Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
The Evolution of Buildings, Buildings Codes & Building
Science:What does it mean for today’s
building professionals?
03.12.2019
ELYSE INGLESETECHNICAL MARKETING MANAGER; INSULATION
TECHNICAL SUPPORTBUILDING CODESSUSTAINABILITY
LEARNING OBJECTIVES
• UNDERSTAND CHANGING CONSTRUCTION PRACTICE
• BUILDING SCIENCE INFLUENCE ON BUILDING
• UNDERSTAND THE EVOLUTION OF BUILDING CODES
• WHERE ARE WE NOW – WHERE ARE WE GOING
• CURRENT STATUS IN NORTH CAROLINA AND SOUTH CAROLINA
CHANGES IN CONSTRUCTION PRACTICE
Construction
US CONSTRUCTION METHODS – FRAMING
BALLOON FRAMING PLATFORM FRAMING
5
US CONSTRUCTION METHODS – WALL
FRAMING
6
US CONSTRUCTION METHODS
ROOF RAFTERSKEY COMPONENTS
RafterRidge Board (not always)Collar Ties
BENEFITSAllow for finished attic spacesUse for storage
7
US CONSTRUCTION METHODS
ROOF TRUSSES
CAN BE BUILT…On RoofOn groundPre-fabricated offsite
BENEFITSEfficient to build
8
US CONSTRUCTION METHODS – FLOOR
FRAMING
9
OTHER BUILDING & CONSTRUCTION
METHODOLOGIESMANUFACTURED/PRE-FAB
CONCRETE CONSTRUCTIONPoured Concrete WallsInsulating Concrete Forms (ICF)
10
OTHER BUILDING & CONSTRUCTION
METHODSSTRUCTURALLY-INSULATED
PANELS (SIPS)Constructed in a variety of options
SUPERIOR WALLSFoundation Systems
11
BUILDING METHODOLOGIES – SIDEWALL
12
HEAT AIRMOISTURE
Building Science Principals
14 /
Builders are taking a Strategic Approach to…
Meet evolving building code requirements
Balancing approaches to Manage
• Heat Flow• Air Flow• Moisture Flow
Heat
Flow
Air
Flow
Moisture
Flow
15 /
Are Driving
Towards
Building Codes
Heat
Flow
Air
Flow
Moisture
Flow
Increased
Focus
Increased
Risk
IN MANAGING HEAT FLOW,WE TRY TO KEEP IT IN OR OUT…
BUILDING METHODS TO CONTROL HEAT FLOW
CAVITY INSULATION
Fiberglass
Mineral Wool
Cellulose
Spray Foam
Reflective Insulation
Radiant Barriers
Hybrid Systems
INSULATING SHEATHINGS
Expanded Polystyrene (EPS)
Extruded Polystyrene (XPS)
Polyisocyanurate (PIR/PUR)
Fiberglass
Stone Wool
BUILDING METHODS TO CONTROL HEAT FLOW
EXTERNAL RIGID FOAM BOARD < 2”
• Advantage: shifts the wooden frame to the inner side of the house
• But requires a high R-value to be efficient
Ex. R5 XPS + R15 Fiberglass, 70F inside, 20F outside 32F on external sheathing (cold!)
