EcoSystem C5-XPJ-16A Switching Power Module

369409d 1 04.07.17

EcoSystem Switching Power Module for Non-Dim LoadsLutron EcoSystem Switching Power Module allows integration of non-dim loads into a Lutron EcoSystem Bus. The Power Module combines digital commands and sensor data to control the load.

Features

•Capableofswitching16Aofhighin-rushlightingload (LED, magnetic fluorescent ballast, electronic fluorescent ballast, incandescent, magnetic low-voltage, electronic low-voltage, neon / cold cathode and motor loads)

•Provides20V-powerforandrespondstooneoccupantsensor,oneEcoSystem daylight sensor, andoneEcoSystempersonalcontrolinput(infraredreceiver or wallstation)

•CommunicatesstatusandsensorlevelsovertheEcoSystem Bus

•Universalvoltageinput:100to277V~50/60Hz•Non-volatile(EEPROM)memorystoresspecificsysteminformationfor10yearsfrompowerdowntopowerrestored

•100%performancetestedatfactory

Note:FrequentswitchingofHIDloadsmayaffectthelifetimeofthelampsorballasts.PleasecontactthelamporballastmanufacturersformoreinformationaboutcompatibilitywithHIDloads,especiallywhenusedwithoccupancysensors.

EcoSystem One-Line

12

34

56

78

Non-DimLoad

Wallstation

EcoSystem Bus

EcoSystem Ballast

Lighting Remote

OccupancySensor

Daylight Sensor

EcoSystem Ballast

EcoSystem Ballast

EcoSystem Switching Power Module

EcoSystem BusSupply*

IRReceiver

To additional ballasts andmodules(upto64total)

*DoesnotcountasoneoftheballastsormodulesontheEcoSystemBus.ThebussupplycanbeanEnergiSavrNodeunitorcanbelocated in a Quantum hub.

Page 2: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 2 04.07.17

Specifications

Regulatory Approvals

•UL®916ListedandCSA184Certified•MeetsANSIC62.41CategoryAsurgeprotectionstandardsuptoandincluding6000V~

•ManufacturingfacilitiesemployESDreductionpracticesthatcomplywiththerequirementsofANSI/ESDS20.20

•LutronQualitySystemsregisteredto ISO9001.2000

•NOM•Complieswithrequirementsforuseinotherspacesusedforenvironmentalair(plenums)per NEC®2014300.22(C)(3)

•MeetstheCanadianNationalBuildingCodeplenumrequirementsforaconcealedspaceusedasaplenumwithinafloororroofassembly

•Forcommercialuse,ClassAonly

Power

•OperatingVoltage:100to277V~50/60Hz•OutputRating:16ASoftswitchmaximumnon-dim

load•IECPELV/NEC®Class2SensorPower:20V- 50 mAmaximum

Switchable Load Types

•LED•Magneticfluorescentballast•Electronicfluorescentballast•IncandescentandHalogen•Magneticlow-voltagetransformer•Electroniclow-voltagetransformer•NeonorColdCathode•MotorLoads -1/4HPat100to120V~

-1/2HPat200to277V~

Note:Donotusetoswitchreceptacles.

Environment

•AmbientTemperatureOperatingRange:32ºFto104ºF(0ºCto40ºC)

•Relativehumidity:lessthan90%non-condensing•Forindooruseonly

Module Wiring (see Wiringpagesforwiringdiagrams)

•Terminalblocksacceptwiresofthefollowingsize: EcoSystem Bus(E1,E2):

-22AWGto12AWG(0.5mm2to2.5mm2) solid wire IEC PELV/NEC®Class2Sensors: -22AWGto12AWG(0.5mm2to2.5mm2)

solid wire•Wiringbetweenmoduleandloadis3conductors: SwitchedHot

Neutral Ground•Wiringbetweenmoduleandsensorsshallnot exceedmanufacturer’sspecifications.

