Upload
charles-moncy
View
1.008
Download
61
Embed Size (px)
Citation preview
8/9/2019 FCT Not Determined
1/53
2014 ETAP
Arc FlashFault Clearing Time Determination
6/17/2014
1
8/9/2019 FCT Not Determined
2/53
2014 ETAP2
S.NO CONTENTS
1. FCT not determined message
2. Cause1 : No Protective device
3. Solution1
4. Cause2 : Interlocks are missing
5. Solution2
6. Cause3 : Missing Library information
7. Solution3
8. Cause4: Magnitude of arc current is low
9. Solution4
10. Cause5: Bus Levels and Source current contribution.
11. Solution5
12. Symptoms and diagnosis
13. Tools and debugging techniques from ETAP
8/9/2019 FCT Not Determined
3/53
2014 ETAP
Definitions
FCTFault Clearing Time in seconds or cycles LVCB Low Voltage Circuit Breaker
HVCBHigh Voltage Circuit Breaker
IbfBolted fault current
IaArc current
PDProtective device
OCROvercurrent Relay
TCCTime Current Characteristics
CTCurrent Transformer
PTPotential Transformer
SQOPSequence of Operation
3
8/9/2019 FCT Not Determined
4/53
2014 ETAP
FCT not determined message
4
ETAP eliminates the manual work related to determining the
protective device(s) that clear arc faults and FCT. In some
situations, the program provides a message that reads: FCT
not determined.This message indicates that ETAP did not find
source protective device(s) to de-energize every singleenergizing branch.
This article summarizes the causes of why ETAP will display this
message and how to troubleshoot the system to pinpoint the
reason(s).
NOTE: The problem can be caused by a single item or
combination of any of the issues described in this document
8/9/2019 FCT Not Determined
5/53
2014 ETAP
Causes for FCT not determined
FCT NotDetermined
1. No Protectivedevice in
energizing path
2. Interlocks are
missing
3. Missing Libraryinformation
4. Magnitude of
arc current is toolow
5. Bus levels awayto find Source PD
and Multiplesource
contribution levels
5
8/9/2019 FCT Not Determined
6/53
2014 ETAP
CAUSE1NO PROTECTIVE DEVICE IN ENERGIZING PATH
6
8/9/2019 FCT Not Determined
7/53 2014 ETAP
Cause1
If there is no protective device to de-energize the fault, the
message is displayed.
In this example , the utility source is directly connected to
the MainBuswithout any protective device.
7
8/9/2019 FCT Not Determined
8/53 2014 ETAP
Cause - 1
The message will appear If the option User-defined from
Bus Editor is enabled from the study case AF FCT page (as
shown below), and the bus user-defined FCT value is set tozero.
In the images below, the User defined FCT section has no
values and the study case shows FCT is based on User-
defined from bus editor
8
8/9/2019 FCT Not Determined
9/53 2014 ETAP
SOLUTION1
ADDING PROTECTIVE DEVICE IN THE ENERGIZING
PATH
9
8/9/2019 FCT Not Determined
10/53 2014 ETAP
Solution -1
The following protective devices are available in ETAP that
can be added in the energizing path to trip the circuit in the
event of a fault
1. Disconnect Switch interlocked to a Relay
2. Fuse3. LVCB with self trip unit or interlocked to a Relay
4. HVCB interlocked to a Relay
5. Contactor interlocked to a Relay
6. Overload Heater & In-Line Overload Relay7. Recloser
10
8/9/2019 FCT Not Determined
11/53 2014 ETAP
Solution -1
In this case, CB29 (HVCB) is introduced between Utility and
Main Bus in order to de-energize the circuit in the event of afault at the bus, with FCT as 0.236 seconds, which includes the
relay and breaker trip time.
11
Note that the message FCT Not Determined will still be
displayed for a arc fault on the line-side (source-side) of the
newly added protective device.
8/9/2019 FCT Not Determined
12/53 2014 ETAP
CAUSE2
INTERLOCKS ARE MISSING
12
8/9/2019 FCT Not Determined
13/53 2014 ETAP
Cause -2
Protection schemes with relay devices require an interlock
between the relay and the protective device.
