المتجددةلطاقةء والكهربا وزارة اMinistry of Electricity and Renewable Energy لقا الشركة ا بضة لكهرباء مصرEgyptian Electricity Holding Company EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION Date: 15-12-2020 Page 1 of 21 EDMS 02-300-2 TECHNICAL SPECIFICATION FOR LOW VOLTAGE DISTRIBUTION PANELS FOR POWER TRANSFORMERS UP TO 2500 KVA (INDOOR / OUTDOOR) Issue: Dec. -2020 / Rev- 2 ( اريحىد اختيىجذ ت تOption items انتىزيع قثم انطرح تىاسطح شركح يجة تحذيذها) ق يىارفا يهسو اتش فيىزروجاخ سىينح انخىز في حاتش في صفح انسىيEDMS 19-302

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

  • Upload
    others

  • View
    13

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 1 of 21

EDMS 02-300-2

TECHNICAL SPECIFICATION

FOR

LOW VOLTAGE DISTRIBUTION PANELS

FOR POWER TRANSFORMERS

UP TO 2500 KVA

(INDOOR / OUTDOOR)

Issue: Dec. -2020 / Rev- 2

( تىجذ تىد اختياريحOption itemsيجة تحذيذها تىاسطح شركح انتىزيع قثم انطرح )

صفح انسىيتش فيىز في حانح انخروجاخ سىيتش فيىز يهسو ارفاق يىاEDMS 19-302

Page 2: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 2 of 21

CONTENTS

3 GENERAL SPECIFICATION ………………………….……………………………. 1.

4 TECHNICAL SPECIFICATIONS ……………………….………………….............. 2.

4 BUS-BARS …………………………........................................................................... 2.1

5 CIRCUIT-BREAKERS AND SWITCH FUSES …………………………………….. 2.2

5 LOW VOLTAGE FIXED CAPACITORS WITH M.C.C.B…………………………. 2.3

7 DESIGN CRITERIA ………………………………….………….…………………... 3.

10 STANDARDS……………………………….……….………………………………. 4.

10 MARKING ……………………………….………………………………………….. 5.

10 INSPECTION AND TESTING………………………………………………............. 6.

11 DRAWINGS, CATALOGUES, SAMPLES, AND GUARANTEE TABLES………. 7.

11 SPARE PARTS ………………………………………...…………………................. 8.

16 REQUIREMENTS ………………………………………...…………………........... 9.

18 GUARANTEE TABLES ………………………………………….………………... 10.

Page 3: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 3 of 21

1. General Specification

- These specifications cover the design, manufacturing,

assembly, and supply of 50 c/s, 0.4KV low voltage

distribution panels (some items are concerned with

the contractor only).

- The distribution panels should be connected to 0.4

KV solidly-earthed networks and should be fed

from distribution transformers with variable rating

up to 2500KVA according to the load.

- The panel should be earthed (by the contractor) and

connected to the earthing bus-bar using a stranded

copper conductor of cross-section as following:

35 mm2 for transformers for 50, 63, 100 KVA.

50 mm2 for transformer for 200 KVA.

70 mm2 for transformer for 300 KVA.

95 mm2 for transformer for 500 KVA.

150 mm2 for transformers ≥1000 KVA.

- The dimensions of the panels should comply with the

size of the inner components and according to the

technical industrial standards.

- The panel should be made from sheet steel

(galvanized or non-galvanized according to …EDC

requirements) with a thickness of at least 2 mm

(before painting) and the doors should be provided

with vertical metal support (Or any other suitable

supporting method accepted by …EDC).

- The panel should be painted with a light gray rust-

resistant electrostatic powder painting.

- The panel should be firmly locked and weather-

proof with a degree of protection "IP54" or "IP41"

for indoor or outdoor, respectively.

- In case of outdoor installation, connection with TR.

Via cables, cable entry from the bottom with glands,

the panel should be installed inside an enclosure

with thickness 2.5 mm, the panel should be

provided with a sloping roof to prevent rain accumulation (slope angle should not be less than

6° horizontally) to achieve a protection degree of

IP54.

انعاو انىصف -1

ااطفبد رظ١ , رظ١غ , رغ١غ رس٠ذ ؽبد رغط ز -

رثزثخ /صب١خ 04ن.ف. , رشدد 4,0رص٠غ اغذ اخفغ عذ

)رعذ ثؼغ اجد خبطخ ثمبي ازشو١جبد فمؾ( .

ع١ز رط١ ز اؽبد ثشجىبد اغذ اخفغ راد ازأس٠غ -

٠غ ؾلاد رص اجبشش عزغز شجىخ اغذ ازعؾ ػجش

ن.ف.أ ؽجمب ؾ. 2044عؼبد ؾزفخ ؽز

٠غت ػ امبي رأس٠غ اؽخ رط١ب ثجبسح الاسػ ػ -

- ؽش٠ك طلاد ؾبط غذخ ثغبؽخ مطغ وبلار:

50 2 ن.ف.أ 044 , 35, 04ؾلاد عؼخ

04 2 ن.ف.أ. 244عؼخ ؾلاد

04 2 ن.ف.أ. 544عؼخ ؾلاد

50 2 ن.ف.أ. 044عؼخ ؾلاد

004 2 ن.ف أ . 0444≤ بد ؾلاد عؼ

رظغ اؽخ ثأثؼبد بعجخ ؽجمب ب ٠زطج ؽغ ابد اشوجخ -

ظبػخ.داخب ؽغت الأطي اف١خ

رظغ اؽخ أاػ اظت )رى غفخ أ غ١ش غفخ ؽجمب -

لج اذب 2 زطجبد ششوبد ازص٠غ( ثغه لا ٠م ػ

الأثاة ضدح ثؼظت ؽ اذاخ )أ ب ٠ؾمك ازذػ١

(.اىب لاثاة ثطش٠مخ أخش مجخ ششوبد ازص٠غ

رذ اؽخ ثجدسح اىزشعزبر١ه ثب اشبد افبرؼ امب -

ظذأ.

