68
Prof. Rowaldo R. del Mundo Department of Electrical & Electronics Engineering University of the Philippines EE 256 - POWER SYSTEM PROTECTION Line Protection Line Protection

EE 256 Notes 4 - Line Protection

Embed Size (px)

DESCRIPTION

lecture notes

Citation preview

  • Prof. Rowaldo R. del MundoDepartment of Electrical & Electronics Engineering

    University of the Philippines

    EE 256 - POWER SYSTEM PROTECTION

    Line ProtectionLine Protection

  • University of the Philippines

    Department of Electrical & Electronics Engineering2

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    TRANSMISSION AND DISTRIBUTIONLINE PROTECTION

    4.1 Overcurrent Protection andCoordination

    4.2 Distance Relaying

    4.3 Pilot Relaying

  • University of the Philippines

    Department of Electrical & Electronics Engineering3

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    GENERAL PROCEDURE ON COORDINATION OF OVERCURRENT PROTECTION

    1. Gather data required for coordination.

    a. Updated Single Line Diagram of the system

    - show the type & ratings of protective devices (CB, recloser, relay, fuse, CT, PT and other related information)

    b. Line currents that goes through the protective devices (normal, max. and emergency)

  • University of the Philippines

    Department of Electrical & Electronics Engineering4

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    c. Short circuit currents (min. & max.)

    - all types of faults (symm.& asymm)

    d. Time-current characteristic curves of protective device.

    2. Select current & voltage reference to be used in the log-log paper & scale all quantities to this reference (base)

    a. Log-log paper has 4.5 decades

    b. Current scale must show lowest normal current & max. short circuit current

  • University of the Philippines

    Department of Electrical & Electronics Engineering5

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    c. Voltage scale: use one reference voltage (voltage of distribution)

    *refer the current values to the chosen reference voltage

    3. Plot current characteristics of equipment to be protected (inrush, starting, damage curves & points)

    4. Plot the TCCs of devices being coordinated

    -select settings or ratings based on principles of coordination

    5. Draw the line diagram of the portion that you are coordinating & label the devices

  • University of the Philippines

    Department of Electrical & Electronics Engineering6

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    Overcurrent protection is directed primarily to the clearance of faults. The settings are usually adopted to obtain some measure of overload protection.

    Coordination is the selection of ratings, settings and characteristics of overcurrent protective devices to ensure that the minimum unfaulted load is interrupted when protective devices isolate a fault or overload.

  • University of the Philippines

    Department of Electrical & Electronics Engineering7

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    WHEN DO YOU CONDUCT COORDINATION?

    New electrical system is being designed

    Significant loads are added to the system

    Existing equipment are replaced with higher rated equipment

    Available short circuit current is increased

    A fault on the periphery of the system shuts down a major portion of the system

  • University of the Philippines

    Department of Electrical & Electronics Engineering8

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    DATA REQUIREMENTS

    Single line diagram

    Impedances

    Short circuit currents

    Starting and Inrush currents

    Peak/Full load currents

    Decrement curves of generators

    Time-current characteristics (TCC) curves

    Performance curves of CTs

  • University of the Philippines

    Department of Electrical & Electronics Engineering9

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    COORDINATION PROCEDURE

    Update and/or develop the single line diagram

    Calculate fault currents (maximum and minimum)

    Determine protection requirements of various elements of the system (motors, transformers, generators, feeders, etc.)

    Prepare load analysis (maximum load and characteristics of load)

    Obtain TCC of protective devices

    Select proper scale (voltage and current) using a log-log paper

    Select rating or setting which provide coordination margin

  • University of the Philippines

    Department of Electrical & Electronics Engineering10

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    COORDINATION MARGIN

    The time interval between the operation of two adjacent relays depends on the following factors:

    circuit breaker interrupting time

    Overshoot time of the relay

    Errors

    Final margin

    Recommended Time: 0.3 0.5 seconds

  • University of the Philippines

    Department of Electrical & Electronics Engineering11

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Overcurrent Protection andCoordination

