EMTP simul(14)

  • Upload
    kjfen

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

  • 7/27/2019 EMTP simul(14)

    1/14

    156 Power systems electromagnetic transients simulation

    Table 6.8 Pole/zero information from PSCAD V2 (attenuationfunction)

    Zeros7.631562e+03Poles6.485341e+034.761763e+045.469828e+055.582246e+05H 9.952270e01

    and the reverse transform:

    VaVb

    Vc

    =

    1

    K2

    1 1 1

    1 a2 a

    1 a a2

    .

    V0V+

    V

    where a = ej120 = 1/2 + j

    3/2.

    The power industry uses values of K1 = 3 and K2 = 1, but in the normalisedversion both K1 and K2 are equal to

    3. Although the choice of factors affect the

    sequence voltages and currents, the sequence impedances are unaffected by them.

    6.7 Summary

    For all except very short transmission lines, travelling wave transmission line models

    are preferable. If frequency dependence is important then a frequency transmission

    line dependent model will be used. Details of transmission line geometry and conduc-

    tor data are then required in order to calculate accurately the frequency-dependent

    electrical parameters of the line. The simulation time step must be based on the

    shortest response time of the line.

    Many variants of frequency-dependent multiconductor transmission line models

    exist. A widely used model is based on ignoring the frequency dependence of the

    transformation matrix between phase and mode domains (i.e. the J. Marti model inEMTP [14]).

    At present phase-domain models are the most accurate and robust for detailed

    transmission line representation. Given the complexity and variety of underground

    cables, a rigorous unified solution similar to that of the overhead line is only possible

    based on a standard cross-section structure and under various simplifying assump-

    tions. Instead, power companies often use correction factors, based on experience,

    for skin effect representation.

    6.8 References

    1 CARSON, J. R.: Wave propagation in overhead wires with ground return, Bell

    System Technical Journal, 1926, 5, pp. 53954

  • 7/27/2019 EMTP simul(14)

    2/14

    Transmission lines and cables 157

    2 POLLACZEK, F.: On the field produced by an infinitely long wire carrying

    alternating current, Elektrische Nachrichtentechnik, 1926, 3, pp. 33959

    3 POLLACZEK, F.: On the induction effects of a single phase ac line, Elektrische

    Nachrichtentechnik, 1927, 4, pp. 1830

    4 GUSTAVSEN, B. and SEMLYEN, A.: Simulation of transmission line tran-

    sients using vector fitting and modal decomposition,IEEE Transactions on Power

    Delivery, 1998, 13 (2), pp. 60514

    5 BERGERON, L.: Du coup de Belier en hydraulique au coup de foudre en elec-

    tricite (Dunod, 1949). (English translation: Water hammer in hydraulics and

    wave surges in electricity, ASME Committee, Wiley, New York, 1961.)

    6 WEDEPOHL, L. M., NGUYEN, H. V. and IRWIN, G. D.: Frequency-

    dependent transformation matrices for untransposed transmission lines using

    Newton-Raphson method, IEEE Transactions on Power Systems, 1996, 11 (3),

    pp. 1538467 CLARKE, E.: Circuit analysis of AC systems, symmetrical and related

    components (General Electric Co., Schenectady, NY, 1950)

    8 SEMLYEN, A. and DABULEANU, A.: Fast and accurate switching transient cal-

    culations on transmission lines with ground return using recursive convolutions,

    IEEE Transactions on Power Apparatus and Systems, 1975, 94 (2), pp. 56171

    9 SEMLYEN, A.: Contributions to the theory of calculation of electromagnetic

    transients on transmission lines with frequency dependent parameters, IEEE

    Transactions on Power Apparatus and Systems, 1981, 100 (2), pp. 84856

    10 MORCHED, A., GUSTAVSEN, B. and TARTIBI, M.: A universal modelfor accurate calculation of electromagnetic transients on overhead lines and

    underground cables, IEEE Transactions on Power Delivery, 1999, 14 (3),

    pp. 10328

    11 DERI, A., TEVAN, G., SEMLYEN, A. and CASTANHEIRA, A.: The complex

    ground return plane, a simplified model for homogenous and multi-layer earth

    return, IEEE Transactions on Power Apparatus and Systems, 1981, 100 (8),

    pp. 368693

    12 BIANCHI, G. and LUONI, G.: Induced currents and losses in single-core sub-

    marine cables, IEEE Transactions on Power Apparatus and Systems, 1976, 95,pp. 4958