رى اؽخ ؾىخ اغك غضح ػذ اؼا اغ٠خ رى -

( ف ؽبخ ازشو١ت داخ IP54 )أ( IP41دسعخ اؾب٠خ ) راد

ازشر١ت. خبسع ػ أاج

٠ى اشثؾ غ اؾي ػ ف ؽبخ ازشو١ت خبسط اج -

ػ ؽش٠ك علاذاد أعفؽش٠ك وبثلاد, دخي اىبثلاد

لج اذب 2.0غه ث اظبط ؽب٠خرػغ اؽخ داخ

دسعبد 3ا١ لا رم ػ )صا٠خثغمف بئ الا١ىزشعزبر١ى

.IP54غ الافم( ٠ؾمك دسعخ ؽب٠خ

Page 4: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 4 of 21

- The front doors of the panel should be installed

using galvanized metal hinges and locked with a

nickel-plated lock with a master key and

provided with an internal mirror for C.Bs &

switch fuse.

- No mechanical process should take place after painting.

2- Technical Specification

2.1 Bus-bars:

- All the bus-bars should be rectangular high-grade

electrolytic copper with a purity of at least

99.999% (conductivity 57 SM/m) (supplier should

be submitting a certificate from independent and

approved lap and …EDC reserve its right to take a

random sample during examination and testing for

analysis at supplier's expense

- All the bus-bars should be insulated with "heat-

shrinkable" colored in (red, yellow, blue, and

black) for the 3-phases and neutral bus-bars,

respectively.

- The cross-section area of the neutral bus-bar

should be at least 60% of the CSA of the phases

bus-bars.

- The cross-section area of the earth bus-bar should

be at least 25% of that of the phases bus-bars.

- The bus-bars should be mounted on insulators

made from porcelain or cast resin according to the

IEC Standard.

- The bus-bars and the insulators should withstand

thermal and mechanical effects resulting from

short circuit current according to IEC 61439-1

- The neutral bus-bar should be equipped with the

necessary compression lugs Bimetal (Al / Cu)

suitable for connection to Aluminum neutral

conductors and PVC insulated cables (concerned

by the contractor).

ؽخ ثاعطخ فظلاد اؾذ٠ذ رشوت الأثاة الأب١خ -

MASTERاغف رمف الأثاة ثمف ط ثب١ى ثفزبػ

KEY ػ اماؽغ اغ٠زش رغض اؽخ ثشا٠ب داخ١خ

ف١ص

اذب.لا ٠ز اعشاء ا ػ١بد ١ىب١ى١خ ثؼذ الازبء ػ١خ -

2- انىاصفاخ انفيح :-

- كهرتائ:قضثا تىصيم انتيار ان 2-1

٠غت ا رظغ ع١غ اجبساد ف اؽخ اؾبط الاىزش١ز -

% 55.555اجطؾ غزط١ اشى ر دسعخ مبح لا رم ػ

) ٠غت رمذ٠ شبدح عخ ع١ض( 00) ازط١١خ لا رم ػ

ؾب٠ذح ؼزذح ٠ؾك ششوخ ازص٠غ أخز ػ١خ ػشائ١خ أصبء

ره زؾ١ب ف اؽذ اؼب اؼزذح ػ س افؾض الإخزجب

فمخ اسد (.

٠غت ا رى ع١غ اجبساد اشئ١غ١خ )الأع اشئ١غ١خ -

ازؼبدي( ؼضخ ثببث١ت اىبش١خ خ ثبلاا )أؽش ,

.ػ ازشر١ت أطفش , اصسق , اعد(

% ٠34غت ا ٠ى لؼ١ت ازؼبدي ر غبؽخ مطغ لا رم ػ -

الاع. غبؽخ مطغ ثبسح

٠ى ر غبؽخ مطغ لا رم ػ أسػ ٠غت لؼ١ت الأ -

الاع.% غبؽخ مطغ ثبسح 20

( اشارظ)اجسع١ أ ػاصي ٠غت رضجذ امؼجب ػ -

.(IEC)ؽجمب اطفبد ام١بع١خ

٠غت أ رزؾ امؼجب اؼاصي ازأص١ـشاد اؾشاس٠خ ام -

. IEC 61439-1ب١ى١خ از رزظ ػ ر١بس امظش ؽجمب ـ ا١ى

٠غت أ ٠غض لؼ١ت ازؼبدي ثطلاد بعجخ صبئ١خ اؼذ -

أ١( زط١ ثمؼجب رؼبدي ظػخ / )ؾبط

) PVCالأ١ وزه ازط١ ثىبثلاد ؼضخ ثبـ

.اخزظبص مبي ازشو١جبد(

Page 5: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 5 of 21

2.2 Circuit-Breakers and Switch fuses:

A. For incomings: -

- The panel includes one main 3-poles CB (ACB or

MCCB) complete with overload current and short

circuit current Protection and without under

voltage release coil to avoid voltage dips (as

shown in Table-1).

B. For outgoings: -

- The panel should include a number of outgoing

MCCB or switch fuse (as shown in Table-1) and

according to the attached specifications.

- The main C.B should be installed at separate

compartment (cell). It is totally prohibited to install

switch fuses or MCCBs below the main CB.

2.3 Low voltage fixed capacitors with M.C.C.B

- The capacitor unit should be dry type or oil-

impregnated or filled with gas and has self-healing

properties.

- The thickness of the dielectric insulation depends

on the voltage rating.

- The metal part and the capacitor's terminals make

the capacitor withstand high currents and make a

capacitor's capacity value stable when operating at

high operating temperatures.

- The capacitor and its components should have the

following technical data: -

Design voltage (Un): 525 Volt

Operating voltage: 400 Volt

Frequency: 50 Hz

- Capacitor rate should be related to operating

voltage

- Discharge resistors: the capacitor discharges up to

50 Volt within 60 Sec or up to less than the initial

peak voltage of √2 times of rated voltage Un.

