FCT Not Determined

Embed Size (px)

Citation preview

  • 8/9/2019 FCT Not Determined

    1/53

    2014 ETAP

    Arc FlashFault Clearing Time Determination

    6/17/2014

    1

  • 8/9/2019 FCT Not Determined

    2/53

    2014 ETAP2

    S.NO CONTENTS

    1. FCT not determined message

    2. Cause1 : No Protective device

    3. Solution1

    4. Cause2 : Interlocks are missing

    5. Solution2

    6. Cause3 : Missing Library information

    7. Solution3

    8. Cause4: Magnitude of arc current is low

    9. Solution4

    10. Cause5: Bus Levels and Source current contribution.

    11. Solution5

    12. Symptoms and diagnosis

    13. Tools and debugging techniques from ETAP

  • 8/9/2019 FCT Not Determined

    3/53

    2014 ETAP

    Definitions

    FCTFault Clearing Time in seconds or cycles LVCB Low Voltage Circuit Breaker

    HVCBHigh Voltage Circuit Breaker

    IbfBolted fault current

    IaArc current

    PDProtective device

    OCROvercurrent Relay

    TCCTime Current Characteristics

    CTCurrent Transformer

    PTPotential Transformer

    SQOPSequence of Operation

    3

  • 8/9/2019 FCT Not Determined

    4/53

    2014 ETAP

    FCT not determined message

    4

    ETAP eliminates the manual work related to determining the

    protective device(s) that clear arc faults and FCT. In some

    situations, the program provides a message that reads: FCT

    not determined.This message indicates that ETAP did not find

    source protective device(s) to de-energize every singleenergizing branch.

    This article summarizes the causes of why ETAP will display this

    message and how to troubleshoot the system to pinpoint the

    reason(s).

    NOTE: The problem can be caused by a single item or

    combination of any of the issues described in this document

  • 8/9/2019 FCT Not Determined

    5/53

    2014 ETAP

    Causes for FCT not determined

    FCT NotDetermined

    1. No Protectivedevice in

    energizing path

    2. Interlocks are

    missing

    3. Missing Libraryinformation

    4. Magnitude of

    arc current is toolow

    5. Bus levels awayto find Source PD

    and Multiplesource

    contribution levels

    5

  • 8/9/2019 FCT Not Determined

    6/53

    2014 ETAP

    CAUSE1NO PROTECTIVE DEVICE IN ENERGIZING PATH

    6

  • 8/9/2019 FCT Not Determined

    7/53 2014 ETAP

    Cause1

    If there is no protective device to de-energize the fault, the

    message is displayed.

    In this example , the utility source is directly connected to

    the MainBuswithout any protective device.

    7

  • 8/9/2019 FCT Not Determined

    8/53 2014 ETAP

    Cause - 1

    The message will appear If the option User-defined from

    Bus Editor is enabled from the study case AF FCT page (as

    shown below), and the bus user-defined FCT value is set tozero.

    In the images below, the User defined FCT section has no

    values and the study case shows FCT is based on User-

    defined from bus editor

    8

  • 8/9/2019 FCT Not Determined

    9/53 2014 ETAP

    SOLUTION1

    ADDING PROTECTIVE DEVICE IN THE ENERGIZING

    PATH

    9

  • 8/9/2019 FCT Not Determined

    10/53 2014 ETAP

    Solution -1

    The following protective devices are available in ETAP that

    can be added in the energizing path to trip the circuit in the

    event of a fault

    1. Disconnect Switch interlocked to a Relay

    2. Fuse3. LVCB with self trip unit or interlocked to a Relay

    4. HVCB interlocked to a Relay

    5. Contactor interlocked to a Relay

    6. Overload Heater & In-Line Overload Relay7. Recloser

    10

  • 8/9/2019 FCT Not Determined

    11/53 2014 ETAP

    Solution -1

    In this case, CB29 (HVCB) is introduced between Utility and

    Main Bus in order to de-energize the circuit in the event of afault at the bus, with FCT as 0.236 seconds, which includes the

    relay and breaker trip time.

    11

    Note that the message FCT Not Determined will still be

    displayed for a arc fault on the line-side (source-side) of the

    newly added protective device.

  • 8/9/2019 FCT Not Determined

    12/53 2014 ETAP

    CAUSE2

    INTERLOCKS ARE MISSING

    12

  • 8/9/2019 FCT Not Determined

    13/53 2014 ETAP

    Cause -2

    Protection schemes with relay devices require an interlock

    between the relay and the protective device.

