SCOPE: THIS STANDARD SHOWS SIZES AND TYPES OF CONDUITS APPROVED FOR USE ON THE CITY OF ANAHEIM'S U.G. ELECTRICAL SYSTEM, UNLESS OTHERWISE SPECIFIED ON THE WORK ORDER DRAWINGS. 2000 1000 500 350 4/0 1/0 #2 CABLE SIZE VOLTAGE 600 VOLTS VOLTAGE 6.9KV VOLTAGE 12KV 4" 4" 3" 3" 3" 6" 6" 4" 4" 4" 6" 4" 4" 4" 6" 6" VOLTAGE 69KV 6" GUIDE FOR CONDUIT SIZE-RISER-MINIMUM 750 4" 6" 6" 2000 1000 500 350 4/0 1/0 #2 4" 4" 3" 3" 3" 6" 6" 6" 4" 4" 4" 6" - 6" GUIDE FOR CONDUIT SIZE-DUCT BANKS-MINIMUM 750 4" 6" 6" - - - 4" 6" A. ALL PRIMARY RISER CONDUITS SHALL BE PVC, SCHEDULE 80, FOR THE FIRST 8 FEET FROM FINISHED GRADE, PVC SHEDULE 40 MINIMUM COULD BE USED FOR THE REST OF THE RISER. GALVANIZED STEEL CONDUITS ARE ACCEPTABLE WHEN SPECIFIED IN WORK ORDER DRAWING FOR THE FIRST 8'. B. ALL RISERS SHALL BE BUILT IN ACCORDANCE WITH THE CITY OF ANAHEIIM CONSTRUCTION STANDARD CO 1101AND GO95 RULE 54.6E. C. PVC REDUCER, IF REQUIRED, WILL BE SPECIFIED BY T&D ENGINEERING FOR CONNECTION OF RISER TO THE UNDERGROUND CONDUIT. A. ALL PRIMARY AND SECONDARY CONDUITS SHALL BE MINIMUM DB-100, CONCRETE ENCASED PER CONSTRUCTION STANDARD CU 1600-4. PVC SCHEDULE 80 AND GALVANIZED STEEL CONDUITS ARE ACCEPTABLE WHEN SPECIFIED IN WORK ORDER DRAWINGS. B. ALL CONDUITS CROSSING RAILROAD TRACKS, FREEWAYS, FLOOD CONTROL CHANNELS AND OTHER MAJOR CROSSING SHALL BE INSTALLED IN RIGID GALVANIZED STEEL CONDUIT PER CONSTRUCTION STANDARD CU 1600-96E. C. CONDUITS INSTALLED FOR STREETLIGHTS AND SUMP PUMPS SHALL BE 2" MINIMUM PVC SCHEDULE 80. FOR ALL STREET CROSSINGS, MINIMUM 2" HOT DIPPED GALVANIZED CONDUIT SHALL BE INSTALLED. D. CONDUITS INSTALLED FOR CITY OF ANAHEIM FIBER OPTIC AND AUTOMATION SHALL BE 4" MINIMUM CABLE SIZE VOLTAGE 600 VOLTS VOLTAGE 6.9KV VOLTAGE 12KV VOLTAGE 69KV 4" 4" NOTES NOTES - - - - - - - - - - - - - - - - - - - - 4 4 4 " 4 4 4 4 4 4 4 4 4 4 4 " 4 4 4 " " 4 4 4 4 4 4 4 4 4 4 4 4 " 4 4 4 4 4 4 4 4 4 4 4 4 " 4 4 4 " " 4 4 4 4 4 4 4 4 4 APPROVALS T&D MGR CITY OF ANAHEIM ELECTRICAL DIVISION PUBLIC UTILITIES DEPARTMENT FILENAME: REVISION KEYS: ADDED / REVISED TEXT NEW SHEET CONSTRUCTION STANDARD: ADDED / REVISED MATERIAL SHEET OF REVISION NO. ISSUE DATE : FIELD MGR OPER. MGR T&D CONSTRUCTION STANDARDS APPROVED CONDUIT TYPES, SIZES, AND APPLICATION CU1600-4A REV 1 1 01-11 1 2 CU 1600-4A

DRAWINGS. GUIDE FOR CONDUIT SIZE-RISER-MINIMUM

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DRAWINGS. GUIDE FOR CONDUIT SIZE-RISER-MINIMUM

SCOPE: THIS STANDARD SHOWS SIZES AND TYPES OF CONDUITS APPROVED FOR USE ON THE CITY OFANAHEIM'S U.G. ELECTRICAL SYSTEM, UNLESS OTHERWISE SPECIFIED ON THE WORK ORDERDRAWINGS.

