Upload
duongbao
View
261
Download
5
Embed Size (px)
Citation preview
EASERGY T300A modern approach to distribution network automation
Confidential Property of Schneider Electric
Gideon Ferreira
Schneider Electric. All rights reserved
Easergy T300 Presentation
a compact and modular design for all
customer applications
an up to date communication for customer
future proof systems
a modern solution entirely designed to make
easier the installation, commissioning and
maintenance
Simple
a concentrate of innovation dedicated to customer
performance
Powerful
Flexible
Connected
to secure all control and data acquisition for
the operation of customer electric system
Secure
Easergy T300, Customer Values
Schneider Electric. All rights reserved
Easergy T300 Presentation
Easy customization thanks to modern
architecture, scalability, and simple on-site
upgradability
Compliant with the latest standards, with local
or remote maintenance (IEC61850-90-5,
Ready for 4G)
Installation (Wireless and self-powered
sensors), commissioning, and maintenance
made easier (Web Server)
SimpleAdvanced features (Native IEC61850), enabling
powerful monitoring (IEC61557-12 & IEC61000-4-30),
control, and automation functions (IEC61131-3
framework)
Powerful
Flexible
Connected
Compliant with the latest cyber security
standards and regulations (IEEE P1686,
IEC62351)
Secure
Easergy T300, Offer values
Page 4Confidential Property of Schneider Electric |
1Answer the challenges of today.
And tomorrow
2 Easergy T300
3 Ordering
4 Cyber Security
5 Technical description
Schneider Electric. All rights reserved
Easergy T300 Presentation
The traditional grid
Electrical
utilities
The modern grid
vs.
Electrical
utilities
Renewables
Distributed
Generation
As network complexity grows, so does the need
for a better network management
Electrical utilities
Having the right
Feeder RTU is key
MV network control
MV Fault Detection
Centralized or decentralized
network reconfiguration
MV Volt/VAR optimization
support
LV network management and
Volt/VAR support
MDM(Mobile
device
Managemen
t) / AMM
Network control centre
SCADA / DMSOther services
The distribution network becomes a Smart Grid communication node
HV/MV
MV/LV
Easergy
T300
Easergy
HU250
Easergy
SC150
Easergy
LV150
Easergy
LV110
Easergy
PS50
Easergy
PS25
A modular solution… for any secondary distribution application
Easergy T300 Presentation
Easergy PS50
Communicating power supply designed for
control and monitoring of the entire
substation
> Dedicated supplies for switchgear motor,
electronic
and communication devices
> Designed to continue monitoring during
long outages or interruptions
> Complete battery management with
periodic testing and lifetime estimations.
Easergy LV150 & Easergy LV110 (*)
Easy to install and operate LV network
management (*)
> Complete power measurement to IEC 61557-12
> Power quality monitoring to IEC 61000-4-30 Class
S
> Transformer temperature monitoring*
> New LV applications such Fuse Blown and
Broken Conductor detection*
Easergy SC150
Compact unit with complete functionality for all MV
line and switchgear management
> Switchgear remote control and monitoring
> Advanced fault detection that now includes
Distributed Generation
> Complete power measurement (IEC 61557-12) (*)
> Power quality monitoring (IEC-61000-4-30 Class S)
(*)
> Standardized data model to IEC 61850
> Embedded operator interface for complete local
operation
> Open to any standard of VTs, Low Power VTs, and
CTs
Easergy HU250
Head Unit with every advanced Feeder
RTU function
> Secure remote connectivity to any
SCADA
> Support for all standard communication
media
> Support for all standard protocols
> Secure Wi-Fi connectivity
> Web server for easy configuration and
maintenance
> Third-party substation device integration
MDM / AMM
Other services
Network
control
SCADA / DMS
* Consult us for availability
Easergy HU250 Easergy SC150 Easergy LV150 (*)
Easergy LV110( *)
Easergy PS50
Modular, modern Feeder Automation
Schneider Electric. All rights reserved
Easergy T300 Presentation
Flexible and scalable architectures
Scalable solution on-siteo Just one click and one eth jumper!
o Wireless and self-powered power meter for LV
feeder
Open to 3rd party deviceso Power supply
o IED
o Sensors
Up to 24 modules
Wireless LV
current sensors
Eth
jumper
Flexibility built ino Modular architecture modulo one
o DIN mounting
o Simple Ethernet bus via jumper
Schneider Electric. All rights reserved
Easergy T300 Presentation
A powerful Easergy Feeder RTU configurable to your exact needs
Packaged solutions
• Complete packaged
solutions available off-
the-shelf for fast delivery
and installation
• Also available for
retrofit
Delliver with MV cubbicle
• Easergy T300 can be
delivered ready to use
with the Schneider MV
cubicle.