    13 NODA, T.: Development of a transmission-line model considering the skin

    and corona effects for power systems transient analysis (Ph.D. thesis, Doshisha

    University, Kyoto, Japan, December 1996)

    14 MARTI, J. R.: Accurate modelling of frequency-dependent transmission lines in

    electromagnetic transient simulations, IEEE Transactions on Power Apparatus

    and Systems, 1982, 101 (1), pp. 14757

  • 7/27/2019 EMTP simul(14)

    3/14

  • 7/27/2019 EMTP simul(14)

    4/14

    Chapter 7

    Transformers and rotating plant

    7.1 Introduction

    The simulation of electrical machines, whether static or rotative, requires an

    understanding of the electromagnetic characteristics of their respective windings and

    cores. Due to their basically symmetrical design, rotating machines are simpler in this

    respect. On the other hand the latters transient behaviour involves electromechani-

    cal as well as electromagnetic interactions. Electrical machines are discussed in this

    chapter with emphasis on their magnetic properties. The effects of winding capaci-

    tances are generally negligible for studies other than those involving fast fronts (such

    as lightning and switching).

    The first part of the chapter describes the dynamic behaviour and computer sim-ulation of single-phase, multiphase and multilimb transformers, including saturation

    effects [1]. Early models used with electromagnetic transient programs assumed a

    uniform flux throughout the core legs and yokes, the individual winding leakages

    were combined and the magnetising current was placed on one side of the resultant

    series leakage reactance. An advanced multilimb transformer model is also described,

    based on unified magnetic equivalent circuit recently implemented in the EMTDC

    program.

    In the second part, the chapter develops a general dynamic model of the rotating

    machine, with emphasis on the synchronous generator. The model includes an accu-

    rate representation of the electrical generator behaviour as well as the mechanical

    characteristics of the generator and the turbine. In most cases the speed variations

    and torsional vibrations can be ignored and the mechanical part can be left out of the

    simulation.

  • 7/27/2019 EMTP simul(14)

    5/14

    160 Power systems electromagnetic transients simulation

    7.2 Basic transformer model

    The equivalent circuit of the basic transformer model, shown in Figure 7.1, consists

    of two mutually coupled coils. The voltages across these coils is expressed as:v1v2

    =

    L11 L21L12 L22

    d

    dt

    i1i2

    (7.1)

    where L11 and L22 are the self-inductance of winding 1 and 2 respectively, and L12and L21 are the mutual inductance between the windings.

    In order to solve for the winding currents the inductance matrix has to be

    inverted, i.e.

    d

    dti

    1i2 = 1L11L22 L12L21 L22 L21L12 L11 v1v2 (7.2)

    Since the mutual coupling is bilateral, L12 and L21 are identical. The coupling

    coefficient between the two coils is:

    K12 =L12

    L11L22(7.3)

    Rewriting equation 7.1 using the turns ratio (a = v1/v2) gives:

    v1av2

    =

    L11 L21aL12 a

    2L22

    d

    dt

    i1

    i2/a

    (7.4)

    This equation can be represented by the equivalent circuit shown in Figure 7.2,

    where

    L1 = L11 a L12 (7.5)L2 = a2L22 aL12 (7.6)

    Consider a transformer with a 10% leakage reactance equally divided betweenthe two windings and a magnetising current of 0.01 p.u. Then the input impedance

    with the second winding open circuited must be 100 p.u. (Note from equation 7.5,

    av2

    i1 L1 L2

    aL12

    R1 R2 ai2i2

    v1 v2

    Ideal

    transformer

    a : 1

    Figure 7.1 Equivalent circuit of the two-winding transformer

  • 7/27/2019 EMTP simul(14)

    6/14

    Transformers and rotating plant 161

    Ideal

    transformer

    a : 1

    v2v1

    i1L1 L2 i2

    Figure 7.2 Equivalent circuit of the two-winding transformer, without the magnetis-ing branch

    Ideal

    transformer

    1 : 1

    i1 i2 i2L1=0.05p.u.

    L2=0.05p.u.

