® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 1 04.07.17
EcoSystem Switching Power Module for Non-Dim LoadsLutron EcoSystem Switching Power Module allows integration of non-dim loads into a Lutron EcoSystem Bus. The Power Module combines digital commands and sensor data to control the load.
Features
•Capableofswitching16Aofhighin-rushlightingload (LED, magnetic fluorescent ballast, electronic fluorescent ballast, incandescent, magnetic low-voltage, electronic low-voltage, neon / cold cathode and motor loads)
•Provides20V-powerforandrespondstooneoccupantsensor,oneEcoSystem daylight sensor, andoneEcoSystempersonalcontrolinput(infraredreceiver or wallstation)
•CommunicatesstatusandsensorlevelsovertheEcoSystem Bus
•Universalvoltageinput:100to277V~50/60Hz•Non-volatile(EEPROM)memorystoresspecificsysteminformationfor10yearsfrompowerdowntopowerrestored
•100%performancetestedatfactory
Note:FrequentswitchingofHIDloadsmayaffectthelifetimeofthelampsorballasts.PleasecontactthelamporballastmanufacturersformoreinformationaboutcompatibilitywithHIDloads,especiallywhenusedwithoccupancysensors.
EcoSystem One-Line
12
34
56
78
Non-DimLoad
Wallstation
EcoSystem Bus
EcoSystem Ballast
Lighting Remote
OccupancySensor
Daylight Sensor
EcoSystem Ballast
EcoSystem Ballast
EcoSystem Switching Power Module
EcoSystem BusSupply*
IRReceiver
To additional ballasts andmodules(upto64total)
*DoesnotcountasoneoftheballastsormodulesontheEcoSystemBus.ThebussupplycanbeanEnergiSavrNodeunitorcanbelocated in a Quantum hub.
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 2 04.07.17
Specifications
Regulatory Approvals
•UL®916ListedandCSA184Certified•MeetsANSIC62.41CategoryAsurgeprotectionstandardsuptoandincluding6000V~
•ManufacturingfacilitiesemployESDreductionpracticesthatcomplywiththerequirementsofANSI/ESDS20.20
•LutronQualitySystemsregisteredto ISO9001.2000
•NOM•Complieswithrequirementsforuseinotherspacesusedforenvironmentalair(plenums)per NEC®2014300.22(C)(3)
•MeetstheCanadianNationalBuildingCodeplenumrequirementsforaconcealedspaceusedasaplenumwithinafloororroofassembly
•Forcommercialuse,ClassAonly
Power
•OperatingVoltage:100to277V~50/60Hz•OutputRating:16ASoftswitchmaximumnon-dim
load•IECPELV/NEC®Class2SensorPower:20V- 50 mAmaximum
Switchable Load Types
•LED•Magneticfluorescentballast•Electronicfluorescentballast•IncandescentandHalogen•Magneticlow-voltagetransformer•Electroniclow-voltagetransformer•NeonorColdCathode•MotorLoads -1/4HPat100to120V~
-1/2HPat200to277V~
Note:Donotusetoswitchreceptacles.
Environment
•AmbientTemperatureOperatingRange:32ºFto104ºF(0ºCto40ºC)
•Relativehumidity:lessthan90%non-condensing•Forindooruseonly
Module Wiring (see Wiringpagesforwiringdiagrams)
•Terminalblocksacceptwiresofthefollowingsize: EcoSystem Bus(E1,E2):
-22AWGto12AWG(0.5mm2to2.5mm2) solid wire IEC PELV/NEC®Class2Sensors: -22AWGto12AWG(0.5mm2to2.5mm2)
solid wire•Wiringbetweenmoduleandloadis3conductors: SwitchedHot
Neutral Ground•Wiringbetweenmoduleandsensorsshallnot exceedmanufacturer’sspecifications.
