46
Available Amenities 1. Electricity Electricity for the entire airport and surroundings will be provided by the Trinidad and Tobago Electricity Commission (T&TEC). 2. Water Supply It is expected that part of the daily domestic water requirement for the entire facility will be provided through municipal mains supply from the Water and Sewerage Authority (WASA). If the supplier is unable to maintain the daily supply it is recommended that 4 tube wells be inserted into the complex to provide the domestic water requirement on need basis. 3. Waste Water Treatment The estimated amount of waste water flow is approximately 2500m 3 /day from the entire facility. This effluent will be discharged into the effluent and sewage treatment plants which will be located in the vicinity of the airport. The plants will be managed and operated by SWMCOL. Effluent Treatment Plant The effluent treatment plant shall have a capacity of approximately 1500m 3 /day and the quality of the treated

draft - copy.doc

Embed Size (px)

Citation preview

Available Amenities

1. Electricity

Electricity for the entire airport and surroundings will be provided by the Trinidad and Tobago Electricity Commission (T&TEC).

2. Water Supply

It is expected that part of the daily domestic water requirement for the entire facility will be provided through municipal mains supply from the Water and Sewerage Authority (WASA). If the supplier is unable to maintain the daily supply it is recommended that 4 tube wells be inserted into the complex to provide the domestic water requirement on need basis.

3. Waste Water Treatment

The estimated amount of waste water flow is approximately 2500m3/day from the entire facility. This effluent will be discharged into the effluent and sewage treatment plants which will be located in the vicinity of the airport. The plants will be managed and operated by SWMCOL.

Effluent Treatment Plant

The effluent treatment plant shall have a capacity of approximately 1500m3/day and the quality of the treated effluents shall be of a quality suitable for re-use as flushing water in the WCs.

Sewage Treatment Plant

The sewage treatment plant shall have a capacity of 1300m3/day and the quality of the treated effluent shall be suitable for re-use water in the cooling towers of the air conditioning systems as well as for use in horticulture activities. It is also proposed to use activated sludge process based o the principle of extended aeration based on a Diffused Aeration System.

4. Telecommunications and Satellite Services.

Telecommunications will be provided by the Telecommunication Services of Trinidad and Tobago. Satellite services will be provided by VSAT and Satellite Technologies.

5. Fire Services

6. Police Services.

Conceptual Design Conceptual design in civil engineering refers to a vague and creative phase at the beginning of the construction process. In the later phases of a project, only a small part of the building is under elaboration whereas in conceptual design the entire building, its functionality and usage are all taken into consideration. The purpose of a conceptual design is to determine the most feasible alternative. At this stage the objective is to study a number of possible schemes and select the most cost effective one. To determine this, detailed calculations are unnecessary however member sizes and reinforcement content must be estimated in order to determine the relative amounts of materials which will then determine the cost of the project.

The conceptual design of any project must consider the intended functionality of the structure so that there is no ambiguity concerning the function which the end product must serve. Based on the given design brief, the design of the airport terminal and control tower must fulfil the wishes of the client which are to provide a unique, safe and feasible structure to accommodate the growing economy and to improve transport links. The client also wishes that the airport be seen as a reflection of the nation and that they both display outstanding design qualities. Economy must also be maintained since the airport proposal must set new standards in cost effectiveness and quality.

For this conceptual design a number of alternatives were created for each structure. This was done by a combination of research and sketches producing a number of possible ideas. Each member of the group produced an individual concept for the terminal as well as the control tower. From this, sketches were produced combining a number of ideas and possibilities. From the different ideas and possibilities generated, each alternative was passed through a design matrix and from this the most feasible option was chosen for a terminal and control tower. The entire airport facility should encompass:

i. Main terminal building

ii. Transport interchange facilities

iii. Runways

iv. Car parks

v. Control tower

vi. Water and waste management facilities

vii. Aircraft maintenance

viii. Future passenger terminal expansion

All of the above were taken into consideration for each conceptual design.Preliminary design The preliminary design phase is the phase in which high level design concepts are generated. The objective of the preliminary design is to map out how the structure will perform the functions specified in the requirements. The main activities for the preliminary design phase are:

i. Create a high level design description

ii. Identify the major components of the structure

iii. Include reliability, maintenance and tests features that are necessary to meet the performance and quality requirements

iv. Identify constraints on the structure that are a result of high level design.

