition Transformer.132569 Contact Cleaner.FSP5004 Tester (120 V only).118760B Remote Reset Cover.Q520A1089 Subbase (3-sided)—for mounting inside a

suitable enclosure, 20 terminals.Q520A1121 Subbase (4-sided)—serves as suitable wiring

enclosure, 20 terminals.

MAIN BURNER FLAME EARLY SPARKORDER PREPURGE ESTABLISHING PERIOD TERMINATION WITH POSTPURGE USE WITH

NUMBER f (sec) (sec) (sec) COVER (sec) (order separately)

R4140G1015 60 10 or 30 — No 15 R7247, R7248, or

R4140G1064 60 10a 5 No 15 R7249 amplifier

R4140G1106 60 10 or 15 — No 15 and

R4140G1114 d 70 10, 30 or 60 5 No 25 rectification, infrared,

R4140G1122 e 70 10, 30 or 60 5 No 25 or ultraviolet

R4140G1148 60 10 or 15 5 No 15 flame detector

R4140G1171 70 10, 30 or 60 5 No 25 and

R4140L1014 60 10 or 15 — No 15 Q520A Mounting

R4140L1030 b 60 10 or 15 — No 15 Subbase.

R414OL1105 60 10 or 15 5 No 15

R4140L1147 60 10, 15 or 30 5 No 15

R414OM1012 30 10a — No 15

R4140M1020 c 42 10a 5 Yes 15

R4140M1038 c 42 10a 5 No 15

R4140M1046 c 90 10a 5 Yes 25

R4140M1053 c 90 10a 5 No 25

R4140M1178 c 96 10a 5 No 25aIntermittent pilot terminal also available e208 V, 60 HZbTimer cannot be rotated manually f All models 120 V, 60 Hz except R4140G1114 and R4140G1122.cOpen Damper Prepurge, Low Fire Interlock, Isolated Damper All models can be operated at 50 Hz, however, timings noted must

Motor Contact. be multiplied by 1.2.d 240 V. 60 Hz

Page 9: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

R7247, R7248, R7249, R7476 FLAME SAFEGUARD AMPLIFIERS

R7248

R7249

R7247

Solid State Plug-In Units respond to FlameDetector signal and indicate presence of flame.

R7476

Used with BC7000; R4140; R4075C, D, E; R4138C, D;FSP5075 flame safeguard controls and appropriate flamedetector. Refer to ordering table for application andspecifications. Listed by Underwriters Laboratories Inc.:File No. MP268, Guide Nos. MCCZ2; Industrial Risk In-~surers (formerly FIA) approvable; CSA certified: File No.LR1 620, Guide Nos. 140-A-2, 300-1-0-2; Factory Mutual ap-proved: Report No. 24181.01.

a Dynamic Self Check circuitry tests all electronic components in flame detection system (amplifier and detector) 60 to 240 times aminute during burner operation and shuts down burner if detection system fails.

b Circuitry tests only flame signal amplifier during burner operation and shuts down burner if amplifier fails.c Order flame rod separately; see instruction sheet for holder.d Can also be used with rectifying photocells and C7012A or C ultraviolet flame detectors, but then circuitry tests only flame signal

amplifier during operation and shuts down burner if amplifier fails.

Page 10: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Microcomputer Burner Control Systems

The BC7000 “Blue Chip” is an intelligent microcomputer-based integrated control system designedfor automatic fired commercial and industrial single burner applications. The BC7000 System not on-ly provides higher levels of protection, but also reaches far beyond the capability and scope of con-ventional flame safeguard “programmers” to reduce service, maintenance, downtime, and energycosts.

THE BC7000 BLUE CHIP MICRO-COMPUTER BURNER CONTROL SYSTEM:

Referred to as the Blue Chip because of its computer“chip” technology and its distinctive blue color, theBC7000 provides a return on investment (ROI/Payback): areal Blue Chip investment! The BC7000 Blue Chip Systemdelivers the following new and significant features in asingle integrated burner control system:

❑ Dynamic Self Check Logic—ProvidesMajor Safety Improvement

A major breakthrough in safety through advancedmicrocomputer technology has allowed the extensionof the original Honeywell Dynamic Self Check/MaxSafety concept (formerly restricted to the flame detec-tion circuit) to the basic program logic system. CalledDynamic Self Check Logic, it is a comprehensive familyof unique safety provisions that continuously monitorthe total system performance to provide the highestdegree of safety available.

Annunciation and Self-Diagnostics—CutService CostsControl and burner system startup, troubleshooting,and repair have never been easier, thanks to theBC7000 Microcomputer Burner Control System. in-tegral First-Out Annunciation and Self-Diagnostic func-tions reduce service costs and minimize the inconve-nience and cost associated with downtime. These im-portant new features are called “Plug-Instant” becausethey are a standard provision of the BC7000 System—no additional hardware need be purchased, installed, ormaintained.

Energy Saving Innovations—Reduce FuelConsumptionUnnecessary purge-related heat losses are minimizedby innovative BC7000 System program logic provisions.Microcomputer intelligence is employed to reduce fuelconsumption by optimizing the prepurge and ter-minating wasteful blower operation when the systemencounters an inoperative field interlock. This conditioncan cause conventional sequencers to permanentlystall in an unproductive purge.

Universal System Chassis—Minimizes In-ventory InvestmentNow, through the flexibility of microcomputertechnology, a single control chassis can be universallyapplied to perform any standard burner program. Solidstate program modules plug in to implement the re-quired burner sequence of operation, timings anddesired features. The universal BC7000 System chassisallows you to cover the full range of applications, sup-ports standardization, and minimizes inventoryinvestment.

SPECIFY THE BC7000 BLUE CHIPWhen ordering a new burner, packaged boiler, or control replacement, specify the new standard in burnerand flame safety control performance—the BC7000 “Blue Chip” Microcomputer Burner Control System.

❑ Enhanced safety improves plant protection

❑ Energy savings features provide on-going fuel savings and payback

❑ Plug-lnstant annunciation and diagnostics reduce service and downtime costs

❑ Universal system chassis supports standardization and minimizes inventory investment

❑ Plug-in program modules and flame amplifiers provide control flexibility and cut maintenance costs

Page 11: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

BC7000 ‘BLUE CHIP’ MICROCOMPUTER BURNER CONTROL SYSTEMThe BC7000 provides flameout protection,automatic sequencing, dynamic self-check logic,plug-instant annunciation, self diagnostics andenergy conservation for commercial and in-dustrial single burners. Requires a PM720G, L, orM program module.Directly replaces R4150 and R4140 in most applications;mounts directly on the same Q520A subbase. Sequencesburner motor, firing rate motor (PM720G and L models on-ly), ignition, pilot valve, and main fuel valve(s). ExpandedSafe Start Check. Dynamic Self Check Logic. Plug-InstantAnnunciation. Self Diagnostics. Energy Conservation. Safe-ty shutdown on flame failure (lockout). Ten second pilotflame establishing period. Flame failure response time: 2-4seconds. Lockout switch timing: less than 1 second.

Accessories:FSP5004 R4150/R4140/BC7000 Tester—provides a quick

operational check of BC7000 Microcomputer BurnerControl System.

Q520E1002 Service Tool—allows all programmerterminals to be monitored with the programmeroperating.

WI 36A1045 Test Meter (includes 196146 Meter ConnectorPlug)—has SPL position with damping for testing selfchecking flame detection systems.

ORDER NUMBER USE WITH

BC7000L1000 PM720G, L, or M Program Module, R7247,R7248, R7249, R7476 amplifier and matchingrectification, infrared, or ultraviolet flame de-

Ambient Operating Temperature Rating: tector. Mounts on Q520A Mounting Subbase.

Wall mounted: 32°F to 130°F [10°C to 55°C].Horizontal mounting: 32°F to 125°F [0°C to 53°C].

Electrical Ratings:Voltage and Frequency: 120 Vac [plus 10, minus 15%],60 Hz, (plus, minus 8%).Power Consumption (no loads connected):BC7000—25W maximum.

