Improving Safety Instrumented System Reliability

®

Page 2: fisher fire stop

2 | Improving Safety Instrumented System Reliability

Page 3: fisher fire stop

afety instrumented systems are intended to help protect against therisks posed by hazardous processes.

Processes that involve toxic or highly flammable fluids typically rely uponsafety instrumented systems (SIS) to protect against upsets or failures thatmight threaten worker safety, cause environmental concerns, or damageoperating equipment.

A safety instrumented system typically consists of sensors to monitor theprocess, logic solvers that compare process conditions to predetermined processlimits, and final control elements that shut down or vent the process shouldconditions reach a trip point.

Meant to ProtectSafetyInstrumentedSystems

S

Improving Safety Instrumented System Reliability | 3

Will the Shutdown Valve Work?

All SIS components must work on demand so that the systemoperates as planned.

The operating integrity of the SIS most often dependsupon its final control elements. These valves typicallyremain in one position until called upon to respond. Infact, they may never be instructed to stroke from astandby position, which means they eventually maybecome stuck, unable to operate.

If a shutdown valve fails, the safety instrumented systemmay not be able to take the process to a safe state.

Determining Shutdown Valve Readiness.

Traditional ways of checking valve readiness can createproblems.

The periodic stroke testing of the final control elementgives an indication that the valve will perform whenneeded. Traditional test methods, however, pose severalproblems:

•• The process must be shut down, or the shutdown valve bypassed, to allow a full-stroke test of the final control element. Either approach proves time-consuming and costly.

•• Partial-stroke testing requires a manual device or other method to limit the movement of the shutdown valve. If the device is not removed following a test, the valve’s range of movement may be restricted, making the SIS ineffective should a demand arise.

•• Emergency valves must be taken “off-line” during a stroke test, which makes them unavailable should an event occur.

•• Worker safety becomes a concern since most tests require direct involvement with the SIS on the plant floor.

•• The testing procedure is labor intensive and therefore, costly.

Page 4: fisher fire stop

Automated Partial Stroke Testing: The FIELDVUE® Digital Solution

4 | Improving Safety Instrumented System Reliability

Emerson’s industry-leading Fisher® FIELDVUE® digital valve controllerbrings significant new advantages to performance testing of safetyshutdown valves.

Emerson’s FIELDVUE instruments, with their microprocessor basedcapabilities, provide automated performance monitoring andtesting.

As part of the emergency valve package, the FIELDVUE instrumentenables partial stroke testing while the valve is online.

Importantly, test personnel can remain within the safety of acontrol room or maintenance facility to initiate the test sequence.They can communicate with the FIELDVUE instrument using ahand-held communicator or a personal computer, without havingto go onto the plant floor. Using a LCP100 local control panel(shown below), they can initiate the test locally. The visualindicators and manual controls make it easy for personnel to assessand change the status of the valve.

Diagnostic Data: A Key to Improved SIS Performance.

FIELDVUE instruments help take the guesswork out of valvemaintenance.

Determining when an emergency valve needs to be maintained isoften a guessing game.

The traditional approach to SIS valve maintenance relies upon the fullor partial stroke test to indicate whether or not the valve will operateupon demand. Little to no additional insight is gained about theoverall mechanical condition of the valve.

The FIELDVUE instrument automatically checks the condition ofthe final control element during each partial stroke test. Itevaluates the pneumatic supply, the actuator pressure values, andthe valve position to determine whether or not valve components,including solenoid valves, are in proper working condition.

As the FIELDVUE instrument receives a test command from thelogic solver, it applies a time and date stamp to the partial stroketest and solenoid valve test. This information is saved automaticallywithin the device or a PC workstation, making regulatorycompliance efforts much easier.

The data gathered allows diagnostic interpretation and analysisusing AMS™ ValveLink® software. For instance, a valve signaturetest generated by a FIELDVUE instrument provides insight to valvepacking friction, air path leakage, valve sticking, shaft integrity,stick slip, actuator spring rate, and bench set. Comparing currentdata to previous test values may identify a potential valve failurelong before the valve quits working. Armed with this knowledge,maintenance personnel can schedule repair activities rather thanhaving to react to an unexpected valve failure.

