Upload
mohammed-bashri
View
241
Download
0
Embed Size (px)
Citation preview
7/24/2019 6.1-Busbar protection.pdf
1/54
6.1 BusBar protection
7/24/2019 6.1-Busbar protection.pdf
2/54
Ref : APP14
Last Release : October 2010
Schneider Electric - Jean Marmonier - 20/01/2011
Pro ram
PART 1 : GENERALITY
PART 2 : OPERATING PRINCIPLES
PART 3 : OTHER SUBSTATION TOPOLOGIES
Advantages / Disadvantages
PART 4 : HIGH IMPEDANCE DIFFERENTIAL PROTECTION
PRINCIPLE
PART 5 : LOW IMPEDANCE PROTECTION PRINCIPLE
PART 6 : FRAME LEAKAGE PROTECTION - PRINCIPLE
PART 7 : BLOCKING SCHEME PROTECTION
2Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : OTHER APPLICATIONS
7/24/2019 6.1-Busbar protection.pdf
3/54
PART 1 : Generality
PART 2 : Operating Principle
Advantages / Disadvantages
PART 4 : High Impedance Differential
Protection Princi le
PART 5 : Low Impedance Protection Principle
PART 6 : Frame Leakage Protection - PrinciplePART 7 : Blocking Scheme Protection
3Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
Busbar protection
Objective :
Clear a fault inside a substation as quickly as
possible
CA B
To Protect :
- The operator and workers
- HV equipment
4Schneider Electric - Jean Marmonier - 20/01/2011
-
7/24/2019 6.1-Busbar protection.pdf
4/54
7/24/2019 6.1-Busbar protection.pdf
5/54
Differential Protection
The grading between overcurrent protections is difficult to guarantee
The max clearance time is critical for HV equipment or network
Applicable for :
Generators,
,
Overhead lines, Underground cables,
busbars,
7Schneider Electric - Jean Marmonier - 20/01/2011
Motors.
Busbar Faults Are Usually Permanent
Falling debris
Insulation failures Circuit breaker failures
Current transformer failures
Isolators switchs operated on load or outside their ratings
Safety earths left connected
Therefore :
Circuit breakers should be tripped and locked out by busbar protection
8Schneider Electric - Jean Marmonier - 20/01/2011
rec os ng mus e one a er ns a a on c ec
7/24/2019 6.1-Busbar protection.pdf
6/54
Busbar Protection must be
Failure to trip could cause widespread damage to the substation
STABLE
False tripping can cause widespread interruption of supplies to
customers / ossible ower s stem instabilit
DISCRIMINATING
ou r p e m n mum num er o rea ers o c ear e au
FAST
9Schneider Electric - Jean Marmonier - 20/01/2011
To limit damage and possible power system instability
Protection Methods
High Impedance
Low Impedance
Medium Impedance with Bias Characteristic (no more used)
Directional Comparison Protection (Blocking Scheme)
10Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
7/54
PART 1 : Generality
PART 2 : Operating Principle
Advantages / Disadvantages
PART 4 : High Impedance Differential
PART 5 : Low Impedance Protection Principle
PART 6 : Frame Leakage Protection - Principle
PART 7 : Blockin Scheme Protection
11Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
Biased Differential Scheme
21
I1 - I2
21
I1 - I2
Differential
Current
Differential
CurrentHI LII1 - I2
Trip
I1 - I2
Trip
no Trip
12Schneider Electric - Jean Marmonier - 20/01/2011
Mean Through
CurrentI1
2
I2+Mean Through
CurrentI1
2
I2+
7/24/2019 6.1-Busbar protection.pdf
8/54
Biased Differential Scheme
Differential
I1 - I2
Trip
no Trip
Mean ThroughCurrent
I1 I2+
13Schneider Electric - Jean Marmonier - 20/01/2011
2
Biased Differential Scheme
Differential
I1 - I2
Trip
no Trip
Differential Current
Mean Through Current
Mean Through
Current
I1 I2+I1 I2+
I1 I2+
14Schneider Electric - Jean Marmonier - 20/01/2011
2Differential Current = 2 X Mean Through Current
7/24/2019 6.1-Busbar protection.pdf
9/54
Protective Zone definitions
BS
Bus Section / Bus Disconnector
one
Zone 3 Zone 4
Zone 2
BC1 BC2
F1 F2 F3 F4
15Schneider Electric - Jean Marmonier - 20/01/2011
No Busbar Protection
Advantages
There are fewer faults on busbars than on
other parts of the power system.