    ETAP will not determine the clearing time if the interlock is

    missing since the overall fault clearing time is the sum of the

    PD opening time plus the relay trip time.

    13

  • 8/9/2019 FCT Not Determined

    14/53 2014 ETAP

    SOLUTION2

    DEFINE INTERLOCKS

    14

  • 8/9/2019 FCT Not Determined

    15/53 2014 ETAP

    Solution -2

    Interlocks are defined in the Output page of the Relay editor.

    In this example, the OCR 1 (Overcurrent Relay) is interlockedwith CB29 , such that on the event of the fault, the relay

    sends the trip signal to Open the circuit breaker.

    The following interlocks are available for a relay

    Interlock to HVCB, LVCB, Switch, Contactor.

    15

  • 8/9/2019 FCT Not Determined

    16/53 2014 ETAP

    CAUSE3MISSING LIBRARY INFORMATION

    16

  • 8/9/2019 FCT Not Determined

    17/53 2014 ETAP

    Cause -3

    If the protective device from the library is missing then the

    program cannot find the FCT. See image below. This applies to all protective devices with curves in the library

    such as LVCB, Fuses, Relays, Reclosers, etc .

    17

  • 8/9/2019 FCT Not Determined

    18/53 2014 ETAP

    SOLUTION3

    SELECT LIBRARIES

    18

  • 8/9/2019 FCT Not Determined

    19/53 2014 ETAP

    Solution -3

    Select the model from the library from the OCRpage of the

    Relay editor to provide TCC information for the determinationof trip time.

    19

  • 8/9/2019 FCT Not Determined

    20/53 2014 ETAP

    Solution -3

    Check that the relays, protective devices, current transformers

    that are involved in fault clearing have data defined from thelibrary.

    RelaysDefinition of CT and Breaking Device

    1. TCC curves for the trip signal

    2. CTTurns Ratios and Burden3. LVCBTCC curves from the Trip Unit

    4. Recloser - TCC curves from the Controller

    5. FuserMelting curves from the manufacturer rating

    6. Overload Heater - TCC curves from the Heating Unit

    7. In-line overloadTCC curves from the Thermal library

    20

  • 8/9/2019 FCT Not Determined

    21/53 2014 ETAP

    CAUSE4MAGNITUDE OF ARC CURRENT IS TOO LOW

    21

  • 8/9/2019 FCT Not Determined

    22/53 2014 ETAP

    Cause-4

    The arc current Iais typically less than the available bolted

    short circuit current; especially in low voltage systems

    (Typically less than 1kV).

    ETAP displays FCTnot determined if the arc current is too

    low such that it falls below the long-time pick up value of the

    trip unit.

    In this example, when Bus1 is faulted, the arc current is too

    low and it lies on the left-hand-side region of the Fuse TCC

    below any possible pickup time

    22

  • 8/9/2019 FCT Not Determined

    23/53

    2014 ETAP

    The magnitude of arc

    current is 10.87kA at

    0.48 kV and does not

    intersect with the

    available TCC curve inorder to clear the

    fault.

    Cause4

    23

  • 8/9/2019 FCT Not Determined

    24/53

    2014 ETAP

    SOLUTION4

    CONSIDER ALTERNATIVE PROTECTIVE DEVICE SIZESOR INCIDENT ENERGY MITIGATION SCHEMES

    24

  • 8/9/2019 FCT Not Determined

    25/53

    2014 ETAP

    Solution4

    Make sure that the protective device selected is capable of

    tripping under the arc fault current conditions. If the fault clearing time of the selected protective device is

    high, a message which indicates high incident energy value

    may appear on the one-line diagram.

    25

  • 8/9/2019 FCT Not Determined

    26/53

    2014 ETAP

    CAUSE5

    BUS LEVELS AWAY TO FIND SOURCE PD ANDMULTIPLE SOURCE CONTRIBUTION LEVELS

    26

  • 8/9/2019 FCT Not Determined

    27/53

    2014 ETAP

    Cause5

    The search for source protective devices has some definable

    capability limits. This section describes how those limits areapplied.