• Reduced installation
time on-site
Open solutions
• Completely tailored and
configured solutions to
serve advanced network
architectures
• Designed and configured
to your exact need
Common Modules, applicable for any configuration, with plug&play connectivity
Schneider Electric. All rights reserved
Easergy T300 Presentation
Easergy T300 and Cyber Security
MDM / AMM Other services Network control centre
SCADA / DMS
Schneider Electric. All rights reserved
Easergy T300 Presentation
RBAC Roles Suggested by IEC 62351-8
Smart RMU for grid management
Presented by: Gideon Ferreira
Confidential Property of Schneider Electric
Smart RMU with flexible integration
Confidential Property of Schneider Electric |
Easergy T300
FBXRM6 Ringmaster
RMURTU
PanelModules for a
flexible integration
LPVT
Sensors
CTVPIS/VDS
• Take profit of the installed
base and Schneider Electric
leadership worldwide
• RMU metal-enclosed, indoor/outdoor
associated to a RTU ready to use
• Delivered and guaranteed as a
tested, validated, and documented
solution to guaranteed interoperability
Easergy T300 typical applications
Confidential Property of Schneider Electric
V1-2 – 2016-07
Page 50Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Distribution network applications
Page 51Confidential Property of Schneider Electric |
MV control & automation
FLISR : Fault location, isolation and service restoration
Customer challenges
Ensure Network Availability: Improve SAIDI(System Average
Interruption Duration Index)
Integrate distributed production on MV & LV sides
Manage energy growth with quality and efficiency
Optimizing assets & reducing field site visits
What is our solution ? Remote control of 20% of the MV/LV substations and remote
monitoring in the other ones
Having the right Feeder RTU to improve SAIDI
Benefits
Detect the MV faults, broken conductors and voltage loss
Reconfigure the network automatically after a fault detection,
with standard communication protocols and local automatisms.
Detect the LV outage (including blown fuse)
Comprehensive measured values to monitor the load of
distribution network
Small, modular, and rugged to be embedded on the switchgears
1 X Head Unit
communication
gateway
(HU250)
IEC 101/104,
DNP3…
GPRS, 3G,
radio, PSTN
Network control
SCADA / DMS
N X Switch Controller,
(SC150) monitoring and FPI
N=number of feeders
1 X LV Management
(LV150)
1 X Power Supply
(PS50)
M
MV/LV Substation Control
LBS controller
Page 52Confidential Property of Schneider Electric |
Priority area to equip with a controlled versus monitored Substation depend on the location of
the substation and the Smart Grid abilities. I.e.
1- rural location on a radial robust network distributing few customers may includes a local monitoring
without digital communication.
2- location with distribution production with voltage fluctuation on LV may have a remote monitoring
abilities
3- location with open ring meshed network may have remote control of 20% of the MV/LV
substations and additional 20% with remote monitoring.
4- Peer-to-peer communication with self healing abilities is dedicated to critical area which then
dramatically reduces the isolation and service restoration time. This is a smart, cost-effective way to
enhance the reliability of underground electrical distribution, simple roll-out, with no DMS required.
Architecture choice …
Architecture Smart Grid abilities
N°1 - No digital communication • Manage voltage , Fault indication , but limited
• integrate distributed production on LV side
• optimize assets
N°2 -Digital communication with remote Monitoring • integrate distributed production on MV & LV sides
• manage energy growth with quality and efficiency
• Optimize assets & reduce field site visits
N°3 -Digital communication with remote Control • Ensure Network Availability: Improve SAIDI
N°4 Peer-to-peer communications • Avoid unwanted islanding
• Self healing capabilities
1
2
3
remote control and monitoring
Decentralized peer-to-peer com.
Fault detection: Easergy T300 detects the MV fault whatever the grounding
system is, thanks to dedicated cost effective current and voltage sensors. These
sensors doesn’t need to have the same capabilities has protection relays but are
designed for a fast and easy installation on existing substations. Permanent faults
alarm the DMS to better localize the faulty part of the network. Transient faults are
logged to identify the weak lines.
Remote control: Fault location, isolation and supply restoration (FLISR) centrally
and remotely manages all T300 located on the feeders, with the objective of
isolating the faulty section, and restoring power to a maximum number of grid users.
To ensure robust, reliable remote control of the MV network, the T300 have to meet
a high level of electromagnetic compatibility immunity (EMC standards) that
traditional industrial controllers do not reach .The smart power supply of the T300 is
both to communicate and to operate the switches remotely during outage. Having
the capability to monitor and test the health of the local battery and the battery
charger contributes to reaching SAIDI(System Average Interruption Duration Index)
objectives and to reduce battery maintenance costs.
Broken conductors including blown fuses detection are automatically detected
thanks to MV and LV voltage measurement.
LV monitoring detects quickly the LV outages and compute SAIDI or others key
performance indicators.
