Upload
kjfen
View
214
Download
0
Embed Size (px)
Citation preview
7/27/2019 EMTP simul(14)
1/14
156 Power systems electromagnetic transients simulation
Table 6.8 Pole/zero information from PSCAD V2 (attenuationfunction)
Zeros7.631562e+03Poles6.485341e+034.761763e+045.469828e+055.582246e+05H 9.952270e01
and the reverse transform:
VaVb
Vc
=
1
K2
1 1 1
1 a2 a
1 a a2
.
V0V+
V
where a = ej120 = 1/2 + j
3/2.
The power industry uses values of K1 = 3 and K2 = 1, but in the normalisedversion both K1 and K2 are equal to
3. Although the choice of factors affect the
sequence voltages and currents, the sequence impedances are unaffected by them.
6.7 Summary
For all except very short transmission lines, travelling wave transmission line models
are preferable. If frequency dependence is important then a frequency transmission
line dependent model will be used. Details of transmission line geometry and conduc-
tor data are then required in order to calculate accurately the frequency-dependent
electrical parameters of the line. The simulation time step must be based on the
shortest response time of the line.
Many variants of frequency-dependent multiconductor transmission line models
exist. A widely used model is based on ignoring the frequency dependence of the
transformation matrix between phase and mode domains (i.e. the J. Marti model inEMTP [14]).
At present phase-domain models are the most accurate and robust for detailed
transmission line representation. Given the complexity and variety of underground
cables, a rigorous unified solution similar to that of the overhead line is only possible
based on a standard cross-section structure and under various simplifying assump-
tions. Instead, power companies often use correction factors, based on experience,
for skin effect representation.
6.8 References
1 CARSON, J. R.: Wave propagation in overhead wires with ground return, Bell
System Technical Journal, 1926, 5, pp. 53954
7/27/2019 EMTP simul(14)
2/14
Transmission lines and cables 157
2 POLLACZEK, F.: On the field produced by an infinitely long wire carrying
alternating current, Elektrische Nachrichtentechnik, 1926, 3, pp. 33959
3 POLLACZEK, F.: On the induction effects of a single phase ac line, Elektrische
Nachrichtentechnik, 1927, 4, pp. 1830
4 GUSTAVSEN, B. and SEMLYEN, A.: Simulation of transmission line tran-
sients using vector fitting and modal decomposition,IEEE Transactions on Power
Delivery, 1998, 13 (2), pp. 60514
5 BERGERON, L.: Du coup de Belier en hydraulique au coup de foudre en elec-
tricite (Dunod, 1949). (English translation: Water hammer in hydraulics and
wave surges in electricity, ASME Committee, Wiley, New York, 1961.)
6 WEDEPOHL, L. M., NGUYEN, H. V. and IRWIN, G. D.: Frequency-
dependent transformation matrices for untransposed transmission lines using
Newton-Raphson method, IEEE Transactions on Power Systems, 1996, 11 (3),
pp. 1538467 CLARKE, E.: Circuit analysis of AC systems, symmetrical and related
components (General Electric Co., Schenectady, NY, 1950)
8 SEMLYEN, A. and DABULEANU, A.: Fast and accurate switching transient cal-
culations on transmission lines with ground return using recursive convolutions,
IEEE Transactions on Power Apparatus and Systems, 1975, 94 (2), pp. 56171
9 SEMLYEN, A.: Contributions to the theory of calculation of electromagnetic
transients on transmission lines with frequency dependent parameters, IEEE
Transactions on Power Apparatus and Systems, 1981, 100 (2), pp. 84856
10 MORCHED, A., GUSTAVSEN, B. and TARTIBI, M.: A universal modelfor accurate calculation of electromagnetic transients on overhead lines and
underground cables, IEEE Transactions on Power Delivery, 1999, 14 (3),
pp. 10328
11 DERI, A., TEVAN, G., SEMLYEN, A. and CASTANHEIRA, A.: The complex
ground return plane, a simplified model for homogenous and multi-layer earth
return, IEEE Transactions on Power Apparatus and Systems, 1981, 100 (8),
pp. 368693
12 BIANCHI, G. and LUONI, G.: Induced currents and losses in single-core sub-
marine cables, IEEE Transactions on Power Apparatus and Systems, 1976, 95,pp. 4958
13 NODA, T.: Development of a transmission-line model considering the skin
and corona effects for power systems transient analysis (Ph.D. thesis, Doshisha
University, Kyoto, Japan, December 1996)
14 MARTI, J. R.: Accurate modelling of frequency-dependent transmission lines in
electromagnetic transient simulations, IEEE Transactions on Power Apparatus
and Systems, 1982, 101 (1), pp. 14757
7/27/2019 EMTP simul(14)
3/14
7/27/2019 EMTP simul(14)
4/14
Chapter 7
Transformers and rotating plant
7.1 Introduction
The simulation of electrical machines, whether static or rotative, requires an
understanding of the electromagnetic characteristics of their respective windings and
cores. Due to their basically symmetrical design, rotating machines are simpler in this
respect. On the other hand the latters transient behaviour involves electromechani-
cal as well as electromagnetic interactions. Electrical machines are discussed in this
chapter with emphasis on their magnetic properties. The effects of winding capaci-
tances are generally negligible for studies other than those involving fast fronts (such
as lightning and switching).