    A B C D E

    MAX 7850AMIN 3920A

    120A 170A 80A 50A

    R4 R3 R2 R1

    4500A2860A

    2690A2003A

    1395A1182A

    500/5 400/5 200/5 100/5

    Determine settings of R1 to R4 using the following relay data:

    Normal Inverse Curve (see manufacturers TCC) Current Tap Setting: 0.5 2.5 x In (multiples of 0.5) Time Multiplier: 0.05 1.0 (multiples of 0.05) Instantaneous: 2.5 20 x In (multiples of 0.5)

  • University of the Philippines

    Department of Electrical & Electronics Engineering12

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering13

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering14

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering15

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Distance Relaying

    Distance relaying provides discriminating zones of protection, provided that fault distance is a simple function of impedance

    Distance Relay Types

    Impedance Relay

    Reactance Relay

    Mho Relay

  • University of the Philippines

    Department of Electrical & Electronics Engineering16

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Distance Relaying

    ZONES OF PROTECTION

    Zone 1 (instantaneous zone)

    - Choose relay ohmic setting of 80% of the protected line impedance (to provide an ample margin against over-reach)

    Zone 2

    - 100% of the protected line

    - Plus 50% of the next shortest line (to deal with possible under-reach)

    Zone 3

    - 100% of the protected line

    - Plus 100% of longest second line

    - Plus 25% of longest third line (to provide back-up)

  • University of the Philippines

    Department of Electrical & Electronics Engineering17

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Distance Relaying

    Transmission LinesZ1 = 2.5 + j5Zo = 7.5 + j20.5

    Radial FeedersZ1 = 3.5 + j7Zo = 10.5 +j28.7

    34.5 kV

    34.5 kV

    500 MVA fault @ 115 kV

    R

    Determine the settings of the distance relay using:

    a. Impedance relayb. 45 Mho relay

    36kV/ 120V

    400/5Assignment:Compute minimum voltage at relay for a fault at Zone 1 reach

    a. Phase faultb. Ground fault

    Transformers50MVA, 115/34.5kVZ = 10%

  • University of the Philippines

    Department of Electrical & Electronics Engineering18

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Pilot Relaying

    Pilot Relaying is an adaptation of the principles of differential relaying that avoids the use of control cable between terminals for fast clearing of faults of transmission lines

    Communication Channels

    Power Line Carrier (PLC)

    Microwave

    Fiber Optics

    Pilot Wire

  • University of the Philippines

    Department of Electrical & Electronics Engineering19

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Pilot Relaying

    Directional Comparison

    Blocking Scheme

    Unblocking Scheme

    Tripping Scheme

    Underreaching Transfer Trip

    Overreaching Transfer Trip

    Phase Comparison

  • University of the Philippines

    Department of Electrical & Electronics Engineering20

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering21

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering22

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering23

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering24

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering25

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering26

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering27

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering28

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering29

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering30

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering31

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering32

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering33

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering34

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Lateral Tap Fusing

    Fuse must clear a Bolted SLGF in 3

    seconds; or

    Bolted SLGF = 6 X Fuse rating; or

    Fuse must clear a SLGF with a 30-

    ohm fault resistance in 5 seconds

  • University of the Philippines

    Department of Electrical & Electronics Engineering35

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Expulsion Fuse Expulsion Fuse Coordination

    Downstream Fuse (referred to as the Protecting Fuse)

    should operate before the Upstream Fuse (the

    Protected Fuse)

    Total Clearing Time of the Protecting Fuse should be less

    than the Damage Time of the Protected Fuse [Note: Damage Time is 75% of the Minimum Melting Time]

    Fuse-Fuse Coordination Table provides maximum fault currents that the protecting and protected fuse are

    coordinated

  • University of the Philippines

    Department of Electrical & Electronics Engineering36

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Backup Current Limiting Fuse Coordination

    CLF protecting Expulsion Fuse

    Select a Backup CLF that have a maximum melting I2t below the

    maximum clearing I2t of the expulsion element (Matched-Melt

    Coordination Principle)