Should a valve become stuck, the FIELDVUE instrument through itsAMS ValveLink software generates an Event Messenger alert.Critical alerts can be sent to personnel via email, pager, or phone.

The LCP100, partnered withthe DVC6000 SIS instrument,initiates partial stroke testsand resets the valve and tripafter an emergency.

Page 5: fisher fire stop

Improving Safety Instrumented System Reliability | 5

Greater Safety at Less Cost

FIELDVUE instruments bring money-saving advantagesto SIS design, implementation, and operation.

Consider the potential time and cost-savings offeredby partial stroke testing:

Lower Cost of Ownership - Unlike full-stroke tests,partial stroke testing does not require a bypassaround the emergency valve, which avoids the costof additional piping and full-size bypass valves.

Automated testing eliminates the expensive,pneumatic panels typically required by manual testprocedures. And maintenance diagnostics help avoidunnecessary and costly valve repair.

Reduced Labor Requirements - Valve testing fromthe control room eliminates the time-consuming andlabor-intensive manual testing of emergency valves.

For instance, manual testing often involves theinstallation and subsequent removal of mechanicalvalve interlocks. Repeated trips onto the plant floorare no longer required to conduct the SISperformance test, thus helping to increase personnelsafety.

Increased System Availability - The simple and securemethod of partial stroke testing allows morefrequent assessment of a valve's ability to move.These tests can be conducted at a time best suited tooperators' schedules. The need to stop the processcompletely for full-stroke testing is minimized,increasing system availability.

To avoid spurious trips, FIELDVUE pneumatic relaysallow instruments to improve loop availability uponloss of instrument signal.

Page 6: fisher fire stop

Proof of Performance

Saudi Aramco facilities use FIELDVUE instruments toenhance SIS performance.

Production and processing operations at Saudi Aramcogas plants and refineries use FIELDVUE instruments oncritical, emergency isolation valves.

Online since early 2000, the FIELDVUE units haveexceeded system operators’ expectations by enablingthe systematic, partial stroke testing of emergencyshutdown valves without impacting production rates.

Partial stroke testing helps operations personneldetermine that shutdown valves within safety systemsare capable of operating should a demand occur. Patrick Flanders, instrument engineer at Saudi Aramco,credits FIELDVUE instruments with bringing a new levelof security to safety instrumented systems.

“Before the FIELDVUE SIS concept evolved, it wasdifficult to functionally test these valves and very difficultto document any meaningful test results,” Flandersexplains. “Now, thanks to the FIELDVUE design, it’s notonly possible to check valves, but we can also do somore safely, at less cost, and with greater efficiency.”

Commenting that FIELDVUE technology is easy to applyin safety applications, Flanders states, “This is oneproduct truly based on a customer’s requirements anddirection for limited valve-travel testing. What was oncea very manual process is now semi-automatic. With theFIELDVUE unit in the SIS loop, valve travel is controlled topredetermined limits, and test data are collected duringboth online partial-stroke tests and during full-stroketests. The device does automate the testing process,greatly simplifying the testing procedures and reducingthe time required of our operators.”

6 | Improving Safety Instrumented System Reliability

FIELDVUE DVC6000 Series digital valvecontroller in SIS solution mounted on aquarter-turn actuator.

Page 7: fisher fire stop

Improving Safety Instrumented System Reliability | 7

Successful product testing by a third-party authorityleads to a rigorous review of components for safetyinstrumented systems.

FIELDVUE DVC6000 SIS instruments have beencertified by TÜV Product Services (Germany) to be inaccordance with IEC61508 for use in SafetyInstrumented Systems up to safety integrity level 3(SIL). By evaluating devices per IEC and ISA standards,the TÜV certification process determines whether aproduct is fit for use in a specified safety application.

TÜV certification is issued along with a reportexplaining how the product was tested and whatapplication criteria must be met for the product toretain its certification. With the report, systemanalysts and designers can better understand how aproduct contributes to meeting the required riskreduction level.

To obtain a copy of the TÜV approval report onFIELDVUE instruments, contact your nearest EmersonProcess Management sales location.

SIL — Explaining the Acronym.