20001000

5003504/01/0#2

CABLESIZE

VOLTAGE600 VOLTS

VOLTAGE6.9KV

VOLTAGE12KV

4"4"3"3"3"

6"6"4"4"4"

6"

4"4"4"

6"6"

VOLTAGE69KV

6"

GUIDE FOR CONDUIT SIZE-RISER-MINIMUM

750 4" 6" 6"

20001000

5003504/01/0#2

4"4"3"3"3"

6"6"

6"

4"4"4"

6"

-6"

GUIDE FOR CONDUIT SIZE-DUCT BANKS-MINIMUM

750 4" 6" 6"

- - -

4"6"

A. ALL PRIMARY RISER CONDUITS SHALL BE PVC, SCHEDULE 80, FOR THE FIRST 8 FEET FROM FINISHED GRADE, PVCSHEDULE 40 MINIMUM COULD BE USED FOR THE REST OF THE RISER. GALVANIZED STEEL CONDUITS ARE ACCEPTABLEWHEN SPECIFIED IN WORK ORDER DRAWING FOR THE FIRST 8'.

B. ALL RISERS SHALL BE BUILT IN ACCORDANCE WITH THE CITY OF ANAHEIIM CONSTRUCTION STANDARD CO 1101ANDGO95 RULE 54.6E.

C. PVC REDUCER, IF REQUIRED, WILL BE SPECIFIED BY T&D ENGINEERING FOR CONNECTION OF RISER TO THEUNDERGROUND CONDUIT.

A. ALL PRIMARY AND SECONDARY CONDUITS SHALL BE MINIMUM DB-100, CONCRETE ENCASED PER CONSTRUCTIONSTANDARD CU 1600-4. PVC SCHEDULE 80 AND GALVANIZED STEEL CONDUITS ARE ACCEPTABLE WHEN SPECIFIED IN WORKORDER DRAWINGS.

B. ALL CONDUITS CROSSING RAILROAD TRACKS, FREEWAYS, FLOOD CONTROL CHANNELS AND OTHER MAJOR CROSSINGSHALL BE INSTALLED IN RIGID GALVANIZED STEEL CONDUIT PER CONSTRUCTION STANDARD CU 1600-96E.

C. CONDUITS INSTALLED FOR STREETLIGHTS AND SUMP PUMPS SHALL BE 2" MINIMUM PVC SCHEDULE 80. FOR ALL STREETCROSSINGS, MINIMUM 2" HOT DIPPED GALVANIZED CONDUIT SHALL BE INSTALLED.

D. CONDUITS INSTALLED FOR CITY OF ANAHEIM FIBER OPTIC AND AUTOMATION SHALL BE 4" MINIMUM

CABLESIZE

VOLTAGE600 VOLTS

VOLTAGE6.9KV

VOLTAGE12KV

VOLTAGE69KV

4"4"

NOTES

NOTES

-- -

--

-------

------

- -

444"44444444444"444""444444444

444"444444444444"444""444444444

APPROVALST&D MGR

CITY OF ANAHEIMELECTRICAL DIVISION

PUBLIC UTILITIES DEPARTMENT

FILE

NAME

:

REVISION KEYS: ADDED / REVISED TEXT NEW SHEET

CONSTRUCTION STANDARD:

ADDED / REVISED MATERIAL

SHEET OF

REVISION NO.ISSUE DATE :

FIELD MGR OPER. MGR

T&D CONSTRUCTION STANDARDS APPROVED CONDUIT TYPES,SIZES, AND APPLICATION

CU16

00-4

A RE

V 1

101-11

1 2

CU 1600-4A

Page 2: DRAWINGS. GUIDE FOR CONDUIT SIZE-RISER-MINIMUM

NOTES:

ALL CONDUIT SHALL BE INSTALLED PER CITY SPECIFICATIONS AND SHALL BE WATERTIGHT.