Storage Temperature Rating–30°F to + 150°F [–34°C to + 66°C].

Approval Bodies:Underwriters Laboratories Inc. listed—Section of

Primary Safety Control, File No. MH11790; Guide No.MCCZ.

Canadian Standards Certified: LR1620-520.Factory Mutual Approved: (When used with PM720L

Program Module.) Report No. J.I. 1F6A1.AF.Industrial Risk Insurers (formerly F.I. A.) approvable.

Power FLAMEESTABLISHING POST. ENERGY

PREPURGE supply EARLY PERIOD (sec) PURGE INTER. FIRING SAVINGORDER TIMING Frequency SPARK TIMING LOCK RATE PREPURGE

NUMBER (sec) (Hz) TERMINATION PILOT MAIN (sec) CIRCUITS CIRCUIT (ESP)

PM720G2005 40 60 Yes 10 10 or 15b 15 Preignition, 4-wire NoPM720G2013 40 60 Yes 10 10 or 15 Running modulating No

inter- Low Firemittent

PM720G2039 40 50 Yes 10 10 or 15 No15/30b

PM720L1030 30 60 Tes 10 10 or 15 15 Preignition, 4-wire No

PM720L1139b 30 60 Yes 10 10 or 15 15 Lockout, modulating No

PM720L2004 30 60 Yes 10 10 or 15 15 Low Fire, Yes

PM720L2012 30 50 Yes 10 10 or 15 15 High Fire No

PM720L2020 10 60 Yes 10 10 or 15 15 No

PM720M2002 30/90a 60 Yes 10 10 or 15 Preignition, 2-wire Nointer- Running isolated ON-

mittent Low Fire OFF-ONcontacts

PM720M2036 30/7c 60 Yes 10 15 Preignition, None NoRunning

PM720M2044 30/90a 50 Yes 10 10 or 15 Preignition, 2-wire Nointer- Running isolated ON-

mittent Low Fire OFF-ONcontacts

PM720M2051 30/7C 50 Yes 10 15 Preignition, None NoRunning

a90 sec; 30 sec if terminal 15 is jumpered to terminal 8.bd15 sec; 30 sec if terminal 15 is jumpered to jumper 8.c30 sec; 7 sec if terminal 15 is jumpered to terminal 8. Replaces PM720M2036.dincreases sensitivity to intermittents/bouncing limit switches.

Page 12: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

V5055A-E INDUSTRIAL GAS VALVE

Safety shutoff valves used with V4055, fluidpower actuators to control gas flow to industrialburners

Valve Capacities: Based on gas with 1000 Btu/cu. ft.,.064 sp gr at one in. wc pd. [37.3 MJ/m3, .064 sp gr at 0.25kPa p.d.].

AMERICAN GASASSOCIATION

VALVE SIZERATED CAPACITY

(In.) cfh m3/hr

3/4 665 18.8

1 960 27.2

1-1/4 1406 39.8

1-1/2 1717 48.6

2 3620 102.5

2-1/2 4250 120.3

3 5230 148.0

4 (V4055A) 10200 288.8

4 (V4055B,C) 9180 259.9

Valve-Actuator Pressue Ratings

Maximum operating pressure differential (diff.).

Maximum close off pressure without seat leakage (closeoff).

VALVE V4055A, D, F, G

V5055A,C3/4-3 in.

V5055A,C4 in.

5 psi [35 kPa] diff.;15 psi [105 kPa]

close off

3 psi [21 kPa] diff.;15 psi [105 kPa]

close off

V5055B 5 psi [35 kPa] diff.;3/4-3 in. 15 psi [105 kPa]

close off

V5055B 3 psi [21 kPa] diff.;4 in. 15 psi [105 kPa]

close off

V5055D,E3/4, 1, 1-1/4,

1-1/2 in.

5 psi [35 kPa] diff.;75 psi [525 kPa]

close off

V5055D,E 5 psi [35 kPa] diff.;2, 2-1/2, 3 in. 45 psi [315 kPa]

close off

V4055B,E

15 psi [105 kPa] diff.;15 psi [105 kPa]

close off

5 psi [35 kPa] diff.;15 psi [105 kPa]

close off

15 psi [105 kPa] diff.;15 psi [105 kPa]

close off

5 psi [35 kPa] diff.;15 psi [105 kPa]

close off

25 ps i[175 kPa] diff.;75 psi [525 kPa]

close off

15 psi [105 kPa] diff.;45 psi [315 kPa]

close off

Used with natural, mixed, manufactured, or LP gases.Refer to ordering table for application, valve, size, andother specifications. Mounting Means: Directly in gas supp-ly line, 1/4 in NPT upstream and downstream tap and plugis standard on all V5055 valves; 4-in. models have flangedconnections only. Ambient Temperature Rating: – 40°F to+ 150°F [–40°C to + 66°C]

VALVE-ACTUATOR APPROVALSThe following combinations of V5055 Valves and V4055Fluid Power Actuators are approved by these agencies.

INDUSTRIAL RISK INSURERS (FORMERLY FIA)APPROVABLEUNDERWRITERS LABORATORIES INC. LISTED—V4055A, B, D, E, F, G/V5055A-E, 3/4-4 in.

FACTORY MUTUAL APPROVED and A.G.A. CERTIFIED—V4055A/V5055A V4055E/V5055EV4055D/V5055C V4055F/V5055C,EV4055A/V5055B V4055G/V5055A,B,DV4055B/V5055D

C.G.A. CERTIFIED—V4055A,B,D,E/V5055A,B,C,D,E (sizes 3/4 x 3/4 through4 x 4 in.)

Replacement PartsReplacement Seal Assembly—includes valve seal, bonnetseal, and tube of lubricant.

133393A for 3/4, 1, 1-1/4, and 1-1/2 in. valves133392A for 2, 2-1/2 and 3 in. valves.137253A for 4 in. valves.

Replacement Bonnet Assembly—includes complete bon-net assembly, plus the required replacement sealassembly.

Page 13: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Page 14: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

V4055A, B, D, E, F, G ON-OFF FLUID POWER GAS VALVE ACTUATORS

1/2 Hpa

Used with V5055 valve to control gas supply tocommercial and industrial burners.

Refer to ordering table page 15 for application. Rated forfinal safety shutoff service when used with V5055 valve. in-dicators on valve and actuator provide constant visual in-dication of valve position. Valve and actuator can bemounted in any position. Actuator mounts directly to valvebonnet with 2 setscrews. Ambient TemperatureRating: –40°F to + 150°F [–40°C to + 66°C] for 60 Hzmodels. Closing time: 1 second maximum. Pressure ratingsand approvals for these actuators depend on the valve us-ed. Refer to VALVE-ACTUATOR APPROVALS andPRESSURE RATINGS

Electrical Ratings:V4055A, D, F, G

DAMPER ARM RATING (electrically drivesdamper in 1 direction only)Standard models—20 lb. maximum at 2-11/16 in. radius at20°F to 150°F and 5 lb. at –40°F to +20°F [9 kg max-imum at 68 mm radius at –7°C to + 66°C and 2.3 kg at–40°C to –7°C].

Models with Damper Shaft Return Spring—10 lb, maximumat 2-11/16 in. radius at 20°F to 150°F and 5 lb. at –40°Fto + 20°F [4.5 kg at 68 mm radius at – 7°C to + 66°C and2.3 kg at –40°C to –7°C].

Maximum Damper Shaft Rotation52 angular degrees.Auxiliary and Valve Closed (Factory Mutual)Switch, Ratings:

LOAD 120 V 240 V

Full Load 9.8 A 4.9 A

Locked Rotor 58.8A 29.4 A

aMaximum total connected power to both switches (if used) is1800 VA.

Accessories:133568 Auxiliary Switch Bag Assembly

133569 Valve Closed Switch Bag Assembly. (Do not usewith V5034 valve body.)

7616BR Damper Arm (damper arm and clip.)