ETAP will not determine the clearing time if the interlock is
missing since the overall fault clearing time is the sum of the
PD opening time plus the relay trip time.
13
8/9/2019 FCT Not Determined
14/53 2014 ETAP
SOLUTION2
DEFINE INTERLOCKS
14
8/9/2019 FCT Not Determined
15/53 2014 ETAP
Solution -2
Interlocks are defined in the Output page of the Relay editor.
In this example, the OCR 1 (Overcurrent Relay) is interlockedwith CB29 , such that on the event of the fault, the relay
sends the trip signal to Open the circuit breaker.
The following interlocks are available for a relay
Interlock to HVCB, LVCB, Switch, Contactor.
15
8/9/2019 FCT Not Determined
16/53 2014 ETAP
CAUSE3MISSING LIBRARY INFORMATION
16
8/9/2019 FCT Not Determined
17/53 2014 ETAP
Cause -3
If the protective device from the library is missing then the
program cannot find the FCT. See image below. This applies to all protective devices with curves in the library
such as LVCB, Fuses, Relays, Reclosers, etc .
17
8/9/2019 FCT Not Determined
18/53 2014 ETAP
SOLUTION3
SELECT LIBRARIES
18
8/9/2019 FCT Not Determined
19/53 2014 ETAP
Solution -3
Select the model from the library from the OCRpage of the
Relay editor to provide TCC information for the determinationof trip time.
19
8/9/2019 FCT Not Determined
20/53 2014 ETAP
Solution -3
Check that the relays, protective devices, current transformers
that are involved in fault clearing have data defined from thelibrary.
RelaysDefinition of CT and Breaking Device
1. TCC curves for the trip signal
2. CTTurns Ratios and Burden3. LVCBTCC curves from the Trip Unit
4. Recloser - TCC curves from the Controller
5. FuserMelting curves from the manufacturer rating
6. Overload Heater - TCC curves from the Heating Unit
7. In-line overloadTCC curves from the Thermal library
20
8/9/2019 FCT Not Determined
21/53 2014 ETAP
CAUSE4MAGNITUDE OF ARC CURRENT IS TOO LOW
21
8/9/2019 FCT Not Determined
22/53 2014 ETAP
Cause-4
The arc current Iais typically less than the available bolted
short circuit current; especially in low voltage systems
(Typically less than 1kV).
ETAP displays FCTnot determined if the arc current is too
low such that it falls below the long-time pick up value of the
trip unit.
In this example, when Bus1 is faulted, the arc current is too
low and it lies on the left-hand-side region of the Fuse TCC
below any possible pickup time
22
8/9/2019 FCT Not Determined
23/53
2014 ETAP
The magnitude of arc
current is 10.87kA at
0.48 kV and does not
intersect with the
available TCC curve inorder to clear the
fault.
Cause4
23
8/9/2019 FCT Not Determined
24/53
2014 ETAP
SOLUTION4
CONSIDER ALTERNATIVE PROTECTIVE DEVICE SIZESOR INCIDENT ENERGY MITIGATION SCHEMES
24
8/9/2019 FCT Not Determined
25/53
2014 ETAP
Solution4
Make sure that the protective device selected is capable of
tripping under the arc fault current conditions. If the fault clearing time of the selected protective device is
high, a message which indicates high incident energy value
may appear on the one-line diagram.
25
8/9/2019 FCT Not Determined
26/53
2014 ETAP
CAUSE5
BUS LEVELS AWAY TO FIND SOURCE PD ANDMULTIPLE SOURCE CONTRIBUTION LEVELS
26
8/9/2019 FCT Not Determined
27/53
2014 ETAP
Cause5
The search for source protective devices has some definable
capability limits. This section describes how those limits areapplied.
The main reason for these limits is to optimize the
calculation time by reducing memory consumption byexcluding unnecessary data
Bus Levels Away to Find Source PD - This limit indicates the
number of bus levels away from the faulted location thatETAP will search to find the source PD. The source PD is then
used to determine the FCT.