accidental operation of busbar protection.F2F1
Drawbacks
Slow fault clearance.
Busbar faults at F1 and F2 are cleared by
remote time delayed protection on circuits
feeding the faults:
Time Delayed Overcurrent or
16Schneider Electric - Jean Marmonier - 20/01/2011
Time Delayed Distance Protection (Zone 2)
7/24/2019 6.1-Busbar protection.pdf
10/54
With Busbar Protection
ZONE
breakers at the busbars F1
Fast Tripping but only for the
Cirscuit breakers of the selectied
ZONE 1
F2F1
ZONE 2
zone
17Schneider Electric - Jean Marmonier - 20/01/2011
With Busbar Protection
1/2SS SS SS
87BB
87BB
1
2 3
21 21
18Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
11/54
With Busbar Protection
2/2
87BB
87BB
21 21
19Schneider Electric - Jean Marmonier - 20/01/2011
Without Busbar Protection
1/2
21 21 21
21 21
20Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
12/54
Without Busbar Protection
2/2
21 21 21
21 21
21Schneider Electric - Jean Marmonier - 20/01/2011
With Busbar protection
87BB
87BB
21 21
Without Busbar protection
21 21 21
22Schneider Electric - Jean Marmonier - 20/01/2011
21 21
7/24/2019 6.1-Busbar protection.pdf
13/54
PART 1 : Generality
PART 2 : Operating Principle
Advantages / Disadvantages
PART 4 : High Impedance Differential
Protection Princi le
PART 5 : Low Impedance Protection Principle
PART 6 : Frame Leakage Protection - PrinciplePART 7 : Blocking Scheme Protection
23Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
Topology & Architecture of the HV
Most basic, simple andSingle breaker - Single bus
.
Main use :
- distribution,- lower transmission voltages
Drawback :
- Lack of flexibilit for bus
faults
- maintenance
enera y no pro ec e y a
busbar protection if one or
two infeeds exist.
24Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
14/54
Topology & Architecture of the HV
Sin le buses connected with bus tie number of circuits exist.
Main use :
- Distribution networks,
- Industrial substations with or
without co-generation.
Advantages :
- Flexibility, specially when the
substation is fed by two
separa e power supp es
(generators).
- A bus fault only causes the
loss of half a bar
25Schneider Electric - Jean Marmonier - 20/01/2011
Double breaker - Double bus2 Busbars ; 2 Circuit Breakers
X
kV)
Advantage :- Increased operating flexibility,
- Both busbars are independent,
specially from a protection point of
X X X X
.
- All switch disconectors are normally
closed and no bus couplor is used.
- The loss of one bus dos not affect
e ransm e power.
Drawback :
- The line rotection must be
26Schneider Electric - Jean Marmonier - 20/01/2011
connected to both CTs.
7/24/2019 6.1-Busbar protection.pdf
15/54
Main and transfer buses with single
Main
Reserve / Transfer
By-passIsolator
By-passIsolator
27Schneider Electric - Jean Marmonier - 20/01/2011
Main and transfer buses with single
Main
Transfer
Reserve
TransferCB
rans er
Be carefull to the CT ocation on the Bus Transfer in order to
28Schneider Electric - Jean Marmonier - 20/01/2011
clearly defined the protected zone
7/24/2019 6.1-Busbar protection.pdf
16/54
Breaker and a half bus arrangementWidely used for larger multicircuit and higher voltage systems
Advantage :
- ,- Line faults trip two circuit breakers but does not cause loss of
services of other lines and busbars.