    Check the TCC The expulsion link should always clear fault

    currents in the low current operating region, especially below the

    minimum interrupting current of the CLF

    Estimating maximum melting I2t of expulsion links Take the

    minimum calculated from the minimum melting TCC at 0.0125

    sec. and multiply by 1.2 for Tin or 1.1 for Silver links

  • University of the Philippines

    Department of Electrical & Electronics Engineering37

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering38

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Recloser Expulsion Fuse Coordination

    Adjust Fast Curve (A) of the recloser

    For one fast operation: A curve time x 1.25

    For two fast operation with a reclosing time greater or equal to 1 sec.: A curve time x

    1.25

    For two fast operation with a reclosing time

    from 25 to 30 cycles: A curve time x 1.8

    Smallest fuse must coordinate with the fast operation (A

    curve) of the recloser.

    Largest fuse must coordinate with the delayed operation (B

    or C curve) of the recloser. Choose C curve if largest fuse

    cannot coordinate with B curve

  • University of the Philippines

    Department of Electrical & Electronics Engineering39

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Recloser Recloser Coordination

    Hydraulically-controlled Reclosers (Cooper)

    Series-Coil Operated: Need more than 12 cycles

    Solenoid Closing: Need 8 cycles separation

    Coordinating Instantaneous Elements

    Find a setting where the instantaneous relay will not operate for faults downstream of the

    second protective device. The upstream relay will not operate if its pickup is above the

    available fault current at the location of the downstream element. The instantaneous pickup

    on the element must be higher than its time-overcurrent pickup.

    [Note: This rules out hydraulic reclosers which have the same pickup for the fast (A) curve &

    delayed curves (A&B)]

    Use a time delay on the upstream instantaneous element. Choose enough time delay (6 to

    10 cycles), to allow downstream device to clear before the station device operates.

    Sequence Coordination If the device senses current above some minimum trip setting and

    the current does not last long enough to trip based on the devices fast curve, the device

    advances its control-sequence counter as if the unit had operated on its fast curve. So when

    the downstream device moves to its delayed curve, the upstream device with sequence

    coordination also is operating on its delayed curve.

    Station device detects and counts faults (but does not open) for a fault cleared by a

    downstream protection on the fast trip

    If the fault current occurs again (usually because the fault is permanent), the station device

    switches to the time-overcurrent element because it counted the first as an operation.

  • University of the Philippines

    Department of Electrical & Electronics Engineering40

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Station Relay and Recloser Settings

    Phase Time-Overcurrent (TOC) Relay

    Pickup at 2X the normal designed peak load on the circuit

    Pickup < 75% of the bolted LTLF

    Ground Time-Overcurrent (TOC) Relay

    Pickup at 0.75X the normal designed peak load on the

    circuit

    Pickup < 75% of the SLGF current at the end of the line or

    the next protective device

    Must coordinate with the largest lateral fuse

    Instantaneous Phase and Ground Relays

    2X the TOC relay pickup

  • University of the Philippines

    Department of Electrical & Electronics Engineering41

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

    Sequence Coordination

    Even with coordinated Fast Curves, nuisance momentary interruptions occur for faults cleared by downstream recloser

    Sequence:

    R2 operates on its A curve. (R1 will not operate)

    After a delay, R2 recloses. The fault is still there, so R2 operates on its delayed B curve

    R1 operates too on its a curve which operates before R2s curve

    After R1 recloses, R2 should then clear the fault on its B curve, which should operate before R1s B curve

    The fault is still cleared properly, but customers upstream of R2 have extra momentary interruptions

  • University of the Philippines

    Department of Electrical & Electronics Engineering42

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering43

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering44

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering45

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering46

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering47

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering48

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering49

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering50

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering51

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering52

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering53

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering54

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering55

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering56

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering57

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering58

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering59

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering60

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering61

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering62

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering63

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering64

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering65

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering66

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering67

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo

  • University of the Philippines

    Department of Electrical & Electronics Engineering68

    EE 256 Power System ProtectionProf. Rowaldo R. del Mundo