133533A Short Stem Adapter for mounting actuator onV5034 valve with short stem.

133534A Long Stem Adapter for mounting actuator onV5034 valve with long stem.

VOLTAGE/ OPENING (Standard) OPENING (Fast) HOLDING

FREQUENCY INRUSH W A VA INRUSH W A VA W A VA

120/60 3.9 50.0 0.94 115 5.4 71.0 1.33 160 9.5 0.12 14

208/60 2.7 54.0 0.59 115 4.0 73.0 0.80 160 9.1 0.07 14

240/60 2.6 51.0 0.45 115 4.0 71.5 0.68 160 9.2 0.06 14

V4055B, E

VOLTAGE/ OPENING (Standard) OPENING (Fast) HOLDING

FREQUENCY INRUSH W A VA INRUSH W A VA W A VA

120/60 5.4 60.0 0.94 115 — — — — 9.5 0.16 19

Page 15: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

OPENlNGTIME(sec)a

ORDERNUMBER

DESCRIPTION/APPLICATION

VOLTAGE(60 Hz)a

120

120

120

INCLUDES

V4055A1007 ON-OFF ACTUATOR, Normallyused with V5055A, B valvebodies. Low pressure.

26

V4055A1031 13

26V4055A1064 Damper shaft

V4055A1080 240 26

13

13

13

V4055A1098 120

V4055A1114 240

V4055A1296

V4055A1304

120 Installed auxiliary switch

120 26

26

Damper shaft and return spring installed

NEMA 4 enclosure.

Damper shaft.

V4055A1312 120

V4055B1021

V4055B1039

ON-OFF actuator. Normallyused with 4 in. V5055A, B andall V5055D valve bodies. Highpressure.

120 26

13

26

13

13

13

13

13

120

V4055D1001

V4055D1019

Damper shaft.ON-OFF actuator includesFactory Mutual “Proof ofClosure” and UnderwritersLaboratories Inc. “Valve SealOvertravel Interlock” switch.Meets Factory Mutual andUnderwriters Laboratories Inc.requirements when used withV5055C valve bodies. Lowpressure.

120

120

V4055D1027 120 Installed auxiliary switch and NEMA 4enclosure.

120V4055D1035

V4055D1043

installed aux. switch.

120

V4055E1016 Damper shaft.ON-OFF actuator includesFactory Mutual “Proof ofClosure” and UnderwritersLaboratories Inc, “Valve SealOvertravel Interlock” switch.Meets Factory Mutual andUnderwriters Laboratories Inc.requirements when used with4 in. V5055C and all V5055Evalve bodies. High pressure,

120

V4055E1024 120 With damper shaft, installed auxiliaryswitch NEMA enclosure.

26

V4055E1040 120 13 With damper arm, installed aux. switch,NEMA 4 enclosure.

V4055F1006 Manual Reset ON-OFF ac-tuator includes FM “Proof ofClosure” and UnderwritersLaboratories Inc. “Valve SealOvertravel Interlock” switch.Meets Factory Mutual onUnderwriters Laboratories Inc.requirements when used withV5055C valve bodies. Lowpressure.

120 13

13V4055G1004 Manual Reset ON-OFF Ac-tuator. Normally used withV5055A, B valve bodies. Lowpressure.

120

aCan also be used at 50 Hz, however, opening time will increase by 20 percent.

Page 16: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Gas Valves

NEW!

V5097 Industrial Gas ValvesSafety shutoff valves used with V4055,V4062 and V9055 fluid power actuatorsto control gas flow to commercial andindustrial burners.

Use with natural or LP gases.Mount directly in gas supply line.Two valve body types. Small body typefor 3/4 in., 1 in., 1 1/4 in., 1 1/2 in. and 2 in.pipes. Large body type for 2 in., 2 1/2 in.

3/4

1 1/4

and 3 in. pipes.Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSPthreaded connections.Provides three 1/4 in. upstream and two 1/4 in. downstream tap andplug. CE version provides an additional downstream tap andplug.Yellow SHUT indicator attached to the valve stem provides anindication of the valve closed position.Write protect link included to safeguard configuration settings.

1 1/2

21/2

TEMPERATURE RATINGS:Ambient: –40 F to 150 F (–40 C to 66 C); –40 F to 125 F (–40 C to

52 C) when used with V9055.DIMENSIONS, APPROXIMATE: See illustration.MATERIAL: Die-cast aluminum.VALVE BODY RATING: 75 psi (517.1 kPa).

VALVE CAPACITIESa:

American Gas Association

Valve Size Rated Capacity

(in.) cfh m 2/hr

665 18.8

1 960 27.2

1406 39.8

1717 48.6

2 3620 102.5

4250 120.3

3 5230 148.0

4(V4055A) 10200 288.8

4(V4055B,C) 9180 259.9a Based on 0.64 sp gr natural gas at 1 in. wc (0.25 kPa) pressure

drop.

MOUNTING: Mounts directly in the gas supply line.WEIGHT:

3/4 in., 1 in., 1 1/4 in.; 1 1/2 in. (small) valve: 3.68 lb (1.67 kg).2 in., 2 1/2 in., 3 in. (large) valve: 8.0 lb (3.64 kg).

continued next page

Page 17: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Gas ValvesV5097 continued

REPLACEMENT PARTS:133393A Replacement Seal Assembly for small valves; includes

valve seal, bonnet seal and tube of lubricant.133392A Replacement Seal Assembly for large valves; includes

valve seal, bonnet seal and tube of lubricant.133398AA Replacement Bonnet Assemblya for 3/4, 1, 1 1/4, and 1 1/2

in. V5097A valve.133417AA Replacement Bonnet Assemblya for 2, 2 1/2 and 3 in.

V5097A valve.133398BA Replacement Bonnet Assemblya for 3/4, 1, 1 1/4, and 1 1/2

in. V5097B valve

133417BA Replacement Bonnet Assemblya for 2, 2 1/2 and 3 in.V5097B valve.

136308AA Replacement Bonnet Assemblya for 3/4, 1, 1 1/4, and 1 1/2in. V5097D valve

136307AA Replacement Bonnet Assemblya for 2, 2 1/2 and 3 in.V5097D valve.

a Includes complete bonnet assembly and the required replace-ment seal assembly.

V5097 dimensions in in. (mm).

ALLOW 2 IN, (51MM) CLEARANCE FOR ACTUATOR REMOVAL.

VALVESIZE(IN.)

DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F DIM. G DIM. H DIM. J OCTAGON

IN MM IN. MM IN. MM IN. MM IN. MM IN. MM IN.IN. M M I N . MM IN. M M MM

3/4 11-1/8 283 2-3/4 70 8-3/16 208 8-1/4 210 2-7/16 62 5 127 2-5/16 58 7/8 23 3-15/16 100 2-13/16 71

1 11-1/8 283 2-3/4 70 8-3/16 208 8-1/4 210 2-7/16 62 5

2-3/4 7 0 8-3/16 208 8-1/4 210 2-7/16 62 5

127 2-5/16 58 7/8 23 3-15/16 100 2-13/16 71

1-1/4 11-1/8 283 127 2-5/16 58 7/8 23 3-15/16 100 2-13/16 71

1-1/2 11-1/8 283 2-3/4 70 8-3/16 208 8-1/4 210 2-7/16 62 5 127 2-5/16 58 7/8 23 3-15/16 100 2-13/16 71

2 11-3/4 298 3-3/8 86 8-5/16 211 11-3/4 298 3-5/8 91 8 203 4-7/16 113 1-1/2 38 6-1/2 165 4-1/2 114

2-1/2 11-3/4 298 3-3/8 86 8-5/16 211 11-3/4 298 3-5/8 91 8 203 4-7/16 113 1-1/2 38 6-1/2 165 4-1/2 114

3 11-3/4 298 3-3/8 86 8-5/16 211 11-3/4 298 3-5/8 91 8 203 4-7/16 113 1-1/2 3 8 6-1/2 165 4-1/2 114