87
Zone to
protect
separately
29Schneider Electric - Jean Marmonier - 20/01/2011
87
Other Busbar TopologiesRing Bus
OHL FEEDER
No busbar
Advantage :X
X- One circuit breaker for two lines,
- No busbar is required (not
applicable) as the bus protection is
XX XX
X
protection themselves.
- The ring can be opened without loss
of power.
Drawback :
- If the ring is opened, a fault on a line
ma se arate the other lines and the
30Schneider Electric - Jean Marmonier - 20/01/2011
TRANSF. FEEDERbus.
7/24/2019 6.1-Busbar protection.pdf
17/54
Mesh Busbar
T1 T3
31Schneider Electric - Jean Marmonier - 20/01/2011
F4 F2
Mesh Busbar ProtectionF1 F3
87R1
87R3
T1 T3
T4 T2
32Schneider Electric - Jean Marmonier - 20/01/2011
F4 F2R4 R2
7/24/2019 6.1-Busbar protection.pdf
18/54
and Number
33Schneider Electric - Jean Marmonier - 20/01/2011
Effect of CT location on the global
ro ec on er ormanceBus
Feeder
FeederProtection
Protection
Feeder
BusProtection
BusProtection
BusProtection
51
34Schneider Electric - Jean Marmonier - 20/01/2011
CT Overlap s on ne s e
Feeder
7/24/2019 6.1-Busbar protection.pdf
19/54
PART 1 : Generality
PART 2 : Operating Principle
PART 3 : Other Substation To olo iesAdvantages / Disadvantages
PART 4 : High Impedance Differential
ro ec on r nc p e
PART 5 : Low Impedance Protection Principle
PART 6 : Frame Leakage Protection - Principle
35Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
Single Bus Substation
P1 S1 P1 S1 P1 S1
P2 S2 P2 S2 P2 S2
36Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
20/54
Single Bus Substation
37Schneider Electric - Jean Marmonier - 20/01/2011
Single Bus Substation
38Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
21/54
Single Bus Substation
39Schneider Electric - Jean Marmonier - 20/01/2011
Double Bus Substation
40Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
22/54
Double Bus Substation
Bus A
Bus B
P1 S1 P1 S1 P1 S1
P1
P2
S1
S2
P2 S2
P2 S2 P2 S2 P2 S2 P1 S1
ab
Current
41Schneider Electric - Jean Marmonier - 20/01/2011
Double Bus Substation
Bus A
Bus B
ab
42Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
23/54
Double Bus Substation
Bus A
Bus B
ab
Current
43Schneider Electric - Jean Marmonier - 20/01/2011
Double Bus Substation
Bus A
Bus B
ab
Current
44Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
24/54
Double Bus Substation
Bus A
Bus B
ab
Current
45Schneider Electric - Jean Marmonier - 20/01/2011
Double Bus Substation
Bus A
Bus B
ab
Current
46Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
25/54
Double Bus SubstationBus A
Bus B
a
Tripping ab
47Schneider Electric - Jean Marmonier - 20/01/2011
Double Bus Substation
Interposing CTs are not acceptableMain CT must be identical urren sw c ng v a aux ary re ay s no accep a e.Requirement of number of position contact (Disconnector switch) is
high
48Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
26/54
Double Bus Substation
No auxiliary contact must be used
for current switchinSupplementary delay on current switching
Reliabiliby
Auxiliary relays must be designed
so that :
They get closed before
the bus disconnector is closed
The et o en after
the bus disconnection is open
49Schneider Electric - Jean Marmonier - 20/01/2011
Check Zone Supervision
Bus A
A B
TripBus
TripBus
Zone AZone B
50Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
27/54
Check Zone Supervision
Bus A
A B
TripBus
TripBusurren
switching
failure
Zone AZone B
51Schneider Electric - Jean Marmonier - 20/01/2011
False
Tripping
Check Zone Supervision
Bus A
A B
TripBus
TripBus
Zone AZone B
52Schneider Electric - Jean Marmonier - 20/01/2011
Check
Zone
7/24/2019 6.1-Busbar protection.pdf
28/54
Check Zone Supervision
Bus A
A B
TripBus
TripBus
Zone AZone B
53Schneider Electric - Jean Marmonier - 20/01/2011
Check Zone Supervision
Bus A
A B
TripBus
TripBus
54Schneider Electric - Jean Marmonier - 20/01/2011
Check
