Excitation System

  • Upload
    junsana

  • View
    45

  • Download
    3

Embed Size (px)

DESCRIPTION

Presentation on Excitation system

Citation preview

  • GE Power Services

    June 28, 2002

  • GE Power Services

  • GE Power Services

    To build-up and maintain constant terminal voltage.

    To supply reactive power to the system.

    Other sources of reactive power are:

    Generator-transformer.

    Synchronous condenser.

    Series / shunt compensation.

    To keep the generator parameters within the

    Capability chart.

    Functions of an Excitation System

  • GE Power Services

    To protect the transformer from over-fluxing.

    To ensure system stability in DYNAMIC state by

    providing damping to the electro-mechanical

    transients.

    Functions of an Excitation System

  • GE Power Services

    To ensure system stability under TRANSIENT

    conditions.

    To ensure fast voltage recovery after fault

    clearance.

    Also, most of the generator protection features can

    be incorporated.

    Functions of an Excitation System

  • GE Power Services

    Evolution of Excitation Systems

    Over 40 Years of Static Exciter Design Experience

    1960 65 70 75 80 85 90 95

    00

    Static Excitation

    Alterrex

    Althyrex

    Generrex / Shunt SCR

    Bus Fed

    Digital

  • GE Power Services

    Various Types of Excitation Systems

    DC excitation through DC exciter (Figure 1)

    AC excitation through AC exciter (Figure 2)

    Brush-less excitation through AC exciter and rotating diodes

    (Figure 3)

    Static excitation system (Figure 4)

    Most commonly used Excitation Systems

    Brush-less excitation system

    Static excitation system

  • GE Power Services

    Excitation System with DC Exciter

    SCR

    PT

    CT

    E G

    Feedback to

    Regulator

    Feed from Generator Terminals

    or Auxiliary Bus

    Figure 1

  • GE Power Services

    Excitation System with AC Exciter

    SCR

    PT

    CT

    E G

    Feedback to

    Regulator

    Feed from Generator Terminals

    or Auxiliary Bus

    Figure 2

  • GE Power Services

    Excitation System with Brush-less Exciter

    SCR

    PT

    CT

    E G

    Feedback to

    Regulator

    Feed from Generator Terminals

    or Auxiliary Bus

    Figure 3

  • GE Power Services

    Static Excitation System

    SCR

    PT

    CT

    G

    Feed from Generator Terminals

    or Auxiliary Bus

    Field

    Flashing

    Figure 4

  • GE Power Services

  • GE Power Services

    +

    -

    CONTROLLER

    FEEDBACK

    SYSTEM

    SENSOR

    REFERENCE

    INPUT

    CONTROLLED

    OUTPUT

    ERROR

    SIGNAL

    DISTURBANCES

    A Feedback Control System

    S

    Figure 5

  • GE Power Services

    General Functional Block Diagram for Excitation Control System

    Excitation

    Control

    Elements

    Exciter

    Voltage

    Transducer /

    Load

    Compensator

    Synchronous

    Machine / Power

    System

    PSS and

    Other

    Controls

    VREF

    VUEL

    VOEL Vc

    VR VT

    VS1

    EFD

    IFD IT

    Figure 6

  • GE Power Services

    General Arrangement of Static Excitation System

    AC/DC

    Field Flashing

    Stator

    Current

    Limiter

    Rotor

    Angle

    Limiter

    Power

    System

    Stabilizer

    Auto Control

    Rotor

    Current

    Limiter

    Excitation

    Transformer

    Protection

    EXCITATION

    TRANSFORMER

    Figure 7

    FIELD

    BREAKER

    Inner Loop Control

    Auto

    Reference

    Value

    Manual

    Reference

    SCR

    PT

    CT

    G

  • GE Power Services

    Major Feedback Control Systems Affecting Generator Parameters

    Load-Frequency control loop (P-F loop).

    Reactive Power-Voltage control loop (Q-V loop).

    Relation between Q, V & PF.

    Is there any interaction between P-F & Q-V control loops?

  • GE Power Services

    Ceiling Voltage

    It is the maximum (positive or negative) voltage that can be

    injected on the field under specified conditions. In static

    excitation system ceiling voltage ranges from 1.6-2.0 times

    the rated one (Figure 8).

    Acts for up to 10 seconds.

    Decides fastness of change of excitation.

    Basic Concepts of Excitation System

  • GE Power Services

    IEEE 421 High Initial Response Definition

    Attain 95% of Ceiling Voltage

    in 100 m sec. or less

    EX2000 reaches 95% of

    Ceiling Voltage in 25 m sec.