M11682

Page 18: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-121/99

Order Number Application Pipe Adapter

V5097A1004 Low pressure On-Off (with quick opening guide) 32000109-001—3/4 in. NPT32000109-002—1 in. NPT32000109-003—1-1/4 in. NPT32000109-004—1-1/2 in. NPT32000109-005—2 in. NPT

V5097A1012 32001605-001—2 in. NPT 32001605-002—2-12 in. NPT32001605-003—3 in. NPT

V5097B1002 Low pressure characterized guide (provides slowly increasing gas flow on 32000109-001—3/4 in. NPTopening) 32000109-002—1 in. NPT

32000109-003—1-1/4 in. NPT32000109-004—1-1/2 in. NPT32000109-005—2 in. NPT

V5097B1010 32001605-001—2 in. NPT32001605-002—2-12 in. NPT32001605-003—3 in. NPT

V5097C1000 Low pressure, double seat (use with actuators having valve seal overtravel 32000109-001—3/4 in. NPTinterlock) 32000109-002—1 in. NPT

32000109-003—1-1/4 in. NPT32000109-004—1-1/2 in. NPT32000109-005—2 in. NPT

V5097C1018 32001605-001—2 in. NPT32001605-002—2-12 in. NPT32001605 -003—3 in. NPT

V5097D1008 High pressure On-Off (with quick opening guide) 32000109-001—3/4 in. NPT32000109-002—1 in. NPT32000109-003—1-1/4 in. NPT32000109-004—1-1/2 in. NPT32000109-005—2 in. NPT

V5097D1016 32001605-001—2 in. NPT32001605-002—2-12 in. NPT32001605-003—3 in. NPT

V5097E1005 High pressure, double seat (use with actuators having valve seal overtravel 32000109-001—3/4 in. NPTinterlock) 32000109-002—1 in. NPT

32000109-003—1-1/4 in. NPT32000109-004—1-1/2 in. NPT32000109-005—2 in. NPT

V5097E1013 32001605-001—2 in. NPT32001605-002—2-12 in. NPT32001605-003—3 in. NPT

Page 19: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

81-00-30-12

NEW!V4295A, S and V8295A, S Solenoid Gas Valves

V4295A and V8295A are normally closed and V4295S andV8295S are normally open (vent) solenoid gas valves.Suitable for use on furnaces, ovens, atmosphericburners, commercial water heaters, roof-top make-up airunits, power burners, and commercial/industrial boilers.

Selection Guide

CURRENT DRAW:V4295A, S are used with 120 Vac controllers;V8295A, S are used with 24 Vac controllers.Models available in Normally Closed and Normally Openconfiguration.Normally Closed models, for safety shut-off applications,consist of a direct on/off operator for opening and closingof the valve.Normally Open models, for vent (double block and bleed)valve applications, consist of a direct electric on/offoperator for closing and opening of the valve.Models are suitable for the control of gaseous fluids in gasconsuming appliances according to internationalstandards.Models have inlet and outlet pressure taps.Models have inlet screen to protect the valve from theentry of dirt.

MODELS:V4295A Normally Closed (N.C.) Safety Shutoff Valve.V4295S Normally Open (N.O.) Vent Valve.V8295A Normally Closed (N.C.) Safety Shutoff Valve.V8295S Normally Open (N.O.) Vent Valve.

APPROVAL BODIES:Underwriters Laboratories Inc. Component Recognized: File No.

MH18476, Guide No. YLOZ.American Gas Association, Certificate No. C2030014.Canadian Gas Association certified, Certificate No. C2030014.Factory Mutual Approved (3/8, 1/2, and 3/4 in. only).CSD-1 Acceptable.IRI Acceptable.

AMBlENT TEMPERATURE RANGE: Ð40ÁF to +145ÁF [Ð40ÁC to+63ÁC].RATED PRESSURE: 2 psi and 5 psi.ELECTRICAL RATINGS:

V4295A,S: 120 Vac, 50/60 Hz.V8295A,S: 240 Vac, 50/60 Hz.

GAS TYPE: Air, natural, manufactured, mixed and LP gas.VALVE CAPACITIES: Refer to Figure 1.VALVE PATTERN: Straight through, non-offsetBODY MATERIAL: Die cast aluminum.

ELECTRICAL TERMINATIONS: Screw terminal connections.VALVE OPENING TIME: Less than 1 second.VALVE CLOSING TIME: Less than 1 second.MAXIMUM OPERATING PRESSURE: 3/8-inch through 3-inchpipe sizes: 2 psi and 5 psi models.

aBased on natural gas at 1000 BTU/cfh, 0.64 sp. gr. and 1 in.w.c. pressure drop.

Order Number ValveType

NPT PipeSize (in.)

Capacitycfha

PressureRating(psi)

Normallyclosed

V4295A1007

V4295A1098V4295A1015

V4295A1106V4295A1023V4295A1114V4295A1031V4295A1122

V4295A1049V4295A1130V4295A1056V4295A1148V4295A1064V4295A1155V4295A1072

V4295A1080V4295S1005V4295S1013V4295S1021V8295A1008V8295A1016V8295A1024V8295A1032

V8295A1040V8295A1057V8295A1065

V8295S1006V8295S1014V8295S1022

Normallyopen(vent)

Normallyclosed

Normallyopen(vent)

3/83/8

230230

2

2

2

2

2

2

2

2

2

222

2

222

222222

2

5

5

5

5

5

5

5

3/8, 1/2, 3/4, and 11-1/41-1/2

22-1/2

3

0.160 A0.340 A0.300 A0.525 A0.575 A

0.675 A

0.80 A1.60 A1.70 A2.80 A

N/AN/A

0.80 A

2.40 A0.340 A0.160 A3/4 and 1

1-1/4

Normally Open (N.O.)Pipe Size (inch)

Normally Closed (N.C.)Pipe Size (inch)

V4295S120 Vac

120 Vac

V8295S24 Vac

24 VacV8295AV4295A

1/21/2

2502506453/4

3/4

3/4

1

1

1

1-1/41-1/4

1-1/4

1-1/21-1/2

22-1/2

2

645790790145014502190219034653465

5070

6100350

4201100230250

645

3

3/81/2

3/4

3/4

1

1

1-1/4

1-1/4

790145021903465

1-1/2

350420

1100

Page 20: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Table 1. Models availableModel Voltage/Frequency Maximum pressure Pipe size (inch) Thread type

psi mbar

V4295A (N. C.) 110/120 Vac, 50/60 Hz 2.0 140 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2, 2-1/2, 3 NPT

V4295S (N. O.) 110/120 Vac, 50/60 Hz 2.0 140 3/4, 1, 1-1/4 NPT

V8295A (N.C.) 24 Vac, 50/60Hz 2.0 140 3/8, 1/2, 3/4, 1, 1-1/4, 1-1/2, 2 NPT

V8295S (N.O.) 24 Vac, 50/60Hz 2.0 140 3/4, 1, 1-1/4 NPT

Capacity in cfh at pressure drop of 1 inch water column sp. gr. = 0.64 for V4295A, V8295A (N.C.)3/8” 1/2” 3/4” 1” 1-1/4”

230 250 645 790 1,450 2,190 3,465 5,070 6,100

1-1/2” 2” 2-1/2"* 3"*

* V4295A only

Capacity in cfh at pressure drop of 1 inch water column sp. gr. = 0.64 for V4295S, V8295S (N.O.)3/4” 1” 1-1/4”

350 420 1,100

Page 21: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Figure 1. Valve capacities

Figure 2. Dimensions and weight

WARNING!!!If the flow is not in the same direction of arrow, valvemay not shut off.

Figure 3.Dimensions and weight

Pipe size A (inch) B (inch) C (inch) D (inch) E (inch) Weight (lbs)

3/4” NPT

1 ” N P T

1-1/4” NPT

1-1/2” NPT

Normally Closed (Fig. 2.)