A. THE MINIMUM RADIUS FOR BENDS IS:24" FOR 2" DIA. CONDUIT36" FOR 3" DIA.CONDUIT60" FOR 4", 5" & 6" DIA. CONDUITS

B. THEMINIMUMRADIUS FOR SWEEPS OF ALL SIZE CONDUITS IS 12'-6" FOR 12KV AND 25' FOR 69KV UNLESSOTHERWISE SPECIFIED ONWORK ORDER DRAWINGS.

C. ALL COUPLINGS, ADAPTERS, SEGMENTS, END BELLS, ETC. SHALL BE STANDARD TYPES, RECOMMENDED BYTHEMANUFACTURER AND APPROVED BY UTILITIES INSPECTORS.

D. UIT INSTALLATIONS TO FORM SWEEPSSHORT LENGTHS OF CONDUIT, PROPERLY COUPLED MAY BE USED IN CONDUIT INSTALLATIONS TO FORM SWEEPSSHORT LENGTHS OF CONDUIT PROPERLY COUPLED, MAY BE USED IN CONDUIT INSTALLATIONS TO FORM SWEEPSSHORT LENGTHS OF CONDUIT PROPERLY COUPLED MAY BE USED IN CONDSSSHHHOOORRRRTTT LLEEENNNGGGGTTTHHHSSS OOOFFF CCCOOONNNDDDUUUITTT PPPRRROOOOPPPEEERRRRLLYYYY CCCOOOOUUUPPLLEEEDDDD MMMAAAAYYYY BBBEEE UUUSSSEEEDDDD INN CCCOOONNNDDDUUU TTT INNNSSSTTTAAALLLLAAATTTIOOONNNSSS TTTOOOO FFFOOORRRMMMM SSSWWWWWEEEEEEPPPSSSSSSHHHOOOORRRTTT LLEEENNNGGGTTTHHHSSS OOOOFFF CCCOOOONNNDDDUUU TTT PPPRRROOOPPPEEERRRLLLYYY CCCCOOOUUUPPPLLLEEEDDD MMMMAAAYYY BBEEE UUUSSSSEEEDDD INNN CCCOOOONNNDDDUUUITTT NNNSSSTTTAAAALLLLLAAAATTTIOOOONNNSSS TTTTOOO FFOOOORRRRMMM SSSWWWWEEEEEPPPSSSSSSHHHOOORRRRTTT LLEEENNNGGGGTTTHHHSSS OOOFFF CCCCOOOONNNDDDUUUITTT PPPRRROOOOPPPEEERRRRLLYYYY CCCOOOOUUUPPPLLEEEDDDD MMMMAAAAYYYY BBBEEE UUUSSSEEEDDDD INNN CCCOOOONNNDDDUUU TTT INNNSSSTTTAAALLLLLAAATTTIOOONNNSSS TTTOOOO FFFOOOORRRMMMM SSSWWWWWEEEEEEPPPSSSSSSHHHOOOORRRTTT LLEEENNNGGGTTTHHHSSS OOOOFFF CCCOOOONNNDDDUUU TTT PPPRRROOOPPPEEERRRLLLYYY CCCCOOOUUUPPPLLLEEEDDD MMMMAAAYYY BBEEE UUUSSSSEEEDDD INNN CCCOOOONNNDDDUUUITTT NNNSSSTTTAAAALLLLLAAAATTTIOOOONNNSSS TTTTOOO FFOOOORRRRMMM SSSWWWWEEEEEPPPSSSSSSHHHOOORRRRTTT LLEEENNNGGGGTTTHHHSSS OOOFFF CCCCOOONNNDDDUUUITTT, PPPRRROOOOPPPEEERRRRLLYYYY CCCOOOOUUUPPPLLEEEDDDD, MMMMAAAAYYYY BBBEEE UUUSSSEEEDDDD INNN CCCOOONNNDDDUUU TTT INNNSSSTTTAAALLLLLAAATTTIOOONNNSSS TTTOOOO FFFOOOORRRMMMM SSSWWWWWEEEEEEPPPSSS, , OFOOOFFFOOOOFFOOOFFFOOOOFFOOOFFFRADIUS SWEEPS SHOULD BE LIMITEDLARGER RADIUSES. THE MAXIMUM NUMBER OF SEGMENTS USED FOR 12 -6 RADIUS SWEEPS SHOULD BE LIMITEDLARGER RADIUSES THE MAXIMUM NUMBER OF SEGMENTS USED FOR 12 -6 RADIUS SWEEPS SHOULD BE LIMITEDLARGER RADIUSES THE MAXIMUM NUMBER OF SEGMENTS USED FOR 12’ 6”LLAAARRRRGGGEEERRR RRRRAAAADDDIUUUSSSEEESSS TTTHHHEEE MMMMAAAXXXIMMMUUUUMMM NNNUUUMMMMBBBEEERRRR OOOFF SSSEEEGGGGMMMEEENNNTTTSSS UUUSSSEEEDDD FFFOOOORRR 1222’ 666” RRRAAAADDDIUUUSSS SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLLDDD BBBEEE LLLIMMMMITTTEEDDDLLLAAAARRRGGGGEEERRR RRRAAADDDDIUUUSSSEEESSS TTTHHHEEE MMMMAAAAXXXXIMMMMUUUMMMM NNNUUUMMMMBBBEERRR