-انصهراخ: وسكاكيقىاطع انتيار 2-2

نهذخىلاخ:تانسثح - أ

رؾز ؽخ ازص٠غ ػ لبؽغ اؽذ سئ١غ صلاص الأعخ -

( لبث ؼجؾ ػذ ص٠بدح از١بس ر١بس امظش أ مت )ائ

ف اغذ الإخفبعثذ ف فظ غذ اخفغ زفبد

(0- ج١ ثبغذي سل )وب

-تانسثح نهخروجاخ : - ب

رؾز ؽخ ازص٠غ ػ ػذد لاؽغ اخشط امجخ أ -

( ؽجمب0-عىبو١ اظشاد )وب ج١ ثبغذي سل

اطفبد اشفمخ.

الازضا ثؼذ امبؽغ اشئ١غ ثخ١خ فظخ غ ٠ى أ٠غت -

مبؽغ اشئ١غ.ػغ ع٠زش ف١ص أ لاؽغ أعف ا

انجهذ انخفض تانقاطع انثاتتح راخانكثفاخ 2-3

اع اغبف أ اشجغ ثبض٠ذ أ اىضف ٠غت أ ٠ى -

ئ ثبغبص خبط١خ الإزئب ازار.

٠ى عه اؼضي ث١ ششائؼ اىضف ؽجمب غذ ام. -

ػاىضف رغؼ اىضف لبدسا أؽشافاغضء اؼذ -

عؼخ اىضف غزمشح غ ل١خ رغؼرؾ ر١بساد ػب١خ

دسعبد اؾشاسح اؼب١خ أصبء ازشغ١.

-: انتانيحيجة أ يكى انكثف ويكىاته نهى انثيااخ انفيح -

فذ. 020 :اغذ ازظ١

فذ. 044 :عذ ازشغ١

١شرض. 04 :ازشدد

٠ز رؾذ٠ذ عؼخ اىضف ػذ عذ ازشغ١. -

صب١خ ؽز 34مببد ازفش٠غ: ٠ز رفش٠غ شؾخ اىضف خلاي -

فذ أ أل ألظ ل١خ ثذائ١خ غذ رجغ اغزس 04أل

. 2Un√ازشث١ؼ غذ ازمذ٠ش

Page 6: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 6 of 21

- Losses: Dielectric losses < 0.2 W/KVAR

Total losses < 0.5 W/KVAR.

- Maximum permissible continuous current at design

voltage and design frequency should not be less

than 1.3 times of design current.

- Maximum inrush current at design voltage and

design frequency: not less than 200 times of design

current.

- Capacitance tolerance: -5% to +10%.

- Ambient temperature: -5: 55°C.

- Max humidity: 95 %

- Lifetime of capacitor at continuous normal

operating conditions: not less than 130000 hours

(class D).

- Capacitor unit should have internal overpressure

protection for 3- phase, whether at vertical or

horizontal position.

- Connection: Each capacitor unit should be in delta

connection

- Insulation level: -

- Min. Rated power-frequency test voltage (r.m.s.):

2.5 KV for 1 min. (between phases and body).

- Rated lightning impulse voltage: 8kV - 1.2/50µsec.

- Capacitance measurement.

- Loss angle.

- Discharge resistance.

اد /ن فبس 4,2افبل١ذ: ٠غت أ رى فبل١ذ اؼضي أل -

اد/ن.فبس. 4,0افبل١ذ اى١خ أل

٠غت أ ٠زؾ اىضف ل١خ ألظ ر١بس غزش غػ ث ػذ -

شح 0,5اغذ ازظ١ ازشدد ازظ١ ٠غت ألا ٠م ػ

از١بس ازظ١.

ر١بس دفؼ غػ ث ػذ ٠غت أ ٠زؾ اىضف ل١خ ألظ -

شح ٠244غت ألا ٠م ػ ازشدد ازظ١ اغذ ازظ١

.از١بس ازظ١

%.04ؽز + %0-اغبؽ١خ ف ل١خ عؼخ اىضف -

°. 00ؽز 0-دسعخ ؽشاسح اج١ئخ اؾ١طخ : -

%.50ألظ سؽثخ: -

٠م ػش اىضف ف ظشف ازشغ١ اؼبد ثشى غزش لا -

(.class Dدسعخ ؽشاسح ) ػذ عبػخ 054444ػ

اىضف ٠غت أ رى ث لب٠خ ػذ إسرفبع اؼغؾ ثذاخ ػ -

أفم.الأع اضلاصخ عاء وب ف ػغ سأع أ

ازط١: ٠ز رط١ ؽذح اىضف ف شى دزب. -

يستىي انعسل: -

اؼبد ددازش ػذ دل١مخ 0 ذح. ف.ن 2.0 عذ ػذ الإخزجبس -

.اغغ الأع ث١

.1.2/50µsecن.ف. ـ 8 اخزجبس عذ اضجد اذفؼ : -

.اىضف عؼخ ل١بط -

.افمذ صا٠خ -

.ازفش٠غ مبخ -

Page 7: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 7 of 21

-: معايير التصميم -3

٠غت أ ٠ى ؾ اؼلالخ اؼىغ١خ ز١بس غ اض فبد -

IECخ ام١بع١رشغ١ اماؽغ ؽجمب لأخش إطذاس اطفبد

اؼب١خ.

ثؼؼبرم اغبفخ ث١ امؼجب اشئ١غ١خ ثؼذ ػضب ألا٠غت -

ع ثبغجخ ؽبد اؾلاد ثمذسح ال 2ف أ ىب ػ

ن.ف.أ 044 ثمذسح ع ؽبد اؾلاد 0 ن.ف.أ, 044

اغطشح.فأوجش غ ػشسح اعزخذا ػبصي ؽب

سح ف ػغ سأع ألا ٠غت أ رى ع١غ اماؽغ زغب -

رم اغبفخ ث١ اماؽغ ثؼؼب ث١ أ لبؽغ عغ اؽخ

2ث١ اغ٠زش ف١ص ثؼؼب لا رم ػ ع اغبفخ 3ػ

ع.

٠غت أ رى ع١غ الأعضاء اطخ ف اؽخ ظػخ -

55,555اؾبط الاىزش١ز ػب اغدح ثغجخ دسعخ مبح

ااد اؼبصخ غ١ش لبثخ لاشزؼبي لا رزض أ % وزه رى

رزأصش ثبشؽثخ.