Method of Selection of Alternatives

To determine the most feasible alternative for the airport terminal as well as the control tower a Design matrix was configured. To develop this rational method for selection of the final alternative, key influential factors were identified and evaluated thoroughly to determine their impact on the final choice. The main and most crucial factors which were selected for this matrix were as follows:

i. Performance

ii. Costs

iii. Constructability

iv. Accessibility

v. Environmental impact

vi. Safety

vii. Aesthetics.

Performance

The performance criterion will be used to assess the variances in the client and stakeholders demand satisfaction for each alternative. It will qualitatively assess whether or not the demands of the affected parties were abundantly satisfied. The airport terminal must provide a reasonable financial return to the stakeholders as well as provide efficient passenger services. Future expansion of the terminal also falls under this category. Some key factors which are to be used for the determination of performance of the best terminal are:

i. Passenger flow

ii. Level of service for passengers

iii. Performance standards

iv. Walking distance

v. Traffic peaking characteristics

vi. Future growth

vii. Ease of way-finding

viii. Retail

Costs

This includes capital, operation and maintenance costs. For any preliminary design the major objective is to determine the most feasible alternative. This will be dependent on the cost of the structure. The capital costs are the total costs which are needed to implement the project and may be considered as the costs incurred on the purchase of construction to be used in the rendering of services.

Operation costs are the recurring expenses which are related to the operation of the facility while maintenance costs result from actually maintaining the facility. From this, the overall cost of the entire structure for both terminal and control tower will be determined for each alternative and based on this criterion, the best one will be chosen.

Constructability

This may be defined as the optimum use of knowledge and experience in designing, planning and field operations to achieve the overall objectives of the project. Ares under consideration for this are, simplicity, ease of construction, economy and statutory restrictions. Careful attention must be paid to in this criterion since economy plays a heavy role as well as ease and speed of construction of the project. In order to determine the best alternative based on this criterion, the costing of each structure was determined as well a project schedule. The most feasible will then be chosen.

Circulation or Accessibility

This refers to the ease with which passengers and vehicular traffic can flow into, out of and within the facility. Each alternative will be assessed based on:

i. Movement through the structure/ structures with the differently capable in mind.

ii. Provision for vehicular traffic flow around the facility at entrances and exits as well as flow into and out of the facility.

iii. Zoning layout that provides ease of access between terminal element and control tower.

iv. Provisions for aircraft and machinery mobility around and about the concourse areas.

v. Provisions for movement and transport of cargo within the facility.

vi. Proper and adequate parking facilities.

Environmental Impact

Environmental considerations such as effect on wildlife ecology, ground water runoff, air pollution as well waste water management systems all fall under this criterion. Ecological impacts may be a result of poor construction practice and induced development by the presence of the airport and hotels. Careful disposal of waste, waste water handling and re-use must also be heavily considered so that nearby existing water bearing zones will not become polluted. For this design a waste water treatment facility is to be implemented. An adequate water distribution system must also be implemented for the entire facility.

Sites near bird habitats must also be avoided since there are many previous accidents involving birds colliding with airplanes as well as ingestion into jet engines.

Safety

For this criterion the layout of each structure is critical. This means that the building must be designed to accommodate large volumes of human traffic. The building must be carefully assessed for earthquake resistant design, wind and hurricane design as well as fire design. To determine this, careful analysis for earthquake and wind loading must be done in detail in accordance with the relevant codes and standards. Each component of the structure must comply with the required standards for fire resistant design. The type of glass sheeting and proper bracing must also be heavily considered.