2-3/163/8” NPT 2-7/8 4-7/16

2-3/161/2” NPT 2-7/8 4-7/16

2-3/163-7/16 5 - 1 / 4

2-3/163-15/16 5-1/4

2-1/25-15/16 8

3-3/85-15/16 8-3/8

3-3/82” NPT 6-11/16 9

4-9/162-1/2” NPT 9–1/2 12-3/4

4-9/169-1/2 12-3/4

3-3/4 2-3/16 2.5

3-3/4 2-3/16 2.5

3-3/4

3-3/4

4-1/16

4-15/16

4-15/16

6-1/8

6-1/8

2-3/4

3

4-3/8

4-3/8

5-3/8

7-7/8

7-7/8

4.0

4.5

12.8

12.8

14.0

28.5

31.03 ” N P T

Normally Open (Fig. 3.)

A (inch)Pipe size B (inch) C (inch) D (inch) E( inch) Weight (lbs.)

2-3/163/4 NPT 3-7/16 5-1/2

2-3/161” NPT 3-15/16 5-1/2

8-3/4 2-1/2

3-3/4

3-3/4

4-1/16

2-3/4

3

4-3/8

4.0 lbs

4.5 lbs

12.8 lbs1-1/4” NPT 5-15/16

Page 22: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

C437D, E, F, G, H; C637B GAS/AIR PRESSURE SWITCHES

Pressure or Differential Pressure limit controlsfor industrial gas systems.

C437 has spst switching; C637 has spdt switching. Modelsfor lockout applications must be manually reset beforeresuming operation. Models with pressure range of 1 to 26in. wc [0.25 to 6.5 kPa] have restrictive orifice in inletpressure channel to compensate for momentary surges ingas pressure. Ambient Temperature Rating: 32°F to 125°F0°C to 52°C]. Connections: 1/2 in. NPT female for main orhigh pressure; 1/8 in. NPT female for vent or low pressure.Listed by Underwriters Laboratories Inc.: File No. MP2168,Guide No. MFHX; Industrial Risk Insurers (formerly FIA) ap-provable; CSA certified: File No. LR1620, Guide No.180-W-1.16; Factory Mutual approved: Report Nos. 22018,24127, J.I. IF4A3.AF.

Replacement Parts:

106729 Cover Glass, 6 in. [152.5 mm] diameter.

139870A Cover Glass for Rainproof Enclosures

106747 Cover Retaining Ring for C437 and C637 modelsmanufactured before 1973.

137631 Cover Retaining Ring for C437 and C637 modelsmanufactured in 1973 and 1974.

137558 Retaining Clip for Retaining Ring on C437 andC637 models manufactured in 1973 and 1974.

118733 Retaining Clip for C437 and C637 models manufac-tured since 1975.

Equivalent Simetric Units:

PRESSURE WATERRANGE mm kPa

1/2 to 5-1/2 in. water 10.0 to 150.0 0.124 to 1.337

1 to 26 in. water 50.0 to 700.0 0.249 to 6.464

1/2 to 5 psi 351.5 to 3516.0 3.447 to 34.47

1 to 10 psi 703.0 to 7031.0 6.895 to 68.95

1-3/4 in. water 44.5 0.44

1/2 psi 351.5 3.447

1 psi 703.0 6.895

0.25 in. water 6.5 0.062

0.15 in. water 3.8 0.037at at at

1/2 in. water 12.7 0.1243

Switch Ratings (amperes):

MODEL

C437D,E,G,H

C437F,J,K

C637B

120 240LOAD Vac Vac

Full Load 8.0 5.1Locked Rotor 48.0 30.6Res. Load 10.0 5.0

Full Load 8.0 5.1Locked Rotor 48.0 30.6Res. Load 10.0 5.0

62.5 VA at 120 and 240 Vac,Pilot Duty

120 240Vdc Vdc

2.4 1.224.0 12.05.0 2.0

2.0 1.020.0 10.08.0 4.0

Accessories:

4074BWK Mounting Brackets, for surface mounting.

4074BWN Orifice Tool.

388448U Orifice — 0.006 in. [0.15 mm] dia.

388448N Orifice — 0.008 in. [0.20 mm] dia.

388448C Orifice — 0.011 in. [0.28 mm] dia.

388448E Orifice — 0.018 in. [0.46 mm] dia.

Page 23: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

MAXIMUM SURGEPRESSURE

ORDERNUMBER

PRESSURERANGE DIFFERENTIAL psi kPa

5.0 34.5

15.0 103.4

30.0 206.8

1-3/4 in.

1/2 psi

1 psi

1-1/4 in.

Spst Rise YesC437D1005 1 to 26 in. water

1/2 to 5 psi

1 to 10 psi

1 to 26 in. water

1/2 to 5 psi

1 to 10 psi

1/2 to 5-1/2 in. water

1 to 26 in. water

Spst Rise YesC437D1013

Spst Rise YesC437D1021

Spst Fall YesC437E1004 5.0 34.5

15.0 103.4

30.0 206.8

3.0 20.7

Spst Fall YesC437E1012

C437E1020

C437E1038

1/4 psi

Spst Fall Yes1/2 psi

Spst Fall Yes0.25 in.

2 Spsta Fall and Rise NOC437F1003

C437F1011

C437F1029

1-1/4in. 5.0 34.5

2 Spsta Fall and Rise NO15.0 103.41/2 to 5 psi 1/4 psi

30.0 206.8 2 Spsta Fall and Rise No1 to 10 psi 1/2 psi

C437F1037 1/2 to 5-1/2 in. water 0.25 in. 3.0 20.7 2 Spsta Fall and Rise No

C437F1045 e 1 to 26 in. water 1 1/4in. 5.0 34.5 2 Spsta Fall and Rise No

C437F1052 e 1/2 to 5 psi 1/2 psi 15.0 103.4 2 Spsta Fall and Rise No

C437F1060 e 1 to 10 psi 1/2 psi 30.0 206.8 2 Spsta Fail and Rise No

C437F1078 e 1/2 to 5 1/2 in. water 0.25 in. 3.0 20.7 2 Spsta Fall and Rise No

C437G1002 1 to 26 in. water 1-1/4 in. 5.0 34.5 Spst Rise No

C437G1028 1/2 to 5 psi 1/4 psi 15.0 103.4 Spst Rise No

C437G1036 1 to 10 psi 1/2 psi 30.0 206.8 Spst Rise No

C437G1069e 1 to 26 in. water 1-1/4 psi 5.0 34.5 Spst Rise No

C437G1077e 1/2 to 5 psi 114 psi 15.0 103.4 Spst Rise No

C437G1085e 1 to 10 psi 1/2 psi 30.0 206.8 Spst Rise No

C437H1001 1 to 26 in. water 1-1/4 in. 5.0 34.5 Spst Fall No

Spst Fall No

Spst Fall No

Spst Fall No

Spst Fall No

Spst Fall No

C437H1027 1/2 to 5 psi 1/4 psi 15.0 103.4

C437H1035 1 to 10 psi 1/2 psi 30.0 206.8

C437H1043 1/2 to 5-1/2 in. water 0.25 in. 3.0 20.7

C437H1076e 1 to 26 in. water 1-1/4 in. 5.0 34.5

C437H1084e 1/2 to 5 psi 1/4 psi 15.0 103.4

C437H1092e 1 to 10 psi 1/2 psi 30.0 206.8

C437J1008b 1 to 26 in. water 1-3/4 in. 5.0 34.5

C437J1016b 1/2 to 5 psi 112 psi 15.0 103.4

C437K1007b 1 to 26 in. water 1-1/4 in. 5.0 34.5

C437K1015b 1/2 to 5 psi 1/4 psi 15.0 103.4

C637B1002 1 to 26 in. water 1-1/4 in. 5.0 34.5

C637B1010 1 to 10 psi 112 psi 30.0 206.8

Spst Fall No

2 Spsta Fall and Rise Yesc

2 Spsta Fall and Rise Yesc

2 Spsta Fall and Rise Yesd

2 Spsta Fall and Rise Yesd

Spdt Fallf No

Spdt Fallf No

Spdt Fallf No

Spdt Fallf No

C637B1028 1/2 to 5 psi 1/4 psi 15.0 103.4

C637B1036 1/2 to 5-1/2 in. water 0.15 in. 3.0 20.7

a Two separate circuits. One circuit breaks and the other makes on a pressure rise or fall.b Dual spst switch (one normally open and one normally closed) with 4 leads serves function of spdt switch.c Lockout on rise. d Lockout on fall.e Weatherproof enclosure (NEMA 3R). f Breaks R-W and makes R-B on fall.