أؽشاف اخشط ماؽغ ٠غت أ رى ضدح ثمؼجب ؾبع١خ -

إػبف١خ ثغبؽخ مطغ بعجخ غؼخ امبؽغ ٠غت ػضب

ثئعزخذا أبث١ت إىبش١خ اغبفخ ث١ ز اجبساد بعجخ

امؼجب اؾبع١خ الإػبف١خ ز١بس ام مبؽغ ٠غت أ رى

ػاصي رضج١ذ ػذ اؾبعخ زه ػثبؽاي بعجخ غ رؾ١ب

ؽجمب طت ششوبد رص٠غ اىشثبء.

٠غض اغ٠زش ف١ص ثضلاد ؾبع١خ ثغبؽخ مطغ ٠غت أ -

اضلاد ػؼضخ ثأبث١ت إىبش١خ شثؾ اىبثلاد 2 204

ف١ص غ٠زش ١ص ره ؾب٠خ ااغ٠زش ف ػثذلا اشثبؽ

ز١غخ اؾشاسح اضائذح. الإرلاف

الأعضاء اؼذ١خ از رظ لبػذح و ظش ثطشف رغض -

ف١ص اخبطخ ثشثبؽ اىبثلاد( ثغبس غ٠زش ا أؽشاف) اىبث

أ ظف ثطخ( ث سدر١ ثذ سدح 02)غف

ععزخ طبخ غف١.

3. DESIGN CRITERIA

- The inverse time-current characteristic of the release

coils should comply with the latest applicable IEC

standards.

- Anywhere within the panel, the clearance distance

between the main insulated bus-bars should be at

least 2 cm for panels for transformers less than 500

KVA and 4 cm for panels for transformers from 500

KVA and above with using the supporting insulator

(BB sandwich).

- All C.B. should be adjacent and in a vertical position,

the distance between the C.Bs. and between any C.B.

and the panel should not be less than 6 cm and the

distance between switch fuses should not be less than

2 cm.

- All the conducting parts within the panel should be

made from high-quality electrolytic copper purity

99.9 % while the insulating materials should be non-

flammable and non-hygroscopic.

- Moulded case circuit breakers output terminals

should be provided with additional copper bars that

have a suitable cross-sectional area and insulated

with heat shrinkable tube with suitable length using

supporting insulators when needed and as per ….

EDC requirements.

- The switch fuse should come with copper droppers

(with CSA 250 mm2) which are insulated with heat-

shrinkable tubes to connect the cables to protect the

switch fuses from being damaged due to overheating.

- The metal parts connecting every fuse base with

cable terminal should be provided with a galvanized

bolt (12 mm or 0.5 inches) with two washers, one

spring washer, and one nut, all washers and nuts

should be galvanized.

Page 8: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 8 of 21

غبء اظشادازلاظ ث١ اماػذ أعطؼ٠غت ا رى -

١ىش. 0ربب ط١خ ثطجمخ افؼخ ثغه لا ٠م ػ

رغض لؼجب ازؼبدي ثأخشا رشث١ؾ وبثلاد ازغز٠خ غ رس٠ذ -

اظا١ اسد وزهاغب١شالاصخ اؾذ٠ذ اغف

اجذ اسد اغعزخ اخزفخ.

اؼذ١خ ٠ى ثب غب١ش زأس٠غ.ع١غ أعضاء اؽخ -

اسرفبع بعت )لا ػسثبؽ اىبثلاد أؽشاف٠ض ا رى -

.اؽخ( أعفع ػ ٠00م ػ

رضد اؽخ ثبمفضا الاصخ زضج١ذ اىبثلاد ثؾ١ش ٠ى لطش -

ع )خبطخ ثؽبد اغ٠زش ف١ص(. 8امف١ض لا ٠م ػ

ؽخ زؼط أفؼ صل١خ أب أصبء ازشغ١ رظ ا -

.ازشو١تافؾض اظ١بخ,

زؼب ٠غت اطي غ١غ ىبد اؽخ ثطش٠مخ ٠غ ا -

.ؼب

-وانهىحح: تي انحىل طريقح انرتظ -

اؼ٠خ اؾي اؽخ ػ ؽش٠ك اجبساد اشثؾ ث٠١ى -

خلاي ع 24رفبع سئ٠ض أ رى اجبساد خبسع ب ث

ػ ػبصي افجش لح ػضي بعجخ رى ثفظ غبؽخ

.مطغ اجبساد اشئ١غخ ثبؽخ

سثؾ غخع 3اغبفخ ث١ اجبساد أػ اؽخ ػ ا٢ رم -

.اجبساد أ رى ف غز أفم اؽذ

ؽز مبؽ رى ع١غ اجبساد اشئ١غ١خ افشػ١خ ٠غت أ -

.ىبش١خ خإثبؽخ ؼضخ ثأبث١ت ػضي ثبؽ اش

- The main contacts for fuse-holders should be totally

smooth and silver plated with a minimum coating

thickness of 4 microns.

- Neutral bus bars should be prepared with holes to

install feeders and also with necessary galvanized

bolts, nuts, washers, and spring washers.

- All metal parts of the panel should have earthing bolts.

- All cable terminals should be at a proper height (not

less than 55 cm from the panel bottom).

- The panel should be provided with necessarily needed

cable ties of 8 cm diameter at least (for switch fuse

panels only).

- The distribution panel should be designed to provide

maximum reliability and safety.

- All the components of the distribution panel should be

accessed in a manner that is easy to handle.

- Method of connection between the transformer and

the distribution panel:

- The connection between the transformer and the panel

is via upper busbars, these outgoing upper busbars

should be coming out from the panel with the height

of 20 cm, through an insulated fiber plate with a

suitable degree of insulation and the upper outgoing

busbars should be of the same cross-section area of the

main busbars in the panel.

- The distance between the upper busbars above the

panel should not be less than 6 cm and of the

same horizontal level.

- All main and subsidiary Bars up to the connections

points of the panel should be insulated with colored

heat shrinkable tubes.