Aesthetics

This is the most subjective criterion considered for the selection of the final alternative since it relies on the ability to discriminate at a sensory level. Considerations will be given to how each alternative meets the wishes of the client and how each alternative blends with the environment. Since the client wishes that the airport terminal and control tower be a representation of the nation as well depict a Gateway to the sky, the model which best suits this description will be considered.Selection modelsCriteria consideration rating of alternatives

Based on the aforementioned selection criteria, several selection models were developed and compared based on their weaknesses and strengths. To determine the most feasible alternative from all five alternatives, it was agreed that two basic models will be used one of a qualitative and quantitative measure. Holistic approach This model was used to rate the three alternatives under each criterion using a consideration index. This consideration index, rated each alternative based on their level of consideration towards the criterion. The consideration index is as follows:

i. High consideration (H) alternative reflects a high level of considerationii. Moderate consideration (M) - reflects a moderate level of consideration towards criterion.

iii. Low consideration (L) reflects a low level of consideration towards criterion.

Each alternative was severely critiqued and from this, Table...... below was produced giving a model which employs a qualitative approach. The design alternative which gives the highest consideration to criteria will be selected. CONSIDERATION SELECTION MODEL - QUALITATIVE APPROACH

TERMINAL BUILDING

Concrete

Steel

Alternative 1

Alternative 2

Performance H

H

Environmental ImpactM

H

Costs (capital, operation and maintenance costs)M

H

ConstructabilityH

H

Circulation (movement around site)M

M

SafetyM

L

AestheticsH

H

TOWER

Concrete

Steel

Performance

Environmental Impact

Costs (capital, operation and maintenance costs)

Constructability

Circulation (movement around site)

Safety

Aesthetics

From the table above it can be seen that the holistic design approach of alternative............ gave the most consideration to the selection criteria making it the most suitable option.

Weakness of model and recommendations

More suitable for rapid evaluations and there is the possibility of the same final result

Since little emphasis is placed in the detailing of each criterion, the index can misrepresent the individual effects as opposed to an overall effect.

Index allocation is based highly on emotions versus scientific research.

Recommendations for improvement of model

Each of the selection criteria in the above table may be sub divided into sub criteria so that they will be more specific to a particular area of the main criteria. This would require less guess work and more precise answers.

Total Weighting Approach

For this approach each criterion was marked based on the importance to the provision of the terminal and control tower. Each criterion was assigned a relative weighting factor which then determined the weight of that particular criterion. This was done for all the criteria for each alternative and the total weighted score for each alternative was tallied. The ranking is as follows and it should be noted that the criterion with the highest ranking is of the greatest importance. One major weakness of this model is that the ranking is still based on emotion rather than scientific approaches.

Ranking Values

0 No relation

1 Totally incompatible

2 Very unsatisfactory

3 No satisfaction

4 Poor satisfaction

5 Moderate satisfaction

6 Average satisfaction

7 Good satisfaction

8 Excellent satisfaction

The ranking values were t hen distributed on the basis of the main objective, that is, the economical development of a high performance environmentally friendly airport facility. A weighting factor of 0-4 stems unsatisfactory results whereas from 5-8 shows ranges of high satisfaction. Table........... shows the distribution of the weighting factors for each alternative below.TOTAL WEIGHTING SELECTION MODEL - QUANTITATIVE APPROACH

TERMINAL BUILDING

DESIGN CRITERIAAlternative 1Alternative 2Ranking

Performance

Environmental Impact

Costs (capital, operation and maintenance costs)

Constructability

Circulation (movement around site)

Safety

Aesthetics

TOWER

DESIGN CRITERIAAlternative 1Alternative 2Ranking

Performance

Environmental Impact

Costs (capital, operation and maintenance costs)

Constructability

Circulation (movement around site)

Safety

Aesthetics

The total weighting for each alternative was calculated by summing the products of the weighting and ranking for each criterion for that particular alternative. Allocation of weighting Terminal Performance Alternative..... showed the highest levels of performance also taking into account room for future performance.

Capital costsAlternative..... was allocated the highest weighting value since it requires less capital to construct and maintain. The building is of a simple design and very cost effective.

ConstructabilityThe highest weighting was given to alternative..... as this option was simple to design, economical and with desirable speeds of construction.

