Upload
votram
View
220
Download
0
Embed Size (px)
Citation preview
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 1 06.04.12
LCP128T Spec Grade Dimming System
System Overview
LCP128T is a combination dimming and switching system that provides a complete lighting control solution. The system consists of panels and control station devices. An integrated astronomical time clock provides system automation capability.
System Features
•32programmablelightingscenesandoff.•Connectupto8powerpanels(specgradeand
standard) for up to 128 dimmed/switched outputs.•Connectupto32wallstationsorcontroldevicesfor
multiple points of control.•EntiresystemisprogrammedusingtheLCD
controller mounted in the panel.•Astronomicaltimeclockprovidesautomated
selection of lighting scenes.•Worksdirectlywithincandescent,magneticlow-voltage,electroniclow-voltage,neon,LutronR Tu-Wire® and switched load types.
•WorkswithDSI,DALIR,and0-10V- dimming ballastsusing10Vmodulesinthepanel.
•WorkswithLutronREco-10®andHi-Lume® FluorescentDimmingBallasts.
•Feed-throughorbranchcircuitbreakerpanelsareavailable.
•Panelispre-wiredandpre-tested.•Spec-gradepanelmaybesurfacemountedonly.
LCP128TSpec-GradePanel
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 2 06.04.12
LCP128T Controller
Overview
Lighting control may be automated by using the astronomical time clock integrated into the LCP128T controller.ThecontrollerhasanLCDscreenforeasyprogramming.
Features
•LCDinterfacesimplifiesscene,timeclockevent,andcontrol station programming.
•Timeclockeventsautomaticallyrecallpresetsataspecifictimeofdayoratanoffsetfromsunriseorsunset.
•Upto500totaleventsareprogrammablewithin7 dailyschedulesand40holidayschedules.
•Holidayschedulesareprogrammabletorunonceorrepeatupto90daysinarow.
•Twointegratedcontactclosureinputsprovideaninterface with occupancy sensors or building management systems.
•Selectsystemlocationfromabuilt-incitydatabaseor by entering latitude and longitude.
•Timeclockisbatterybacked;timeandevent settings are remembered even after power failures.
•Programmableflash-warnfeature.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 3 06.04.12
Specifications
Standards
•ULRListed(Reference:ULFileE42071)•CSACertified•CaliforniaEnergyCommissionListed•SeismicCertified(TestMethodAC156.ReferenceOSHPDPreapprovalOSP-0215-10)
•NOMcertifiedmodelsavailable.
Power
•Inputpower:100-127V and277V ,50/60Hz,phase-to-neutral.
•BranchCircuitCapacity: -120-127V :upto2000W/VA -277V :4500W/VA•Branchcircuitbreakers(ifapplicable):UL-rated
thermal magnetic. AICrating: -100-127V :10,000A
-277V 14,000A
NOTE:Seepage4forSCCRratings.•Lightningstrikeprotection:meetsANSI/IEEE standard62.41-1980.Canwithstandsurgesofupto6000V andupto3000A.
•10-yearpowerfailurememory:automaticallyrestoreslighting to scene selected prior to power interruption.
•RTISSfiltercircuittechnologycompensatesforincominglinevoltagevariations:novisibleflickerwith+/-2%changeinRMSvoltage/cycleand +/-2%Hzchangeinfrequency/second.
Lighting Sources/Load Types
Operates these sources with a smooth continuous SquareLawdimmingcurveoronafullconductionnon-dimbasis:
•Incandescent(tungsten)/halogen.•Magneticlow-voltagetransformer.•LutronRTu-Wire®.•Neon.•HID(full-conductionnon-dimbasisonly).•Switchedlightingloads.•DSI,DALI,and0-10V dimming ballasts using 10Vmodulesinthepanel.
•Electroniclow-voltagetransformer.•Magneticfluorescentlampballasts•LutronRHi-Lume®andEco-10®fluorescentdimming
ballasts are controlled directly
Physical Design
•Enclosure:NEMA-Type1,IP-20protection(Type2availableuponrequest);16U.S.gaugesteel. Indoorsonly.
