Upload
cbetree1732
View
233
Download
0
Embed Size (px)
Citation preview
8/16/2019 Equipment Protection.pdf
1/56
Equipment Protection
8/16/2019 Equipment Protection.pdf
2/56
Types of Transformers Generator Transformer
Power Transformer
Distribution Transformer Pole-mounted lighting Transformer
Grounding Transformer
Regulating Transformer
Welding Transformer Converter Transformer
Instrument Transformer (CT & PT)
8/16/2019 Equipment Protection.pdf
3/56
Types of connection Types of connection: Y-Y, Y- Δ, Δ-Y, Δ- Δ
Y- Δ and Δ-Y introduce phase shift b/w
primary & secondary side. Since the ends of the transformer are
physically closed together, we use differential
protection
8/16/2019 Equipment Protection.pdf
4/56
Phasor Diagram for a 3-phase transformer
8/16/2019 Equipment Protection.pdf
5/56
In star side, line currents, I A, IB & IC
In delta side, the phase currents are
8/16/2019 Equipment Protection.pdf
6/56
Each line current on delta side is the phasor
sumof two of the phase currents.
There is a phase shift of 30° b/w line currentof two sides of Y- Δ transformer
8/16/2019 Equipment Protection.pdf
7/56
Schematic representation of Y- Δ
transformer
8/16/2019 Equipment Protection.pdf
8/56
Phasor diagram showing 30° phase
shift b/w line currents on two sides of
transformer
8/16/2019 Equipment Protection.pdf
9/56
Schematic diagram- 1 phase transformer
8/16/2019 Equipment Protection.pdf
10/56
Equivalent circuit
8/16/2019 Equipment Protection.pdf
11/56
Equivalent ckt of transformer Z shunt branch > Z series branch
In SC, series branch decides the SC current.
If Zse= 0.08 pu, then SC current = 1/0.08 = 12.5 pu
8/16/2019 Equipment Protection.pdf
12/56
Model for finding SC current
8/16/2019 Equipment Protection.pdf
13/56
Types of Faults in transformer
Winding core fault – weakening of insulation
Phase fault inside transformer – rare
Phase fault in transformer terminals (outside) – fall within transformer protection zone
Variation in fault current – depends – type of
connection, method of grounding and current
being refereed to primary or secondary
8/16/2019 Equipment Protection.pdf
14/56
Variation in fault current wrt location in
Δ-Y transformer
8/16/2019 Equipment Protection.pdf
15/56
For resistance earthed star connected
winding- winding to earth fault - fault current
depends on earthing resistance value and
distance of the fault from neutral
Minimum value of If occurs at 30 – 40% of the
distance end of winding from the neutral end
8/16/2019 Equipment Protection.pdf
16/56
•••••••••••
Q)
c
0.4 u 4
oe :::J
•••••••
••••••
••••••
1.0 Jo 10 e;,"
....... 0.8
c ::::> "-
R e = 1 p.u. C:>'f'tj
....... 8
c :::J RE = 0 I "- Q)
a. 0.6
a. 6
....... c
Q) "- "- ::::>
.(
....)
.
Q) "- "- :::J
.......
::::> ro
8/16/2019 Equipment Protection.pdf
17/56
Variation of If wrt location for Y-Δ transformer
8/16/2019 Equipment Protection.pdf
18/56
For delta, minimum voltage on delta winding
is at the centre of one phase and 50% of
normal phase to earth voltage.
The range of If values are less than star
connected wndg.
The minimum value of If occurs at the centre
of one phase winding.
8/16/2019 Equipment Protection.pdf
19/56
Over current Protection of
transformer
8/16/2019 Equipment Protection.pdf
20/56
In fig two number of phase-fault over current relaysand one number ground fault over current relay isprovided for either primary protection for small
transformers and back up protection for biggertransformers.
The pickup value is set not to pickup maximumpermissible overload but sensitive to smallest phasefault.
The neutral current is because of load unbalance. The third harmonic currents ends up as zero
sequence current & flows through neutral.
8/16/2019 Equipment Protection.pdf
21/56
••
••••
••••• Percentage differential protection of
transformers
Delta-star transformer
with neutral grounded
•
•••••••••
•••••••
8/16/2019 Equipment Protection.pdf
22/56
Star point is grounded – turns ratio 1:1
8/16/2019 Equipment Protection.pdf
23/56
••
•••
•
••••• Determination of IL on two sides of
transformers Delta-star transformer with neutral grounded
l c- I a
l c
• •••••••••
••• •••
••• •
8/16/2019 Equipment Protection.pdf
24/56
Determine instantaneous direction of Ia, Ib, Ic throughsecondary winding
Primary winding currents are then determined I A=Ia,
IB=Ib, IC=Ic ( turns ratio is 1:1) Line currents on star side is determined (same as
phase currents Ia, Ib, Ic )
Line currents on delta side is determined (IC-I A),(I A-IB), (IC-I A) [phasor difference]
If Secondary wndg of CTs are connected in star,spill current is produced (currents will not matchup)
If secondary wndg of CTs on the star side isconnected in delta – currents are same – providedCTs on delta side is connected in star.