    Vfield

    0.95 (Vceiling - Vrated)

    Vceiling

    Vrated Time (sec.)

    0.025 0.5

    Conventional

    Rotating Exciter

    HIR Exciter

    0.1

    EX2000

    Figure 8

  • GE Power Services

    Response

    It is the rate of change (increase or decrease) of excitation

    system output voltage.

    Response ratio is generally obtained as the excitation

    system response in volts per seconds measured over first

    0.5 seconds (Figure 9).

    Steady State Accuracy

    This indicates the steady state error offered by the system.

    Basic Concepts of Excitation System

  • GE Power Services

    VO

    Vt

    VF

    Time (Seconds)

    VF - VO

    RESPONSE RATIO =

    0.5

    0.5

    Figure 9

  • GE Power Services

    General Block Representation

    Time Constant (Figure 10).

    Integrator (Figure 11).

    Lead-Lag Network (Figure 12).

    Basic Concepts of Excitation System

    PID Controls

    Proportional Control (Output error signal)

    Integral Control (Output is Difference between initial & final values)

    Derivative Control (Output is rate of change of error signal)

  • GE Power Services

    Simple Integrator with Limiter

    1

    s U X

    Y

    B

    A

    dy / dt = U

    If A >= y >= B, then x = y

    If y > A, then x = A

    If y < B, then x = B

    Figure 10

  • GE Power Services

    1

    1 + sT U X

    Y

    B

    A

    dy / dt = (u - y) / T

    If B A, then x = A

    If y < B, then x = B

    Simple Time Constant

    Figure 11

  • GE Power Services

    1+sT1

    1+sT2 U X

    Y

    B

    A

    If T1 = T2, then y = u

    If B

  • GE Power Services

    General Specifications

    Overall response (Figure 13)

    Overshoot / undershoot which should ideally be limited to one

    overshoot and one undershoot.

    Rise time should be very small.

    Settling time should be as short as possible.

  • GE Power Services

    OVERSHOOT

    SETTLING TIME

    (95% VALUE)

    TIME

    RISE TIME

    1.0

    0.9

    0.1

    General Specifications

    Figure 13

  • GE Power Services

  • GE Power Services

    Technical Features

    Maintains constant terminal voltage.

    AC power tapped from generator terminals / PMG / Auxiliary

    source.

    Rectified through 3, full-wave rectification using Diodes /

    Thyristors controlled through the Regulator.

    Frequency range 47-52 Hz.

  • GE Power Services

    Range of excitation control in Manual channel 75-125%.

    Range of Auto control 90-110%.

    Voltage control accuracy 0.5%.

    Maximum change in terminal voltage after Auto to Manual

    changeover 1%.

    Technical Features

  • GE Power Services

    Response ratio 3-5.

    Fast response (typically 50 milliseconds for analog

    systems and ~ 20 milliseconds for digital regulators).

    % Transformer compensation up to 15%.

    Keeps the machine within the stability region.

    Technical Features

  • GE Power Services

    Protects the generator transformer from over-fluxing.

    Provides damping to electro-mechanical oscillations.

    Technical Features

  • GE Power Services

    Excitation system maintains system stability (Load-Angle Diagram).

    AVR provides both Synchronizing & Damping torque.

    Damping is important under steady state. Voltage response is

    secondary.

    Effect of AVR is to reduce stability region in P-Q plane.

    Introduction of PSS enhances stability region in P-Q plane.

    AVR gain reduction in transient condition (Figures 14 & 15).

    Technical Aspects

  • GE Power Services

    Vref

    Vt

    + -

    +

    +

    -

    1 + s TB

    1 + s TC

    s KF

    1 + s TF

    KAVR

    1 + s TA

    1

    1 + s TR

    Efd

    VS

    IEEE Type ST1A Transfer Function Model of Static Excitation System

    Transfer function

    of terminal

    Voltage transducer

    Figure 14

    S S

    Transient Gain

    Reduction (TGR)

  • GE Power Services

    Transfer function

    of terminal

    voltage transducer

    Efd + -

    +

    1

    1 + s TR

    Vt

    Vref

    VS

    KA

    1 + s TA

    Simplified IEEE Type ST1A Transfer Function Model of Static Excitation System

    (Transient Condition)

    Figure 15

    S

    KA = KAVR * TB / TC

  • GE Power Services

  • GE Power Services

    Capability Chart

    Indicates the operating parameters like MW, MVAR, KV, KA, Field volts,

    Field current, Power factor, Load angle and Operating margins of the

    machine.