•Panelweight: -Spec-grade:115to175lb(52to79kg)•SeismicCertificationLimits:SDS=2.5g,z/h=1.0,IP=1.5.ContactLutronfordetails.
Mounting
•Spec-gradepanelssurfacemountonly;allowspacefor ventilating.
Environment
•32to104°F(0to40°C).•Relativehumiditylessthan90%non-condensing.
Heat Dissipation
•Panelscoolbyconvection.Nofans.
Wiring
•Internal:prewiredbyLutron.•Systemcommunications:IECPELVNECR Class 2
wiring connects dimming panels to other components.•Line(mains)voltage:feedandloadwiringonly.Nootherwiringorassemblyrequired.
LCP128T Controller
•ConfiguresentireLCP128T system. •Twolow-voltage(15-24V )contactclosureinputs,momentaryormaintained,pull-uporpull-down.
•Emergencysensing.•Astronomicaltimeclock.•Digitalcontrollink.•MountedinsideLCP128T panel.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 4 06.04.12
Specifications (Continued)
Filter Chokes (spec-grade panel)
•Loadcurrentrisetimeismeasuredata90degreeconduction angle.
•10to90%ofloadcurrentwaveform: -350µsrisetimeat50%dimmercapacity. -400µsrisetimeat100%dimmercapacity.•0-100%ofloadcurrentwaveform: -525µsrisetimeat50%dimmercapacity. -600µsrisetimeat100%dimmercapacity.•Atnopointinthewaveformcantherateofcurrentchangeexceed300mAperµs.
•ConsultLutronforhigherrisetimeoptions.
Astronomical Time Clock
•Capableofupto500events.•7dailyschedulesand40holidayschedulesare
available.•25eventsperday.•Holidayeventsareprogrammableoneyearin
advance.•Holidayschedulesareprogrammabletorunforupto90days.
•ATClocationprogrammablebybuilt-incitydatabaseorbyenteringlatitudeandlongitude,plusasunriseor sunset offset to adjust for local geography.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuousoperation.ULRListedspecificallyforeachlightsource.
•Arcless-relayairgap-offswitches(oneperloadcircuit)ensure open load circuits when off function selected. Eliminatearcingatmechanicalcontactswhenloadsare switched
Control Station Devices
•OnetosevenbuttonseeTouch® wallstations.•Buttonsareprogrammabletoselectscenesor patterns,togglecircuits,oractivatedelay-to-off.
•ButtonsareprogrammedattheLCP128T controller.•Keyswitchcontrolisalsoavailable.•Controlsarepoweredbyandcommunicateviathe
LCP128Tlow-voltagecommunicationlink.•OMX-CCO-8integratesthirdpartymotorized windowtreatmentsorA/Vequipment.
•OMX-AVinterfaceswithoccupantorphotosensors.•OMX-RS232interfacestheLCP128TsystemtoaPC,touchscreen,orbuildingmanagementsystem.
•ODMX-512interfacestotheatricalstageboards.•Seespecificproductspecificationsheetsforfurther
details.
LCP Spec Grade Panels Short Circuit Current Ratings (other ratings available)Panel Type V~ Standard SCCR Rating
LCPSpecGradeMainLug(standardandlargesize)
120,277 25,000A
LCPSpecGradeMainBreaker(standardsize)
120 10,000A
LCPSpecGradeMainBreaker(standardsize)
277 18,000A
LCPSpecGradeMainBreaker(largesize)
120 25,000A
LCPSpecGradeMainBreaker(largesize)
277 25,000A
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 5 06.04.12
seeTouch® Wallstations
Description
•EachseeTouchRwallstationfeaturesengraved,backlitbuttonsallowingquickandeasyrecalloflightingpresets,eveninlowlightconditions.
•Buttonfunctionalityisfullyprogrammable.
Specifications
•Low-voltagetypeIECPELV/NECR Class 2 Operating voltage:24V-.
•MeetsIEC801-2.Testedtowithstand15kVelectrostatic discharge without damage or memory loss.
•Faceplatesnapsonwithnovisiblemeansof attachment.
•Terminalsacceptuptotwo18AWG(1.0mm2) wires typical.