27
C 5
8/9/2019 FCT Not Determined
28/53
2014 ETAP
The default value for this entry is ten(10). The maximum level is
fifty (50). It is recommended that this entry be left as default,
unless the source PD is located more than 10 levels away.
The circled PDs has to be within the Bus levels away to Find
source PD , Otherwise, ETAP cannot determine the FCT
Note that protective devices which are considered as Load PDs
are not considered for determining the bus FCT as they cannot
isolate the fault at the bus as mentioned in the image below.
Cause5
28
C 5
8/9/2019 FCT Not Determined
29/53
2014 ETAP29
Cause5
8/9/2019 FCT Not Determined
30/53
2014 ETAP
Cause5
Multiple Source Contribution - This value indicates the
number of multiple sources contribution levels to beconsidered. A level is encountered every time two sources
mesh upstream from the fault location.
If the corresponding sources are not seen by the limit that isset up, the program still displays the message. The default for
multiple source level search is two (2) as can be seen in the
following image.
However, there may be some systems in which the source PDs
are located further away in higher levels of multiple source
contributions
30
Cause 5
8/9/2019 FCT Not Determined
31/53
2014 ETAP
Cause5
31
Cause 5
8/9/2019 FCT Not Determined
32/53
2014 ETAP
Cause5
32
8/9/2019 FCT Not Determined
33/53
2014 ETAP
SOLUTION -5OPTIONS (PREFERENCES)
33
Solution 5
8/9/2019 FCT Not Determined
34/53
2014 ETAP
Solution -5
The Tools Options(Preferences) Arc Flash Section has the
following two entries that can help to determine the FCT for
Cause5.
The number of levels can be changed by modifying the entry
in Tools/Options (Preferences) Bus Levels Away to Find
Source PD = 10 (default).
Multiple Source Contribution Levels : The searchable area of
the program is limited by the number of meshed source fault
current contributions and the number of bus levels away.
The search area can be increased by modifying the following
entry under Tools\Options (Preferences) section: Multiple
Source contribution levels = 2 (default) 34
Solution 5
8/9/2019 FCT Not Determined
35/53
2014 ETAP
Solution -5
Using a very high number for both above options can cause
performance issues with arc flash calculations.
The Highest level of meshed source contribution is level 4 .
Multiple utility sources energize this location.
In a real system, the individual sources could be wind
turbines, PV arrays or synchronous generators.
Whatever the case may be, every time a source contributionis meshed, the program will require a higher level number as
shown in the image (which requires Level 5)
35
Solution 5
8/9/2019 FCT Not Determined
36/53
2014 ETAP36
Solution -5
8/9/2019 FCT Not Determined
37/53
2014 ETAP
SYMPTOMS AND DIAGNOSIS
37
8/9/2019 FCT Not Determined
38/53
2014 ETAP
Symptoms
Symptoms
1. Main PDIsolation
2. DecayMethod
3.SinglePhase
Breaker
4. Back feedfrom Tie-breaker
38
Main PD Isolation
8/9/2019 FCT Not Determined
39/53
2014 ETAP
Main PD Isolation
Symptom
The program reports FCT Not Determined for a
particular bus, yet the main protective device has beenproperly configured with libraries, interlocks, etc.
The main PD may not be properly isolated from the main bus
or individual compartments (i.e. the line side of the main PD is
exposed or there is chance the arc fault will expand into thissection. If the upstream PD is not properly configured, the FCT
may not be determined.
Note 1: This option is applicable only for systems rated 15kV
or less. Note 2: The main PD isolation option can be removed by un-
checking it from the Study Case editor -> AF FCT tab.