    The main reason for these limits is to optimize the

    calculation time by reducing memory consumption byexcluding unnecessary data

    Bus Levels Away to Find Source PD - This limit indicates the

    number of bus levels away from the faulted location thatETAP will search to find the source PD. The source PD is then

    used to determine the FCT.

    27

    C 5

  • 8/9/2019 FCT Not Determined

    28/53

    2014 ETAP

    The default value for this entry is ten(10). The maximum level is

    fifty (50). It is recommended that this entry be left as default,

    unless the source PD is located more than 10 levels away.

    The circled PDs has to be within the Bus levels away to Find

    source PD , Otherwise, ETAP cannot determine the FCT

    Note that protective devices which are considered as Load PDs

    are not considered for determining the bus FCT as they cannot

    isolate the fault at the bus as mentioned in the image below.

    Cause5

    28

    C 5

  • 8/9/2019 FCT Not Determined

    29/53

    2014 ETAP29

    Cause5

  • 8/9/2019 FCT Not Determined

    30/53

    2014 ETAP

    Cause5

    Multiple Source Contribution - This value indicates the

    number of multiple sources contribution levels to beconsidered. A level is encountered every time two sources

    mesh upstream from the fault location.

    If the corresponding sources are not seen by the limit that isset up, the program still displays the message. The default for

    multiple source level search is two (2) as can be seen in the

    following image.

    However, there may be some systems in which the source PDs

    are located further away in higher levels of multiple source

    contributions

    30

    Cause 5

  • 8/9/2019 FCT Not Determined

    31/53

    2014 ETAP

    Cause5

    31

    Cause 5

  • 8/9/2019 FCT Not Determined

    32/53

    2014 ETAP

    Cause5

    32

  • 8/9/2019 FCT Not Determined

    33/53

    2014 ETAP

    SOLUTION -5OPTIONS (PREFERENCES)

    33

    Solution 5

  • 8/9/2019 FCT Not Determined

    34/53

    2014 ETAP

    Solution -5

    The Tools Options(Preferences) Arc Flash Section has the

    following two entries that can help to determine the FCT for

    Cause5.

    The number of levels can be changed by modifying the entry

    in Tools/Options (Preferences) Bus Levels Away to Find

    Source PD = 10 (default).

    Multiple Source Contribution Levels : The searchable area of

    the program is limited by the number of meshed source fault

    current contributions and the number of bus levels away.

    The search area can be increased by modifying the following

    entry under Tools\Options (Preferences) section: Multiple

    Source contribution levels = 2 (default) 34

    Solution 5

  • 8/9/2019 FCT Not Determined

    35/53

    2014 ETAP

    Solution -5

    Using a very high number for both above options can cause

    performance issues with arc flash calculations.

    The Highest level of meshed source contribution is level 4 .

    Multiple utility sources energize this location.

    In a real system, the individual sources could be wind

    turbines, PV arrays or synchronous generators.

    Whatever the case may be, every time a source contributionis meshed, the program will require a higher level number as

    shown in the image (which requires Level 5)

    35

    Solution 5

  • 8/9/2019 FCT Not Determined

    36/53

    2014 ETAP36

    Solution -5

  • 8/9/2019 FCT Not Determined

    37/53

    2014 ETAP

    SYMPTOMS AND DIAGNOSIS

    37

  • 8/9/2019 FCT Not Determined

    38/53

    2014 ETAP

    Symptoms

    Symptoms

    1. Main PDIsolation

    2. DecayMethod

    3.SinglePhase

    Breaker

    4. Back feedfrom Tie-breaker

    38

    Main PD Isolation

  • 8/9/2019 FCT Not Determined

    39/53

    2014 ETAP

    Main PD Isolation

    Symptom

    The program reports FCT Not Determined for a

    particular bus, yet the main protective device has beenproperly configured with libraries, interlocks, etc.

    The main PD may not be properly isolated from the main bus

    or individual compartments (i.e. the line side of the main PD is

    exposed or there is chance the arc fault will expand into thissection. If the upstream PD is not properly configured, the FCT

    may not be determined.

    Note 1: This option is applicable only for systems rated 15kV

    or less. Note 2: The main PD isolation option can be removed by un-

    checking it from the Study Case editor -> AF FCT tab.