•Environment:32to104°F(0to40°C).Relative humiditylessthan90%non-condensing.
seeTouchR Models
•Modelsavailablewithonetosevenbuttons,with or without raise/lower.
•UseSOseriesmodelnumbers.•Availablewithallstandardcolorsandengraving.•Availablewithbuilt-incontactclosureinputsor
with optional occupant sensor inputs.
Button Programming
•Eachbuttonmaybeprogrammedforscene selection,toggle,delay-to-off,raise,orlower functionality.
•Buttonprogrammingcanbeusedtoprovide specializedmanualcontrolofmultipleareas.
Button Engraving
Custom engraving is available using button/ faceplate replacement kits.
Toorder,contactLutronCustomerServiceat 1.888.LUTRON1(1.888.588.7661).
seeTouchRWallstation (SO-4SN-WH-EGN)
Off
Typicalwallboxdimensions:3.74in(95mm)Hx2.17in(55mm)Wx2.75in(70mm)D.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 6 06.04.12
Feed-Through Model Numbers
Example
LCP12-120FTML
NumberofCircuits in Panel
Voltage
Feed-Through Type
Branch Circuit Breaker Model Numbers
Example
LCP24-1204ML-20
NumberofCircuits in Panel
Voltage
Feed Type
Feed Branch Circuit Rating
Number of Circuits in Panel
Indicatesnumberofswitchingcircuitsinthepanel: 8,12,16,20,or24
Voltage
120for120V
277for277V
Load Circuit Rating
16Apercircuit
Frequency - All Model Numbers and Voltages
50/60Hz
Output Voltages
120V or277V
Feed Input Ratings
4for3phase4wire 120/208V or277/480V
3for1phase3wire120/240V
2for1phase2wire120V or277V
Feed Type
M or ML for main lugs
DTML for dual tap main lugs
Mxxxformainbreaker(xxx=breakersizeinamps)
Branch Circuit Rating
20for20Abranchcircuitbreakers
20Abranchcircuitbreakershavea16A continuous load rating
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 7 06.04.12
Ratings: LCP8-24 Spec-Grade
Onlystandardpanelslisted;consultLutronforfurtheroptions
120-127 V Power
Panel Branch Ratings
Number of Circuits
Feed Type Panel Feed Maximum Feed
Circuit Breakers1
Maximum Dimmed Hot Load2
LCP8 1Ø,2W MainLugsOnly 175A 20A 2000W/VA
1Ø,3W MainLugsOnlyDualTapMainLugs80AMainBreaker
175A225A80A
20A20A20A
2000W/VA2000W/VA2000W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs60AMainBreaker
175A225A60A
20A20A20A
2000W/VA2000W/VA2000W/VA
LCP12 1Ø,3W MainLugsOnlyDualTapMainLugs
175A225A
20A20A
2000W/VA2000W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs80AMainBreaker
175A225A80A
20A20A20A
2000W/VA2000W/VA2000W/VA
LCP16 1Ø,3W MainLugsOnlyDualTapMainLugs175AMainBreaker
175A225A175A
20A20A20A
2000W/VA2000W/VA2000W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs125AMainBreaker
175A225A125A
20A20A20A
2000W/VA2000W/VA2000W/VA
LCP20 1Ø,3W MainLugsOnly 225A 20A 2000W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs150AMainBreaker
175A225A150A
20A20A20A
2000W/VA2000W/VA2000W/VA
LCP24 1Ø,3W MainLugsOnly 225A 20A 2000W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs150AMainBreaker
175A225A175A
20A20A20A
2000W/VA2000W/VA2000W/VA
120/16A,15/12Acontinuous load rating.2Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 8 06.04.12
Ratings: LCP8-24 Spec-Grade
Onlystandardpanelslisted;consultLutronforfurtheroptions
277 V Power
Panel Branch Ratings
Number of Circuits
Feed Type Panel Feed Maximum Feed
Circuit Breakers1
Maximum Dimmed Hot Load2
LCP8 1Ø,2W MainLugsOnly 175A 20A 4500W/VA
3Ø,4W MainLugsOnlyDualTapMainLugs60AMainBreaker
175A225A60A
20A20A20A
4500W/VA4500W/VA4500W/VA
LCP12 3Ø,4W MainLugsOnlyDualTapMainLugs80AMainBreaker
175A225A80A
20A20A20A
4500W/VA4500W/VA4500W/VA
LCP16 3Ø,4W MainLugsOnlyDualTapMainLugs125AMainBreaker
175A225A125A
20A20A20A
4500W/VA4500W/VA4500W/VA
120/16A,15/12Acontinuous load rating.2Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 9 06.04.12
LCP8-24 Spec-Grade Panel DimensionsDimensionsshownas:in(mm).
