Fans Static Head Calculation Sheet

Embed Size (px)

Citation preview

  • 7/27/2019 Fans Static Head Calculation Sheet

    1/1

    PROJECT: SITE : RIYADH Date : 5/5/2009

    UNIT.NO. : EF-05 BUILDING : 1st, 2nd & 3rd FLR Revision : 0

    GENERAL DATA

    DUCT MATERIAL : G. I. Sheet

    ROUGHNESS COEF. : 0.93

    ALTITUDE : 611 Meters

    ALTITUDE COEF. : 0.935

    AIR DENSITY : 1.09 Kg/m3

    DUCTS PRESSURE LOSSES BOARD

    SECTION 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TOTAL

    FLOW CFM 980 980 980.0 490 490 390 200

    FLOW M3/H 1666 1666 1666 833 833 663 340

    LENGTH M 1.00 1.50 4.15 4.15 7.10 3.40 4.10 25.4 m

    DIAM. mm 382.61 382.61 382.61 299.07 299.07 244.06 218.63

    DIAM. EQUIV. 382.61 382.61 382.61 299.07 299.07 244.06 218.63

    WIDTH mm 350 350 350 250 250 250 200

    HEIGHT mm 350 350 350 300 300 200 200

    AREA M2 0.11 0.11 0.11 0.07 0.07 0.05 0.04

    VELOCITY M/S 4.03 4.03 4.03 3.29 3.29 3.94 2.52

    PD per Meter Pa 0.53 0.53 0.53 0.50 0.50 0.89 0.45

    PD x LENGTHPa 0.53 0.80 2.22 2.08 3.56 3.02 1.84 14.06 P

    Co 1 2 3 4 5 6 7 8 9 10 11 12 13 14 TOTAL

    ELBOW 30 0.07

    ELBOW 45 0.09

    ELBOW 90 0.15 1 2 1 1

    TEE 45 0.3

    TEE 90 1

    END TEE 1.5

    BRANCH TEE 0.05 1 1 1

    TRANSITION 0.22

    CONTRACTION 0.05

    WIRE MESH 0.04

    TOTAL Co 0.15 0.05 0.05 0.05 0.30 0.15 0.15 0.90

    DUCTS PD Pa 1.32 0.44 0.44 0.30 1.77 1.27 0.52 6.06 P

    PRESSURE DROP Pa 1.86 1.24 2.66 2.38 5.33 4.29 2.36 20.12 P

    SPECIAL FITTING PRESSURE DROPS0.70 W

    DESIGNATION PD (PA) QTY TOTAL STATIC PRESSURE AT 100% 175 Pa

    FIRE DAMPER 10 1 10 FLOW AT 100% 1666 m

    VOLUME DAMPER 10 1 10 * DUCTS PRESSURE DROP : 20 Pa

    SUPPLY GRILLE 15 * FITTING PRESSURE DROP : 155 Pa

    RETURN GRILLE 10

    FRESH AIR LOUVER 20

    VAV BOX 100

    ALUMINUM FILTER 80

    BAG FILTER 150PLENUM BOX 50 1 50

    DUCT HEATER 5

    DISC EXHAUST VALVE 70 1 70

    FLEXIBLE DUCT CONNECTION 15 1 15

    SOUND ATTENUATOR 75

    TOTAL 155 Pa