    Development of Capability Chart for a Turbo-Generator

    INFINITE-BUS

    V, F = FIXED G

    E Xd V0

    Xd = Xd Machine + X External

    = Power angle for generator

    Figure 16

  • GE Power Services

    jIXd

    I

    A

    V

    B

    E

    O

    This is a voltage triangle.

    Divide all sides by jXd.

    I

    A

    V/X

    B

    E/X

    O

    V

    This is a current triangle.

    VI

    A

    V2/Xd

    B

    EV/Xd

    O

    Ceiling

    Excitation 2Per Unit

    Excitation

    P

    Theoretical

    Limit

    - Q + Q

    1 Per Unit

    Excitation

    Multiplying current triangle by V converts the current triangle into a power triangle.

    Figure 17

  • GE Power Services

    Analysis

    Point B: operating point of the machine

    V/xd indicates If0

    If0 is the field current at no load, which produces generation

    voltage equal to the terminal voltage.

    At no load = 0, E = V

  • GE Power Services

    +Q is the reactive power delivered to system

    -Q is the reactive power absorbed from the system

    The operating point lies on a certain excitation locus.

    For any excitation the maximum power delivered to the system

    is achieved for = 90.

    The maximum reactive power absorbed = - V2 / Xd.

    E V

    P = Sin = V I Cos

    Xd

    Analysis

  • GE Power Services

    Constraints on Capability Chart

    Turbine capacity (MW limit)

    Stator current limitation

    Ceiling excitation limitation

    Practical stability limit

    Minimum excitation corresponding to 10% of rated power

  • GE Power Services

    VI

    A

    V2/Xd

    B

    EV/Xd

    O

    P

    - Q + Q

    1 Per Unit

    Excitation

    Ceiling

    Excitation

    MW Limit

    Field

    Current

    Limit

    Stator

    Current

    Limit

    Theoretical

    Limit

    Practical

    Limit

    Minimum

    Excitation

    Limit

    Figure 18

    Capability Chart

  • GE Power Services

  • GE Power Services

    Start up Sequence

    Turbine start / Speed up

    Adjust AC reference

    Synchronizing

    Power System

    Field flashing command Field breaker closing

    Voltage build up on AC

    Field flashing stops at 70% KV

    Full speed & rated voltage

  • GE Power Services

    Constant voltage Constant VAR Constant PF

    AVR modes of operation

    Different AVR Modes

    Figure 19

  • GE Power Services

  • GE Power Services

    Field breaker is used to limit the fault current and also to

    avoid high voltage across the rotor. It also discharges the

    stored energy through field discharge resistance (Figure 20).

    They are generally DC breakers.

    Single pole or double pole breakers used.

    Generator field breaker

  • GE Power Services

    Over-voltage

    Protection

    Excitation

    System

    Field Discharge

    Resistance

    Generator

    Rotor

    Generator Field Breaker

    Generator field breaker

    Figure 20

  • GE Power Services

    Field discharge resistance (nonlinear) is provided.

    They are make-before-break type.

    While closing discharge pole opens first and the main pole

    closes later.

    While opening discharge pole closes first and the main poles

    open later.

    The rise and decay in field current is not too fast due to large

    time constant of the field. So minor overlapping will not matter

    much. However, the condition of the contacts must be monitored

    during annual overhauls.

    Generator field breaker

  • GE Power Services

    Over voltage protection (thyristorised / vacuum based) to check

    induced voltage rise during any fault on stator side.

    Basic components of field breakers are:

    Main poles

    Discharge poles with arc chutes

    Closing coil

    Trip coil

    Auxiliary circuits

    Generator field breaker

  • GE Power Services

  • GE Power Services

    Field Flashing Circuit

    Required for starting the excitation system.

    Start-up may be through AC and / or DC supply (Figure 21).

    During starting voltage builds-up to 30% due to field flashing only.

    At 30% voltage level, the excitation system gets activated

    sufficiently and starts functioning. The two raise the voltage level to

    70%. At 70% field flashing gets cut off and excitation system works

    independently. The auto changeover is realized through a voltage

    operated relay.

  • GE Power Services

    Generator

    Excitation

    System

    Generator

    Rotor

    AC

    DC

    Generator

    Field

    Breaker

    Field Flashing Circuit

    Figure 21

  • GE Power Services

  • GE Power Services

    Serves as power source for the excitation system.