Suggestedfeedwiringentry; punch cover
Suggestedfeedwiringentry; punch cover
Removabletopcoverisshippedthe box with the panel.
28(711)
12 (304) 12
(304)
2(50)
13 (330)
33 (838)
37 (940)
35 (889)
4(100)
2(50)
Left Side
Top View
Front View Right Side
Bottom View
2(50)
Requiredcontrol wiring entry
Keyholeacceptsamaximum5/16in(8mm)mountingbolt(1/4in[M8]recommended).
IECPELV/NECRClass 2entryknockoutis7/8in(22mm)diameter.
Notice: Thisequipmentisair-cooled.Ventsmustnotbeblockedorthewarrantywillbevoided.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 10 06.04.12
Notes
•ForIndoorUseOnly.NEMA,Type1enclosure,IP20.•Relativehumiditymustbe<90%non-condensing.•Panelgeneratesheat.Mountwhereambient temperatureis32to104ºF(0to40ºC).
•Reinforcewallstructureforpanelweightand local codes.
•Mountwithin7ºoftruevertical.•Panelclearancesare12in(305mm)aboveandbelowand0intoeachside.Allowroomfor IECPELV/NECR Class 2 clearance.
Panel Max. BTUs/Hour (Kcal/Hour)
Weight without Packaging lb (kg)
LCP8 1365(343.98) 115(52)
LCP12 2045(515.34) 120(54)
LCP16 2725(686.70) 145(66)
LCP20 3405(858.06) 160(73)
LCP24 4085(1029.42) 175(80)
Panel Mounting: LCP8-24 Spec-Grade
Front View Side View
Feed Wiring (topentry)
Load Wiring (topentry)
Wiringraceway
IECPELV/NECR Class 2 wiring to controls
12 in (305mm) minimum
12in(305mm) minimum clearance
Airflow
Wall
Notice:Dimmingpanelswillhumslightlyandinternalrelayswillclickwhileinoperation.Mountwhereaudiblenoise is acceptable.
Notice:Mountpanelsoline(mains)voltagewiringwillbeatleast6ft(1.8m)fromsoundorelectronicequipmentand its wiring.
Notice:Thisequipmentisair-cooled.Ventsmustnotbeblockedoryouwillvoidthewarranty.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 11 06.04.12
Front View Side View
Feed Wiring
Load Wiring
Wiringraceway
IECPELV/NECR Class 2 wiring
IECPELV/NECR Class 2 wiring
Panel Mounting: LCP8-24 Spec-Grade
Atleast8ft8in(265cm)betweenfloorandsuspendedceilingisrequiredforthislayout.
6in(152mm)minimum*
3ft45 in (103cm)tomounting holes
6ft6in(195cm)NEC® breaker height limit
7ft55 in (228cm)tomounting holes
8 ft 8 in (265cm)minimum to ceiling
*6in(152mm)approvedforthislayoutonly.
Warning:ShockHazard.Toavoidtheriskofelectricshock,installpanelswheretheywillnotgetwet.Waterdamagespanels.
Airflow
Airflow
12 in (305mm)minimum
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 12 06.04.12
Wiring Overview: LCP8-24 Spec-Grade
Wire Sizes
•Power Feed Standard Main Lugs 14AWG(2.0mm2)to2/0AWG(70.0 mm2)
• Power Feed Dual Tap Main Lugs 6AWG(10.0mm2)to4/0AWG (120mm2)
• Neutral Feed: 6AWG(10.0mm2)to350MCM(177.0 mm2)
•DimmedHot/Live: 14AWG(2.0mm2)to10AWG (4.0mm2)
•LoadNeutral: 14AWG(2.0mm2)to6AWG (10.0mm2)
Wiring Tips
WiretheLCP8-24similartowiringalightingDistributionPanel:
•Runfeedandloadwiring.Nootherwiringorassemblyrequired.