Ensure Network Availability
Rate of users not affected by an outage …
- without Feeder automation
- with FPIs
- with Remote control
Page 54Confidential Property of Schneider Electric |
Easergy T300 configuration is flexible to create a smart MV/LV
substation application. Pre-configuration may be adapted and
downloaded for large number of homogeneous devices.
Main applications …
Typical Configuration Functions
1-MV/LV switching
substation
1 HU 250 – 7 SC150 - 1
PS100
• incomer and feeder remote control &
monitoring
• protection relay and FPI monitoring
• substation power supply (protections, PM)
• sectionalizer automatism of OH feeders
• Auto Transfer Source of incomers, coupling
2- Ring Main Unit, kiosk,
Chamber substation
1 HU 250 – 2 SC150 - 1 PS50
• incomer remote control
• incomer FPI
3- MV/LV distribution
substation
1 HU 250 – 4 SC150 - 1 PS50
- 1 LV150
• incomer and feeder remote control &
monitoring
•sectionalizer automatism of OH feeders
• Transfo monitoring
4- Pole mounted controller
1 HU 250 – 1 SC150 - 1 PS50
• LBS or CAP remote control & monitoring
• sectionalizer automatism
• Transfo monitoring
5- MV/LV consumer (opt.
double incomer)
1 HU 250 – 2 SC150 - 1 PS50
• incomer and feeder remote control &
monitoring
•Auto Transfer Source of incomers
1
2
3
5
Pole mounted
controller 4
Preferred architectures to remote control the MV/LV substation
MV/LV substation
Monitoring
application
Network control centre
SCADA / DMS
Benefits : thanks to 1xHU250,3xSC150,1xLV150,1xPS50 and
wireless LV150 sensors this solution adds a powerful
monitoring of LV feeders and transformer and multiple access
to other services.
Remote control & monitoring
MV/LV substation
Network control centre
SCADA / DMS
Benefits : thanks to 1xHU250,2xSC150,1xPS25 this solution
monitors the Fault Passage Indicators and the loads of the
feeders.
MV/LV substation
Network control centre
SCADA / DMS
Benefits : thanks to 1xHU250,3xSC150,1xPS50 this solution
controls the MV feeders and monitors the FPI, the MV load
flow and VoltVAR functions of the SCADA / DMS
Basic monitoring
IEC 60870-5-104,
DNP3, MODBUS
Radio, PSTN, GSM,
GPRS/3G, ADSL
IEC 60870-5-104,
DNP3, MODBUS
Radio, PSTN, GSM,
GPRS/3G, ADSL
IEC 60870-5-104,
DNP3, MODBUS
Radio, PSTN, GSM,
GPRS/3G, ADSL
Smart substation
Remote access to the
embedded Web serverRemote access to the
embedded Web server
Remote access to the
embedded Web server
Page 56Confidential Property of Schneider Electric |
Easergy T300 connection with a 3rd party switchgear is easily achieved
due to dedicated options like split CT sensors, control interface with the
switchgear motorization, voltage sensors … It has been pre-engineered with
most of the existing MV switchgears.
Factory-tested solution
A solution that has been standardized, industrialized, and fully factory-tested
beforehand saves commissioning time, reduces the number of voltage
outages during installation, and is flexible enough to accommodate future
network development. One interesting aspect is that such an approach may
also apply to existing substations, retrofitting them to open a new field of
smart applications.
Embedded Application Workbench with powerful and intuitive graphical and
textual editors for IEC 601131-3 automation design allows to customize the
customer needs. The main factory-tested solutions are listed in the following
slides.
Typical automation solutions
FLISR
Fault location, isolation and supply restoration (FLISR) centrally and remotely
manages all smart devices located on the feeders, with the objective of
locating faults accurately and quickly, isolating the faulty section, and
restoring power to a maximum number of grid users.
Centralized automation
NO
Fault occurrence with over current
- FPIs memorises the fault current
- upstream protection opens
Isolation faulty circuits remotely
Restore supply remotely
Manual isolation of the faulty section
Restore supply to all customers remotely
Local AutomaticTransfer Source ATS *
An ATS system allows a critical load (such as a network section, a hospital or
plant) to have increased supply availability by switching between a primary and a
backup supply upon voltage failure conditions.
• Automatically transfers between alternate supplies if one is lost
• Can be set to automatically reconfigure when the preferred supply is restored
•Can compute a busbar coupling switch (Bus Tie coupling)
Distributed Automatic Transfer Source *
The principle is the same as local ATS with a peer-to-peer communication
between two distant underground substations or overhead LBS.
Automatic transfert source
(* )consult us for availability
Sectionalizer
Due to their higher vulnerability, a self-healing solution for overhead lines that uses a combination of reclosers and LBS would
be recommended. Sectionalizer of the T300 controls a LBS (Load Break Switch) installed downstream of a MV overhead feeder
protected by a recloser. It counts the number of fault current (corresponding to the cycles of the recloser), and it opens when a
preset number has been reached. Selectivity can thus be obtained by installing several sectionalisers in series on a MV feeder.