8/16/2019 Equipment Protection.pdf
25/56
••••••
lA- lc /A Ia
-
/A! Ia Ia
••••••
l'b 0
0
-o
z
i 3 ro
I a -o •••••••••
Q)
••••• lA- lc lc
(_)
c: ro
•••• Is- lA
Is-lA lo- Ialo (ij
.0
(ij c...:. 2 X
Is- lA
w lo
.. 0
3::
Is! =
lo ro
l c lc- Ia ro
E
lc- Ia
lcl ilc
lc - lo 0
lc
r-- 1
lc- Is : lc - /0 I I I
I
I
I
I
I
I
I I
:Zero
8/16/2019 Equipment Protection.pdf
26/56
••••••
lA- lc /A Ia
- I
•------------- --
: Ia - lc I I
I
I
I
I
8/16/2019 Equipment Protection.pdf
27/56
/A
••••• l(f
• •
I
.,lc •••••
/Al Ia
••••••••
lt:J- Ia lo
•••••••••
Ia-
lA llJ
lo
lsl /lJ lo
lc
lc - lo
r
c-g external fault
•---------------4I
Percentage differential relay
External fault (c-g)
8/16/2019 Equipment Protection.pdf
28/56
Due to fault in C, over current in Phase C.
The If is supplied through two lines on delta
side. Due to delta connection, the CTs in star carry
the current.
Hence no spill path.
The scheme is stable in c-g fault.
L
8/16/2019 Equipment Protection.pdf
29/56
L l A- l c / A I a
•••••
+-- •••••
l A - l c l c
/Al j I a I a ••••••••
Ia- / A l b- I a l b
•••••••••
+-- Ia - lA
I a- l A
l al i /b
l b • • +--
l b
l c- I a
l b, l c
c -g internal fault l c - lb
l c
l c- I a I
Spill : Unitcurrent : operates = l e- l a•
l b - I a
Unitrestrains
Unitoperates
I
I
•---------------I
Percentage differential relay
Internal fault (c-g)
8/16/2019 Equipment Protection.pdf
30/56
Since the fault is internal, no If through the
primaries of CTs on star side.
The fault current flows through spill path,causing the differential units to operate and
tripping the transformer.
8/16/2019 Equipment Protection.pdf
31/56
•••••••••
Inrush Phenomenon •••••• ••••••••
••• •
Switch-on Flux
= 1/lR + 1/lm COS 9 - 1/Jm COS (OJ t + 9)
AC supply
""'Flux
Inrush
Open circuit
\ /Full load
8/16/2019 Equipment Protection.pdf
32/56
•• •••
• • ••••
•••••••• ••• •••
••• •
Let the flux in the transformer be written as
qy = ¢rn sin w t
The induced voltage can then be written as
- N d¢ v- dt
= N
8/16/2019 Equipment Protection.pdf
33/56
8/16/2019 Equipment Protection.pdf
34/56
Inrush Phenomenon
•
8/16/2019 Equipment Protection.pdf
35/56
••••••
•••• ••• ••••
281--------------------- -----=.-:..:-..-::.-::.:-:...-::..;;;...;::..:-:----;---- -- ::
Bm --------
('\J
E ..0
co
Excitation characteristics of core
Steady-statemagnetizing current
l o 8/o
Inrush current
H(AT/m)
•
8/16/2019 Equipment Protection.pdf
36/56
••••••
•••••••••
•••••••••
••••••
'+' Operating
torque Restraining
torque
CT secondary
(/1 - /2) currents /1, /2 (/1 + /2)/ 2
_., ....
1 I
Spi!l current
I I Circulating current I
I Filter l Unfiltered
l Fundamental All harmonics
Fundamental +
component all harmonics
I
L
Reiay
•
8/16/2019 Equipment Protection.pdf
37/56
••••••
•••••••••
•••••••••
•••••• CT
Transformer
Fundamental + Harmonics
[I] [TI
Passes only thefundamental
Fundamental + Harmonicscirculating current
All harmonicsspill current
Fundamentalspill current
8/16/2019 Equipment Protection.pdf
38/56
•
8/16/2019 Equipment Protection.pdf
39/56
••••••
••
•••
•
Transformer
•••••••••
••• •••
••• •
L 0
ad
Reach of restrictedearth fault relay
OC relay
•••
8/16/2019 Equipment Protection.pdf
40/56
••••••••••
•••••
••••••••••
••••••
Zero
400 kV
J3
It= 5000 A
Inter-tum fault 11 kV
t J3
5V Rt = 1 mn
•••
8/16/2019 Equipment Protection.pdf
41/56
••••••••
••••• ••
••••••
•••••
Conservator Alarm
Breather
Buchholzrelay
Trip
Transformer
Oil
Tank
••••
8/16/2019 Equipment Protection.pdf
42/56
•
••
•••
• •••• •••••••• ••• ••• •••
•
Alarm
- - - - - - - - - Oil level
To conservator Vane
To tank
Buchholz trip
8/16/2019 Equipment Protection.pdf
43/56
••••••
8/16/2019 Equipment Protection.pdf
44/56
•••••
••••
-•••••••
-
•
Steam
Wret
governor
••••••••• •
Steam control Actual speed
valve
Induceddraft
mill
Steam
Condenser
,------ •,'151515'.:..