The first part of the chapter describes the dynamic behaviour and computer sim-ulation of single-phase, multiphase and multilimb transformers, including saturation
effects [1]. Early models used with electromagnetic transient programs assumed a
uniform flux throughout the core legs and yokes, the individual winding leakages
were combined and the magnetising current was placed on one side of the resultant
series leakage reactance. An advanced multilimb transformer model is also described,
based on unified magnetic equivalent circuit recently implemented in the EMTDC
program.
In the second part, the chapter develops a general dynamic model of the rotating
machine, with emphasis on the synchronous generator. The model includes an accu-
rate representation of the electrical generator behaviour as well as the mechanical
characteristics of the generator and the turbine. In most cases the speed variations
and torsional vibrations can be ignored and the mechanical part can be left out of the
simulation.
7/27/2019 EMTP simul(14)
5/14
160 Power systems electromagnetic transients simulation
7.2 Basic transformer model
The equivalent circuit of the basic transformer model, shown in Figure 7.1, consists
of two mutually coupled coils. The voltages across these coils is expressed as:v1v2
=
L11 L21L12 L22
d
dt
i1i2
(7.1)
where L11 and L22 are the self-inductance of winding 1 and 2 respectively, and L12and L21 are the mutual inductance between the windings.
In order to solve for the winding currents the inductance matrix has to be
inverted, i.e.
d
dti
1i2 = 1L11L22 L12L21 L22 L21L12 L11 v1v2 (7.2)
Since the mutual coupling is bilateral, L12 and L21 are identical. The coupling
coefficient between the two coils is:
K12 =L12
L11L22(7.3)
Rewriting equation 7.1 using the turns ratio (a = v1/v2) gives:
v1av2
=
L11 L21aL12 a
2L22
d
dt
i1
i2/a
(7.4)
This equation can be represented by the equivalent circuit shown in Figure 7.2,
where
L1 = L11 a L12 (7.5)L2 = a2L22 aL12 (7.6)
Consider a transformer with a 10% leakage reactance equally divided betweenthe two windings and a magnetising current of 0.01 p.u. Then the input impedance
with the second winding open circuited must be 100 p.u. (Note from equation 7.5,
av2
i1 L1 L2
aL12
R1 R2 ai2i2
v1 v2
Ideal
transformer
a : 1
Figure 7.1 Equivalent circuit of the two-winding transformer
7/27/2019 EMTP simul(14)
6/14
Transformers and rotating plant 161
Ideal
transformer
a : 1
v2v1
i1L1 L2 i2
Figure 7.2 Equivalent circuit of the two-winding transformer, without the magnetis-ing branch
Ideal
transformer
1 : 1
i1 i2 i2L1=0.05p.u.
L2=0.05p.u.