Zone
7/24/2019 6.1-Busbar protection.pdf
29/54
Protection Sensitivity
55Schneider Electric - Jean Marmonier - 20/01/2011
Stability for External Faults
RCT RCT2RL 2RLM
ZM A ZM
2RL
RCT
56Schneider Electric - Jean Marmonier - 20/01/2011
MRCT
2RL
7/24/2019 6.1-Busbar protection.pdf
30/54
7/24/2019 6.1-Busbar protection.pdf
31/54
7/24/2019 6.1-Busbar protection.pdf
32/54
7/24/2019 6.1-Busbar protection.pdf
33/54
7/24/2019 6.1-Busbar protection.pdf
34/54
Requirements
65Schneider Electric - Jean Marmonier - 20/01/2011
CT Wiring Supervision (2)I1
CT1
Super
vision
V
RST
R
RZM2 ZM3 ZM4
relaynsupervisiobymeasuredVoltage
reay
I1
relansu ervisiotheo eratecurrent tobalance-of-Out
VsettingrelaynsupervisioIf
)// Z// Z// Z(RV
SP
M4M3M21
Z
V
Z
V
Z
V
R
V
M3
SP
M3
SP
M2
SPSP
66Schneider Electric - Jean Marmonier - 20/01/2011
..
7/24/2019 6.1-Busbar protection.pdf
35/54
Differential Relay CircuitB
C
N
Zone bus wires
95X
95X
95X
Bus wire short contacts
Supervision relay95
Stabilising resistors
87 87 87
v v vresistors
67Schneider Electric - Jean Marmonier - 20/01/2011
High Impedance Protection
Stability is entirely due to a stabilising resistor in the circuit..
,
The CTs must have the same ratio & must be of high
accuracy (low magnetizing current) - class X
The CT knee point voltage needs to be relatively high
The magnetising current can desensitise the scheme
The scheme can be very fast
Isolator contacts are needed to switch the full CT secondary
current between the zones.
There are risks to o en the secondar side of CTs
Extending the scheme is quite simple (if CTs not too old)
Metrosil and Buswire supervision is required
68Schneider Electric - Jean Marmonier - 20/01/2011
a n enance ru es are s r c
7/24/2019 6.1-Busbar protection.pdf
36/54
One Breaker and a Half
Substation
69Schneider Electric - Jean Marmonier - 20/01/2011
One and Half Circuit Breaker
P1
P2
S1
Bus A Bus
B
P1 P2 P1P2
S1 S2 S1S2
Use of one additional
Protection
High Impedance
Differential rela
Low Impedance
Differential relay (3
windin transformer
70Schneider Electric - Jean Marmonier - 20/01/2011
relay)
7/24/2019 6.1-Busbar protection.pdf
37/54
One and Half Circuit Breaker
Bus A Bus
B
71Schneider Electric - Jean Marmonier - 20/01/2011
One and Half Circuit Breaker
Bus A Bus
B
72Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
38/54
One and Half Circuit Breaker
Bus A Bus
B
73Schneider Electric - Jean Marmonier - 20/01/2011
One and Half Circuit Breaker
Bus A Bus
B
74Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
39/54
One and Half Circuit Breaker
Bus A Bus
B
75Schneider Electric - Jean Marmonier - 20/01/2011
One and Half Circuit Breaker
Bus A Bus
B
P1 P2 P1P2
S1 S2 S1S2
P1 P2 P1P2
S1 S2 S1S2
76Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
40/54
PART 1 : Generality
: pera ng r nc p e
PART 3 : Other Substation Topologies
van ages sa van ages
PART 4 : High Impedance Differential Protection
r n c p e
Principle
: rame ea age ro ec on - r nc p ePART 7 : Blocking Scheme Protection
77Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
GENERAL SCHEME
BB1bBB1a
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Peripheral
Unit
Unit
Centralle
Peripheral UnitsOptical Fibres Optical Fibres
Peripheral Units
78Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
41/54
Bias Characteristic Principle
idiff (t)
Tri in Area
X X1
X XX
I >2 Blocking Area
2
ISID>1
ni 3
Differentail Current: idiffnoeud (t) = i1 + i2 + i3 + + inO eratin Quantit : i t = i t = i
bias
79Schneider Electric - Jean Marmonier - 20/01/2011
Bias Quantity: ibias(t) = |i1|+ |i2|+ | i3| + + |in| = |in|
INTEGRATED FUNCTIONS
Peripheral Units Objective
Local Signal Processing (magnitude, angle, saturation detection )
Local Back-up Protections (Max I)
Central Unit objective
Automatic Ada tation of zone number
Differential Calculation Element for each zone
