4
safety valve SV SAFETY VALVE SV Ver. /201 - 10 6 en WE SAY: SAFETY IS MAXIMISED BY EDER!

EN - brochure safety valve v1 - EDER Heizung€¦ · maximum 1 m lenght as well as its own air ... Safety valves are built according to EN-ISO 4126-1 „safety devices for ... EN

Embed Size (px)

Citation preview

Page 1: EN - brochure safety valve v1 - EDER Heizung€¦ · maximum 1 m lenght as well as its own air ... Safety valves are built according to EN-ISO 4126-1 „safety devices for ... EN

1

safe

ty v

alv

eSV

SAFETY VALVESV

Ver. /201 -10 6 en

WE SAY:SAFETY IS MAXIMISEDBY EDER!

Page 2: EN - brochure safety valve v1 - EDER Heizung€¦ · maximum 1 m lenght as well as its own air ... Safety valves are built according to EN-ISO 4126-1 „safety devices for ... EN

2

FUNCTIONAL PRINCIPLE / ASSEMBLY

Functional principleTo ensure that the maximum operating pressure is not exceeded, each heat generator of aheating system has to be assured by a safety valve. Safety valves have to able to release vapour,water resp. a mixture of water and vapour, so that the pressure within the heating system doesnot exceed more than 10% of the set maximum operating pressure.

This means, that a safety valve has to be able to drain the total heating output of the heatgenerator. During normal system function safety valves will not start to function.

elko-flex eder . elko-mat eder Vresp S safety valves are suitable for closed heating systemsaccording to the standards EN 12828 a:2013-01-01 nd ÖNORM H5151-1:2010-12-15

AssemblySafety valves have to be installed at an easy accessible position at the highest point of the heatgenerator of in close proximity in the flow pipe of the heat generator.

Between the heat generator and the safety valve no shut-off device may be located!

Each safety valve has to be built in vertical position and has to have its own rising pipe withmaximum 1 m lenght as well as its own air outlet pipe. The air outlet pipe has to be onedimension larger than the connecting pipe to the safety valve. For details please compare therelevant standards.

Caution!

The discharge pipe of the safety valve may not be installed with a rise!

Especially important is a low flow resistance of this exhaust pipe. Hence it should freely

lead into a proper discharge hopper as close as possible to the safety valve and the

exhaust pipe must be as short as possible.

Too long exhaust pipes with too high flow resistance may result in a defective membrane

of the safety valve during blowing. This is even necessary to prevent the plant from

exceeding pressure also in case of inadequate installation. Such damages are never

covered by any kind of guarantee.

Page 3: EN - brochure safety valve v1 - EDER Heizung€¦ · maximum 1 m lenght as well as its own air ... Safety valves are built according to EN-ISO 4126-1 „safety devices for ... EN

3

TECHNICAL DATA

Performance table and available types

set pressure p [ bar ]SV

max. permitted heating capacity of the water heatingsystem related to the input-sided size and the[ kW ],

actuation over-pressure p [ bar ]SV

3 120 128 354 729 949 1322

4 undeliver-able

undeliver-able 436 898 1168 1626

5 undeliver-able

undeliver-able 515 1060 1378 1920

6 200 213 591 1216 1582 2203

8 undeliver-able

undeliver-able 743 1529 1989 2770

10 undeliver-able

undeliver-able 889 1830 2380 3315

t eyp SV 1/2" 3/4" 1" 5/4" 6/4" 2"

d simension A “ Rp 1/2 Rp 3/4 Rp 1 Rp 5/4 Rp 6/4 Rp 2

B “ Rp 3/4 Rp 1 Rp 5/4 Rp 6/4 Rp 2 Rp 2 1/2

sizes C mm 21 30 40 48 53 62

D mm 67 90 135 193 206 222

weight kg 0,15 0,25 0,6 1,65 2,15 3

Safety valves are built according to EN-ISO 4126-1 „safety devices for protection againstexcessive pressure”.

Other safety valve designs with divergent or special requirements on request! (e.g. specialactuation over-pressure, other max. heating capacity, safety valve with TÜV individualacceptance incl. individual setting certificate...)

SV 5/4" - SV 2"SV 1/2" - SV 1"SV 1/2" incl.anometerm

A

B

C

D

Page 4: EN - brochure safety valve v1 - EDER Heizung€¦ · maximum 1 m lenght as well as its own air ... Safety valves are built according to EN-ISO 4126-1 „safety devices for ... EN

4

www.eder-heizung.at

ANTON EDER GMBHStahl- & Kesselbau, Energie- & VerfahrenstechnikBramberg | Lienz | Salzburg | WienWeyerstraße 350 | A-5733 Bramberg | Tel: 06566/7366 Fax: 06566/8127 | Mail: [email protected]

elko-mat eder multicontrol MCK

elko-mat eder multicontrol MCM

elko-mat eder topcontrol TCM

elko-flex eder

BETTER HEATING. SAFE BET.

plant complexity(generating capacity,

static height,total content,

working pressure)