Current standards and guidelines applicable to thedesign of safety instrumented systems areperformance oriented. The standards do notmandate technology, level of redundancy, or testintervals. Rather, they identify “safety integritylevels.”

IEC61511 has been developed as a process sectorimplementation of the international standardIEC61508: “Functional safety of electrical, electronic,programmable electronic safety related systems."

IEC61511 defines four safety integrity levels for safetyinstrumented system design.

The devices that make up a specific SIS design, fromthe input units through the logic solver to the finalcontrol element, determine a SIL. It reflects deviceintegrity, the architecture of the system, devicetesting and diagnostics coverage, and the commonmode failures inherent to the SIS.

Within IEC61511, SIL 1 represents the highestprobability of system failure on demand as shownin the following table. Note that IEC61511suggests that applications requiring a SIL 4function are rare in the processing industries.

Safety Probability of Risk Reduction Integrity Failure on FactorLevel Demand

per Year SIL 4 ≥ 10-5 to < 10-4 100,000 to 10,000SIL 3 ≥ 10-4 to < 10-3 10,000 to 1000SIL 2 ≥ 10-3 to < 10-2 1000 to 100SIL 1 ≥ 10-2 to < 10-1 100 to 10

Sensor to Final Control Element: TheEmerson PlantWeb® Approach to Safety.

Only Emerson takes a smart SIS approach bycontinuously diagnosing the sensors, logic solvers,and final control elements as an entity to monitorthe ability to operate on demand. The key to thisapproach is Emerson’s DeltaV™ SIS system, sensorsfrom Rosemount and Micro Motion divisions, andfinal control elements from Fisher and VADdivisions that are suitable for use up to SIL 1-3applications. It's joined by integrated, easy-to-useconfiguration software and embedded digitalcommunications for safety applications of any size.

The Emerson approach provides improved:• Risk reduction• Reduced project capital requirements• Reduced maintenance costs • Easier regulatory compliance

When it comes to safety applications such asemergency shutdown, burner management, andfire and gas systems, Emerson's trainedprofessional safety personnel and global projectservices organizations have the knowledge toperform process hazard analyses and riskassessment. They also provide safety instrumentedsystem design, implementation andcommissioning. Within the framework ofPlantWeb SIS Solutions, Emerson providesintegrated, reliable, easy to use safetyinstrumented system for a lower lifecycle cost.

TÜV Certification

Page 8: fisher fire stop

NORTH AMERICAEmerson Process ManagementMarshalltown, Iowa 50158 USAT 1 (641) 754-3011F 1 (641) 754-2830www.EmersonProcess.com/Fisher

ASIA PACIFICEmerson Process Management Singapore 128461 SingaporeT +(65) 6777 8211F +(65) 6777 0947www.EmersonProcess.com/Fisher

LATIN AMERICAEmerson Process ManagementSorocaba, Sao Paulo 18087 BrazilT +(55)(15)238-3788F +(55)(15)228-3300www.EmersonProcess.com/Fisher

EUROPEEmerson Process ManagementCernay 68700 FranceT +(33) (0)3 89 37 64 00F +(33) (0)3 89 37 65 18www.EmersonProcess.com/Fisher

MIDDLE EAST & AFRICAEmerson FZEDubai, United Arab EmiratesT +971 4 883 5235F +971 4 883 5312www.EmersonProcess.com/Fisher

D350866X012 / D350866X412 / MQ53-CD119 / Printed in U.S.A. / 4M AQ, 1M A4 / 08-07

This mark indicates a corecomponent of Emerson’sPlantWeb® digital plantarchitecture.

© Fisher Controls International LLC 2007 All Rights Reserved.

Fisher, FIELDVUE, ValveLink, and PlantWeb are marks owned by one of the companies in the Emerson Process Management, LLLP business division of EmersonElectric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are theproperty of their respective owners.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy they are notto be construed as warranties or guarantees, expressed or implied, regarding the products or services described herein or their use or applicability. All salesare governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications ofsuch products at any time without notice. Neither Emerson, Emerson Process Management, Fisher, nor any of their affiliated entities assumesresponsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solelywith the purchaser and end-user.