Repartition of sectionalizers and reclosers
60% - 70% of faults are of a transient (temporary) nature :
Conductors clashing in the wind, tree branches falling on
overhead conductors, animals or birds, lightning strikes.
An autoreclose cycle should clear the fault.
Some are more permanent : Careless motor vehicle drivers,
operating error: leaving grounds connected, etc.
A lockout (no further recloser operation) of the faulted
section: operator intervention required.
Automation with overhead lines
Page 61Confidential Property of Schneider Electric |
Loop automation
Traditionally the so called loop automation solution that uses recloser
cycles and delays to reclose the ring on the tie point allows for isolating
the fault and reconfiguring the ring without any communication between
controllers.
A new self-healing solution has been successfully deployed using some
short communication bandwidth between feeder RTUs to better manage
the grading system of reclosers and to reduce the stress of the lines by
eliminating unnecessary re-energisation of faults.
Decentralized self healing system
Substation
CB’s
10km15km
10km
7.5km
Midpoint
4
Midpoint
3
2D
Feeder 2
2B
10km
2A
1A
Midpoint
2 7.5km
1D
1B
7.5km
Feeder 1
2C
1C
5km
B
•Fault isolated
•Power restored to unfaulted sections in less than 1 minute
•No operator intervention
•Alternate source prevented from Closing onto fault
Close
dTrippe
d
Switchgea
r
LiveDead
Line
Modbus Trip Request
Tie
Modbus Close Request
Midpoint
1 B+SS
BB+SS
Example of self healing system
Real case of Self-healing in Vietnam Brazil
and Australia …
Page 63Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Easergy T300 typical
applications
Page 64Confidential Property of Schneider Electric |
Volt-VAR optimization support
Volt-VAR control, MV monitoring, Load management
Customer challenges
Improving quality of service : distributed energy generation
needs to reinforces the network stability
Managing voltage: Voltage level increase due to in-feed, over
the limits for some end users
Better balancing MV feeder loads
Defer new distribution substation construction
What is our solution ?
Volt-VAR management support, thanks to accurate Voltage
measurement cl0.5 full chain & 1ms time synchro. & record files
according to & IEC61000-4-30 class S)
Energy quality deliver, 4 quadrants (IEC61557-12)
Smart sensors
Benefits
Feed the VVO function (Volt VAR optimization) of the DMS
Allow distributed regulation of voltage
Optimize the DER (distributed energy resources) extension of
distribution network
Detect unbalanced networks
Network control
SCADA / DMS
1 X MV Management (SC150)
U, I, P, Q measurement
Recording
1 X Head Unit
communication
gateway (HU250)
IEC 101/104,
DNP3…
GPRS, 3G,4G,
radio, PSTN
Power supply
(PS25)
Page 67Confidential Property of Schneider Electric |
Volt-VAR control solutions (1/2)
EOL
+
Meteo forecast
Cons/prod Load profiles
SS real-time measures
PS real-time mesures
Vopt AVR controller
Cap bankEOL
Vopt
ADMS
MV End of Line monitoring
• End of line (EOL) monitoring device supports Volt-VAR control and optimization, participating to a centralized or
decentralized system.
• In most of cases, existing smart meters are not adapted to support the voltage regulation because of real time
communication issue, compute missing like the sliding average over few minutes. A dedicated EOL device would be
recommended, with optimized communication with either the SCADA or the OLTC(On-load Tap Changer) regulator.
• From 1 to 3 EOL installed on each weak feeders will provide a synchronized Voltage information. It allows to check
and optimize the complete voltage plan of the MV feeder.
EOL
SS real-time measures
PS real-time mesures
AVR controller
///
Decentralized Volt-VAR control (closed
loop on a local area)Centralized Volt -VAR control with ADMS
VVO
Real case study : The ADMS takes into consideration
Voltages at Primary Substation and also Voltages at other
substations to set the tap changer and to optimize the
location of the normally open point.
Optimal network reconfiguration
Better balancing the load flow by
optimizing the location of the normally
open point of the MV rings which
consequently reduce the technical
losses and limit the overload circuits.
Tap changer setting
Easergy T300 records days and
seasons voltage profiles for
recommendation of the best position for
the off-load tap changers, and then
increase PV integration rate, by
minimizing the voltage problems they
may cause to the grid.
Reactive energy analysis
It includes the monitoring and analysis
of the reactive energy that flows on MV
feeders for each of the phases and
feeders of the secondary substation. For
example, the T300 monitors and
controls the switched MV capacitor
banks. The results of these analysis
would allow to locate the areas of the
grid with more reactive energy. The
utility experts or the Schneider Electric
specialist would be able to work closely
with the utility team to come up with
several alternatives aiming at minimizing
the reactive energy impact on the
analyzed circuits.