OOOOFFF SSSEEGGGMMMMEEENNNNTTTSSS UUUSSSEEEDDD FFOOOORRRR 11222’ 66”” RRRRAAADDD UUUSSS SSSWWWWEEEEEEPPPSSS SSSHHHOOOUUULLDDD BBBEEE LL MMMITTTEEEDDDLLAAARRRRGGGEEERRR RRRRAAAADDDIUUUSSSEEESSS TTTHHHEEE MMMMAAAXXXIMMMUUUUMMM NNNUUUMMMMBBBEEERRRR OOOFF SSSEEEGGGGMMMEEENNNTTTSSS UUUSSSEEEDDD FFFOOOORRR 1222 666 RRRAAAADDDIUUUSSS SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLLDDD BBBEEE LLLIMMMMITTTEEDDDLLAAAARRRGGGGEEERRR RRRAAADDDDIUUUSSSEEESSS TTTHHHEEE MMMMAAAAXXXXIMMMMUUUMMMM NNNUUUMMMMBBBEERRR OOOOFFF SSSEEGGGMMMMEEENNNNTTTSSS UUUSSSEEEDDD FFOOOORRRR 11222 --66 RRRRAAADDD UUUSSS SSSWWWWEEEEEEPPPSSS SSSHHHOOOUUULLDDD BBBEEE LL MMMITTTEEEDDDLLAAARRRRGGGEEERRR RRRRAAAADDDIUUUSSSEEESSS TTTHHHEEE MMMMAAAXXXIMMMUUUUMMM NNNUUUMMMMBBBEEERRRR OOOFF SSSEEEGGGGMMMEEENNNTTTSSS UUUSSSEEEDDD FFFOOOORRR 1222 666 RRRAAAADDDIUUUSSS SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLLDDD BBBEEE LLLIMMMMITTTEEDDDTOTTTOOOTTTOOOOTTTOOOTTTOOOOTTTOOOE MAXIMUM DEFLECTION PER LENGTHFOUR PIECES AND FOR 25 SWEEPS SHHOULD BE LIMITED TO FIVE PIECES THEE MAXIMUM DEFLECTION PER LENGTHFOUR PIECES AND FOR 25’SWEEPS SHHOULD BE LIMITED TO FIVE PIECES. THEFOUR PIECES AND FOR 25 SWEEPS SHOULD BE LIMITED TO FIVE PIECES THE MAXIMUM DEFLECTION PER LENGTHHOULD BE LIMITED TO FIVE PIECES THEFFFOOOUUURRR PPPIEEECCCCEEESSS AAAANNNDDD FFOOOORRRR 22555’SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLDDD BBBEEE LLIMMM TTTEEEDDD TTTOOOO FFIVVVVEEE PPP EEECCCEEESSS TTTHHHEEE MMMMAAAXXXIMMMUUUMMMM DDDEEEFFFLLEEECCCCTTTIOOOONNN PPPEEERRR LLEEENNNGGGTTTHHHFFOOOOUUURRRR PPPIEEECCCEEESSS AAANNNDDDD FFFOOOORRR 222555’SSSWWWWEEEEEEPPPSSS SSSHHHOOOUUULLLDDD BBBEEE LLLIMMMMITTTEEEDDDD TTTOOO FFFIVVVEEE PPPIEEECCCCEEESSS TTTHHHEEE MMMAAAAXXXXIMMMMUUUMMM DDDEEEFFFLLLEEECCCTTTIOOONNN PPPEEERRRR LLLEEENNNGGGGTTTHHHFFFOOOUUURRR PPPIEEECCCCEEESSS AAAANNNDDD FFOOORRRR 22555 SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLDDD BBBEEE LLIMMM TTTEEEDDD TTTOOOO FFIVVVVEEE PPP EEECCCEEESSS TTTHHHEEE MMMMAAAXXXIMMMUUUMMMM DDDEEEFFFLLEEECCCCTTTIOOOONNN PPPEEERRR LLEEENNNGGGTTTHHHFFOOOOUUURRRR PPPIEEECCCEEESSS AAANNNDDDD FFFOOOORRR 222555 SSSWWWWEEEEEEPPPSSS SSSHHHOOOUUULLLDDD BBBEEE LLLIMMMMITTTEEEDDDD TTTOOO FFFIVVVEEE PPPIEEECCCCEEESSS TTTHHHEEE MMMAAAAXXXXIMMMMUUUMMM DDDEEEFFFLLLEEECCCTTTIOOONNN PPPEEERRRR LLLEEENNNGGGGTTTHHHFFFOOOUUURRR PPPIEEECCCCEEESSS AAAANNNDDD FFOOOORRRR 22555 SSSWWWWWEEEEEEPPPSSS SSSHHHOOOOUUULLDDD BBBEEE LLIMMM TTTEEEDDD TTTOOOO FFIVVVVEEE PPP EEECCCEEESSS. TTTHHHEEE MMMMAAAXXXIMMMUUUMMMM DDDEEEFFFLLEEECCCCTTTIOOOONNN PPPEEERRR LLEEENNNGGGTTTHHHOFOOOFFOOOOFFFOOOFFOOOOFFFOOOFF