Page 9: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 9 of 21

اشثؾ ث١ اؾي ؽخ اغذ اخفغ ػ ؽش٠ك ف ؽبخ -

ىبثلاد اذخي زا ٠ض رغ١ض فزؾبد أعف اؽخ وبثلاد,

8 ٠م ػى وبث ثمطش لا )فزؾخوزه وبثلاد اخشط

ػ ع( رضد افزؾبد ثغابد وبرش لإؽىب امف

.داخ اؽخ اضاؽفاىبثلاد ؼذ دخي

.٠ز غك أبو فزؾبد دخي خشط اىبثلاد ثطش٠مخ بعجخ -

-يجة أ تسود انهىحح تأجهسج انقياش الآتيح : -

ػذد ( 4صلاصخ أ١زش سل-x ) 4.0دلخ أج١ش .

0.0( فذ دلخ 044 – 4)سل اؽذ فز١زش ػذد .

( ػذد صلاصخ ؾلاد ر١بس عؼخX /5 أج١ش , دلخ )4.0 .

جبد ث١ب وبخ ثبف١صادػذد صلاصخ (LED ج١ب )

.عد اغذ ػ خلا٠ب اذخي

اطبلخ اشص٠زخ١بط لاؽخ ضدح ثىب زشو١ت ػذاد

.الأصخ زط١ وزه سص٠زبد إؽز١بؽ١خ

.٠غت أ رضد فزؾبد اؽخ ثغلاذاد غ الأرشثخ اذخي -

لبثخ لإشزؼبي اذاخ١خ غ١ش رى أعلان ازط١ أ٠غت -

غبؽخ PVCرى ػجبسح ػ طلاد ؾبع١خ ؼضخ ثبـ اششوخ امبثؼخ ىشثبء ذحؼز 2 2مطؼب لا ٠م ػ

ظش.

344عذ ؽز٠غت ا ٠زؾ ػضي اعلان ازط١ اذاخ١خ - فذ.

( وزهM.C.Bفذ ثفزبػ لب٠خ ) 224رضد اؽخ ثجش٠ضح -

لإبسح.لب٠خ فظ اد ثفزبػ 5ثجخ ١ذ لا رم ػ

ضلاد 5د ٠ز رشو١ت ضلاد ؾبع١خ )ثبساد( غ١غ اماؽغ ثؼذ -

ع ػب ثأ وضبفخ 0خز١بس( لا ٠ض٠ذ ؽب ػ إ 3)ػذد ػ أ ٠ى غز اجبسح 2أج١ش / 0.0ػ ض٠ذاز١بس لا ر

الا اضبضخ. افبصح اعط خزف ػ ثبسحافبصح

- In case, the connection between the transformer and the

low voltage distribution panel to be via cables, the

distribution panel should be equipped with bottom holes

of the panel for incoming and outgoing cables, the slot

for each cable should have a diameter of at least 8 cm

and equipped with gaskets to tighten the lock on cables

and to prevent reptiles from entering the panel.

- All opening of Incoming and outgoing cables should be

closed by a suitable method.

- The panel should be equipped with the following:

Three Digital Ammeters (0-X) A. CL 0.5.

one Digital Voltmeter (0-500) V, CL 1.5.

Three Current Transformers (X/5) A, CL 0.5.

Three indication Lamps (LED Type),

Space for KWH meter with its terminals for

connection, as well as a spare it.

- All holes in the panel must be provided with glands to

prevent dust from entering the panel.

- The internal wiring should be non-flammable and made

of copper conductors insulated with PVC and with

C.S.A at least 2 mm2 and approved by the Egyptian

electricity holding company (EEHC).

- The insulation (PVC) of the internal wiring should

withstand voltage up to 600V.

- The panel should be provided with socket 220 volt with

M.C.B. and lightening lamp LED (not less than 9 watts)

with separate M.C.B.

- All MCCB circuit breakers should be supplied with 3

extension copper bars (6 bars as an option) of vertical

length not more than 7 cm with current density not more

than 1.5A/mm2 and the middle phase bar must be in a

different level than other adjacent phases bars.

Page 10: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 10 of 21

-: . المواصفات القياسية4

ااطفبد,ثبلإػبفخ ؼشسح أ رى ابد طبثمخ ز -

فئ و ىبد ؽخ ازص٠غ ٠غت أ رطبثك آخش إطذاس

ااطفبد ام١بع١خ اؼب١خ

& IEC 60947 IEC 61439-1 -بيانات: . ال5

ؽببخ ث١ببببد ػبب٠غببت وزبثببخ ث١ببببد ؽببخ ازص٠ببغ ىبرببب

- الار:ذ ثب اؽخؼذ١خ ػ اعخ

اسى انشركح انصعح:

:سح انصع

:انرقى انسهسم

:انسعح الأيثيريح نهىحح

أير تىريذ رقى )( نسح )(:

اسى انعيم: تىزيع انكهرتاء.. ن...شركح

6. الفحص والإختبارات :-

س شالجخ الإخزجبساد رؾزفع ششوخ ازص٠غ ثؾمب ف ؽؼ (0

اشر١١خ ؽخ.

ب ٠ض ػ غ١ش ره أ ٠ز اافمخ وزبثخ ثاعطخ (2

ششوبد ازص٠غ فئ ؽخ ازص٠غ ٠غت أ رخزجش ؽجمب لأخش

.IECإطذاس اطفبد ام١بع١خ اؼب١خ

ؽجمب ىبد اؽخ٠غت أ رز الإخزجبساد اشر١١خ غ١غ (5

ثاعطخ اظغ ف ؼ اظغ أ IECـ طذاس لاخش إ

ػف ؼ ؼزذ ظش مجي ششوخ ازص٠غ

.فمخ اسد

٠م اسد ثزف١ش و شبداد الإخزجبساد شبداد امجي. (0

اسد ثزغ١ غخخ رمبس٠ش الإخزجبساد ٠غت أ ٠م (0

غذاػ١خ ماؽغ اىضفبد ثبؽخ شوض أثؾبس ا

.IECافبئك ؽجمب اطفبد ام١بع١خ اؼب١خ

الإخزجبساد ازص٠غ شاؽ ازظ١غؽؼس ذع ششوخ (3

غئ١ز اىبخ ػ إزبط ؽخ ازص٠غ ٠ؼف اظغ

زطجبد ااطفخ ٠ؼط١ اؾك ف ازخض أ٠خؽجمب

عد ػ١ت ف ؽبخ ششوخ ازص٠غرطبت ثب رؼ٠ؼبد

.خببد غ١ش مجخ أ ازشط١ت اخبؽئ اعزخذارظ١غ أ

4. Standards:

In addition to the specifications above, all the distribution panel components should comply with the relevant latest applicable standards issued by the IEC 61439 -1 & IEC 60947

5. Marking:

The marking (labeling) of the distribution panel

components should be on a name plate as shown: -

Manufacturer Name:

Manufacturing Year:

Serial No.:

Panel current:

P.O No. /Year

Customer: ..… EDC

6. Inspection and Testing:

1) …EDC preserves its rights to witness the routine

testing of distribution panel.