L12= 100p.u.v2v1 v2
Figure 7.3 Transformer example
L1 + L12 = L11 since a = 1 in the per unit system.) Hence the equivalent inFigure 7.3 is obtained, the corresponding equation (in p.u.) being:
v1v2
=
100.0 99.95
99.95 100.0
d
dt
i1i2
(7.7)
or in actual values:
v1v2
= 1
SBase
100.0 v2Base_1 99.95 vBase_1vBase_2
99.95 vBase_1vBase_2 100.0 v2Base_2
d
dt
i1i2
volts
(7.8)
7.2.1 Numerical implementation
Separating equation 7.2 into its components:
di1
dt =L
22L11L22 L12L21 v1
L21
L11L22 L12L21 v2 (7.9)
di2
dt= L12
L11L22 L12L21v1 +
L11
L11L22 L12L21v2 (7.10)
7/27/2019 EMTP simul(14)
7/14
162 Power systems electromagnetic transients simulation
Solving equation 7.9 by trapezoidal integration yields:
i1(t ) =L22
L11L22
L12L21
t
0
v1 dtL21
L11L22
L12L21
t
0
v2 dt
= i1(t t) +L22
L11L22 L12L21
ttt
v1 dt
L21L11L22 L12L21
ttt
v2 dt
= i1(t t) +L22t
2(L11L22 L12L21)(v1(t t) + v1(t))
L21t
2(L11L22 L12L21)(v2(t
t)
+v2(t)) (7.11)
Collecting together the past History and Instantaneous terms gives:
i1(t) = Ih(t t) +
L22t
2(L11L22 L12L21) L21t
2(L11L22 L12L21)
v1(t)
+ L21t2(L11L22 L12L21)
(v1(t) v2(t)) (7.12)
where
Ih(t t) = i1(t t)
+
L22t
2(L11L22 L12L21) L21t
2(L11L22 L12L21)
v1(t t )
+ L21t2(L11L22 L12L21)
(v1(t t) v2(t t)) (7.13)
A similar expression can be written for i2(t ). The model that these equations represents
is shown in Figure 7.4. It should be noted that the discretisation of these models using
the trapezoidal rule does not give complete isolation between its terminals for d.c. Ifa d.c. source is applied to winding 1 a small amount will flow in winding 2, which
in practice would not occur. Simulation of the test system shown in Figure 7.5 will
clearly demonstrate this problem. This test system also shows ill-conditioning in
the inductance matrix when the magnetising current is reduced from 1 per cent to
0.1 per cent.
7.2.2 Parameters derivation
Transformer data is not normally given in the form used in the previous section. Either
results from short-circuit and open-circuit tests are available or the magnetising currentand leakage reactance are given in p.u. quantities based on machine rating.
In the circuit of Figure 7.1, shorting winding 2 and neglecting the resistance gives:
I1 =V1
(L1 + L2)(7.14)
7/27/2019 EMTP simul(14)
8/14
Transformers and rotating plant 163
2(LkkLmmLkmLmk)
tLmk
2(LkkLmmLkmLmk)
t(LmmLmk)
2(LkkLmmLkmLmk)
t(LkkLmk)
Im (tt)Ik(tt)
Figure 7.4 Transformer equivalent after discretisation
L=0.1H
R=1000110 kV 110 kV110kV
Leakage = 0.1p.u.
Figure 7.5 Transformer test system
Similarly, open-circuit tests with windings 2 or 1 open-circuited, respectively give:
I1 =V1
(L1 + aL12)(7.15)
I2 =a2V2
(L2 + aL12) (7.16)
Short and open circuit testsprovide enough information to determine aL12, L1 and L2.
These calculations are often performed internally in the transient simulation program,
and the user only needs to enter directly the leakage and magnetising reactances.
The inductance matrix contains information to derive the magnetising current
and also, indirectly through the small differences between L11 and L12, the leakage
(short-circuit) reactance.
The leakage reactance is given by:
LLeakage = L11 L221/L22 (7.17)
In most studies the leakage reactance has the greatest influence on the results. Thus the
values of the inductance matrix must be specified very accurately to reduce errors due
to loss of significance caused by subtracting two numbers of very similar magnitude.