Circulation or AccessibilityAlternative.... .. showed the highest weighting for this criteria since the layout allows for more accessibility and room for future expansion.

Environmental Impact

Alternative ....... was elected with the highest weighting since this showed the smallest scale of development for the area. Safety For this criterion, alternative.......... was chosen. By looking at the architectural drawings we see that this alternative provides safer surroundings and measures than alternative......

Aesthetics

Both alternatives show contrast however they both enhance the existing environment therefore they were both given the same weighting. From the analysis of the above results it shows that alternative..... is the most suitable option for this preliminary design. The total weighting for this option was ...... which is not to far from the alternative ........ Alternative ...... provides better performance for stakeholders and also leaves adequate room for future expansion. When capital costs are compared for both structures it was seen that alternative....... was the most cost effective option. Therefore it can be said that from the above results alternative....... is the most feasible alternative for the clients.

The same process described above for choosing the most feasible option for the terminal was carried out for the control tower until it was determined that alternative........ was the most suitable alternative for the client.Structural Analysis of the Reinforced Concrete Control Tower Initial sizing of structural members and other materialsThe initial sizing of the beams and columns was done in accordance to the Preliminary Design Guide of Structural Members by Richard Clarke. A detailed analysis of the total loads will be done in the detailed design section. For this preliminary design section, the load cases considered for this stage of design were as follows:

Dead Loads

Live Loads

Earthquake Loads

Wind Loads

Earthquake Loading ConditionsThe base shear is calculated as 10% of the total weight of the structure. For earthquake analysis checks will be performed in the lateral and vertical sections of the building in plan view. Point loading at each level will be distributed by looking at the relative surface area ratios throughout the entire building since the building is not evenly distributed or symmetrical. The figure below shows the distribution of earthquake forces on the control tower.

From the earth analysis the period of the structure was 0.75 Hertz

The total earthquake loading was calculated to be 2057.86 KN.

Figure...... showing distribution of earthquake forces on control tower.In the detailed design this analysis will be done using plane frame analysis. The loading conditions considered are as follows:

1.2D + 0.5L+1.0E

1.4D + 1.6 L

The required longitudinal and transverse steel will be calculated in the detailed design stage.Wind Loading Conditions

Wind loading on the control tower plays a critical part since the tower was designed as a high rise structure. Wind loading on tall buildings needs to be considered in the early design stages so that the size and form of the structure can be optimised to capitalise on the possibilities of reducing the wind loads.

At a height of 52 metres high, wind velocities provide lateral forces throughout the entire length of the building. In Trinidad the wind speed generated for design purposes is that of 45m/s. This is critical to the building since this can cause the tower to sway immensely which can be detrimental to the structural integrity of the tower. A regular rigid frame has its deflections produced by bending of columns and bending of the beams. Dynamic wind loading can cause over-turning if the restoring moment cannot counteract these forces. Figure..... below shows how wind loading is distributed throughout the control tower. The wind loads were calculated for each floor height of the building but the diagram below shows a general distribution of the forces. The wind loads were calculated to produce a total wind load of 2171.0 KN.

Figure....... showing the distribution of wind loads on the structure.Load Path Analysis

Type of frame system

For the preliminary design of the control tower, the type of frame system chosen was critical. Since the airport is being designed for a location in Trinidad and Tobago, the type of system chosen had to be capable of resisting earthquakes. Since most structures are designed to resist the vertical forces of gravity, little additional strength is needed to account for the vertical aspect of seismic forces. However since seismic forces also impart horizontal forces, a successful structural design must account for this additional horizontal force. Although buildings are already designed to resist wind forces, seismic forces are typically greater than wind forces therefore buildings require greater strength components to resist seismic forces. These components form system called an earthquake resistant structural system.An earthquake resistant structural system is a structural system with properties and behaviour that area favourable towards the objective of adequately resisting earthquake forces (Clarke, Earthquake Resistant Design n.d.)The main desiarable quality of such a structural system is ductility. The other desirable properties which promote high ductility and overall favorable responses are:i. Regularity Little change in stiffness, mass and strength from floor to floor

ii. Continuous load path- The absence of gaps between members so that the force is effectively transferred from each member to successive members on its way to the foundation

iii. Short load path- Small offsets in beams, columns and wallsiv. Multiple Load paths the presence of several routes which the force can travel through to the foundation means that if any one member becomes overstressed other members can be relied upon to absorb its energy.