    Primary is connected to the generator terminals.

    Secondary is connected to the thyristors / regulator.

    Selection of transformer depends on the field-forcing voltage and

    the maximum continuous current in the field winding.

    Location of transformer : generally at zero meter level. The free

    surrounding area must be sufficient enough to maintain proper

    ventilation and ambient temperature.

    Excitation Transformer

  • GE Power Services

    Usually a dry, cast coil type of step-down transformer (Rated volts

    / Nominal volts). This results in reduction of size of the transformer.

    Have high overload capacity. Heating time constant is 6-10 times

    higher than the oil filled transformer.

    Impulse strength is comparable to that of oil cooled transformer.

    Cast coil resin is non-hygroscopic.

    There is no partial discharge.

    Excitation Transformer

  • GE Power Services

    Excitation Transformer

    Possibility of liquid leaking is absent.

    Maintenance-free. No dry out required even after a long shutdown.

    The transformer is generally air-cooled with cooling fans which

    operate on over-temperature.

    Connection DY.

    Standards for manufacturing : BS171, IEC76, ANSI, CS7 and VDE

    0532.

    Enclosure is made to IP 20, IP 21 and IP 23.

  • GE Power Services

    G

    Transformer

    Protection

    Rotor

    Current

    Limiter

    AVR

    Thyristors

    Power

    Supply

    REGULATOR

    Power

    Supply

    AUTO

    Power

    Supply

    MANUAL

    Excitation Transformer

    Figure 22

  • GE Power Services

    Overload/short-circuit protection through excitation transformer

    over-current instantaneous and delayed relay (Figure 22).

    (Settings: Instantaneous-200% In, Delayed-120% In).

    The CTs are mounted on the primary side of excitation

    transformer.

    The relays must attenuate the harmonics as they receive signal

    from machine terminals.

    Excitation Transformer Protection

  • GE Power Services

    Excitation Transformer Protection

    Two-stage (Alarm / Trip) over-temperature protection achieved

    through thermisters embedded in all the three limbs of the

    transformer.

    Phase unbalance protection to protect uneven loading of all the

    phases.

  • GE Power Services

  • GE Power Services

    Dual power supply (DC / AC) with filter

    Reference setting controller: DC (Manual) / AC

    DC limiter

    Inner loop regulator

    Pulse generator

    Pulse amplifier

    Pulse transformer

    Thyristors

    Manual / DC Control

  • GE Power Services

    Filter Gate

    Control

    Pulse

    Amplifier

    Pulse

    Final Stage

    Manual / DC

    Limiter

    Manual / DC

    Reference

    Control

    Pulse

    Transformer

    Thyristors

    Manual / DC Control

    Figure 23

  • GE Power Services

  • GE Power Services

    Output of excitation system is controlled by controlling the firing

    angle of thyristors which in turn controls the conduction of

    thyristors (Figures 24, 25 & 26).

    Cooled by fans: monitoring through cooling flow monitoring

    system. Cooling of thyristors is monitored by:

    Monitoring the status of supply continuously.

    Through airflow monitoring unit during running.

    Thyristor Bridges

  • GE Power Services

    Thyristor Bridges

    Thyristors provided with RC networks for protection against hole

    storage effect.

    Blocking of thyristors is achieved by:

    Monitoring the isolators with micro-switches.

    Overcurrent protection of thyristors through semi- conductor

    fuse.

    Healthiness of fuse is checked through micro-switches or

    monitoring system.

    Reactors are provided for smooth voltage build-up.

  • GE Power Services

    LOAD

    3 Phase

    AC

    R

    Y

    B

    3

    5

    6

    2

    1

    4

    +

    -

    Thyristor Bridges

    Figure 24

  • GE Power Services

    CONDUCTION

    OF

    THYRISTOR

    30 60 90 FIRING ANGLE ()

    UST >0 UST=0 UST

  • GE Power Services

    0 1 2 3 4 5 6 7 8 -1

    -0.8

    -0.6

    -0.4

    -0.2

    0

    0.2

    0.4

    0.6

    0.8

    1

    R(+) Y(+) B(+) R(+)

    Y(-) B(-) R(-) Y(-)

    AC

    SUPPLY

    Thyristor Bridges (Diodes)

    Figure 26

  • GE Power Services

    Thyristor Bridges More number of thyristor bridges for higher redundancy.

    N is the number of bridges.

    N-1 meets full load requirements.

    N-2 meets partial load (65%).