•Commonneutralsarenotpermitted.Runseparate neutrals for each load circuit. TheLCP8-24canprovidetemporarylighting.
•Wireallloads.•Donotremovethebypassjumpersthat
protect the dimming modules.•Usebranchcircuitbreakerstoswitchlights
on and off.
IECPELV/NECR Class 2 wiring
Branchcircuit breakers
Terminal block
Bypassjumpers-Donotremove
Typical Load Circuit
Load Neutral Dimmed Hot/LiveLoad
Neutral Feed
Feed Wiring
Power Feed (Hot/Live)
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 13 06.04.12
100-127 V~ and 277 V~ Load Circuits (LCP8-24 Spec-Grade)Incandescent Load Types
DimmedHot(DH)mustbeusedfornon-dimloads whether they will be dimmed or switched
Hi-lume® FDB or Eco-10® fluorescent dimming ballasts
TVM Load Types ELV Load Types
DimmedHot(DH)mustbeusedfornon-dimloads whether they will be dimmed or switched
Load Circuits with Emergency Battery Pack Wiring
SH HDH SH HDH
+ 1 –
+ 2 –
L
N
+
–SH HDH
SH HDH
SH HDH
Bypass jumper
Load terminals
Dimmableornon-dimload
NeutralbusNeutralbus
Ballast
Fluorescent lamp
Load terminals
Bypass jumper
Hi-lumeR or Eco-10R FDBballast
Ballast
TVMLoad terminalsBypass
jumper
Neutralbus
Load terminals
Bypass jumper
Load
Neutralbus
LCPDimmingPanel
NNeutral(White)
DimmedHot(Orange)
SwitchedHot(Black)
Load Terminals
Dimming Ballast
Lamp2(Emerg.)
Lamp 1
BatteryConnector
Indicator Light
EmergencyBallast
BlueBlue
RedRed
Yellow
Red
Yellow/BlackYellow
Blue/WhiteBlue Black(277V )
Orange(120V )White ToNeutral
ToUnswitchedAC}
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 14 06.04.12
IEC PELV/NECR Class 2 Wiring
The LCP128TsystemcommunicatestocontrolstationsusingaIECPELV/NECRClass 2low-voltagelink.Controlstationsincludewallstations,contactclosureinputandoutputdevices,andRS232interfaces.
WiretheIECPELV/NECRClass 2linkaccordingtothefollowingguidelines:•Linkmustbedaisychained.•Mustruninseparatetroughfromline(mains)voltage.•Linkmustbelessthan2000ft(600m)long.•MakewireconnectionsinsidethewallboxandLCP128T panel.•InstallLinkTerminators(LT-1)atthestartandendoftheIECPELV/NECRClass 2daisy-chainedlink.•Theorderofcontrolsonthecontrollinkisnotimportant.•UseLutronRGRX-CBL-46Lcableorequivalent.
LT-1 LT-1
Note:LinkTerminators(LT-1)arerequiredatthestartandendoftheLCP128TIECPELV/NECR Class 2 link.
LCP128T Panels
2000ft(600m)maximum
ControlStations: Wallstations,contactclosureinput,contactclosureoutput,andRS232devices
Maximumtotallengthofthecontrollinkis2000ft(600m). This distance is based on proper shielding of the twisted/shieldedpair,properwiresize,andtheuseoflinkterminators(LT-1)ateachendofthelink.Ifunapprovedcableorsmallerwireisused,controllinklengthmustbede-ratedaccordingtothefollowingchart:
Terminal 1 & 2 Wire Sizes Maximum Control Link Length12AWG(4.0mm2) 2000ft(600m)
14AWG(2.5mm2) 1400ft(425m)
16AWG(1.5mm2) 900ft(275m)
18AWG(1.0mm2) 600ft(180m)
Notice: IfLinkTerminators(LT-1)arenotusedorimproperwiringtopologyisemployed,thesystem will not communicate properly.