The following link gives more detailed analysis for the same.https://helpdesk.etap.com/cgi-in/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Default
39
Decay Method
https://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Defaulthttps://helpdesk.etap.com/cgi-bin/wonderdesk.cgi?do=faq_view_record&faq=1&view_detail=1&faq_id=490&queue=Default8/9/2019 FCT Not Determined
40/53
2014 ETAP
Decay Method
Symptom
-FCT is determined using either the 1/2 Cycle or 1.5-4 cyclemethods
-FCT is no longer determined when using the decay method
The FCT for decay method is obtained by integrating thecurrents from three different stages (subtransient, transient
and steady-state). The integration using IEEE Std C37.2
equation as shown.
40
Decay Method
8/9/2019 FCT Not Determined
41/53
2014 ETAP
Decay Method
In this example, The decay method is used on Bus20
The steady state arc current falls below the relay long
time pickup setting and the magnitude and duration of
subtransient and transient currents were not enough to
cause the relay to trip 41
Decay Method
8/9/2019 FCT Not Determined
42/53
2014 ETAP
To correct this situation, protective device settings adjustments
which cause relay operation need to be implemented 42
Decay Method
8/9/2019 FCT Not Determined
43/53
2014 ETAP
Arc Flash 1-Phase
Symptom
Single-phase system has upstream
protective device in 3-phase region
which is outside the searchable area
when the fault occurs in the 1-phase
system
For 1-phase & panel sub-systems, the
program cannot search the source PD
that is in the three phase system (i.e. it
only searches all 1-phase PDs feeding
the system The image shows Fuse 1 cannot de-
energize the Bus2 as it is single phase.
43
Arc Flash Single Phase
8/9/2019 FCT Not Determined
44/53
2014 ETAP
Arc Flash Single Phase
Adding a source protective device inthe single phase system as shown in
the image (Fuse2) will help to de-
energize the faulted bus and determine
the fault clearing time.
44
8/9/2019 FCT Not Determined
45/53
2014 ETAP
Back Feed from Tie-Breaker
Symptom
- All source PDs appear to be tripping, but the program failsto find the FCT
In case of Meshed or Loop system with tie-PDs involved, there
is a possibility of small arc current flowing back through the
looped path. The magnitude of this back-feed arcing currentmay not be enough to trip feeder relay
ETAP requires that all sources of current be de-energized to
determine the final FCT (regardless of how small of a
contribution they make to the fault location). This is aconservative method since it is not known exactly at what
point an arc fault will self extinguish as multiple sources de-
energize at different times.
45
Back Feed from Tie- Breaker
8/9/2019 FCT Not Determined
46/53
2014 ETAP
Back Feed from Tie Breaker
46
In this example , The upstream breakers clear the fault butthere is a small arc current that is back fed from the source
which prevents the fault from being completely de-energized
Small Magnitude of Ia
Back Feed from Tie- Breaker
8/9/2019 FCT Not Determined
47/53
2014 ETAP
Back Feed from Tie Breaker
If the relay is set to pick up this small magnitude of Ia that
is back fed, then the total fault clearing time can be
determined.
47
8/9/2019 FCT Not Determined
48/53
2014 ETAP
TOOLS AND DEBUGGING TECHNIQUES FROM ETAP
48
8/9/2019 FCT Not Determined
49/53
2014 ETAP
Faulting only one bus
49
Faulting only one bus is a great way to troubleshoot the FCTnot
determinedcondition.
It marks the source protective devices by showing the arc
current next to them. This allows you to graphically see which
source PDs lie on the energizing branches.
Only source PDs are marked with current flows (even though all
the contributions are considered) as shown in the image below.
Tools
8/9/2019 FCT Not Determined
50/53
2014 ETAP
Tools
50
Using the AF SQOP Tool
8/9/2019 FCT Not Determined
51/53
2014 ETAP
Using the AF SQOP Tool
51
The SQOP tool indicates two very important items for
FCT not determined troubleshooting:
1) It lists only the source PDs which energize the fault
location
2) It also lists the source PDs which did not trip. These
are the PDs which are causing the FCT not Determined
condition
Using the AF SQOP Tool
8/9/2019 FCT Not Determined
52/53
2014 ETAP52
Us g t e SQO oo
Using the AF SQOP Tool
8/9/2019 FCT Not Determined
53/53
g Q