    L12= 100p.u.v2v1 v2

    Figure 7.3 Transformer example

    L1 + L12 = L11 since a = 1 in the per unit system.) Hence the equivalent inFigure 7.3 is obtained, the corresponding equation (in p.u.) being:

    v1v2

    =

    100.0 99.95

    99.95 100.0

    d

    dt

    i1i2

    (7.7)

    or in actual values:

    v1v2

    = 1

    SBase

    100.0 v2Base_1 99.95 vBase_1vBase_2

    99.95 vBase_1vBase_2 100.0 v2Base_2

    d

    dt

    i1i2

    volts

    (7.8)

    7.2.1 Numerical implementation

    Separating equation 7.2 into its components:

    di1

    dt =L

    22L11L22 L12L21 v1

    L21

    L11L22 L12L21 v2 (7.9)

    di2

    dt= L12

    L11L22 L12L21v1 +

    L11

    L11L22 L12L21v2 (7.10)

  • 7/27/2019 EMTP simul(14)

    7/14

    162 Power systems electromagnetic transients simulation

    Solving equation 7.9 by trapezoidal integration yields:

    i1(t ) =L22

    L11L22

    L12L21

    t

    0

    v1 dtL21

    L11L22

    L12L21

    t

    0

    v2 dt

    = i1(t t) +L22

    L11L22 L12L21

    ttt

    v1 dt

    L21L11L22 L12L21

    ttt

    v2 dt

    = i1(t t) +L22t

    2(L11L22 L12L21)(v1(t t) + v1(t))

    L21t

    2(L11L22 L12L21)(v2(t

    t)

    +v2(t)) (7.11)

    Collecting together the past History and Instantaneous terms gives:

    i1(t) = Ih(t t) +

    L22t

    2(L11L22 L12L21) L21t

    2(L11L22 L12L21)

    v1(t)

    + L21t2(L11L22 L12L21)

    (v1(t) v2(t)) (7.12)

    where

    Ih(t t) = i1(t t)

    +

    L22t

    2(L11L22 L12L21) L21t

    2(L11L22 L12L21)

    v1(t t )

    + L21t2(L11L22 L12L21)

    (v1(t t) v2(t t)) (7.13)

    A similar expression can be written for i2(t ). The model that these equations represents

    is shown in Figure 7.4. It should be noted that the discretisation of these models using

    the trapezoidal rule does not give complete isolation between its terminals for d.c. Ifa d.c. source is applied to winding 1 a small amount will flow in winding 2, which

    in practice would not occur. Simulation of the test system shown in Figure 7.5 will

    clearly demonstrate this problem. This test system also shows ill-conditioning in

    the inductance matrix when the magnetising current is reduced from 1 per cent to

    0.1 per cent.

    7.2.2 Parameters derivation

    Transformer data is not normally given in the form used in the previous section. Either

    results from short-circuit and open-circuit tests are available or the magnetising currentand leakage reactance are given in p.u. quantities based on machine rating.

    In the circuit of Figure 7.1, shorting winding 2 and neglecting the resistance gives:

    I1 =V1

    (L1 + L2)(7.14)

  • 7/27/2019 EMTP simul(14)

    8/14

    Transformers and rotating plant 163

    2(LkkLmmLkmLmk)

    tLmk

    2(LkkLmmLkmLmk)

    t(LmmLmk)

    2(LkkLmmLkmLmk)

    t(LkkLmk)

    Im (tt)Ik(tt)

    Figure 7.4 Transformer equivalent after discretisation

    L=0.1H

    R=1000110 kV 110 kV110kV

    Leakage = 0.1p.u.

    Figure 7.5 Transformer test system

    Similarly, open-circuit tests with windings 2 or 1 open-circuited, respectively give:

    I1 =V1

    (L1 + aL12)(7.15)

    I2 =a2V2

    (L2 + aL12) (7.16)

    Short and open circuit testsprovide enough information to determine aL12, L1 and L2.

    These calculations are often performed internally in the transient simulation program,

    and the user only needs to enter directly the leakage and magnetising reactances.

    The inductance matrix contains information to derive the magnetising current

    and also, indirectly through the small differences between L11 and L12, the leakage

    (short-circuit) reactance.

    The leakage reactance is given by:

    LLeakage = L11 L221/L22 (7.17)

    In most studies the leakage reactance has the greatest influence on the results. Thus the

    values of the inductance matrix must be specified very accurately to reduce errors due

    to loss of significance caused by subtracting two numbers of very similar magnitude.