CONDUIT SHALL BE: 1/2" FOR LENGTH 2CONDUIT SHALL BE: 1/2" FOR LENGTH 2CONDUIT SHALL BE: 1/2" FOR LENGTH 2CCCOOONNNDDDUUUITTT SSSHHHHAAALLLLL BBBEEE 11//22"" FFFOOOORRR LLEENNNGGGGTTTHHH 222CCCOOOONNNDDDUUUITTT SSSHHHAAAALLLLL BBBEEE: 11/222" FFFOOORRR LLLEEENNNGGGTTTHHH 22CCCOOONNNDDDUUUITTT SSSHHHHAAALLLLL BBBEEE: 11//22 FFFOOOORRR LLEEENNNGGGGTTTHHH 222CCCOOOONNNDDDUUUITTT SSSHHHAAAALLLLL BBBEEE: 11/222 FFFOOORRR LLLEEENNNGGGTTTHHH 22CCCOOONNNDDDUUUITTT SSSHHHAAALLLLL BBBEEE: 11//22 FFFOOOORRR LLEENNNGGGGTTTHHH 22211111112222222' AND SHORTER AND 1" FOR LENGTHS OVER 2' AND SHORTER AND 1" FOR LENGTHS OVER 2' AND SHORTER AND 1" FOR LENGTHS OVER 2' AAANNNDDD SSSHHHOOOORRRTTTEEERRRR AAANNNDDD 1"" FFFOOOORRR LLEEENNNGGGTTTHHHSSS OOOOVVVEEERRR 222' AAAANNNDDD SSSHHHOOOORRRRTTTEEERRR AAAANNNDDDD 11" FFOOORRRR LLLEEENNNGGGGTTTHHHSSS OOOOVVVVEEERRR 22AAANNNDDD SSSHHHOOOORRRTTTEEERRRR AAANNNDDD 1 FFFOOOORRR LLEEENNNNGGGTTTHHHSSS OOOOVVVEEERRR 222AAAANNNDDD SSSHHHOOOORRRRTTTEEERRR AAAANNNDDDD 11 FFOOORRRR LLLEEENNNGGGGTTTHHHSSS OOOOVVVVEEERRR 22 AAANNNDDD SSSHHHOOOORRRTTTEEERRRR AAANNNDDD 1 FFFOOOORRR LLEEENNNGGGTTTHHHSSS OOOOVVVEEERRR 22211111