Page 24: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Limits and Interlocks

C645A,B,D C645C

Positive- or Differential- pressure limit controls.Spdt diaphragm operated snap-acting Micro Switch. C645Emodels for use with distillate fuel oil only. Not for use withnatural or LP gases. Ambient Temperature Rating: – 20° Fto + 125°F [– 32°C to + 52°C]. Connections: 1/4 in. NPTfemale for main or high pressure; 1/8 in. NPT female forventing or low pressure. Listed by UnderwritersLaboratories Inc.: File No. MP2168, Guide No. MFHX(C645A-E); Industrial Risk Insurers (formerly FIA) ap-provable; CSA certified: File No. LR1620, Guide No,140-A-2; Factory Mutual approved: Report Nos. 19268,13233-S3.

Approx. Dimensions:DIAMETER DEPTH

in. mm In. mm

C645A,B,D,E 4-3/4 120.6 3-1/2 88.9

C645C 7-7/8 200.0 3-1/2 88.9

Electrical Ratings (amperes)d

MODEL LOAD 120 VAC 240 VACC645A,B,D,E Full Load 7.4 3.7

Locked Rotor 44.4 22.2

C645C Full Load 8.0 5.1

Locked Rotor 48.0 30.6d2 A at 30 vac.

Accessories:15865AC Mounting Bracket Assembly—C645A,B,D.

112657A Mounting Bracket Assembly—C645C. (Includesscrews for attaching bracket to C645 only.)

137637B Cover with window—C645A.

137637C Cover with window—C645B.

14026 Siphon Loop.

Suitable for DifferentialSwitch Maximum

Scale Range Natural Nominal Maximum Action Sustained

Order (in. or LP (in. (in. On Press.Pressure Cover

Number water) kPa Gases a Air Includes water) kPa water) kPa Fall (psi) kPa Window

C645A1022 b 3.0 to 21.0 0.7 to 5.2 Yes Yes Auto. Recycle 1.0 0.2 3.0 0.7 Breaks 5.0 34.5 No

C645A1030 b 3.0 to 21.0 0.7 to 5.2 Yes Yes Man. Resete 1.0 0.2 3.0 0.7 Breaks 5.0 34.5 No

C645A1055 b 5.0 to 35.0 1.2 to 8.7 Yes Yes Man. Resete 1.0 0.2 4.0 1.0 Breaks 5.0 34.5 Yes

C545A1063 5.0 to 35.0 1.2 to 8.7 Yes Yes Auto. Recycle 1.0 0.2 4.0 1.0 Breaks 5.0 34.5 No

C645A1105 b,g 3.0 to 21.0 0.7 to 5.2 Yes Yes Man. Reset 1.0 0.2 3.0 0.7 Breaks 5.0 34.5 Yes

C645B1013b 3.0 to 21.0 0.7 to 5.2 Yes Yes Man. Resetf 1.0 0.2 3.0 0.7 Makes 5.0 34.5 Yes

C645B1039b 5.0 to 35.0 1.2 to 8.7 Yes Yes Man. Resetf 1.0 0.2 4.0 1.0 Makes 5.0 34.5 Yes

C645B1047 b,d 3.0 to 21.0 0.7 to 5.2 Yes Yes Man. Resetf 1.0 0.2 3.0 0.7 Makes 5.0 34.5 Yes

C645C1020b 0.6 to 5.3 0.1 to 1.3 No Yes Auto. Recycle 0.2 0.05 0.8 0.2 Breaks 1.5 10.3 Yes

C645C1038b 0.6 to 5.3 0.1 to 1.3 No Yes Man. Resete 0.2 0.05 0.8 0.2 Breaks 1.5 10.3 Yea

C645D1029 3.0 to 21.0 0.7 to 5.0 No Yes Auto. Recycle 1.0 0.2 3.0 0.7 Breaks 5.0 34.5 No

C645D1052 2.0 to 20.0 0.5 to 5.0 No Yes Auto. Recycle 1.0 0.2 3.0 0.7 Breaks 5.0 34.5 No

C645E1002 c 3.0 to 21.0 0.7 to 5.2 No Yes Auto. Recycle 1.0 0.2 3.0 0.7 Breaks R-W, 5.0 34.5 NoMakes R-B

a C545A,B also Underwriters Laboratories Inc. approved for distillate fuel oil (No. 1,2 oil) applications. For oil, use 14026 Siphon Loop.b Includes switch position indicator.c Used with distillate fuel oil, cannot be used for natural or LP gases.d With scaleplate set point stop set at 51/4 in. [133.4 mm] wc. Meets A.G.A. high gas pressure switch requirements for burners with inputs

greater than 2.5 million Btuh.e Locks out when pressure fails to set point minus differential; can be reset manually after pressure rises to set point.f Locks out when pressure rises to set point; can be reset manually after pressure fails to set point minus differential.gDevice operates at 1.5 in. wc or less on pressure fall with the scaleplate setting at 3.0 in. WC.

Page 25: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

C7012A, C, E, FSOLID STATE PURPLE PEEPERULTRAVIOLET FLAME DETECTORS

Dimensions of C7012A, E in inches[mm in brackets]

Dimensions of C7012C, F in inches[mm in brackets]

Solid state electronic flame detectors foruse with appropriate Honeywell relays andamplifiers. Sense ultraviolet radiation pro-duced by combustion of gas, oil, coal; orother fuels.Direct replacement for C7012 detectors with vacuumtubes. These flame detectors can be mounted horizon-tally, vertically, or at any angle in between. For C7012E,F notch and arrow on faceplate must be aligned in verti-cal plane for proper shutter operation. Threaded conduitfitting and color-coded leadwires for quick electricalhookup. Two detectors can be wired in parallel to re-duce nuisance shutdowns. Mounting Means: C7012A, E— mounting flange with either 3/4 or 1 in. NPT internalthreads (depending on model) for attaching to sightingpipe; C7012C, F — pipe union with 1 in. NPT internalthreads for attaching to sighting pipe. Power Consump-tion: C7012A, C — 2.5W; C7012E, F — 7.0W. LeadLength: 8 ft (2.4 m). Listed by Underwriters LaboratoriesInc. (120V models only): C7012A and E (exceptC7012E1161)— File No. MP268, Guide No. MCCZ;C7012C, F — File No. E34649, Guide No. ZTSZ. indus-trial Risk Insurers (formerly FIA) approvable; CanadianStandards Association certified (120V models only):C7012A and E — File No. LR1620; Guide No. 140-A-2and 300-1-0.2; Factory Mutual approved, Report No.4740.01.

Replacement PartsAll models—

113228 Ultraviolet Sensing Tube.191286 Ultraviolet Sensing Tube — for operation

down to minus 40°F (minus 40°C) outside case.C7012A and E—

114372 Quartz Viewing Window, rated for 20 psi(137.9 kPa).

114465 Gasket, silicone rubber — for installing view-ing window (3 required).

1120739 Gasket, asbestos-neoprene — heat insula-tion and seal-off for mounting flange.

C7012C and F—122037 Quartz Viewing Window, rated for 100 psi

(689.5 kPa).C7012E and F—

190971B Coil and Shutter Assembly — for 120Vmodels.