Page 3: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 3 04.07.17

DimensionsAlldimensionsshownasin(mm)

C5-XPJ-16A

C5-XPJ-16A

Junctionbox

CEILING

Mounting•MounttheEcoSystemSwitchingModuleontoa 4inx4in(102mmx102mm)standard(1900)junctionbox(notincluded,butavailable; LutronP/N241496)

•Mountonaverticalorhorizontalsurface;allpowerwireconnectionswillbemadeinthejunctionbox;allEcoSystembuswiring(NEC®Class1or IEC PELV/NEC® Class2)andsensorwiring (IEC PELV/NEC®Class2only)connectionswillbemade within the front cover of the unit

•MountinalocationwherethePWRandSTATindicators are visible

•Allfield-installedIEC PELV/NEC®Class2wiringmustbeseparatedfromlinevoltagewiringbyatleast0.25in(6.4mm)

•SomelocalelectricalcodesrequireIEC PELV/NEC®Class2wiringtobeseparatelyrouted in a metal conduit

Electrical Contractors and Engineers

B

A

WALL

7.8 (200)

5.0 (130)

2.5 (64)

Page 4: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 4 04.07.17

•Connecttheinputfeedwiresandtheoutputloadwires to the module as indicated in the wiring diagrams below

Wiring

EcoSystem Power Module Line Voltage Wiring

Distribution Panel

Non-DimLoads

Non-DimLoads

FixtureGround

FixtureGroundGreen*

Green*

White*

White*

Black*

Black*

Green(ground)*

White(neutral)*

Red(switchedhot)*

Green*

White*

Black*

Ground

Neutral

Line/Hot

C5-XPJ-16A

*ColorsindicatethemoduleandLutronballastwirecolorsand/orLutronballastterminalcolors

EcoSystem Power Module

GreenWhite

Red

Black

Page 5: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 5 04.07.17

Wiring (continued)

EcoSystem Bus Wiring

•WiretheEcoSystemBustotheE1andE2terminalson the front of the module.

•WhentheEcoSystem BusiswiredasNEC®Class 1,thebuswiringmustentertheleftsideknockoutandmaintain0.25in(6mm)spacingfromthe IEC PELV/NEC® Class 2sensorwiring.

•WhentheEcoSystem BusiswiredIEC PELV/NEC® Class2,thebuswiringmayentereitherknockoutonthe low voltage wiring area.

EcoSystem Bus Details•E1andE2wiresarenotpolaritysensitive•BuslengthislimitedbythewiregaugeusedforE1andE2asfollows:Wire Gauge (solid wire) Bus Length (max)12AWG(4.0mm2) 2200ft(671m)14AWG(2.5mm2) 1400ft(427m)16AWG(1.5mm2) 900ft(274m)18AWG(1.0mm2) 570ft(174m)

E1-PurpleE2-Purple/White

To additional EcoSystem modules, ballasts, and the

EcoSystem Bus wiringknockout

E1E2

E1E2

IECPELV/NEC®Class2wiringknockout

NOTE: See Specificationspageforwiringspecifications

Lutron,Lutron,Quantum,Softswitch,andEcoSystemaretrademarksofLutronElectronicsCo.,Inc.registeredintheU.S.andothercountries.

EnergiSavrNodeisatrademarkofLutronElectronicsCo.,Inc.

Page 6: EcoSystem Switching Power Module for Non-Dim …...®SPECIFICA AL Page ob ame ob umber Model umbers EcoSystem -P- Switching Power Module 369409d 4 04.07.17 • Connect the input feed

® SPECIF ICAT ION SUBMITTAL Page

Job Name:

Job Number:

Model Numbers:

EcoSystem C5-XPJ-16A Switching Power Module

369409d 6 04.07.17

Wiring to IEC PELV / NEC® Class 2 Sensors•WirecolordesignationsoftheIEC PELV/NEC®Class2Terminals: Red= 20V- Black= Common White= IR(wallstation/IRreceiver) Blue= OccupancySensor Yellow=DaylightSensorSignal

•Wiringbetweenmoduleandsensorsshallnotexceedmanufacturer’sspecifications.

•MakesurethatthesupplybreakertotheswitchingpowermoduleisOFFwhenwiring.

Note:ThemoduleacceptsonlyoneIRInput.UseoftheIRoutputfromtheEcoSystem Daylight Sensor precludestheuseofanIRreceiverorwallstationwith the module. When both a daylight sensor and wallstation/IRreceiverarewiredtothesamemodule,theIRwirefromthedaylightsensorshouldnotbeconnected.

Wiring (continued)

Low Voltage Wiring IEC PELV / NEC® Class 2 Sensors

EcoSystem Daylight Sensor Wired to Module

OccupantSensorWiredtoModule

EcoSystem Daylight Sensor and Wallstation wired to the module(IRwiredonlytokeypad)

IEC PELV/NEC® Class2wiringknockout

White

Red

Black

White

Red

Yellow

Black

Red

Blue

Black

NOTE: See Specificationspageforwiringspecifications

Yellow