v. Strong connections- to ensure that the load path is not broken by excessive deformations or rupture.When all these factors are maximised, the sequence and formation of hinges are such that their energy absorption in the system is maximised. With the above mentioned, the safest and most reliable structural system to be considered was that of a Moment Resisting Frame. Framed Tube Structure

Framed tube structures are a special type of a moment resisting frame. They are constructed with very wide columns closely spaced and relatively deep beams. Framed tubes have narrowly spaced exterior columns combined with beams to form rigid structures to resist lateral loads. This type of framing is usually located on the perimeter of the structure. Due to the added strength of the wide columns and deep beams, this type of system introduces more stiffness. The stiffness is used to overcome the potential problems caused by the horizontal sway which occurs during an earthquake. The framed tube method is frequently used in very tall buildings where swaying can be detrimental to the structural integrity of the building. The first noted example of a framed tube structure is the Dewitt Chestnut Apartments, Chicago Illinois constructed in 1964 as shown in Figure.... below.

Figure ..... showing Dewitt Chestnut Apartments in Chicago constructed using a tube frame structure.The 43 story reinforced concrete tower was designed by Dr. Fazlur Khan at Skidmore Owings and Merrill (SOM). Due to its high relative strength and stiffness the tubular form immediately became a standard in high rise design (D. F. Khan 2006)

For the design of the control tower, the shaft comprises of an inner and outer shaft. The outer shaft which models a framed tube structure has a square base with a total of eight wide columns each 600 x 600 mm in dimension as shown in the figure... below.

Figure .................showing arrangement of columns on outer shaft.

The columns are equally and closely spaced which helps to generate the required stiffness. The inner shaft comprises of a rectangular elevator shaft with columns placed at each corner each column having dimensions of 300 x 300 mm. This shaft acts as a symmetrical shear core due to the arrangement of the columns. On the outer shaft there are deep beams of dimensions 600 x 800 mm spanning between columns whereas in the inner shaft secondary beams are used to join inner to the outer shaft for each floor. This beam and column arrangement can be seen in figure....... which shows how this framed system caters for stiffness in the control tower.Roof StructureThe type of roof chosen for the control tower is that of a domed structure. This was chosen since it will mimic an arched system which is structurally sound as well it adds to the aesthetics of the structure. The dome spans 12 metres in diameter and has a rise of 2 metres. The type of dome chosen is that of a Ferro-cement dome. Ferro-cement is a composite of steel and cementitious material. The large size steel reinforcing bars are replaced with wire meshes, while the coarse aggregate is removed completely from the cementitious matrix. The resultant composite called Ferro-cement lends itself to casting in thin sections. The properties of Ferro-cement such as strength, water tightness light weight, durability, fire resistance and environmental stability are hard to match. (T.P. Singh, High Performance Ferrocement Dome). The dome shell will be designed to be 1 inch thick with 24 nos. longitudinal stiffener ribs in the form of truss frames projecting inwards. An example of this can be seen in Figure..... below which shows the arrangement of the reinforcement being used in the construction of the dome.

Figure..... showing reinforcement detail (Temple in Doraha, India)Six layers of GI wire meshes will be wrapped on the armature. The truss will consist of 2-8 mm bars connected with zig zag lattice bars. The trusses will be curved to follow the shape of the dome. The trusses will be erected on a ring beam of size 300x400mm which will be welded on to dowels left in the beam. At the top the trusses will be arranged and held in place by a pipe ring which will be imbedded in the concrete. The trusses once erected will be wrapped around be hoop steel 6mm diameter MS bars at every 3 inches.