    The following link gives more detailed analysis for the same.https://helpdesk.etap.com/cgi-in/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Default

    39

    Decay Method

    https://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Default
  • 8/9/2019 FCT Not Determined

    40/53

    2014 ETAP

    Decay Method

    Symptom

    -FCT is determined using either the 1/2 Cycle or 1.5-4 cyclemethods

    -FCT is no longer determined when using the decay method

    The FCT for decay method is obtained by integrating thecurrents from three different stages (subtransient, transient

    and steady-state). The integration using IEEE Std C37.2

    equation as shown.

    40

    Decay Method

  • 8/9/2019 FCT Not Determined

    41/53

    2014 ETAP

    Decay Method

    In this example, The decay method is used on Bus20

    The steady state arc current falls below the relay long

    time pickup setting and the magnitude and duration of

    subtransient and transient currents were not enough to

    cause the relay to trip 41

    Decay Method

  • 8/9/2019 FCT Not Determined

    42/53

    2014 ETAP

    To correct this situation, protective device settings adjustments

    which cause relay operation need to be implemented 42

    Decay Method

  • 8/9/2019 FCT Not Determined

    43/53

    2014 ETAP

    Arc Flash 1-Phase

    Symptom

    Single-phase system has upstream

    protective device in 3-phase region

    which is outside the searchable area

    when the fault occurs in the 1-phase

    system

    For 1-phase & panel sub-systems, the

    program cannot search the source PD

    that is in the three phase system (i.e. it

    only searches all 1-phase PDs feeding

    the system The image shows Fuse 1 cannot de-

    energize the Bus2 as it is single phase.

    43

    Arc Flash Single Phase

  • 8/9/2019 FCT Not Determined

    44/53

    2014 ETAP

    Arc Flash Single Phase

    Adding a source protective device inthe single phase system as shown in

    the image (Fuse2) will help to de-

    energize the faulted bus and determine

    the fault clearing time.

    44

  • 8/9/2019 FCT Not Determined

    45/53

    2014 ETAP

    Back Feed from Tie-Breaker

    Symptom

    - All source PDs appear to be tripping, but the program failsto find the FCT

    In case of Meshed or Loop system with tie-PDs involved, there

    is a possibility of small arc current flowing back through the

    looped path. The magnitude of this back-feed arcing currentmay not be enough to trip feeder relay

    ETAP requires that all sources of current be de-energized to

    determine the final FCT (regardless of how small of a

    contribution they make to the fault location). This is aconservative method since it is not known exactly at what

    point an arc fault will self extinguish as multiple sources de-

    energize at different times.

    45

    Back Feed from Tie- Breaker

  • 8/9/2019 FCT Not Determined

    46/53

    2014 ETAP

    Back Feed from Tie Breaker

    46

    In this example , The upstream breakers clear the fault butthere is a small arc current that is back fed from the source

    which prevents the fault from being completely de-energized

    Small Magnitude of Ia

    Back Feed from Tie- Breaker

  • 8/9/2019 FCT Not Determined

    47/53

    2014 ETAP

    Back Feed from Tie Breaker

    If the relay is set to pick up this small magnitude of Ia that

    is back fed, then the total fault clearing time can be

    determined.

    47

  • 8/9/2019 FCT Not Determined

    48/53

    2014 ETAP

    TOOLS AND DEBUGGING TECHNIQUES FROM ETAP

    48

  • 8/9/2019 FCT Not Determined

    49/53

    2014 ETAP

    Faulting only one bus

    49

    Faulting only one bus is a great way to troubleshoot the FCTnot

    determinedcondition.

    It marks the source protective devices by showing the arc

    current next to them. This allows you to graphically see which

    source PDs lie on the energizing branches.

    Only source PDs are marked with current flows (even though all

    the contributions are considered) as shown in the image below.

    Tools

  • 8/9/2019 FCT Not Determined

    50/53

    2014 ETAP

    Tools

    50

    Using the AF SQOP Tool

  • 8/9/2019 FCT Not Determined

    51/53

    2014 ETAP

    Using the AF SQOP Tool

    51

    The SQOP tool indicates two very important items for

    FCT not determined troubleshooting:

    1) It lists only the source PDs which energize the fault

    location

    2) It also lists the source PDs which did not trip. These

    are the PDs which are causing the FCT not Determined

    condition

    Using the AF SQOP Tool

  • 8/9/2019 FCT Not Determined

    52/53

    2014 ETAP52

    Us g t e SQO oo

    Using the AF SQOP Tool

  • 8/9/2019 FCT Not Determined

    53/53

    g Q