• Requires a drainage plane between the sheathing and the insulation
• Complex details at windows/doors and sidewall penetrations
• Cold climates:
XPS or Polyiso: block moisture diffusion towards outside in winter can trap moisture
Concerns with interior Vapor retarder combined with vapor-barrier exterior insulation
If external insulation has to be used, dense Mineral Wool is preferred (safer)
• Hot and humid climates:
Dense foams preferred (EPS, XPS, Polyiso… block moisture from outside)
Source: JLC, 2017
• Challenges attaching cladding and
windows
• Additional anchoring points for cladding
required (larger bending momentum)
• Limited choice of siding (stucco, fiber
cement)
• Can be cost prohibitive in single family
applications
BUILDING METHODS TO CONTROL HEAT FLOW
EXTERNAL RIGID FOAM BOARD >2”
Source:
JLC, 2017
BUILDING METHODS TO CONTROL HEAT FLOW
EXTERNAL CCSPF
• Can be used both in residential and
commercial applications (more
common)
• More common in applications
incorporating cladding that wouldn’t be
impacted by foam surface
inconsistency (e.g. bricks, stucco…)
BUILDING METHODS TO CONTROL HEAT FLOW
EVOLVING TECHNIQUES AND PRACTICES
• Advanced Framing Techniques
• Double-Stud Walls
• Continuous Insulation
• Structural Insulated Panels (SIPs)
• Insulated Concrete Forms (ICFs)
INSULATION PRODUCTS / SOLUTIONS
IN MANAGING HEAT FLOW,IT IS ABOUT USING ROBUST SOLUTIONS…
This means properly installed and high-quality insulation that:• Reduces heat transfer to improve comfort
• Protects homes from moisture damage which improves durability
BUT HOW CAN WE CONTROL HEAT FLOW…
EFFECTIVE INSULATION
INEFFECTIVE INSULATION
• Misaligned insulation causing gaps and voids. This can cause comfort problems in the home by allowing unwanted air flow.
• Pipes compressing insulation reduce the thermal value and effectiveness.
CONTROLLING THERMAL FLOWINEFFECTIVE INSULATION
CONTROLLING THERMAL FLOWINEFFECTIVE INSULATION
Improperly installed insulation can drop due to gravity.
Controlling Thermal FlowBonus Room over Garage
GRADE I – < 2% compression, no more than 30% of insulation depth
GRADE II – < 2% missing, <10% compression
GRADE III – > 2% < 5% missing, open on one side.
MORE THAN 5% - UN-INSULATED
CONTROLLING THERMAL FLOWIECC AND ENERGY STAR REQUIREMENTS
CONTROLLING HEAT FLOW
COMMON CHALLENGES
Roof/Ceiling System
Walls
Windows
Basements
Crawlspaces
Slabs
Cathedral Ceilings
Knee Walls
PRACTICAL SOLUTIONS
Insulate & Seal
Avoid Compression
Install Attic Baffles
Pay Attention to Details
IN MANAGING AIR FLOW,WE TRY TO KEEP IT IN OR OUT…
PRESSURE DIFFERENTIALS
Wind Pressure
Stack Pressure
Mechanical Pressure
BUILDING METHODS TO CONTROL AIR FLOW
INTERIOR AIR BARRIERS
Polyamide Film
Polyethylene Film
Spray Foam
Caulking/Sealing
Drywall
EXTERIOR AIR BARRIERS
Roofing Membrane
Peel & Stick Asphalt Membrane
Built-up Modified Asphalt
Plywood
Polystyrene Board (XPS or EPS)
Polyurethane Board
WRB – Weather Resistive Barrier
AIR-FLOW CONTROL ON THE INSIDE…
INTERIOR AIR-SEALING STRATEGIES
Std. Caulk & Seal Packages
Spray-Applied Sealant Systems
Airtight Drywall Approach
Spray-Foam
Poly/SVR Sheetings + tape
34
AIR-FLOW CONTROL ON THE OUTSIDE…
EXTERIOR AIR-SEALING SOLUTIONS
WEATHER-RESISTIVE BARRIERS (WRB)• Mechanically-Attached• Self-Adhered• Liquid-Applied• Spray-Applied• Trowel-Applied
INTEGRATED SHEATHINGS & TAPES• e.g. Zip System (Huber)
SPRAY-FOAM
35
CONTROLLING THERMAL FLOWTHROUGH CONTROLLING AIR FLOW
Many leakage pathways at windows & junctions between walls and bottom/top plates
Source: Building America report 1506, March 2015, K. Ueno and J. Lstiburek
AIR-FLOW CONTROL ON THE FRAME…
FRAME AIR-SEALING SOLUTIONSEx. NORTON ACCUFRAME PLUS ENERGY SEAL
High performance durable flexible foam,
installed by framers or insulation
contractors
37
CONTROLLING AIR FLOWINDEPENDENT TESTING & INSPECTION
Blower Door Testing
conducted by a (HERS)
Home Energy Rater service.
Whether or not a building
passes the Blower Door test
is solely dependent on the
quality of workmanship done
by the insulation contractor
and his / her installers.