The Ferro-cement dome shell will have 6 layers of GI wire meshes with 3 on each side. Voids in the shell will be filled with PVC grouting nipples. This type of structure was chosen due to its light weight which will in turn reduce the earthquake damage potential to the building. Examples of this particular type of structure can be seen in the temples in Doraha, India built by the Gurudwara Brahm Bunga Trust as well as off shore structures which use the improved Ferro-cement techniques developed by Martin Iorns. Reinforced Concrete BeamsAssume a ductile frame and a beam span of 6 metres

For non-cantilever, d = span/26 + 300 mm (span in mm)

= 6000/26 + 300 = 530 mmUse 600 mm depth beamsFor spans 6000mm < span < 9000mm width (b) of beam = 350 mmFrom the above, use 600 x 800 mm beams in the preliminary design stage.In the detailed design the calculation checks will include beam slenderness, span/effective depth, reinforcement and depth of cover using the BS8110:Part 1:1997.

Reinforced Column Design

Square columns will be used for the preliminary analysis. All columns are braced columns.On each of the 13 floors of the outer shaft 600 x600 mm square columns will be placed each 2.1 metres apart on each side.

On each floor the inner shaft 300 x 300 mm square columns will be placed at each corner of the rectangular shaft.

On the first floor of the cab, 8 square columns of size 400 x 400mm will be used along the perimeter of the slab.

On the second floor of the cab, 8 slanted columns projecting outwards of size 400 x 400 mm will be arranged on the perimeter of the slab. Typical reinforcement is calculated as 4% of the gross cross sectional area of the column. In the detailed design full reinforcement detail will be calculated and verified using the BS8110:Part 1:1997 Structural Use of Concrete: Part 2 Code of Practice for Design and Construction.Floor SystemThe type of floor system chosen is that of a typical two-way solid slab design with beams running underneath forming a grid like pattern. This type of floor system is simple with a typical solid concrete slab of 6 inches thickness and diameter of 9 metres. This was also chosen since this floor system makes use of cantilever beams. In the detailed design the slab will be designed taking into account bending strength and deflection with references to the BS8110:Part 1:1997.Reinforced Concrete Block Walls

These block walls are non-load bearing walls since the beams and columns which make up the frame of the structure transfer the loads from the roof to the foundation. However they will be reinforced so as to add to the general stiffness of the shaft in the control tower. The walls will also serve the purpose of shelter. The blocks will be interlocked however the technique of groove pointing will be employed as a finish.The size of blocks for external and internal walls are 6 inch hollow concrete blocks.

Concrete infill and vertical reinforcement will also be used.

Internal Concrete Stair Case For each floor the stair case will rise 3 metres in height per floor. Each step will have a rise of 0.2 metres and a run of 0.3 metres. The landing top and bottom will be of dimensions 1.5 x 1.5 m. The landing will be of thickness 4 inches. The stair will join the walls of the inner shaft and tie to the walls of the outer shaft forming a wrap throughout the shaft of the control tower. Foundation From the borehole data provided, the type of soil being considered is that of a silty medium to dense sand. This means that we are designing for a shallow foundation. The advantages of using a shallow foundation type are:

Affordable cost

Simple construction procedure

Materials are mostly concrete and reinforcement

The disadvantages of using a shallow foundation type are;

Settlement

Foundation subjected to pull out, torsion and moments.

Irregular ground surface.

The type of foundation chosen is critical since the foundation will act as an anchor to prevent the control tower from over turning. The type of foundation considered for the control tower is that of a pad foundation for the dense silty sand provided. A typical pad foundation is seen in Figure.... below.

Figure .......... showing a typical reinforced pad footing. Picture taken from An Overview of Footings and Foundations A pad foundation normally supports a number of column loads in both horizontal directions. The minimum size of the pad is given by the practical requirement of being able to excavate by hand to the required depth and level off the bottom and to lay brickwork or fix steel for the columns. For this design the pad is continuous with beam foundation. The continuous beam foundation may be required to bridge over weak pockets in the soil or to prevent excessive differential settlement between adjacent columns.