  • 7/27/2019 EMTP simul(14)

    9/14

    164 Power systems electromagnetic transients simulation

    Mathematically the inductance becomes ill-conditioned as the magnetising current

    gets smaller (it is singular if the magnetising current is zero). The matrix equation

    expressing the relationships between the derivatives of current and voltage is:

    ddx

    i1i2

    = 1

    L

    1 aa a2

    v1v2

    (7.18)

    where L = L1 + a2L2. This represents the equivalent circuit shown in Figure 7.2.

    7.2.3 Modelling of non-linearities

    The magnetic non-linearity and core loss components are usually incorporated by

    means of a shunt current source and resistance respectively, across one winding. Since

    the single-phase approximation does not incorporate inter-phase magnetic coupling,

    the magnetising current injection is calculated at each time step independently of the

    other phases.

    Figure 7.6 displays the modelling of saturation in mutually coupled windings.

    The current source representation is used, rather than varying the inductance, as the

    latter would require retriangulation of the matrix every time the inductance changes.

    During start-up it is recommended to inhibit saturation and this is achieved by using

    a flux limit for the result of voltage integration. This enables the steady state to be

    reached faster. Prior to the application of the disturbance the flux limit is removed,

    thus allowing the flux to go into the saturation region.

    Another refinement, illustrated in Figure 7.7, is to impose a decay time on thein-rush currents, as would occur on energisation or fault recovery.

    Typical studies requiring the modelling of saturation are: In-rush current on ener-

    gising a transformer, steady-state overvoltage studies, core-saturation instabilities and

    ferro-resonance.

    A three-phase bank can be modelled by the correct connection of three two-

    coupled windings. For example the wye/delta connection is achieved as shown

    in Figure 7.8, which produces the correct phase shift automatically between the

    s

    Is

    Integration

    Is (t)

    v2 (t)

    Figure 7.6 Non-linear transformer

  • 7/27/2019 EMTP simul(14)

    10/14

    Transformers and rotating plant 165

    s

    Is

    Integration

    Is (t)

    v2 (t)+

    2TDecay1

    Figure 7.7 Non-linear transformer model with in-rush

    LB

    LA

    HB

    HA

    HC

    LC

    Figure 7.8 Stardelta three-phase transformer

    primary and secondary windings (secondary lagging primary by 30 degrees in the

    case shown) [2].

    7.3 Advanced transformer models

    To take into account the magnetising currents and core configuration of multilimb

    transformers the EMTP package has developed a program based on the principle

  • 7/27/2019 EMTP simul(14)

    11/14

    166 Power systems electromagnetic transients simulation

    of duality [3]. The resulting duality-based equivalents involve a large number of

    components; for instance, 23 inductances and nine ideal transformers are required

    to represent the three-phase three-winding transformer. Additional components are

    used to isolate the true non-linear series inductors required by the duality method, as

    their implementation in the EMTP program is not feasible [4].

    To reduce the complexity of the equivalent circuit two alternatives based on an

    equivalent inductance matrix have been proposed. However one of them [5] does not

    take into account the core non-linearity under transient conditions. In the second [6],

    the non-linear inductance matrix requires regular updating during the EMTP solution,

    thus reducing considerably the program efficiency.

    Another model [7] proposes the use of a Norton equivalent representation for

    the transformer as a simple interface with the EMTP program. This model does not

    perform a direct analysis of the magnetic circuit; instead it uses a combination of the

    duality and leakage inductance representation.The rest of this section describes a model also based on the Norton equiva-

    lent but derived directly from magnetic equivalent circuit analysis [8], [9]. It is

    called the UMEC (Unified Magnetic Equivalent Circuit) model and has been recently

    implemented in the EMTDC program.

    The UMEC principle is first described with reference to the single-phase

    transformer and later extended to the multilimb case.

    7.3.1 Single-phase UMEC model

    The single-phase transformer, shown in Figure 7.9(a), can be represented by the

    UMEC of Figure 7.9(b). The m.m.f. sources N1i1(t ) and N2i2(t) represent each

    winding individually. The primary and secondary winding voltages, v1(t ) and v2(t),

    are used to calculate the winding limb fluxes 1(t) and 2(t ), respectively. The

    i1

    4

    3

    3

    25

    4 (t)

    1 (t)

    3 (t)

    2 (t)

    5 (t)

    N1i1(t)

    N2i2 (t)

    1v1 v2

    i2P4

    P5

    P2

    P1

    P3

    +

    +

    Magnetic circuits(a) (b)

    Figure 7.9 UMEC single-phase transformer model: (a) core flux paths; (b) unifiedmagnetic equivalent circuit

  • 7/27/2019 EMTP simul(14)

    12/14

    Transformers and rotating plant 167

    k

    Mk1

    Mk2

    Nkikvk

    ik

    Mk

    Figure 7.10 Magnetic equivalent circuit for branch

    winding limb flux divides between leakage and yoke paths and, thus, a uniform core

    flux is not assumed.