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 15 06.04.12
1
2
3,4,D
1 2 3 4 D 5
CC
I1C
OM
CC
I2C
OM
1 2 3 4 D 5
1
2
3,4,D
5
CC
I1C
OM
CC
I2C
OM
IEC PELV/NECR Class 2 Wiring Panel to Panel and Panel to Control Stations
Wiring Notes:
•Useawireconnectortoattachone 18AWG(1.0mm2) wire for Common (terminal1)andone18AWG(1.0mm2) wirefor24V (terminal2)fromthe IECPELV/NECR Class 2 link to the control.Two12AWG(4.0mm2) wires cannot both be terminated on the controlstation.Maximumwirelengthfromlinktocontrolis8ft(2.5m).
•OnlyconnecttheDrain/Shieldwire (barecopper)toterminal‘D’inLCP128T panels.Maintaintheshieldthroughoutthe link but do not allow it to touch ground(earth)orwallstationcircuitry.
4321
1 2 3 4 D 5
Control station terminal
Drainwire
LCP128T Controller LCP128T Controller
To LCP128T control stations
To additional LCP128T panels
ControlPower:(2)12AWG(2.5mm2) 1:Common 2:24V
EmergencySense: (1)18AWG(1.0mm2) 5:SenseLine
ControlData: (1)twistedshieldedpair 22AWG(0.625mm2) 3:MUX 4:MUX D:Drain/Shield
® Specif icat ion Submittal page
Job Name:
Job Number:
Model Numbers:
Dimming & Switching Systems LCP128TM Spec Grade Power Equipment
369-642a 16 06.04.12
IEC PELV/NECR Class 2 Wiring for ODMX-512
•Makedaisy-chainconnectionstothelow-voltageIECPELV/NECRClass 2MUXlinkterminalsonthefrontofODMX-512interface
•DonotuseT-taps;runallwiresinandoutofterminalblock.•Eachterminalacceptsuptotwo18AWG(1.0mm2) wires.
•Two12AWG(2.5mm2) conductors forcommon(terminal1)and24V (terminal2).Thesewillnotfitinterminals. Connect as shown.
•Oneshielded,twistedpair18AWG(1.0mm2) for datalink(terminals3and4).
•ConnectDrain/Shieldasshown.Donot connecttoGround(Earth)orwallstation/controlInterfaces.Connectthebaredrainwiresandcutoff the outside shield.
•Donotconnecttheextra18AWG(1.0mm2) wire totheODMX-512.ConnectonlytoLCP128T panels as a “sense line” for emergency (essential)lighting.
1 2 3 4 D 5
CC
I1C
OM
CC
I2C
OM
45123
1 2 35 6COM - +DMX 512 INPUT
EXTSW
CONTROLLINK
1 2 3 4
LED1 LED2
1 2 31 2 3
DMX ZONESELECT
EARTH
4 5 6CONTROL LINK EXT SW
COMDMX 512 INPUT
LIN
KC
OM +V
MU
X
MU
X
CONTROL LINK EXT SW
COM4 5 61 2 3 1 2 3
DMX 512 INPUT
SW1 SW2
J1 J2
J3
1 2 3 4 5 1 2 3 4 5
To additional wallstations/control interfaces (16maximum;threefromonecontrolunit
without external 12 V power supply)
1000ft(305m)
maximumCOMData-Data+
ODMX-512
DMXtheatricalcontrol
NovaT*R style wall jack
LutronR Cable GRX-CBL-46LS
IEC PELV/NECR Class 2 Terminal Connections
DataLink-(1)twisted, shieldedpair18AWG(1.0mm2) 3:MUX 4:MUX
D:Drain/Shield
(2)12AWG (2.5mm2)
(2)12AWG (2.5mm2)
(1)18AWG (1.0mm2)
(1)18AWG (1.0mm2)
ODMX-512IECPELV/NECR Class 2 control wiring 1:Common 2:24V