2) Unless otherwise specified or approved in writing by

(…EDC) all distribution panel should be tested under

all relevant latest applicable IEC standards.

3) Routine tests of all components should be carried out

according to the latest IEC standards by the

manufacturer at his lab or any certified and approved

lab and on his charge.

4) All test certificates and the approval certification

should be provided.

5) A copy of the type test certificate for the circuit-

breakers and capacitors of the panel will be delivered to

(…EDC) from "High voltage research center"

according to IEC.

6) Attendance of (…EDC) inspection engineers during

fabrication stages and testing should not relieve the

manufacturer from his full responsibility for

manufacturing the distribution panels under the

requirements of this specification and should not give

him the right to invalidate any claim that (…. EDC)

may make because of defective or unsatisfactory

material or faulty workmanship.

Page 11: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electricity Holding Company بضة لكهرباء مصرالشركة القا

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 11 of 21

-الضمان: الرسومات والكتالوجات والعينات وجداول . 7

٠غ اسد غ ػشػخ اف غخخ وبخ أ٠غت -

وب –( لؼخاىزبعبد اف١خ عذاي اؼب )خزخ

.٠غت رغ١ ب ٠ف١ذ إعشاءاد شالجخ اغدح ثبظغ

ع١ز سفغ اؼطبء از لا ٠زؼ اىزبعبد عذاي -

اؼب.

٠غت ػ ازبلض رمذ٠ خطبة إػزبد اششوخ امبثؼخ -

ىشثبء ظش ؽخ ازص٠غ ىبرب الأعبع١خ

-الغيار: قطع .8

.التوزيع(شركة .... طبقا لطلب)

% من القواطع " أو سكاكين 02يجب علي المورد تسليم سعر البند لـ

م التقديرية للمهمات المصهرات " بنفس النوع المقدم وبنفس القي

المركبة باللوحة وكذلك أية مكونات تطلبها شركة التوزيع كقطع غيار.

7. Drawings, Catalogs, Samples, and Guarantee

Tables:

- The tenderer must deliver with the offer a complete

copy of catalogues and guarantee tables (stamped

and signed) for each component containing the full

technical data and quality assurance processes.

- The offer which is not accompanied by a complete

copy of catalogs and filling guarantee tables will

not be considered.

- The tenderer should submit with his offer an

approval certificate from the Egyptian electricity

holding company (EEHC) for the panel and its

main components.

8. Spare parts: -

(according to .... EDC requirement)

The tenderer should submit an itemized price list for

20% of the circuit-breakers/switch fuse of the same

type and rating of the quantities mounted in the

distribution panels as spare parts.

Page 12: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارج انكهرتاء وانطاقح انتجذدج

Egyptian Electricity Holding Company انشركح انقاتضح نكهرتاء يصر

EDMS 02-300-2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 12 of 21

Table -1

ITEM RATED POWER OF TRANSFORMER KVA

50/63 100 160 200 300 500 800 1000 1500/1600 2000 2500

1. Panel Current 100 160 250 350 550 900 1500 1800 3000 3600 4500

2. Cross section area of

main bus bars (mm2)

100 125 200 250 400 600 1000 1200 2000 2400 3000

3. Cross Section of

Neutral (mm2)

60 80 120 150 300 400 600 800 1200 1600 1800

One main circuit breaker

4. Type: MCCB MCCB MCCB MCCB MCCB ACB ACB ACB ACB ACB ACB

- frame current at 50 ⸰C

ambient temperature, A 125 250 250 400 630 1000 1600 2000 3200 4000 5000

- Nominal breaking at

400 V, Icu = Ics, KA 10 35 35 35 35 50 50 50 65 65 65

- Nominal current at 50 °C In, A

100 160 250 350 630 1000 1600 2000 3200 4000 5000

- Thermal release setting

at 50 ⸰C, A

(0.8-1) In (0.4-1) In

- Magnetic release setting

range, A (5-10) In (2-10) In

- Rated insulation voltage,

(Ui)V 750

- Rated impulse withstands

voltage (Uimp) KV 8

Page 13: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارج انكهرتاء وانطاقح انتجذدج

Egyptian Electricity Holding Company انشركح انقاتضح نكهرتاء يصر

EDMS 02-300-2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 13 of 21

Number of outgoing feeders (Option)

Transformer Rating

(KVA) 50/63 100 160 200 300 500 800 1000 1500/1600 2000 2500

5. Type: 3

MCCB

3

MCCB

3

MCCB

3

MCCB

4

MCCB

5

MCCB

6

MCCB

8

MCCB

8

MCCB

12

MCCB

16

MCCB

- frame current at 50 °C

ambient temperature,

A

63 100 160 200 250 250 250 250 400 400 400

- Nominal breaking at 400

V, Icu = Ics, KA 10 16 25 25 35 35 50 50 65 65 65

- Nominal current at 50 ⸰C

In, A 50/63 100 160 200 250 250 250 250 400 400 400

- Thermal release at 50 ⸰C,

A (0.8-1) In

- Short circuit release

setting range, A (5-10) In

- Rated insulation voltage,

(Ui)V 690 750

- Rated impulse withstands

voltage (Uimp) KV 6 8

N.B

1- B.B Current density 1.5 A/mm2, According to Egyptian Electricity Code Design (Nearest B.B common size).