Page 68Confidential Property of Schneider Electric |
Volt-VAR control solutions (2/2)
+1
+2
-1
- 2
High level of measurement accuracy is now required by Utilities and provided by
Easergy T300 for different raisons.
• Manage voltage limits: Energy suppliers have to guarantee the supply voltage
within the tolerance limits, +/- 10% (EN 50160) which allows a margin of +/- 5% on
MV feeders then the voltage regulation is done within a 1%, which consequently
requires 0.5% measurements to maintain quality and deliver MV and LV stability.
• Improve the quality of service: Electrical values such as current, voltage,
frequency, power, harmonics are performed according to the power quality standard
IEC 61000-4-30 Class S. Measured values can be recorded at synchronous time
intervals on the device or through the communication interface. Long-time recorded
data and events may be evaluated directly in the device according to the power
quality standards, and issued as a report.
• Monitor the stability : alarming on frequency shift of a disconnected area
(microgrid area), alarming on overloading area, etc.
Volt VAR management of the LV network (versus LV) is less critical because it
affects a fewer number of end users. It’s why Utilities prefer to first manage the MV
network (For LV networks, go to the § “Load monitoring application”). However, MV
sensors are sometime difficult to install, particularly the Voltage sensors (see
recommendations on the next table). Consequently, LV voltage measurement are
chosen instead of MV, which may provide a valuable 2% measurement, taking into
account the characteristic of the MV/LV transformer (load, PF, tap position).
Voltage measurement accuracy is needed
RTU functions required for Volt-VAR
• I, U and % unbalanced, accuracy 0.5%
• P,Q, PF, signed accuracy 1%
• Energy, frequency monitoring
• IEC 61000-4-30 class S
• harmonics (H15), voltage dip and swell
• demand value: averages on 1 to 60 mn
• data recording : periodic, dead band, on
threshold
• alarms
• Synchronization of RTUs using
communication protocol (10 ms)
Choice of sensors for Volt-VAR
Smart sensors Features Recommendations
MV current sensor - Split core CTs for an easy installation on MV
unipolar cables with SC150
- dedicated to Fault passage indication
- dedicated to measurement (IEC 60044-1 Class 1)
: phase RMS, residual, P, Q ..
-To be installed on each MV incomers
- may be installed on others MV feeders for Transfo monitoring
- for tripolar cables, only split core balanced CT are suitable, or a
specific shielding must be adapted after the split point.
MV voltage sensor : LPVT -LPVT (Low Power VTs)
- dedicated to measurement for Volt-VAR
application (IEC 60044-7 -Class 0.5)
-Preferred solution for MV End of line monitoring in case of “T”
bushing
-To be installed on each MV incomers
VT - Standard MV/LV VTs with secondary from 57V to
220 Vac according to IEC 60044-2
-dedicated to Tariff metering
- VT is the traditional solution for Voltage measurement of main
substation. However, it could be difficult to install it on some type
of MV/LV substations (foot print, cost, robustness issue, GIS MV
cubicle …) and LPVT would be a preferred solution.
Page 71Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Easergy T300 typical
applications
Page 72Confidential Property of Schneider Electric |
MV current fault detection
Fault Passage Indicator (FPI)
Customer challenges
Distributed Generation are increasing and Fault passage
indicators are not working anymore properly .
Peterson earthing system limits the earth faults and FPIs
don’t detect properly all the faults.
Utilities are not confident on their FPI assets.
What is our solution ?
Advanced FPI functions (directional fault detection,etc.)
Easy configuration thanks to Web Server or IEC61850 data
model
Easy connection with CT, VT, LPVT, VPIS…
Benefits
Detect the faults of all earthing systems
Detect the faults with distributed generation
Detect the MV broken lines
Detect Voltage outage including MV blown fuse
Network control
SCADA / DMS
2 X FPI
(SC150)
M
1 X Head Unit
HU250
communication
gateway
IEC 101/104,
DNP3…
GPRS, 3G,
radio, PSTN
Power supply
PS25
Network control
SCADA / DMS
MV/LV Substation Control
LBS controller
Choice of sensors for FPI
Smart sensors Features Recommendations
MV current sensor - Split core CTs for an easy installation on MV
unipolar cables with SC150
- dedicated to Fault passage indication
- dedicated to measurement (IEC 60044-1 Class 1)
: phase RMS, residual, P, Q ..
-To be installed on each MV incomers
- may be installed on others MV feeders for Transfo monitoring
- for tripolar cables, only split core balanced CT are suitable, or a
specific shielding must be adapted after the split point.
MV voltage using capacitor
interfaces: VPIS-VDS-PPACS
-The SC150 is connected to VPIS -VO or VDS
or directly to external capacitor divider connected
to the MV head cable and MV bushings(PPACS)
- dedicated to Fault passage indication (ANSI
67,67N) and Broken connector detection (ANSI
47, 59N)
-voltage measurement accuracy depend on the capacitor divider .