    Rated field current = 2650 amps, Number of thyristors = 4

    Capacity of each set = 1000 amps

    N = 4, field current = 4000 amps, N = 3, field current = 3000 amps

    N = 2, field current = 2000 amps, N = 1, field current = 1000 amps

    Best redundancy is obtained when two identical sets of thyristors are

    used for obtaining 100% redundancy.

  • GE Power Services

  • GE Power Services

    Dual power supply (DC / AC) with filter.

    AC reference setting controller

    Automatic voltage regulator (AVR)

    Limit acting regulators

    Pulse generator

    Pulse amplifier

    Pulse transformer

    Thyristors

    Elements of AC Control Circuit

  • GE Power Services

    Receives voltage and current feedback signals through the

    respective transducers.

    Converts the feedback signals into a proportional DC signal i.e.

    generates actual value signal.

    Receives the voltage reference signal through AC voltage

    reference setting circuits.

    Compares the actual value with the reference setting i.e.

    performs error detection.

    Automatic Voltage Regulator (AVR) Circuits

  • GE Power Services

    Feeds the error to the control amplifier.

    AVR control amplifier produces minimum conduction signal if

    the error is maximum and vice versa.

    Control amplifier adjusts the conduction of thyristors / diodes

    depending on the error signal (by shifting the position of firing

    pulses).

    Output of the thyristor alters according to the control signal.

    Automatic Voltage Regulator (AVR) Circuits

  • GE Power Services

    Field voltage and the field current vary depending on the thyristors /

    diode conduction.

    Generator terminal voltage changes, accordingly.

    Actual value signal changes and becomes equal to reference signal.

    Output of AVR varies to ensure terminal voltage corresponding to the

    reference signal.

    Automatic Voltage Regulator (AVR) Circuits

  • GE Power Services

    AC Control

    Pulse

    Transformer

    Thyristors

    AUTOMATIC

    VOLTAGE

    REGULATOR

    (AVR)

    AC

    Limiter

    AUTO

    Reference

    Control

    Comparator and

    Follow-up

    Figure 27

    Power System

    Stabilizer

    Stator Current

    Limiter

    Rotor Current

    Limiter

    Rotor Angle

    Limiter

    V / Hz

    Limiter

    PT / CT

    Feedback

    Pulse

    Supervision

    Pulse

    Amplifier

    Pulse

    Final Stage

    Filter

    Gate

    Control

    Voltage

    Supervision

    MANUAL

    Reference

    Control

    Gate

    Control Pulse

    Amplifier

  • GE Power Services

    Ensures unit operation at constant PF / VAR.

    If operating in constant PF mode, VAR undergoes changes

    during operation.

    If operating in constant VAR mode, PF undergoes changes

    during operation.

    PF / VAR Controller

  • GE Power Services

  • GE Power Services

    V / Hz Limiter

    Limit Acting Regulators

    Avoids over-fluxing of the transformer.

    Protects against over-voltages at normal frequencies.

    Protects against normal voltages at lower frequencies.

  • GE Power Services

    Avoids thermal overloading of the stator windings.

    In case of inductive current, a time delay is introduced and

    excitation is reduced.

    In capacitive mode, it acts on AVR instantaneously by

    increasing the excitation.

    Stator Current Limiter

  • GE Power Services

    Avoids thermal overloading of the rotor windings.

    Acts after a delay giving enough time to reach ceiling excitation

    limit and allowing sufficient time required for the rate of rise of

    the field current.

    Rotor Current Limiter

  • GE Power Services

    Acts when the rotor angle exceeds a set point.

    Excitation is increased to restrict load angle.

    Rotor Angle Limiter

  • GE Power Services

    AVR is allowed to demand reactive power (under-excited

    reactive current) from the synchronous machine.

    Ensures minimum magnetization to avoid excessive heating of

    the armature core and the end structure due to eddy current set

    -up by armature reaction flux rotating at synchronous speed.

    Original designed as a slow controller but is now applied in

    faster control loops.

    Under Excitation or Minimum Excitation Limiter

  • GE Power Services

    VI

    A

    V2/Xd

    B

    EV/Xd

    O

    P

    - Q + Q

    1 Per Unit

    Excitation

    Ceiling

    Excitation

    MW Limit

    Field

    Current

    Limit

    Stator

    Current

    Limit

    Theoretical

    Limit

    Practical

    Limit

    Minimum

    Excitation

    Limit

    Figure 28

    Capability Chart

  • GE Power Services