22222'.''..

E. PVC CONDUIT MUST BE MADE BY AN APPROVED MANUFACTURER. CONSULT THE ELECTRICAL ENGINEERINGDIVISIONOR UTILITIES INSPECTOR FOR NAMES OF APPROVED MANUFACTURERS.

F. WHITE CONDUIT (WATER PIPE, ETC.) AND ABS CONDUIT ARE NOT ACCEPTABLE FOR USE ON CITY'SU.G. ELECTRICAL SYSTEM.

G. SEE CU 1600-96M FOR SOLVENT CEMENT JOINING AND PVC PLASTIC CONDUIT INSTALLATION.

H. ALL CONDUIT STUBOUTS SHALL BE CAPPED AND APPROVED 3M ELECTRONIC LOCATORBALL SHALL BE INSTALLED.

I. AND ALL PRIMARY CONDUIT SHALLALL SECONDARY CONDUIT UNDERR ROADS AND DRIVEABLE AREAS AND ALL PRIMARY CONDUIT SHALLALL SECONDARY CONDUIT UNDERR ROADS AND DRIVEABLE AREAS AALL SECONDARY CONDUIT UNDER ROADS AND DRIVEABLE AREAS AND ALL PRIMARY CONDUIT SHALLR ROADS AND DRIVEABLE AREAS AAAAALLLLL SSSEEECCCCOOONNNDDDAAAARRRYYY CCCCOOONNNDDDUUUITTT UUUNNNDDDEERRR RRROOOAAAADDDSSS AAAANNNDDD DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEEAAAASSS AAANNNDDD AAAALLLLL PPPRRRIMMMMAAARRRRYYYY CCCOOONNNDDDUUUITTT SSSHHHAAAALLLLLAAALLLLL SSSSEEECCCOOOONNNDDDDAAARRRYYYY CCCOOOONNNDDDDUUUITTT UUUNNNDDDEEERRRR RRROOOOAAADDDSSS AAANNNDDD DDDDRRRIVVVVEEEAAABBBLLLEEE AAAARRREEEAAASSS AAAANNNDDDD AAALLLLL PPPRRR MMMAAAARRRYYY CCCOOOONNNDDDUUUITTT SSSHHHAAALLLLLAAAALLLLL SSSEEECCCCOOONNNDDDAAAARRRYYY CCCCOOONNNDDDUUUITTT UUUNNNDDDEERRR RRROOOAAAADDDSSS AAAANNNDDD DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEAAAASSS AAANNNDDD AAAALLLLL PPPRRRIMMMMAAARRRRYYYY CCCOOONNNDDDUUUITTT SSSHHHAAAALLLLLAAALLLLL SSSSEEECCCOOOONNNDDDDAAAARRRYYYY CCCOOOONNNDDDDUUUITTT UUUNNNDDDEEERRRR RRROOOOAAADDDSSS AAANNNDDD DDDDRRRIVVVVEEEAAABBBLLLEEE AAAARRREEEAAASSS AAAANNNDDDD AAALLLLL PPPRRRIMMMAAAARRRYYY CCCOOOONNNDDDUUUITTT SSSHHHAAALLLLLAAAALLLLL SSSEEECCCCOOONNNDDDAAAARRRYYY CCCCOOONNNDDDUUUITTT UUUNNNDDDEERRR RRROOOAAAADDDSSS AAAANNNDDD DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEEAAAASSS AAANNNNDDD AAAALLLLL PPPRRRIMMMMAAARRRRYYYY CCCOOONNNDDDUUUITTT SSSHHHAAAALLLLLBEBBBEEEBBBEEEBBBEEEBBBEEEBBBEEEAREAS, PVC SCH 80 OR HOT DIPPEDCONCRETE ENCASED. FOR SECONDDARY CONDUIT IN NON-DRIVEABLE AAREAS PVC SCH 80 OR HOT DIPPEDCONCRETE ENCASED FOR SECONDARY CONDUIT IN NON DRIVEABLE ADARY CONDUIT IN NON DRIVEABLE AAREAS PVC SCH 80 OR HOT DIPPEDCONCRETE-ENCASED FOR SECONDDARY CONDUIT IN NON DRIVEABLE ACCCOOOONNNCCCRRREEETTTEEE EEENNNCCCCAAAASSSEEEDDD FFFOOOORRR SSSEEECCCOOOONNNDDDAAARRRYYYY CCCOOOONNNDDDUUUITTT INNN NNNOOOONNN DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEAAAASSS PPPVVVVCCC SSSCCCHHH 88000 OOOORRRR HHHOOOOTTT DDDIPPPPPPEEEDDDCCCOOOONNNCCCRRREETTTEE EEENNNCCCAAASSSEEEDDD FFOOORRRR SSSEEECCCCOOONNNDDDAAAARRRYYY CCCCOOONNNDDDUUUITTT INNN NNNOOONNN DDDRRRIVVVVEEEAAABBBLLLEEE AAAARRREEEAAASSS PPPVVVCCCC SSSCCCCHHH 888000 OOOORRR HHHOOOTTT DDDIPPPPPEEEDDDCCCOOOONNNCCCRRREEETTTEEE EEENNNCCCCAAAASSSEEEDDD FFFOOOORRR SSSEEECCCOOOONNNDDDAAARRRYYYY CCCOOOONNNDDDUUUITTT INNN NNNOOOONNN DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEAAAASSS PPPVVVVCCC SSSCCCHHH 88000 OOOORRRR HHHOOOOTTT DDDIPPPPPPEEEDDDCCCOOOONNNCCCRRREETTTTEE EEENNNNCCCAAASSSEEEDDD FFFOOORRRR SSSEEECCCCOOONNNDDDAAAARRRYYY CCCCOOONNNDDDUUUITTT INNN NNNOOONNN DDDRRRIVVVVEEEAAABBBLLLEEE AAAARRREEEAAASSS PPPVVVCCCC SSSCCCCHHH 888000 OOOORRR HHHOOOTTT DDDIPPPPPPEEEDDDCCCOOOONNNCCCRRREEETTTEEE EEENNNCCCCAAAASSSEEEDDD. FFFOOOORRR SSSEEECCCOOOONNNDDDAAARRRYYYY CCCOOOONNNDDDUUUITTT INNN NNNOOOONNN DDDRRRRIVVVEEEAAAABBBLLEEE AAARRREEAAAASSS, PPPVVVVCCC SSSCCCHHH 88000 OOOORRRR HHHOOOOTTT DDDIPPPPPPEEEDDDGALVANIZEDGGGAAAALLVVVAAAANNNIZZZEEEDDDDGGGGAAALLLVVVAAANNN ZZZEEEDDDGGGAAAALLVVVAAAANNNIZZZEEEDDDDGGGGAAALLLVVVAAANNN ZZZEEEDDDGGGAAAALLVVVAAAANNNIZZZEEEDDDD