Calibration may be set in the T300 to improve the measurement
(Class 2)
- installation may be complex for 3rd party MV cubicle
MV voltage measured from LV
input down the MV/LV
transformer
- dedicated to Fault passage indication (ANSI
67,67N) and Broken connector detection (ANSI
47, 59N)
- MV voltage may be calculated by SC150 from LV , using the
MV/LV transformer characteristics . It provides an easy solution to
insure Volt VAR measurement with no extra costs. However LV
loads may reduce the accuracy of the measurement (from 2%)
due to the fact that the transformer has a nonlinear response.
Page 76Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Easergy T300 typical
applications
Page 77Confidential Property of Schneider Electric |
Broken conductor detection
Fault location
Customer challenges
In some cases of overhead networks, the broken lines
cannot be detected by the protection relays of the main
substation
Hazardous area appears without alerting
What is our solution ?
Easergy T300 measures the voltage and then detects the
MV broken line or the MV blown fuse
negative sequence overvoltage function (ANSI 47)
Zero phase sequence overvoltage function (ANSI 59N) for
isolated nearthing system
Benefits
Enhanced personal safety thanks to broken conductors
detection
Detect the MV broken lines
Detect Voltage outage including MV blown fuse
1 X Head Unit
communication
gateway (HU250)
IEC 101/104,
DNP3…
GPRS, 3G, radio,
PSTN
Network control
SCADA / DMS
1 X MV Management
(SC150),, U, I, P, Q
measurement
P47 detection
Broken overhead
phase line
Broken
overhead
connector
MV Blown fuse
Power supply
(PS25)
Page 80Confidential Property of Schneider Electric |
Location of the broken conductorUnlike FPIs, the broken conductor is detected by the downstream T300
NO
Fault occurrence with over current
- FPIs memorises the passage of fault current
- upstream protection opens
Fault occurrence with directional FPI
- FPIs memorises the way of fault current
- upstream protection opens
Broken conductor occurrence
- T300 memorises the upstream voltage issue
- upstream protection doesn’t open
Page 81Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Easergy T300 typical
applications
Page 82Confidential Property of Schneider Electric |
Load monitoring
MV monitoring, LV monitoring, load management, losses reduction
Customer challenges
Reduce both technical and non- technical losses
Manage energy growth with right level of quality and efficiency :
Deliver MV and LV stability
Optimize investments
Manage load
Reduce transformer fault and extend life
• Easergy T300 measures the loads on MV and LV feeders with a
modular approach
• Manage local automation: alarms, load shedding, peak shaving
• Customizable, cloud based set of services
What is our solution ?
Benefits Measure the power and energy on the network thanks to
accurate sensors and according to IEC 61557-12
Support the load shedding and peak shaving by automation
Measure historical for a better load flow calculation
Reduce transformer fault and extend life (ageing analysis via
temperature & load)
Head Unit
communication
gateway (HU250)
IEC 101/104,
DNP3…
GPRS, 3G, radio,
PSTN
Load flow
SCADA / DMS
1 X MV monitoring
(SC150)
1 X LV
Monitoring
(LV150)
M
Load Management
Monitoring Application
SFTP over
WAN
Power supply
PS25
Better balancing the MV load flow by optimizing the location of the Normally open point
of the MV rings which consequently reduce the technical losses and limit the overload
circuits.
Optimize assets and reduce field site visits: More accurate information about asset
behavior enables utilities to not only reduce the number of costly field maintenance visits
but also more proactively keep equipment operating efficiently.
MV/LV Transformer Stress Assessment
This service allows to analyze the load of the transformer during a long period for an
optimized solution : transformer replacement, load flow optimization, temperature
monitoring, broken MV fuse detection.
Tap changer setting
Easergy T300 records days and seasons voltage profiles for recommendation of the best
position for the off-load tap changers, and then increase PV integration rate, by minimizing
the voltage problems they may cause to the grid.
MV load management
Real case study : The ADMS takes into consideration
Voltages at Primary Substation and also Voltages at
other substations to set the tap changer and to
optimize the location of the normally open point.
+1
+2
-1
- 2
LV unbalances management
The LV ends of distribution networks are often heavily unbalanced between
transformers, between LV feeders within a transformer, and between the three
phases of one given transformer. With the massive injection of distribution
energy resources (e.g., photovoltaic panels), these imbalances are amplified.
These imbalances cause joules losses in wires and transformers due to the
higher current level on the more heavily loaded part of the network and to
current flow in neutral wires that were usually not designed for such a
situation.
The T300 connected to wireless LV sensors on each feeders is able to identify
imbalances on LV feeders in real time (every 10 minutes, on average) and
solve LV phase balancing.