Page 26: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide11-00-30-12

AccessoriesAll models—

118369 Bushing, galvanized iron, with 3/4 in. NPT in-ternal threads on one end and 1 in. NPT externalthreads on other end. For adapting detector with 1in. NPT internal threads (for mounting) to a 3/4 in.sighting pipe, or to pipe nipple and tee for connec-ting air supply.

WI 36AA1045 Test Meter (includes 196146 MeterConnector Plug).

117053 Meter Connector Plug (for older W136Amodels).

118367A Swivel Mount.

27012A and E—122748 Quartz Viewing Window, rated for 50 psi

(344.7 kPa).124204 Quartz Magnifying Lens, rated for 20 psi

(137.9 kPa); for increasing the ultraviolet radiationsensed by the detector.

120934 Mounting Flange, aluminum, with 3/4 in. NPTinternal threads for attaching to sighting pipe.

124198 Mounting Flange, aluminum, with 1 in. NPTinternal threads for attaching to sighting pipe.

123539 Antivibration Mount.

PipeOrder Application/ Voltage Mounting

Number Description (50/60 Hz) Size

Ambient TemperatureRating

H o u s i n g°F °C

C7012A1145 Use with Honeywell rec- 120 3/4 " NPT + 25 to + 175 –4 to + 79 Violet, cast-aluminumtification type flame safe- cover; mounting flange

C7012A1152 guard controls EXCEPT 120 1 " NPT + 25 to + 175 –4 to + 79 (with heat block) and face-Dynamic Self Check plate are separate to pro-

C7012A1160 models.b Field replaceable 120 1" NPT – 40 to + 175 –40 to + 79 vide heat insulation andviewing window and ultra- seal-off. NEMA 4 stan-

C7012A1186 violet sensing tube. 208 3/4" NPT + 25 to + 175 –4 to + 79 dards (water-tight anddust-tight indoor and

C7012A1194 240 3/4" NPT + 25 to + 175 –4 to + 79 outdoor).

C701C1042 a 120 1" NPT + 25 to + 175 – 4 to + 79 Explosion-proof, 2-piece,violet, cast-aluminum.

C7012E1104 Use only with DynamicSelf check flame safe-

C7012E1112 guard controls.b Field re-C7012E1120 placeable viewing window,

ultraviolet sensing tube,C7012E1146 self-checking coil and

shutter.C7012E1153

C7012E1161 C

C7012E1278d

C7012F1052 a

120 3/4“ NPT –20 to + 175 – 29 to + 79 Violet, cast-aluminum

120 1" NPT –20 to + 175cover; mounting flange

–29 to + 79 (with heat block) and face-120 1" NPT –40 to + 175 –40 to + 79 plate are separate to pro-

vide heat insulation and208 3/4" NPT –20 to + 175 –29 to + 79 seal-off. Meets NEMA 4

240 3/4" NPT –20 to + 175standards (watertight and

–29 to + 79 dust-tight, indoor and

120 1" NPT –20 to + 175 –29 to + 79 outdoor).

120 1" NPT –20 to + 175 –29 to + 79

120 1" NPT –20 to + 175 –29 to + 79 Explosion-proof, 2-piece,violet,cast-aluminum.

aWith explosion-proof housing for use in hazardous atmospheres.bDynamic Self-Check models are R4138A/B, R4181A, R4126/R4127 with R7256B, R4150 with R7253B, and R4075C/D/E, R4138C/D, or14140 with R7247C Amplifier.CWith 10 ft (3.0 m), 5-wire cable with amp connector.dWith 5-pin Brad Harrison Connector Type 41310, Mating Connector Type 41306N or 41307N.

Page 27: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

Flame Sensors

C7024E,F Solid State Purple Peeper Ultraviolet Flame Detectors24 Vdc solid state electronic flame detec-tors for sensing the ultraviolet radiationemitted by the combustion of most car-bon containing fuels, such as naturalgas, LP gases, and oil.

Use with R7824C Dynamic Self-CheckFlame Signal Amplifier.Circuitry provides low power con-sumption and high reliability.Mount horizontally, vertically or at anyangle in between.Field-replaceable UV radiation sens-ing tube and quartz viewing window.Quick electrical installation withthreaded conduit fitting and color-coded leadwires.Reduce nuisance shutdowns by wiring two in parallel.Oscillating shutter interrupts UV radiation 12 times per minutewith R7824C.

APPROVAL BODIES:Underwriters Laboratories Inc. component recognized:

C7024E: File no. MP268.C7024F: For use in hazardous locations; Class 1, Groups C andD; Class 2, Groups E, F and G; File no. E34649.

Canadian Standards Association certified.APPROXIMATE OVERALL DIMENSIONS:

C7024E: 5-1/4 in. [133 mm] wide, 3-3/4 in. [95 mm] high, 7-7/32 in.[183 mm].

C7024F: 8 in. [203 mm] diameter, 9 in. [229 mm] deep.OPERATING AMBlENT TEMPERATURE RANGE (outside case):

-20 F to +175 F [-29 C to +79 C].ELECTRICAL RATINGS:

Voltage: 24 Vdc.Power consumption: 7.8W maximum.

MOUNTING:C7024E: Mounting flange with 3/4 in. NPT internal threads for

attachment to sight pipe.

WIRING CONNECTIONS: NEC CLASS 1 color-coded leadwires, 8ft.[2.4 m] long.

Number of leadwires: Six.Threaded leadwire opening in faceplate:

C7024E: 1/2-14 NPSM or 7/8-20 UNSM internal threads for attach-ing conduit.

C7024F: 1/2-14 NPT internal threads for attaching pipe.REPLACEMENT PARTS:

All models—113228 Ultraviolet Sensing Tube.191286 Ultraviolet Sensing Tube for –40 F [–40 C] operation.190971 G Coil and Shutter Assembly, 24 Vdc.

C7024E—114372 Quartz Viewing Window, rated for 20 psi [138 kPa].114465 Gasket, silicone rubber; for installing viewing window

(three required).120739 Gasket, asbestos-neoprene; heat insulation and seal-

off for mounting flange.C7024F—

122037 Quartz Viewing Window, rated for 100 psi [690 kPa].ACCESSORIES:

All models—W136A Test Meter (includes 196146 Meter Connector Plug).118367A Swivel Mount.

C7024E—122748 Quartz Viewing Window, rated for 50 psi [345 kPa].124204 Quartz Focusing Lens, rated for 20 psi [138 kPa]; for

increasing the ultraviolet radiation sensed by the detector.120934-520 Mounting Flange, aluminum, with 3/4 in. NPT inter-

nal threads for attaching to sight pipe.123539 Antivibration Mount.190105 Water Jacket.

C7024F—118369 Bushing, galvanized iron, with 3/4 in. NPT internal threads

on one end and 1 in. NPT external threads on the other end.For adapting a detector with 1 in. NPT internal threads (formounting) to a 3/4 in. sight pipe, or to the pipe nipple and teefor connecting an air supply.

Available only through Authorized Honeywell 7800 SERIES and Boiler Control System Distributors.

HousingVoltageOrder Number Leadwire Length

C7024E1001 24 Vdc Violet, cast aluminum cover; mounting flange with heat block and faceplate are separate 8 ft. [2.4 m]to provide heat insulation and seal-off, Meets NEMA 4 enclosure requirements (indoor,outdoor protection; raintight, dust-tight, hose directed water).

C7024F1009 Explosion-proof, two-piece, violet, cast aluminum.

Page 28: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

C7027A MINIPEEPER ULTRAVIOLETFLAME DETECTOR

C7027A1049C7027A1064C7027A1072

Compact flame detector for use withRA890G, R7023C, R4795, R4126, R4127,R4075, R4138, R4150, R4140 and BC7000flame safeguard controls with ultravioletamplifiers.Used on gas, oil, coal, or combination burners. Detectsultraviolet radiation from all flames. Sensing tube is notfield replaceable; entire unit can be economically re-placed. Mounting Means: Integral nut for 1/2 in. sightingpipe. Dimensions: 1-1/8 in. (28.6 mm) (mounting nut),3-7/8 in. (98.4 mm) long. Listed by Underwriters Labora-tories Inc; File No. MP268, Guide No. MCCZ; IndustrialRisk Insurers (formerly FIA) approvable; Canadian Stan-dards Association certified, File No. LR1620, GuideNos. 140-A-2, 300-1-0.2; Factory Mutual approved,Report No. 24181.03.