IN MANAGING MOISTURE FLOW,WE TRY TO KEEP IT IN* OR OUT…
Building Methods to Control Moisture Flow
Interior Moisture Barriers
Polyamide Film
Polyethylene Film
Spray Foam
Exterior Moisture Barriers
Roofing Membrane
Peel & Stick Asphalt Membrane
Built-up Modified Asphalt
Plywood
Polystyrene Board (XPS or EPS)
Polyurethane Board
WRBs
KEEPING MOISTURE (VAPOR) IN*…
VAPOR RETARDERS (2012 IRC)R702.7 Vapor retarders.
Class I or II vapor retarders are required on the
interior side of frame walls in Climate Zones 5, 6, 7,
8 and Marine 4.
Exceptions:1. Basement walls.2. Below grade portion of any wall.3. Construction where moisture or its freezing will not damage the
materials.
41
MOISTURE MANAGEMENT – VAPOR RETARDER
VAPOR RETARDER (R702.7.2)
Class I: Polyethylene sheet, unperforated aluminum foil
Class II: Kraft-faced fiberglass batts
Class III: Latex or enamel paint
42(MemBrain, Smart Vapor Retarder)
IECC 2015 REQUIREMENTS – VAPOR RETARDERS
43
Vapor Retarder Required
MOISTURE MANAGEMENT – VAPOR RETARDER
R702.7.1 CLASS III VAPOR RETARDERS
• Class III vapor retarders shall be
permitted where any one of the
conditions in Table R702.7.1 is met
• Reminder: the moisture performance
of the assembly strongly depends on
the R-value on both sides of the
sheathing
Ex. 70F inside and 20F outside (winter)
R13 inside + R5 outside 34F on sheathing
R24 inside + R5 outside 29F on sheathing
R13 inside + R10 outside 42F on sheathing
44
CLIMATE ZONE CLASS III VAPOR RETARDERS PERMITTED FOR:a
Marine4
Vented cladding over wood structural panels.
Vented cladding over fiberboard.
Vented cladding over gypsum.
Insulated sheathing with R-value ≥ 2.5 over 2 × 4 wall.
Insulated sheathing with R-value ≥ 3.75 over 2 × 6 wall.
5
Vented cladding over wood structural panels.
Vented cladding over fiberboard.
Vented cladding over gypsum.
Insulated sheathing with R-value ≥ 5 over 2 × 4 wall.
Insulated sheathing with R-value ≥ 7.5 over 2 × 6 wall.
6
Vented cladding over fiberboard.
Vented cladding over gypsum.
Insulated sheathing with R-value ≥ 7.5 over 2 × 4 wall.
Insulated sheathing with R-value ≥ 11.25 over 2 × 6 wall.
7 and 8Insulated sheathing with R-value ≥ 10 over 2 × 4 wall.
Insulated sheathing with R-value ≥ 15 over 2 × 6 wall.
Table R702.7.1
TYPES OF CLADDING SYSTEMS
SOLAR DRIVEN MOISTURE
MOISTURE STORAGE CLADDINGS CAN ABSORB LARGE AMOUNTS OF WATER
SOLAR ENERGY CAN CAUSE HIGH VAPOR PRESSURES
SMART VAPOR RETARDERS ALLOW WATER VAPOR TO ESCAPE
Weep HoleWeep Hole
Water Resistive BarrierAir / Wind BarrierWater Resistive BarrierAir / Wind Barrier
Smart Vapor RetarderSmart Vapor Retarder
Ventilated Air / Drainage Space
Gypsum SheathingGypsum Sheathing
Moisture Storage Cladding /Brick Façade
Moisture Storage Cladding /Brick FaçadeFlashingFlashing
Gypsum BoardGypsum Board
Fiber GlassFiber Glass
Steel StudsSteel Studs
BUILDING MATERIALS – VAPOR PERMEANCE
EVOLUTION OF BUILDING CODES
Building Codes
Building Code - Evolution
• OCCUPANT SAFETY – FIRE
• STANDARDIZES CONSTRUCTION PRACTICES
• CLIMATE ZONE SPECIFIC CONSIDERATIONS
• BUILDING ENERGY CONCERNS
• OCCUPANT HEALTH AND COMFORT
• ENVIRONMENTAL IMPACT
Presentation title50 /
Fire
THE GREAT CHICAGO FIRE OF 1874
Presentation title51 /
Standardization Types of Construction