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 3 04.07.17
DimensionsAlldimensionsshownasin(mm)
C5-XPJ-16A
C5-XPJ-16A
Junctionbox
CEILING
Mounting•MounttheEcoSystemSwitchingModuleontoa 4inx4in(102mmx102mm)standard(1900)junctionbox(notincluded,butavailable; LutronP/N241496)
•Mountonaverticalorhorizontalsurface;allpowerwireconnectionswillbemadeinthejunctionbox;allEcoSystembuswiring(NEC®Class1or IEC PELV/NEC® Class2)andsensorwiring (IEC PELV/NEC®Class2only)connectionswillbemade within the front cover of the unit
•MountinalocationwherethePWRandSTATindicators are visible
•Allfield-installedIEC PELV/NEC®Class2wiringmustbeseparatedfromlinevoltagewiringbyatleast0.25in(6.4mm)
•SomelocalelectricalcodesrequireIEC PELV/NEC®Class2wiringtobeseparatelyrouted in a metal conduit
Electrical Contractors and Engineers
B
A
WALL
7.8 (200)
5.0 (130)
2.5 (64)
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 4 04.07.17
•Connecttheinputfeedwiresandtheoutputloadwires to the module as indicated in the wiring diagrams below
Wiring
EcoSystem Power Module Line Voltage Wiring
Distribution Panel
Non-DimLoads
Non-DimLoads
FixtureGround
FixtureGroundGreen*
Green*
White*
White*
Black*
Black*
Green(ground)*
White(neutral)*
Red(switchedhot)*
Green*
White*
Black*
Ground
Neutral
Line/Hot
C5-XPJ-16A
*ColorsindicatethemoduleandLutronballastwirecolorsand/orLutronballastterminalcolors
EcoSystem Power Module
GreenWhite
Red
Black
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 5 04.07.17
Wiring (continued)
EcoSystem Bus Wiring
•WiretheEcoSystemBustotheE1andE2terminalson the front of the module.
•WhentheEcoSystem BusiswiredasNEC®Class 1,thebuswiringmustentertheleftsideknockoutandmaintain0.25in(6mm)spacingfromthe IEC PELV/NEC® Class 2sensorwiring.
•WhentheEcoSystem BusiswiredIEC PELV/NEC® Class2,thebuswiringmayentereitherknockoutonthe low voltage wiring area.
EcoSystem Bus Details•E1andE2wiresarenotpolaritysensitive•BuslengthislimitedbythewiregaugeusedforE1andE2asfollows:Wire Gauge (solid wire) Bus Length (max)12AWG(4.0mm2) 2200ft(671m)14AWG(2.5mm2) 1400ft(427m)16AWG(1.5mm2) 900ft(274m)18AWG(1.0mm2) 570ft(174m)
E1-PurpleE2-Purple/White
To additional EcoSystem modules, ballasts, and the
EcoSystem Bus wiringknockout
E1E2
E1E2
IECPELV/NEC®Class2wiringknockout
NOTE: See Specificationspageforwiringspecifications
Lutron,Lutron,Quantum,Softswitch,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.
EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
EcoSystem C5-XPJ-16A Switching Power Module
369409d 6 04.07.17
Wiring to IEC PELV / NEC® Class 2 Sensors•WirecolordesignationsoftheIEC PELV/NEC®Class2Terminals: Red= 20V- Black= Common White= IR(wallstation/IRreceiver) Blue= OccupancySensor Yellow=DaylightSensorSignal
•Wiringbetweenmoduleandsensorsshallnotexceedmanufacturer’sspecifications.
•MakesurethatthesupplybreakertotheswitchingpowermoduleisOFFwhenwiring.
Note:ThemoduleacceptsonlyoneIRInput.UseoftheIRoutputfromtheEcoSystem Daylight Sensor precludestheuseofanIRreceiverorwallstationwith the module. When both a daylight sensor and wallstation/IRreceiverarewiredtothesamemodule,theIRwirefromthedaylightsensorshouldnotbeconnected.
Wiring (continued)
Low Voltage Wiring IEC PELV / NEC® Class 2 Sensors
EcoSystem Daylight Sensor Wired to Module
OccupantSensorWiredtoModule
EcoSystem Daylight Sensor and Wallstation wired to the module(IRwiredonlytokeypad)
IEC PELV/NEC® Class2wiringknockout
White
Red
Black
White
Red
Yellow
Black
Red
Blue
Black
NOTE: See Specificationspageforwiringspecifications