    Although single-phase transformer windings are not generally wound separately

    on different limbs, each winding can be separated in the UMEC. In Figure 7.9(b)

    P1 and P2 represent the permeances of transformer winding limbs and P3 that of

    the transformer yokes. If the total length of core surrounded by windings Lw has a

    uniform cross-sectional area Aw, then A1 = A2 = Aw1. The upper and lower yokesare assumed to have the same length Ly and cross-sectional area Ay. Both yokes are

    represented by the single UMEC branch 3 of length L3

    =2Ly and area A3

    =Ay.

    Leakage information is obtained from the open and short-circuit tests and, therefore,the effective lengths and cross-sectional areas of leakage flux paths are not required

    to calculate the leakage permeances P4 and P5.

    Figure 7.10 shows a transformer branch where the branch reluctance and winding

    magnetomotive force (m.m.f.) components have been separated.

    The non-linear relationship between branch flux (k ) and branch m.m.f. drop

    (Mk1) is

    Mk1 = rk (k ) (7.19)

    where rk is the magnetising characteristic (shown in Figure 7.11).

    The m.m.f. of winding Nk is:

    Mk2 = Nk ik (7.20)

  • 7/27/2019 EMTP simul(14)

    13/14

    168 Power systems electromagnetic transients simulation

    Branch m.m.f

    Branchflux

    k(t)

    Mkl(t)

    nk

    (a) Slope = incremental permeance

    (b) Slope = actual permeance

    Figure 7.11 Incremental and actual permeance

    The resultant branch m.m.f. Mk2 is thusMk2 = Mk2 Mk1 (7.21)

    The magnetising characteristic displayed in Figure 7.11 shows that, as the transformer

    core moves around the knee region, the change in incremental permeance (Pk ) is

    much larger and more sudden (especially in the case of highly efficient cores) than

    the change in actual permeance

    Pk

    . Although the incremental permeance forms

    the basis of steady-state transformer modelling, the use of the actual permeance is

    favoured for the transformer representation in dynamic simulation.

    In the UMEC branch the flux is expressed using the actual permeance

    Pk

    , i.e.

    k (t ) = Pk Mk1(t) (7.22)

    From Figure 7.11, k can be expressed as

    k = Pk

    Nk ik Mk

    (7.23)

    which written in vector form

    =

    Pk [Nk]ik Mk

    (7.24)

    represents all the branches of a multilimb transformer.

  • 7/27/2019 EMTP simul(14)

    14/14

    Transformers and rotating plant 169

    7.3.1.1 UMEC Norton equivalent

    The linearised relationship between winding current and branch flux can be extended

    to incorporate the magnetic equivalent-circuit branch connections. Let the node

    branch connection matrix of the magnetic circuit be [A] and the vector of nodalmagnetic drops Node. At each node the flux must sum to zero, i.e.

    [A]Node = 0 (7.25)

    Application of the branchnode connection matrix to the vector of nodal magnetic

    drops gives the branch m.m.f.

    [A]MNode = M (7.26)

    Combining equations 7.24, 7.25 and 7.26 finally yields:

    = [Q][P][N]i (7.27)

    where

    [Q] = [I] [P][A][A]T[P][A]

    1[A]T (7.28)

    The winding voltage vk is related to the branch flux k by:

    vk = Nk dkdt

    (7.29)

    Using the trapezoidal integration rule to discretise equation 7.29 gives:

    s (t ) = s (t t) +t

    2[Ns]1(vs (t) + vs (t t)) (7.30)

    where

    s (t t ) = s (t 2t ) +t

    2 [Ns]1

    (vs (t t) + vs (t 2t)) (7.31)

    Partitioning the vector of branch flux into branches associated with each

    transformer winding s and using equation 7.30 leads to the Norton equivalent:

    is (t) =

    Yss

    vs (t ) + ins (t ) (7.32)

    where

    Yss = Qss Ps [Ns]

    1 t

    2 [Ns

    ]1 (7.33)

    and

    ins (t ) =

    Qss

    Ps[Ns]

    1 t2[Ns]1vs (t t) + (t t )

    (7.34)