WORK ORDER DRAWINGS.MAY BE USED UNLESS OTHERWISE SPECIFIED ON WWORK ORDER DRAWINGSMAY BE USED UNLESS OTTHERWISE SPECIFIED ON WORK ORDER DRAWINGS.MAY BE USED UNLESS OTHERWISE SPECIFIED ON WMMMMAAAYYY BBEEE UUUSSSEEEDDD UUUNNNLLLEEESSSSSS OOOTTTHHHEEERRRWWWWWISSSEEE SSSPPPEEECCCIFF EEEDDD OOONNN WWWWOOOORRRRKKK OOOORRRDDDEERRR DDDDRRRAAAWWWWWINNNGGGGSSSMMMAAAAYYYY BBBEEE UUUSSSEEEDDD UUUNNNLLEESSSSSSS OOOOTTTHHHEEERRRRWWWWWISSSEE SSSPPPEEECCCCIFFFIEEEDDD OOOONNN WWWWWOOOORRRKKK OOOORRRRDDDEEERRRR DDDRRRRAAAAWWWWINNNGGGSSSMMMMAAAYYY BBEEE UUUSSSEEEDDD UUUNNNLLLEEESSSSSS OOOTTTHHHEEERRRWWWWWISSSEEE SSSPPPEEECCCIFF EEEDDD OOONNN WWWWOOOORRRRKKK OOOORRRDDDEERRR DDDDRRRAAAWWWWWINNNGGGGSSSMMMAAAAYYYY BBBEEE UUUSSSEEEDDD UUUNNNLLEESSSSSSS OOOOTTTHHHEEERRRRWWWWWISSSEE SSSPPPEEECCCCIFFFIEEEDDD OOOONNN WWWWWOOOORRRKKK OOOORRRRDDDEEERRRR DDDRRRRAAAAWWWWINNNGGGSSSMMMMAAAYYY BBEEE UUUSSSEEEDDD UUUNNNLLLEEESSSSSS OOOTTTHHHEEERRRWWWWWISSSEEE SSSPPPEEECCCIFF EEEDDD OOONNN WWWWOOOORRRRKKK OOOORRRDDDEERRR DDDDRRRAAAWWWWWINNNGGGGSSS.

J. MANUFACTURED CONDUIT SEGMENTS ARE AVILABLE IN11°AND22.5°.

TYPE

APPLICATION

XXXXXXXXXXXXXXXXXXXXX(1)

CONDUIT

MATERIAL, COLOR

INCLUDES INTERMEDIATE METAL CONDUIT (IMC)(1)

CONCRETEENCASED

HOT DIPPEDGALVANIZED

STEEL

POLYVINYLCHLORIDE (PVC)

GREY

DB-100(MINIMUM)

SCHEDULE 40

GUIDE FOR CONDUIT TYPE

ANSI SPECC80.1

SCHEDULE 80 XXXXXXXXXXXXXXXXXXXXX

SEE NOTEI(2)

(2))

X

X

X

X

NON-CONCRETECONCNNNOOOONNN CCCCOOOONNNCCCRRREEEETTTEEENNNNOOOONNN CCCOOOONNNCCCCRRRREEETTTEEENNNOOOONNN CCCCOOOONNNCCCRRREEEETTTEEENNNNOOOONNN-CCCOOOONNNCCCCRRRREEETTTEEENNNOOOONNN CCCCOOOONNNCCCRRREEEETTTEEEENCASEDEEENNNCCCCAAAASSSEEEDDDDEEENNNCCCCAAAASSSEEEDDDEEENNNNCCCCAAAASSSEEEDDDDEEENNNCCCCAAAASSSEEEDDDEEENNNNCCCCAAAASSSEEEDDDD

APPROVALST&D MGR

CITY OF ANAHEIMELECTRICAL DIVISION

PUBLIC UTILITIES DEPARTMENT

FILE

NAME

:

REVISION KEYS: ADDED / REVISED TEXT NEW SHEET

CONSTRUCTION STANDARD:

ADDED / REVISED MATERIAL

SHEET OF

REVISION NO.ISSUE DATE :

FIELD MGR OPER. MGR

T&D CONSTRUCTION STANDARDS APPROVED CONDUIT TYPES,SIZES, AND APPLICATION