6
SPECIFICATION SUBMITTAL Page Job Name: Job Number: Model Numbers: EcoSystem C5-XPJ-16A Switching Power Module 369409d 1 04.07.17 EcoSystem Switching Power Module for Non-Dim Loads Lutron EcoSystem Switching Power Module allows integration of non-dim loads into a Lutron EcoSystem Bus. The Power Module combines digital commands and sensor data to control the load. Features • Capable of switching 16 A of high in-rush lighting load (LED, magnetic fluorescent ballast, electronic fluorescent ballast, incandescent, magnetic low- voltage, electronic low-voltage, neon / cold cathode and motor loads) • Provides 20 V- power for and responds to one occupant sensor, one EcoSystem daylight sensor, and one EcoSystem personal control input (infrared receiver or wallstation) • Communicates status and sensor levels over the EcoSystem Bus • Universal voltage input: 100 to 277 V~ 50/60 Hz • Non-volatile (EEPROM) memory stores specific system information for 10 years from power down to power restored • 100% performance tested at factory Note: Frequent switching of HID loads may affect the lifetime of the lamps or ballasts. Please contact the lamp or ballast manufacturers for more information about compatibility with HID loads, especially when used with occupancy sensors. EcoSystem One-Line 12345678 Non-Dim Load Wallstation EcoSystem Bus EcoSystem Ballast Lighting Remote Occupancy Sensor Daylight Sensor EcoSystem Ballast EcoSystem Ballast EcoSystem Switching Power Module EcoSystem Bus Supply* IR Receiver To additional ballasts and modules (up to 64 total) * Does not count as one of the ballasts or modules on the EcoSystem Bus. The bus supply can be an Energi Savr Node unit or can be located in a Quantum hub.

EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 1 04.07.17

EcoSystem Switching Power Module for Non-Dim LoadsLutron EcoSystem Switching Power Module allows integration of non-dim loads into a Lutron EcoSystem Bus. The Power Module combines digital commands and sensor data to control the load.

Features

•Capableofswitching16Aofhighin-rushlightingload (LED, magnetic fluorescent ballast, electronic fluorescent ballast, incandescent, magnetic low-voltage, electronic low-voltage, neon / cold cathode and motor loads)

•Provides20V-powerforandrespondstooneoccupantsensor,oneEcoSystem daylight sensor, andoneEcoSystempersonalcontrolinput(infraredreceiver or wallstation)

•CommunicatesstatusandsensorlevelsovertheEcoSystem Bus

•Universalvoltageinput:100to277V~50/60Hz•Non-volatile(EEPROM)memorystoresspecificsysteminformationfor10yearsfrompowerdowntopowerrestored

•100%performancetestedatfactory

Note:FrequentswitchingofHIDloadsmayaffectthelifetimeofthelampsorballasts.PleasecontactthelamporballastmanufacturersformoreinformationaboutcompatibilitywithHIDloads,especiallywhenusedwithoccupancysensors.

EcoSystem One-Line

12

34

56

78

Non-DimLoad

Wallstation

EcoSystem Bus

EcoSystem Ballast

Lighting Remote

OccupancySensor

Daylight Sensor

EcoSystem Ballast

EcoSystem Ballast

EcoSystem Switching Power Module

EcoSystem BusSupply*

IRReceiver

To additional ballasts andmodules(upto64total)

*DoesnotcountasoneoftheballastsormodulesontheEcoSystemBus.ThebussupplycanbeanEnergiSavrNodeunitorcanbelocated in a Quantum hub.

Page 2: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 2 04.07.17

Specifications

Regulatory Approvals

•UL®916ListedandCSA184Certified•MeetsANSIC62.41CategoryAsurgeprotectionstandardsuptoandincluding6000V~

•ManufacturingfacilitiesemployESDreductionpracticesthatcomplywiththerequirementsofANSI/ESDS20.20

•LutronQualitySystemsregisteredto ISO9001.2000

•NOM•Complieswithrequirementsforuseinotherspacesusedforenvironmentalair(plenums)per NEC®2014300.22(C)(3)

•MeetstheCanadianNationalBuildingCodeplenumrequirementsforaconcealedspaceusedasaplenumwithinafloororroofassembly

•Forcommercialuse,ClassAonly

Power

•OperatingVoltage:100to277V~50/60Hz•OutputRating:16ASoftswitchmaximumnon-dim

load•IECPELV/NEC®Class2SensorPower:20V- 50 mAmaximum

Switchable Load Types

•LED•Magneticfluorescentballast•Electronicfluorescentballast•IncandescentandHalogen•Magneticlow-voltagetransformer•Electroniclow-voltagetransformer•NeonorColdCathode•MotorLoads -1/4HPat100to120V~

-1/2HPat200to277V~

Note:Donotusetoswitchreceptacles.