2- B.B cross-sections are according to In of circuit breaker

Page 14: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارج انكهرتاء وانطاقح انتجذدج

Egyptian Electricity Holding Company انشركح انقاتضح نكهرتاء يصر

EDMS 02-300-2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 14 of 21

Street lighting Option as …EDC requirements

Transformer Rating (KVA) 50/63 100 160 200 300 500 800 1000 1500/1600 2000 2500

6. Type: 1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

1

MCCB

- frame current at 50 °C ambient

temperature, A 32 40 50 50 63 63 63 63 63 63 63

- Nominal breaking at 400 V, Icu

= Ics, KA 10 16 25 25 36 36 50 50 65 65 65

- Nominal current at 50 °C In, A 32 40 50 50 63 63 63 63 63 63 63

- Thermal release at 50 °C, A (0.8-1) In

- One 3Ph. Contactor rated

operating voltage 220V

- Nominal current at 50 C In, A 32 40 50 50 63 63 63 63 63 63 63

- One 1 ph. MCCB 10 A for

lighting control circuit √ √ √ √ √ √ √ √ √ √ √

- One digital Timer or photo cell √ √ √ √ √ √ √ √ √ √ √

The photocell unit should be cadmium sulfide type with high impact acrylic housing and window with alternative inhibitor. Rated 220V, 50 c/s,

1000 W, with normally closed contact. The photo control unit should be complete with an aluminum plug-in twist-lock container with a bracket

mounted on top of a steel structure. The unit should be designed to allow 360° rotation for photocell orientation. (OPTION)

Page 15: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry of Electricity and Renewable Energy وزارج انكهرتاء وانطاقح انتجذدج

Egyptian Electricity Holding Company انشركح انقاتضح نكهرتاء يصر

EDMS 02-300-2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 15 of 21

ITEM RATED POWER OF TRANSFORMER

50/63 100 160 200 300 500 800 1000 1500 2000 2500

7. No. of switch fuse 400/630A

size3 at 500V, breaking capacity

50KA (As option)

3 3 3 3 4 6 8 12 18 20 20

8. 2-Three current transformer,

ring type class 0.5, Ith=10KA

100/5 A

>5VA

200/5 A

>5VA

300/5 A

10 VA

400/5 A

10 VA

600/5 A

10VA

1000/5 A

10VA

1600/5 A

10VA

2000/5 A

10VA

3200/5 A

10VA

4000/5 A

10VA

5000/5 A

10VA

9. Three maximum demand

ammeters with scale range, class

1.5 (*)

0 – 100

A

0 – 200

A

0 – 300

A

0 – 400

A

0 – 600

A

0 – 1000

A

0 – 1600

A

0 – 2000

A

0 – 3200

A

0 – 4000

A

0 – 5000

A

10. One three phase voltmeter with

scale range, class 1.5 with

selector switch – 7 positions. (*)

0 – 500

V

0 – 500

V

0 – 500

V

0 – 500

V

0 – 500

V

0 – 500 V 0 – 500 V 0 – 500

V

0 – 500

V

0 – 500

V

0 – 500 V

11. Three indication lamps √ √ √ √ √ √ √ √ √ √ √

12. Fixed capacitor (KVAR) at

rated voltage 400 V (**) 5 5 7.5/10 10 15 25 40 50 75 100 125

13. M.C.C.B. for Fixed capacitor, A

at 50°c

16 16 32 32 40 63 100 125 200 250 320

14. Rated breaking capacity at 400

V, KA

10 16 25 25 35 36 50 50 65 65 65

(*) The ammeters and voltmeters should be of digital type (multi meter can be used).

(**) The capacitor should be withstanding 525 V continuously .

Page 16: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 16 of 21

-(: Requirements) اشتراطاخ. 9

فه اؼش ىثؾ١ش ٠ لج اذب 2.0ػببد اظت عه لا ٠م ػ ٠ز ثبء اؽخ ػ ١ى اذ -0

.الاعبة رظ ع١غ ىبد اؽخ لبئخ وب

.ػذ اعزخذا غب١ش ع اظبط ف رضج١ذ أ عضء اؽخ ثب ف ره اشا٠ب -2

ذ(.خؾ افم اؽ )ػ٠ض ا رى ثبسح ازؼبدي ف ؾبراح اجبساد اشئ١غ١خ -5

لبػذح ؽخ ٠ز غك فزؾبرب ثغارش وزه ػع ٠04ض ا ٠شرفغ اجبة ػ الأسػ١خ غبفخ لا رم ػ -0

ىب١خ عف اؽخ لإأ ءدخي أ ش١ غثؼذ رضج١ذ اؽخ ثىبب اذ اىزشعزبر١ه ا اغف اظبط

.ثبرلاف ؽذس أ إعف د أؽ اؽخ

ثشى لطش ف ١ى اؽخ لاىب١خ ؽ اؽخ اؽخ(ؾ )وبف١خ ػ الالذد اص١ ن رضج١ذ ػ -0

.ػأ

دسعخ ئ٠خ. 04از١بس ام مبؽغ ػذ دسعخ ؽشاسح شعؼ١خ -3

دسعخ ئ٠خ( 04 )ػذدسعخ ئ٠خ 04وبذ الاخزجبساد اػ١خ لذ رذ ػذ دسعخ ؽشاسح أل إراف ؽبخ -0

ػ الار:٠ز

( ػذ دسعخ ؽشاسح 0ز١بس امبؽغ ثؾ١ش لا رم ػ ام١ اذخ ثبغذي )سل de-ratingعزخذا ل١ إ -

امذ frame current رزض اششوبد اسدح ف ز اؾبخ ثم١ أدسعخ ئ٠خ ػ 04

شاعؼزب ثاعطخ ششوبد دسعخ ؽشاسح ئ٠خ 04 04اسد غ رمذ٠ الاثؼبد ى لبؽغ ػذ

ازص٠غ ره ف اؾبلاد از رؤد ا شبو ف ازشغ١ أ ازشو١ت داخ الاوشبن أ اؽبد

رخبر امشاس.لإ

دسعخ ئ٠خ ػ ا رى اىزبثخ ثطش٠مخ لا 04ػؼ ػ١ب ل١خ از١بس ػذ name plateػبفخ إ٠ز -

٠ى ؾب.