7/27/2019 EMTP simul(14)
9/14
164 Power systems electromagnetic transients simulation
Mathematically the inductance becomes ill-conditioned as the magnetising current
gets smaller (it is singular if the magnetising current is zero). The matrix equation
expressing the relationships between the derivatives of current and voltage is:
ddx
i1i2
= 1
L
1 aa a2
v1v2
(7.18)
where L = L1 + a2L2. This represents the equivalent circuit shown in Figure 7.2.
7.2.3 Modelling of non-linearities
The magnetic non-linearity and core loss components are usually incorporated by
means of a shunt current source and resistance respectively, across one winding. Since
the single-phase approximation does not incorporate inter-phase magnetic coupling,
the magnetising current injection is calculated at each time step independently of the
other phases.
Figure 7.6 displays the modelling of saturation in mutually coupled windings.
The current source representation is used, rather than varying the inductance, as the
latter would require retriangulation of the matrix every time the inductance changes.
During start-up it is recommended to inhibit saturation and this is achieved by using
a flux limit for the result of voltage integration. This enables the steady state to be
reached faster. Prior to the application of the disturbance the flux limit is removed,
thus allowing the flux to go into the saturation region.
Another refinement, illustrated in Figure 7.7, is to impose a decay time on thein-rush currents, as would occur on energisation or fault recovery.
Typical studies requiring the modelling of saturation are: In-rush current on ener-
gising a transformer, steady-state overvoltage studies, core-saturation instabilities and
ferro-resonance.
A three-phase bank can be modelled by the correct connection of three two-
coupled windings. For example the wye/delta connection is achieved as shown
in Figure 7.8, which produces the correct phase shift automatically between the
s
Is
Integration
Is (t)
v2 (t)
Figure 7.6 Non-linear transformer
7/27/2019 EMTP simul(14)
10/14
Transformers and rotating plant 165
s
Is
Integration
Is (t)
v2 (t)+
2TDecay1
Figure 7.7 Non-linear transformer model with in-rush
LB
LA
HB
HA
HC
LC
Figure 7.8 Stardelta three-phase transformer
primary and secondary windings (secondary lagging primary by 30 degrees in the
case shown) [2].
7.3 Advanced transformer models
To take into account the magnetising currents and core configuration of multilimb
transformers the EMTP package has developed a program based on the principle
7/27/2019 EMTP simul(14)
11/14
166 Power systems electromagnetic transients simulation
of duality [3]. The resulting duality-based equivalents involve a large number of
components; for instance, 23 inductances and nine ideal transformers are required
to represent the three-phase three-winding transformer. Additional components are
used to isolate the true non-linear series inductors required by the duality method, as
their implementation in the EMTP program is not feasible [4].
To reduce the complexity of the equivalent circuit two alternatives based on an
equivalent inductance matrix have been proposed. However one of them [5] does not
take into account the core non-linearity under transient conditions. In the second [6],
the non-linear inductance matrix requires regular updating during the EMTP solution,
thus reducing considerably the program efficiency.
Another model [7] proposes the use of a Norton equivalent representation for
the transformer as a simple interface with the EMTP program. This model does not
perform a direct analysis of the magnetic circuit; instead it uses a combination of the
duality and leakage inductance representation.The rest of this section describes a model also based on the Norton equiva-
lent but derived directly from magnetic equivalent circuit analysis [8], [9]. It is
called the UMEC (Unified Magnetic Equivalent Circuit) model and has been recently
implemented in the EMTDC program.
The UMEC principle is first described with reference to the single-phase
transformer and later extended to the multilimb case.
7.3.1 Single-phase UMEC model
The single-phase transformer, shown in Figure 7.9(a), can be represented by the
UMEC of Figure 7.9(b). The m.m.f. sources N1i1(t ) and N2i2(t) represent each
winding individually. The primary and secondary winding voltages, v1(t ) and v2(t),
are used to calculate the winding limb fluxes 1(t) and 2(t ), respectively. The
i1
4
3
3
25
4 (t)
1 (t)
3 (t)
2 (t)
5 (t)
N1i1(t)
N2i2 (t)
1v1 v2
i2P4
P5
P2
P1
P3
+
+
Magnetic circuits(a) (b)
Figure 7.9 UMEC single-phase transformer model: (a) core flux paths; (b) unifiedmagnetic equivalent circuit
7/27/2019 EMTP simul(14)
12/14
Transformers and rotating plant 167
k
Mk1
Mk2
Nkikvk
ik
Mk
Figure 7.10 Magnetic equivalent circuit for branch
winding limb flux divides between leakage and yoke paths and, thus, a uniform core
flux is not assumed.