Reactive energy analysis
The service includes the monitoring and analysis of the reactive energy that
flows for each of the phases and feeders of the secondary substation. The
results of these analysis would allow to locate the areas of the LV grid with
more reactive energy. The utility experts or the Schneider Electric specialist
would be able to work closely with the utility personnel to come up with several
alternatives aiming at minimizing the reactive energy impact on the analyzed
LV segments.
LV load management
Transformer overload due to unexpected
phase unbalance
Non- technical and technical losses
The T300 connected to wireless LV sensors on each feeders is able to calculate
imbalances on LV feeders in real time (every 10 minutes, on average) and solve LV phase
balancing to reduce technical losses.
Aggregated measurement may also help detect non-technical losses at the feeder level.
Easergy T300 records measurements and downloads to a service platform .
This service allows to asses the imbalance per LV feeder, per phases and to produce
recommendations for an optimized solution : transformer replacement, rebalancing action
of some loads …
Compared to the time-stamped Energy of Smart Meters, an analyze may be done by the
DSO or proposed as a service by Schneider Electric, to identify the losses.
Losses identification
Overload due to unexpected imbalance
Wrong energy balance by feeder and losses identification
Schneider Electric monitoring platform may help DSO to analyze
the data and to provide Audit reports and Dashboards. A service
offer, relying on a set of technological bricks, compute data coming
from Easergy T300 but also from existing data (GIS, metering …)
and provide a fast result with a limited investment for the utilities : no
need to manage additional IT infrastructure and counting on the
expertise and analytic procedures obtained by years of intensive
R&D efforts on LV grids
Example of operative model deployed in 3 months:
Choose a set of secondary substations to be investigated.
Deployment of sensors on each secondary substation (no interruption of the
supply, installation in less than 30 min per substation)
One sensor per LV feeder to measure currents.
One T300 per secondary substation to measure voltage, make calculations and
send the data to the Schneider Electric LV-cloud Platform
The data would be collected for a limited period of time (typically about 2-3
months).
If required by the requested services, loading additional data provided by the
utility (from AMI, GIS, etc.) into the Schneider Electric LV-cloud Platform
Schneider Electric specialists would analyze all the collected data :a report per
secondary substation would be provided to the utility with remarkable findings
and recommendations to improve the critical issues found out.
Customizable, cloud based set of services
‒ On live installations
‒ No interruption of the supply
‒ ZigBee communication
‒ In less than 30 minutes per
substation
Page 86Confidential Property of Schneider Electric | Page 86Confidential Property of Schneider Electric |
Schneider Electric
technical expert
DSO
Au
dit re
po
rts
Da
sh
bo
ard
s
Exis
ting
da
taG
IS, m
ete
ring
, …
Load ManagementMonitoring Application
High level of measurement accuracy is now required by Utilities and provided
by Easergy T300 for the same about the same raisons as Volt-VAR.
• Monitor the voltage limits: Energy suppliers have to guarantee the supply
voltage within the tolerance limits, +/- 10% (EN 50160) which consequently
requires 0.5% measurements to maintain quality and deliver MV and LV
stability.
• Improve the quality of service: Electrical values such as current, voltage,
frequency, power, harmonics are performed according to the power quality
standard IEC 61000-4-30 Class S. Measured values can be recorded at
synchronous time intervals on the device or through the communication
interface. Long-time recorded data and events may be evaluated directly in
the device according to the power quality standards, and issued as a report.
• Monitor the stability : alarming on frequency shift of a disconnected area
(microgrid area), alarming on overloading area, etc.
Monitoring the LV network is more and more critical because distributed
generators like photovoltaic panels affects the LV distribution network which
consequently needs to be monitored.
Load monitoring needs accurate measurement
RTU functions required for load monitoring
• I, U and % unbalanced, accuracy 0.5%
• P,Q, PF, signed accuracy 1%
• Energy, frequency monitoring
• IEC 61000-4-30 class S
• harmonics (H15), voltage dip and swell
• demand value: averages on 1 to 60 mn
• data recording : periodic, dead band, on
threshold
• alarms
• Synchronization of RTUs using communication
protocol (10 ms)
Choice of sensors for Load monitoringSmart sensors Features Recommendations
MV current sensor - Split core CTs for an easy installation on MV unipolar
cables with SC150
- dedicated to Fault passage indication
- dedicated to measurement (IEC 60044-1 Class 1) :
phase RMS, residual, P, Q ..
-To be installed on each MV incomers
- may be installed on others MV feeders for Transfo
monitoring
- for tripolar cables, only split core balanced CT are suitable, or
a specific shielding must be adapted after the split point.