Environment

•AmbientTemperatureOperatingRange:32ºFto104ºF(0ºCto40ºC)

•Relativehumidity:lessthan90%non-condensing•Forindooruseonly

Module Wiring (see Wiringpagesforwiringdiagrams)

•Terminalblocksacceptwiresofthefollowingsize: EcoSystem Bus(E1,E2):

-22AWGto12AWG(0.5mm2to2.5mm2) solid wire IEC PELV/NEC®Class2Sensors: -22AWGto12AWG(0.5mm2to2.5mm2)

solid wire•Wiringbetweenmoduleandloadis3conductors: SwitchedHot

Neutral Ground•Wiringbetweenmoduleandsensorsshallnot exceedmanufacturer’sspecifications.

Page 3: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 3 04.07.17

DimensionsAlldimensionsshownasin(mm)

C5-XPJ-16A

C5-XPJ-16A

Junctionbox

CEILING

Mounting•MounttheEcoSystemSwitchingModuleontoa 4inx4in(102mmx102mm)standard(1900)junctionbox(notincluded,butavailable; LutronP/N241496)

•Mountonaverticalorhorizontalsurface;allpowerwireconnectionswillbemadeinthejunctionbox;allEcoSystembuswiring(NEC®Class1or IEC PELV/NEC® Class2)andsensorwiring (IEC PELV/NEC®Class2only)connectionswillbemade within the front cover of the unit

•MountinalocationwherethePWRandSTATindicators are visible

•Allfield-installedIEC PELV/NEC®Class2wiringmustbeseparatedfromlinevoltagewiringbyatleast0.25in(6.4mm)

•SomelocalelectricalcodesrequireIEC PELV/NEC®Class2wiringtobeseparatelyrouted in a metal conduit

Electrical Contractors and Engineers

B

A

WALL

7.8 (200)

5.0 (130)

2.5 (64)

Page 4: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 4 04.07.17

•Connecttheinputfeedwiresandtheoutputloadwires to the module as indicated in the wiring diagrams below

Wiring

EcoSystem Power Module Line Voltage Wiring

Distribution Panel

Non-DimLoads

Non-DimLoads

FixtureGround

FixtureGroundGreen*

Green*

White*

White*

Black*

Black*

Green(ground)*

White(neutral)*

Red(switchedhot)*

Green*

White*

Black*

Ground

Neutral

Line/Hot

C5-XPJ-16A

*ColorsindicatethemoduleandLutronballastwirecolorsand/orLutronballastterminalcolors

EcoSystem Power Module

GreenWhite

Red

Black

Page 5: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 5 04.07.17

Wiring (continued)

EcoSystem Bus Wiring

•WiretheEcoSystemBustotheE1andE2terminalson the front of the module.

•WhentheEcoSystem BusiswiredasNEC®Class 1,thebuswiringmustentertheleftsideknockoutandmaintain0.25in(6mm)spacingfromthe IEC PELV/NEC® Class 2sensorwiring.

•WhentheEcoSystem BusiswiredIEC PELV/NEC® Class2,thebuswiringmayentereitherknockoutonthe low voltage wiring area.

EcoSystem Bus Details•E1andE2wiresarenotpolaritysensitive•BuslengthislimitedbythewiregaugeusedforE1andE2asfollows:Wire Gauge (solid wire) Bus Length (max)12AWG(4.0mm2) 2200ft(671m)14AWG(2.5mm2) 1400ft(427m)16AWG(1.5mm2) 900ft(274m)18AWG(1.0mm2) 570ft(174m)

E1-PurpleE2-Purple/White

To additional EcoSystem modules, ballasts, and the

EcoSystem Bus wiringknockout

E1E2

E1E2

IECPELV/NEC®Class2wiringknockout

NOTE: See Specificationspageforwiringspecifications

Lutron,Lutron,Quantum,Softswitch,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.

EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.

Page 6: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 6 04.07.17

Wiring to IEC PELV / NEC® Class 2 Sensors•WirecolordesignationsoftheIEC PELV/NEC®Class2Terminals: Red= 20V- Black= Common White= IR(wallstation/IRreceiver) Blue= OccupancySensor Yellow=DaylightSensorSignal

•Wiringbetweenmoduleandsensorsshallnotexceedmanufacturer’sspecifications.

•MakesurethatthesupplybreakertotheswitchingpowermoduleisOFFwhenwiring.

Note:ThemoduleacceptsonlyoneIRInput.UseoftheIRoutputfromtheEcoSystem Daylight Sensor precludestheuseofanIRreceiverorwallstationwith the module. When both a daylight sensor and wallstation/IRreceiverarewiredtothesamemodule,theIRwirefromthedaylightsensorshouldnotbeconnected.

Wiring (continued)

Low Voltage Wiring IEC PELV / NEC® Class 2 Sensors

EcoSystem Daylight Sensor Wired to Module

OccupantSensorWiredtoModule

EcoSystem Daylight Sensor and Wallstation wired to the module(IRwiredonlytokeypad)

IEC PELV/NEC® Class2wiringknockout

White

Red

Black

White

Red

Yellow

Black

Red

Blue

Black

NOTE: See Specificationspageforwiringspecifications

Yellow