Differential Calculation Element Check Zone
--
Circuitry Fault Control for each Differential Element
80Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
42/54
OTHER INTEGRATED FUNCTIONS
Pole Discrepency Supervision, for circuit breakers and bus
disconnectors
uperv s on
Inter-Tripping management in case of Internal Bus Fault
Circuit Breaker Failure : ReTrip order (stage 1) or Zone Tripping
(stage 2)
Circuit Breaker Failure Definition of zones to be tripped
Maintenance modes management (per zone differential blocking)
81Schneider Electric - Jean Marmonier - 20/01/2011
Current Circuitry Fault Supervision
iidiff= 0= 0
Under normal operating conditionsUnder normal operating conditions
iidiff 00
=> use of a circuitry fault alarm threshold so that :=> use of a circuitry fault alarm threshold so that :
1.2 x1.2 x ii II >1>1 0.8 x I0.8 x I .
=> Affected zone blocking (option depending on manufacturer)=> Affected zone blocking (option depending on manufacturer)
82Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
43/54
Check Zone Supervision
The Check Zone Element does not take into account the status
of busbar disconnections (assignment to bus A or B)
Total ITotal Idiffdiff= Sum of current node i= Sum of current node idiffdiff
diffdiff == diffdiff ==
Under pole discrepency condition on a circuit breaker or a bus
,
nil, preventing any maloperation of the busbar protection,
=> A trip will be issued only if the differential current measured
b the check zone has reached the tri in threshold.
83Schneider Electric - Jean Marmonier - 20/01/2011
Tripping Threshold Conditions
Differential Current detected by the Check Zone ElementDifferential Current detected by the Check Zone Element
Differential Current above the Tripping Threshold,Differential Current above the Tripping Threshold,generaly set so that :generaly set so that :
1,2 x1,2 x I_highest loaded feederI_highest loaded feeder (ID>2)(ID>2) 0.8 x I0.8 x I Min. shortMin. short--
Fault point inside the Characteristic Operating AreaFault point inside the Characteristic Operating Area
84Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
44/54
7/24/2019 6.1-Busbar protection.pdf
45/54
7/24/2019 6.1-Busbar protection.pdf
46/54
Low Impedance Protection Synthesis
Stability is entirely due to the bias characteristic of the
scheme. Metrosils and Stabilizing resistors are not required,
CTs can have different ratios
Scheme bias characteristic can cater for lesser accuracy
CTs (class 5P), instead of Class X CTs,
,
can manage the saturation effects,
CTs can be shared with other protection, due to low burden,
Number of // circuits does not affect he primary operating
current
Fast Tri in time Decision between 3 to 5 ms
Isolator contact are not needed to switch heavy currents,
Extending the scheme is simple,
89Schneider Electric - Jean Marmonier - 20/01/2011
Self supervision and breaker fail protection is easier to
integrate,
PART 1 : Generality
: pera ng r nc p e
PART 3 : Other Substation Topologies
van ages sa van ages
PART 4 : High Impedance Differential Protection
r n c p e
PART 5 : Low Impedance Protection Principle
PART 6 : Frame Leakage Protection
PART 7 : Blocking Scheme Protection
90Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
7/24/2019 6.1-Busbar protection.pdf
47/54
Frame Leakage Busbar Protection
Principle and Limitations
Limited to Medium Voltage BusBar applications
Can detect only earth faults
Means that the fault current betwwen circuit breaker cells and earth
must be measured :
=> Switchgear must be insulated from earth (by standing on concrete
p n ,
=> Only one single earth conductor allowed on switchgear,
=> All cable glands must be insulated from the cells earth,
=> n y one s ng e p ase s use , e ween ear con uc or an an
instantaneous overcurrent relay. In case of several sections (with couplers), Switchgear sections must
be insulated.