Replacement Parts129685 Flange Gasket.136733 Heat Block.NOTE: UV sensing tube is NOT field replaceable.

ORDER AMBIENT TEMP. RANGE LEAD LENGTHNUMBER °F °C FT M

C7027A1023 0 to + 215 -18 to + 102 6 1.8C7027A1031 -40 to + 215 -40 to + 102 6 1.8

C7027A1049 a 0 to + 215 -18 to + 102 6 1.8

C7027A1064a -40 to + 215 -40 to + 102 24 7.3C7027A1072a -40 to + 215 -40 to + 102 6 1.8

C7027A1023C7027A1031C7207A1080

C7027A1080 b 0 to + 215 - 18 to + 102 6 1.8

a1/2 in. NPT threaded spud connector.blncludes 136733 Heat Block and 390427B Bushing, 1/2 x 3/8in. (12.7 x 9.5 mm) to replace Fireye UV2 sensor.

Page 29: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection Guide81-00-30-12

C7035A MINIPEEPER ULTRAVIOLETFLAME DETECTORCompact flame detector for use withRA890G, R7023C, R4795, R4126, R4127,R4075, R4138, R4150, R4140 and BC7000flame safeguard controls with ultravioletamplifiers.Used on gas, oil, coal, or combination burners. Detectsultraviolet radiation from all flames. Sensing tubing isfield replaceable. Mounting Means: Integral collar for 1in. NPT sighting pipe. Dimensions: 1-1/2 in. (38.1 mm)diameter (mounting collar), 4-1/8 in. (104.8 mm) long.Listed by Underwriters Laboratories Inc., File No.MP268, Guide No. MCCZ; Industrial Risk Insurers (for-merly FIA) approvable; Canadian Standards Associationcertified, File No. LR1620, Guide No. 140-A-2; FactoryMutual approved Report No. 24181.03.

Replacement Parts129808 Flange Gasket.129464M Ultraviolet Sensing Tube [0° F to 250° F

(-18°C to + 121°C)].129464N Ultraviolet Sensing Tube [ – 40° F to + 250° F

(- 40°C to + 121°C)].

ORDER AMBlENT TEMP. RANGE LEAD LENGTHNUMBER °F °C FT M

C7035A1023 0 to + 250 18 to + 121] 6 1.86-40 to + 121-40 to + 250C7035A1031 1.8

-40 to + 250C7035A1056 -40 to + 121 12 3.5

C7035A1080a 0 to + 250 -18 to + 121 6 1.8

a6000 F 6 ft. Ieadwires.

Page 30: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selectbn guide81-00-30-12

C7061A SOLID STATE DYNAMICSELF CHECK ULTRAVIOLET FLAME DETECTOR

Solid state electronic flame detector for use withEC7800 Burner Control family of Flame Safeguardcontrols and amplifier. Senses ultraviolet radiationgenerated by the combustion of gas, oil or other fuels.

Detector may be mounted horizontally or vertically orat any angle in between. The notch and arrow on thefaceplate must be lined up vertically for properoperation of the shutter.

Field replaceable viewing window and ultravioletsensing tube.

Threaded conduit fitting and color-coded leadwiresprovide rapid electrical hookup.

Two detectors can be connected in parallel to reducenuisance shutdowns.

Swivel mount is available as an accessory.

-40° F° (-40° C) rated ultraviolet sensing tube isavailable.

Designed for use with self-checking flame safeguardcontrols such as the R4075 C/D/E, R4138 C/D,R4140, BC7000, R7241, R4343B, R4348 andFSP5075 using the R7061 A plug in amplifier, or withEC7810, EC7820, EC7830, and EC7850 with R7861Aplug in amplifier.

Oscillating shutter interrupts the line of sight of thedetector about 120 times a minute with the R7061Aplug in amplifier to provide self checking. TheR7861A amplifier interrupts the line of sight of thedetector 12 times a minute. Any malfunction in theflame detection system results in a safety shutdown.The coil and shutter assembly is field replaceable.

Housing meets NEMA4 enclosure standards.

Protective heat block built into the mounting flange.

High pressure viewing window (rated for 50 psi(345kPa) magnifying lens, and anti-vibration mountare available accessories.

Page 31: Flame Safeguard Equipment Selection Guide Gas Pressure Switch.pdf · Flame Safeguard Equipment Primary Controls Selection Guide ... torch-ignited pilot or main burner, ... Nonprogramming

Selection guide81-00-30-12

Specifications

ELECTRICAL RATINGS:Voltage and Frequency

The C7061 is powered from the Flame Safeguardunit, which delivers the necessary voltages to oper-ate the tube and shutter through the R7861 Self-Checking Amplifier. The system operates correctlyat a nominal voltage (–15%, +10%), 50/60 Hz.

AMBlENT OPERATING TEMPERATURE RATINGS(Outside the Case)

0°F to +175°F (–18°C to +79°C) with part no.129464M UV Sensing Tube.

–40°F to +175°F (–40°C to +80°C) with part no.129464N UV Sensing Tube.

STORAGE TEMPERATURE RATINGS:–60°F to +175°F (–50°C to +80°C).

HOUSING:Violet, cast-aluminum cover.Mounting flange (with heat block) and faceplate are

separate to provide heat insulation and sealoff.Meets NEMA 4 enclosure requirements (indoor, out-

door protection; rain-tight, dust-tight, hose-directed water).

Optional water jacket available.

PRESSURE RATING OF QUARTZ FOCUSING LENS:20 psi (138 kPa), see Accessories.

MOUNTING:Mounting flange with 3/4 NPT internal threads forattaching to sight pipe.

WIRING CONNECTIONS:NEC Class 1 color-coded leadwire.Length: 8 ft. (2.4m).Threaded Leadwire Opening in Faceplate: 1/2-14

NPSM internal threads for attaching conduit.

WEIGHT: Approximately 2.6 Ibs. (1.2 kg).

APPROVALS:Underwriters Laboratories Inc. Listed.Canadian Standards Association Certified: Master

File LR95329-1.Factory Mutual Approved: 14740.01.Industrial Risk Insurers Acceptable.

REPLACEMENT PARTS:129464M Ultraviolet Sensing Tube.129464N Ultraviolet Sensing Tube; for -40°F (-40°C)

operation.114372 Quartz Viewing Window; rated for 20 psi

(138kPa).114465 Gasket, silicone rubber, for installing viewing

window (three required).120739 Gasket, fiber-neoprene; heat insulation and

sealoff for mounting flange.1909710B Coil and Shutter Assembly.

ACCESSORIES:118369 Bushing, galvanized iron, with 3/4 inch NPT

internal threads on one end, and 1 inch NPTexternal threads on the other end. For adapting adetector with 1 inch NPT internal threads (formounting) to a 3/4 inch sight pipe, or to the pipenipple and tee for connecting an air supply.

118367A Swivel Mount.122748 Quartz Viewing Window, rated for 50 psi

(345 kPa).124204 Quartz Focusing Lens, rated for 20 psi (138

kPa); for increasing the detector-sensed ultra-violet radiation.

120934 Mounting Flange, aluminum, with 3/4 inchNPT internal threads for attaching to sight pipe.

124198 Mounting Flange, aluminum, with 1 inchNPT internal threads for attaching to sight pipe.

123539 Antivibration Mount.190105 Water Jacket

ORDERING INFORMATION:

Model Number Frequency MountingC7061A1012 50-60 3/4” NPTC7061A1038a 50-60 3/4” NPT

aWith 5-pin Brad Harrison Connector Type 41310, Mating Connector Type 41306N or 41307N