Exciterfieldcontrol
Error
Air
Pulverized
Forced draft Water
Water
Water
Actualvol tage
Water Waterspray
-------------- Pond
••••••
8/16/2019 Equipment Protection.pdf
45/56
••••• •••••••••
•••••••••
••••••
Generatortransformer Main CB
EHV bus
t------ "----+----To grid
..... C'O
Q)
c Q)
8/16/2019 Equipment Protection.pdf
46/56
••••• •••••••••
•••••••••
••••••
Alternator Phase a
Main CB To generatortransformer
Phase b
Groundingtransformer(Step-downtransformer )
Phase c
Groundingresistance
t Trip
•••••
8/16/2019 Equipment Protection.pdf
47/56
••
•••
• • ••••
•••••••• ••• ••• •••
•
Field interrupter
Field current
J
Excitation controlsystem
I
\ I
'- _;;.
Exciter coupled toalternator shaft
t
Fieldsupressor
Field windingof generator
DC system is isolated "7'"rl7r from ac ground
••••••
8/16/2019 Equipment Protection.pdf
48/56
•• ••• •
Stator
.,.... Phase f ault
•••••••••
••• •••
••• •
Electr icalfaults
,... Thr ee-phase stator
winding
"'
Rotor
,., Field winding
, Inter -turn f ault on thesame phase
Gr ound f aults
, Short cir cuit to ground
Sta tor
, Electrical .... Three-phase stator _, Unbalanced loadingwinding
Abnormaloperating
conditions
Rotor
.... Field winding .... Loss of excitation
.
.... Mechanical Loss of
,
pnme mover
Over -speedmg
••••••
8/16/2019 Equipment Protection.pdf
49/56
•••••••••
•••••••••
••••••
'
Field windingof generator
Slip ring
Exciter
e
Generator shaft
B Alarm
/
/ I
I I
I
I
: T1me setting
: Plug setting I
-----+.-- Trip circuit of main CB of generator
\
\ \ \
\
' ' ''' ... '
••••••••
8/16/2019 Equipment Protection.pdf
50/56
•••••••••
•••••••••
••••••
Negative sequence component in statorcurrent
Stator armature MMF due to negativesequence currents rotates at -Ns (rpm)
No
Field winding rotating at Ns (rpm)
Relative speed between rotor and the field due
to negative sequence currents = 2N s
Double frequency currents of frequency 2Nspl 120 induced in rotor core and winding
Additional heat generated
••••••••
8/16/2019 Equipment Protection.pdf
51/56
••••••
•• •
Stator currents I a l b l c
Negative sequence f ilter /2 = f (l a, l b. l c)
•••• •••••••
• •
/2 Negative sequence current (rms) '
Over-current relay with inverse
characteristic To p = K/1 Set K for the machine
'If
Trip main CB of generator
••••• •
8/16/2019 Equipment Protection.pdf
52/56
••••••••• •••
Tachogenerator
output
Over -frequency
relay
••••••••••
•••••
Yes
Stop steam supply
to turbine
t Start shutdown of
generator
••••••
8/16/2019 Equipment Protection.pdf
53/56
••• ••••••••••
••••••
Voltage = V rated Oe
••••••
Mechanical -+-...;.....
input
Generator
Speed = N s
Field current lr
'---------P e
Generator
Voltage = VLoE
Mechanical -.lor--
input
Speed > N s
Generator
Field current 1, = zero (Loss of excitation)
r--------------- Pe
Generator
••••• • •••
8/16/2019 Equipment Protection.pdf
54/56
•• ••• •
•••••••••
••• •••
••• •
T II X
Medium initial
Rated initial
output
1
output
2 Low initial output
3
Offset mho relay functioning
as loss of excitation relay
Ill
Time increasing
IV
Locus of apparent
impedance
•••••••
8/16/2019 Equipment Protection.pdf
55/56
•••••••••••
t
••
•••••••••••
•
•
Mechanical
input
Generator
Ns
Oe
Field current 11 excitation
Loss of prime +---T----i Running as motor ..,_... ;
mover
iQ· Field current 11 excitation
••
•••••
8/16/2019 Equipment Protection.pdf
56/56
•••••••
I
Active power Generator
Loss of primemover
Reactive power -- )o
•• ••••••
• t •
Trip
'-----4------J Directional +