ثبسح ؾ١خ خبسط 0اؾبع١خ زضج١ذ اىبثلاد ػ امبؽغ )ثؼذد ابلاد(اجبساد )أ رشز اؾمبد ػ -8

ثبسح غزم١خ(. 2ى ػذد

ػزبد اششوخ امبثؼخ ىشثبء ظش زاد اطشاص أ ٠ى خطبة الاػزبد عبس ب٠خ ذح إ٠ض رمذ٠ -5

الاسرجبؽ.

ربس٠خ شش 53شش ربس٠خ ازشو١ت ػذد 20شح ا ٠ض ذ فزشح اؼب بد اسدح لأي -04

ازس٠ذ.

Page 17: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 17 of 21

TABLE: (1)

Reference Ampere Rating at 40°C (104° F)

Ampere Rating at:

25°C (77° F) 50°C (122° F) 60°C (140° F)

15 17 13 11

20 22 18 16

25 28 23 21

30 33 28 26

35 39 30 25

40 44 37 34

50 55 46 42

60 66 56 52

70 77 65 60

90 99 84 78

100 110 94 87

125 137 114 100

150 165 136 120

175 192 159 140

200 220 182 160

225 247 205 180

250 275 235 220

300 330 276 252

350 385 325 301

400 440 372 340

500 550 468 435

600 660 564 525

700 770 658 613

800 880 754 704

900 990 828 749

1000 1100 900 825

1200 1320 1090 1000

1400 1540 1304 1148

1600 1760 1500 1320

1800 1980 1690 1485

2000 2200 1880 1650

3200 3520 3000 2650

4000 4400 3760 3300

5000 5500 4700 4125

Page 18: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 18 of 21

10. GUARANTEE TABLE NO. 1

ENCLOSURE AND BUS-BARS

FOR ……. A PANEL

1- Enclosure: -

- Manufacturer name :-----------

- Type :-----------

- Material :----------

- Thickness of steel sheet before painting :---------- mm

- Dimensions :----------

* Width : -------- mm

* Depth : -------- mm

* Height : --------- mm

2-Bus-bars: -

- Material : ---------

- Cross section

* Per phase : -------- mm2

* Neutral bus : --------- mm2

* Earth bus : --------- mm2

- Purity of copper : ---------- %

- Conductivity of copper : ---------- SM/m

- Minimum clearance between phases : ---------- mm

- Minimum clearance to earth : ---------- mm

- Continuous current inside the enclosure

* At 50 ◦C for indoor :------------ A

- Dynamic withstand current, peak : ----------- kA

- One- second thermal withstand current : ----------- kA

- Rated insulation voltage : ----------- V

- One- second power frequency withstand voltage : ----------- V

I / We guarantee the technical data given above for the offered equipment.

Signature: -----------------

Date: -----------------

Page 19: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 19 of 21

GUARANTEE TABLE NO. 2

MAIN CIRCUIT - BREAKERS

FOR ….... A PANEL

- Manufacturer name :-----------

- Standard specification :----------

- Type :----------

- Rated current inside the enclosure

* At 50 ◦C :--------- A

- Rated insulation voltage : --------- V

- Rated breaking capacity at 400 V : --------- kA

- Rated making capacity, peak : ---------- kA

- Rated current of thermal release inside the enclosure (Ir):

* At 50 ◦C :----------- A

- Thermal release setting value at 50 ◦C :---------- A

- Short circuit release setting value : ---------- A

- One-second power frequency withstand voltage : ---------- V

- Material of main contacts :---------

- Material of arcing contacts :-----------

- Type of arc control device :---------

- Material of arc control device :--------

I / We guarantee the technical data given above for the offered equipment.

Signature: -----------------

Date: -----------------

Page 20: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 20 of 21

GUARANTEE TABLE NO. 3

OUTGOING CIRCUIT – BREAKERS

FOR ….... KVA TRANSFORMER OF ….... A PANEL

- Manufacturer name :-----------

- Standard specification :----------

- Type :----------

- Rated current inside the enclosure

* At 50 ◦C :--------- A

- Rated insulation voltage : --------- V

- Rated breaking capacity at 400 V : --------- kA

- Rated making capacity, peak : ---------- kA

- Rated current of thermal release inside the enclosure (Ir):

* At 50 ◦C :----------- A

- Thermal release setting value at 50 ◦C :---------- A

- Short circuit release setting value : ---------- A

- One-second power frequency withstand voltage : ---------- V

- Material of main contacts :---------

- Material of arcing contacts :-----------

- Type of arc control device :---------

- Material of arc control device :--------

I / We guarantee the technical data given above for the offered equipment.

Signature: -----------------

Date: -----------------

Page 21: EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS …

Ministry Of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة

Egyptian Electric Holding Company الشركة القابضة لكهرباء مصر

EDMS 02- 300 - 2 EEHC DISTRIBUTION MATERIALS SPECIFICATION

Date: 15-12-2020

Page 21 of 21

GUARANTEE TABLE NO. 4

FOR ….. KVA - LOW VOLTAGE CAPACITOR OF ….. A PANEL

- Manufacturer name : -----------

- Type : -----------

- Type of connection : -----------

- Rated voltage : ----------- kV

- Operating voltage : ------------ kV

- Rated frequency : ----------- Hz

- Rated power : ------------ KVAR

- Rated capacitance : ------------ μF

- Rated current : ------------ A

- Type of dielectric : ----------

- Over pressure disconnected : ----------

- Discharge resistor : --------- Ohm

- Discharge time to 75 V : --------- min

- Dielectric loss (including power loss of discharge resistor) : ----------

- Insulation level:

Rated power frequency Withstand voltage (r.m.s.) : -------- kV

1.2/50 u

s impulse Withstand voltage (pe : -------- kV

- Ambient temperature : --------- oC

- Relative humidity : -----------

- Degree of protection : ---------

- Life time of capacitor : -------- hours

- Material of capacitor tank :----------

I / We guarantee the technical data given above for the offered equipment.

Signature: -----------------

Date: -----------------