Although single-phase transformer windings are not generally wound separately
on different limbs, each winding can be separated in the UMEC. In Figure 7.9(b)
P1 and P2 represent the permeances of transformer winding limbs and P3 that of
the transformer yokes. If the total length of core surrounded by windings Lw has a
uniform cross-sectional area Aw, then A1 = A2 = Aw1. The upper and lower yokesare assumed to have the same length Ly and cross-sectional area Ay. Both yokes are
represented by the single UMEC branch 3 of length L3
=2Ly and area A3
=Ay.
Leakage information is obtained from the open and short-circuit tests and, therefore,the effective lengths and cross-sectional areas of leakage flux paths are not required
to calculate the leakage permeances P4 and P5.
Figure 7.10 shows a transformer branch where the branch reluctance and winding
magnetomotive force (m.m.f.) components have been separated.
The non-linear relationship between branch flux (k ) and branch m.m.f. drop
(Mk1) is
Mk1 = rk (k ) (7.19)
where rk is the magnetising characteristic (shown in Figure 7.11).
The m.m.f. of winding Nk is:
Mk2 = Nk ik (7.20)
7/27/2019 EMTP simul(14)
13/14
168 Power systems electromagnetic transients simulation
Branch m.m.f
Branchflux
k(t)
Mkl(t)
nk
(a) Slope = incremental permeance
(b) Slope = actual permeance
Figure 7.11 Incremental and actual permeance
The resultant branch m.m.f. Mk2 is thusMk2 = Mk2 Mk1 (7.21)
The magnetising characteristic displayed in Figure 7.11 shows that, as the transformer
core moves around the knee region, the change in incremental permeance (Pk ) is
much larger and more sudden (especially in the case of highly efficient cores) than
the change in actual permeance
Pk
. Although the incremental permeance forms
the basis of steady-state transformer modelling, the use of the actual permeance is
favoured for the transformer representation in dynamic simulation.
In the UMEC branch the flux is expressed using the actual permeance
Pk
, i.e.
k (t ) = Pk Mk1(t) (7.22)
From Figure 7.11, k can be expressed as
k = Pk
Nk ik Mk
(7.23)
which written in vector form
=
Pk [Nk]ik Mk
(7.24)
represents all the branches of a multilimb transformer.
7/27/2019 EMTP simul(14)
14/14
Transformers and rotating plant 169
7.3.1.1 UMEC Norton equivalent
The linearised relationship between winding current and branch flux can be extended
to incorporate the magnetic equivalent-circuit branch connections. Let the node
branch connection matrix of the magnetic circuit be [A] and the vector of nodalmagnetic drops Node. At each node the flux must sum to zero, i.e.
[A]Node = 0 (7.25)
Application of the branchnode connection matrix to the vector of nodal magnetic
drops gives the branch m.m.f.
[A]MNode = M (7.26)
Combining equations 7.24, 7.25 and 7.26 finally yields:
= [Q][P][N]i (7.27)
where
[Q] = [I] [P][A][A]T[P][A]
1[A]T (7.28)
The winding voltage vk is related to the branch flux k by:
vk = Nk dkdt
(7.29)
Using the trapezoidal integration rule to discretise equation 7.29 gives:
s (t ) = s (t t) +t
2[Ns]1(vs (t) + vs (t t)) (7.30)
where
s (t t ) = s (t 2t ) +t
2 [Ns]1
(vs (t t) + vs (t 2t)) (7.31)
Partitioning the vector of branch flux into branches associated with each
transformer winding s and using equation 7.30 leads to the Norton equivalent:
is (t) =
Yss
vs (t ) + ins (t ) (7.32)
where
Yss = Qss Ps [Ns]
1 t
2 [Ns
]1 (7.33)
and
ins (t ) =
Qss
Ps[Ns]
1 t2[Ns]1vs (t t) + (t t )
(7.34)