91Schneider Electric - Jean Marmonier - 20/01/2011
Frame Leakage Busbar Protection
>I
Insulation
92Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
48/54
Frame Leakage Busbar Protection
>I
93Schneider Electric - Jean Marmonier - 20/01/2011
Frame Leakage Busbar Protection
>I
94Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
49/54
Frame Leakage Busbar Protection
>I >I
95Schneider Electric - Jean Marmonier - 20/01/2011
Frame Leakage Busbar ProtectionConfirmation by Transformer Neutral protection
False Operation
because induced
loop
>I
>I
Fault)
96Schneider Electric - Jean Marmonier - 20/01/2011
Tripping is confirmed by the
relay, to avoid false trip
7/24/2019 6.1-Busbar protection.pdf
50/54
Frame Leakage Busbar Protection
Confirmation by Transformer Neutral protection
>I
>I
97Schneider Electric - Jean Marmonier - 20/01/2011
Frame Leakage Busbar Protection
Confirmation by Transformer Neutral protection
>I
>I
98Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
51/54
7/24/2019 6.1-Busbar protection.pdf
52/54
Blocking Scheme Busbar ProtectionBUSBAR
PROTECTION
LOGIC>I >I >I >I>I
101Schneider Electric - Jean Marmonier - 20/01/2011
PART 1 : Generality
PART 2 : Operating Principle
Advantages / Disadvantages
Protection Principle
: ow mpe ance ro ec on r nc p e
PART 6 : Frame Leakage Protection - Principle
PART 7 : Blocking Scheme Protection
102Schneider Electric - Jean Marmonier - 20/01/2011
PART 8 : Other Applications
7/24/2019 6.1-Busbar protection.pdf
53/54
Busbar Blocking Protection
Tripping of the Feeder Relay Only
Blocking of the Incommer RelayIncomer
BLOCK
No Blocking of the Incomer Relay
Time Delayed tripping of the
and Fault Clearance IF2
O/C Relay O/C Relay O/C RelayO/C Relay
103Schneider Electric - Jean Marmonier - 20/01/2011
F1
PART 1 : Generality
PART 2 : Operating Principle
Advantages / Disadvantages
Protection Principle
PART 6 : Frame Leakage Protection - Principle
PART 7 : Blocking Scheme Protection
104Schneider Electric - Jean Marmonier - 20/01/2011
7/24/2019 6.1-Busbar protection.pdf
54/54
Bus Protection - other application
Other Application commonly used for Oil & Gas
The 51Relay is limited
to the load current of eachhalf section
I_pilote=I_incomer-I_coupler
Advantage
if TA is in maintenance
105Schneider Electric - Jean Marmonier - 20/01/2011
Bus Protection - other application
Can be used in case of 4 feeders max
No Bus Coupler or Bus Disconnector
87T