MV voltage sensor : LPVT -LPVT (Low Power VTs)
- dedicated to measurement for Volt-VAR application
(IEC 60044-7 -Class 0.5)
-Preferred solution for MV End of line monitoring in case of
“T” bushing
-To be installed on each MV incomers
MV voltage using capacitor
interfaces: VPIS-VDS-PPACS
-The SC150 is connected to VPIS -VO or VDS or
directly to external capacitor divider connected to the
MV head cable and MV bushings(PPACS)
- dedicated to Fault passage indication (ANSI 67,67N)
and Broken connector detection (ANSI 47, 59N)
-voltage measurement accuracy depend on the capacitor
divider . Calibration may be set in the T300 to improve the
measurement (Class 2)
- installation may be complex for 3rd party MV cubicle
MV voltage measured from LV
input down the MV/LV
transformer
- dedicated to Fault passage indication (ANSI 67,67N)
and Broken connector detection (ANSI 47, 59N)
- MV voltage may be calculated by SC150 from LV , using
the MV/LV transformer characteristics . It provides an easy
solution to insure Volt VAR measurement with no extra costs.
However LV loads may reduce the accuracy of the
measurement (from 2%) due to the fact that the transformer
has a nonlinear response.
LV enery sensor
(for each LV feeders)
- LV110 use power harvesting technology, based on
current sensors
-Wireless communication with LV150 based on ZigBee
PRO Green Power
- LV110 is synchronized with LV150 for power
measurement according to IEC 61557-12
- To be installed on LV feeders of substations facing to high
level of integration of photovoltaic energy , long lines, rural
network, ageing infrastructures.
Page 89Confidential Property of Schneider Electric |
1 MV control & automation
2 Volt Var optimization support
3 MV current fault detection
4 MV & LV Broken conductor detection
5 Load monitoring
6 Utility interface for DG
Easergy T300 typical
applications
Utility interface for Distributed Generation
Grid code monitoring, anti islanding
Customer challenges
Increasing renewable contributions to the network and the
system
Manage grid codes and enhance stability
Voltage rise
Unwanted islanding
What is our solution ? Easergy T300 is a dedicated interface to manage data exchange
between DSO and DG from 250 kW
Evolutive platform to allow future regulation functions
Peer to Peer communication
Ability to communicate with meters, protection and inverters
Benefits
Transmission of settings and controls (decoupling order for
unwanted islanding, curtailment, Power limitation during peak
loads, active and reactive power control modes… )
Monitoring of the production . Generation outputs to be
forecasted, Power quality levels to be reported
Easy connection with Tariff Meter, Protection relay or Power
Plant controller of the DG
DSO/TSO
Authority
1 X Head Unit communication gateway
IEC 101/104, DNP3, IEC61850…
GPRS, 3G, radio, PSTN
Network control
SCADA / DMS
DSO(Distribution
System Operators)/
TSO (Transmission
System Operators)
Balance forecast
Protection at the Point of
common coupling (PCC)Tariff
meter
Power plant
Controller (PPC)
IEC 61850, Modbus, Analogs I/O ..
<- Utility interface for DG
Unwanted islanding is where a distributed generator or a set of DGs continues to
power a portion of the grid when the connection to the main public electrical power
grid is no longer present. It is important to avoid unwanted islanding not only
because it may lead to safety hazards for utility field personnel but also because
DG units and network components may be damaged as a consequence of
unsynchronized reclosing of the islanded circuit, unregulated voltage and
frequency, overloaded DER(Distributed Energy Resources), and undefined
earthing. One effective way to avoid unwanted islanding involves communication
capabilities between components attached to a feeder. The principle is to control a
disconnection of DG(Direct Generation), using Easergy T300 communication
capabilities (Fig 1).
Network codes requirements. All power plants must be code compliant . With
rising shares of renewable electricity being injected onto their grid, system
operators are now realizing that the usual network codes designed initially for
conventional generation do not accommodate for the variable nature of renewable
power. New regulation functions need to be implemented: cosφ(P), cosφ(U),
Q(P)… More accurate and faster response times are required. Generation outputs
and Power quality levels have to be reported. Existing installations will have to be
upgraded to comply with grid codes. In Europe, the European Network of
Transmission System Operators for Electricity (ENTSO-E) is defining and
developing a common framework.
Renewable monitoring system is a module of EMS (Energy Management
System) of the TSO. Objectives are to limit TSO balancing needs, to monitor
and forecast power flows and to manage margins & risk situations.
For more information …
Weather data
EMS
DMS
Large farms only
French case : Renewable monitoring system is called IPES (lnsertion
de la Production Eolienne et photovoltaïque sur le Système)
Utility interface for DG
Interface for DGDMS Interface for DG
InhibitInhibit
Open
decoupling
Curtailment, Power limitation during
peak loads, active and reactive power
control modes
PS
Fig 1 Example of decoupling order for unwanted islanding in case of
fault on MV feeder – i.e. ENEL
THANK YOU.
Page 92Confidential Property of Schneider Electric |