• TYPES I AND II • Require non-combustible building
materials, such as iron, steel, concrete and masonry
• TYPE III & IV • Require non-combustible construction
for exterior walls and code-permitted wood construction for interior walls
• TYPE V• Any code-permitted materials
Presentation title52 /
Climate Zone Consideration
Presentation title53 /
Building Energy Use
Presentation title54 /
Occupant Health and Comfort
Presentation title55 /
Environmental Impact
WHERE ARE WE NOWWHERE ARE WE GOING
Building Codes
Building Codes and Standards
Energy Code
Energy Code
Compliance Path - Commercial•ASHRAE 90.1 -2016
•PRESCRIPTIVE (SAME AS 2012 AND 2015)
•C402, C403, C404, C405 and (1) efficiency option in C406
•PERFORMANCE
•Evaluates entire building as a system (by cost)
•C407, C402.5, C403.2, C404 and Mandatory lighting
sections
•Building energy cost < 85% of standard reference building
•PERFORMANCE ALTERNATIVE
•COMCheck
Compliance Path - Residential
Energy Code
Energy Code
Energy Code – State Adoption
2012-18 IECC INCLUDES MANDATORY REQUIREMENTS
• AIR LEAKAGE RATE (ACH – AIR CHANGES/HOUR)
• SECTION R402
Climate Zones 1 & 2: 5 ACH
Climate Zones 3, 4, 5, 6, 7, 8: 3 ACH
Reported at 50 Pascals
67
MANDATORY REQUIREMENTS
Controlling Air FlowAir Flow Basics
Chases
Plumbing Penetrations
Dropped
Ceilings
Access
Panels
Ceiling fixtures
Ducts
Sill Plates
Vents
Window Openings
Door Openings
BUILDING CODE IN NORTH CAROLINA BUILDING CODE IN SOUTH CAROLINA
Current Status
North Carolina
North Carolina
COMMERCIAL AND RESIDENTIAL ENERGY CODE: 2018 NORTH CAROLINA ENERGY CONSERVATION CODE
EQUIVALENT TO: 2015 IECC WITH AMENDMENTS
EFFECTIVE: 1/1/2019
North Carolina
• Commercial Amendments – Less efficient than 2015 IECC and ASHRAE 90.1 -2007
• Table C402.1.3 – R-value requirements• Weakens metal building roof requirements in CZ3. • Increases wood frame ceiling requirements for CZ 4 and CZ5 to R42 (light
commercial). • Add new row of requirements for steel framed roofs. • Increases mass wall R-value in CZ5. • Revises metal building walls to generally less stringent (although All Other in CZ3 is
slightly more stringent). • C402.2.5 – slab insulation protection requirements eliminated. • C403.2.9 – Duct leakage – equations modified.
North Carolina
• Residential Amendments – Less efficient than 2015 IECC
• R403.3 – Duct Leakage Testing (new exception) – duct systems smaller than 750 ft2 do
not have to be tested. This exception excludes small duct systems and thus represents a
weakening of the code.
• R406.2 – ERI Mandatory requirements (modification) – change mandatory duct insulation
from R-6 to R-8 or R-4 or R-0, depending on location of ducts.
• R402.1.1 – Vapor retarder – deleted.
• Table R402.1.2 – R-values – Mixed bag – some up some down, although mostly down. .
• Table R402.1.4 – U-factors – same mixed bag, but mostly decrease in stringency.
• R402.2. Air leakage testing – weakens requirements for NC from 3 to 5 ACH50.
• R403.3 – Duct Insulation – modifies duct requirements with some up and some down.
• R403.3 – Duct Tightness – weakens duct leakage from 5 to 4 for total leakage.
South Carolina
South Carolina
COMMERCIAL ENERGY CODE: 2009 IECC OR ASHRAE 90.1-2007
RESIDENTIAL ENERGY CODE:2009 IECC
EFFECTIVE: 7/1/2013
THANK YOU