The advantages of these foundations are, ease of excavation, any formwork required can be fabricated and assembled in longer lengths and there is more continuity and ease of access for concreting the foundation.For the preliminary design of the pad foundation with continuous beams, it must be sufficiently large so that it can prevent any over-turning moments generated from the cantilever structure. This overturning moment was calculated using wind and earthquake loads and the total weight of the structure as well as the foundation size to produce a Factor of Safety. From the wind and earthquake analysis the base shear generated was more than the total wind loads.

Therefore the Mrot or acting moments due to earthquakes = 43189.2 KNMres (restoring moment due to weight of structure) = 81999.6 KN

Factor of Safety against over-turning = 43189.2 / 81999.6

= 1.9 > 1.5Since this is greater than 1.5 the Design for over-turning is Safe. The length of the foundation must be larger than the top most floor of the control tower. Each column in the external shaft will rest on a pad foundation. The internal columns will also each rest on a pad in the centre of the external shaft. On each side of the external shaft an extra metres of pad foundations will be added on. Each pad is inter connected with ground beams with the beams connecting to the centre of each footing. This foundation arrangement for the control tower can be seen in Figure...... below.

Figure........ showing layout of pad and continuous beam foundation.Dimensions of pad footing:Dead load of tower = 13223.0 KN

Assume a weight of footing = 130.0 KN

Total dead Load = 13353.0 KN

Live Load = 443.5 KN

Design Axial Load (N) = 13353.0 + 443.5

= 13796.5 KN

Load per column on outer shaft = 13796.5 /8

= 1724.56 KN

Bearing capacity of soil = 2 x N x 10N is the SPT value, average SPT value at depth of 1, 2 and 3m = 17 blowsPlan Area of pad footing = 1724.56 / 340 = 5.0m 2Length of footing = 2.25mHence provide a 2.25 m square base.

Depth of footing assumed to be 600 mm thick = 0.6 m

Size of Reinforced Beam connecting to footing = 1500 x 600 mm In order to compensate for over-turning extra footings will be added on to reach a total length of 12m.

The footing will be 1 metre deep to the column footing. Concrete blocks will be placed along the continuous beams or backfill can be used followed by hard core, then sand blinding. Over this layer of sand blinding, polythene will be placed, then a layer of BRC. Over this the ground floor slab will be placed.

From the calculations done, it was observed that the footings will be closely spaced and for this preliminary design it will be more economical to use a raft foundation of size 12 x 12 m.

Figure ...... showing section of footing and fillFinishes The cab of the control tower will be fitted with double glazed laminated glass. This type of glass is structurally sound since it is a composite high performance product which combines the material properties of the glass with the unique properties of PVB such as adhesion to glass, elasticity and impact resistance. When broken it will still remain integral due to the plastic between the glass, remaining safe even when broken. The thickness of the glass is 6.4mm thick which is widely used giving a Class B performance to BS 6206:1981.The ceilings of the cab will be fitted with acoustic ceiling tiles for aesthetic purposes. The floors will be tiled and walls painted. The exterior walls will be groove pointed as well as painted. Double doors will be used at the base of the shaft as well as throughout the shaft windows will be placed to allow for natural lighting. Finally around the first floor of the cab, a metal balcony will be placed so as to provide ease of access to glass panels in the VCR when they need to be cleaned.Structural materials used in the Control Tower Reinforced concreteConcrete is strong in compression but very weak in tension therefore to compensate for this weakness tensile reinforcement will be applied to all concrete sections. For this material selection it is important to note the ease of construction and costs play a critical role since it is less expensive than structural steel.

Some key advantages of reinforced concrete are:

High compressive strength

Economical material for below grade structures

Low maintenance required

Good fire and water resistance

Inexpensive labour requiring less skilled workers for placing and mixing of concrete

Disadvantages of reinforced concrete

Lower strength to volume ratio than steel

Composite material complexities

Lower strength per unit weight compared to steel

Bulky structural member requiring lager foundations

High Tensile Steel High tensile steel will be used as reinforcement for each concrete section of the structure. Sizes range from 16-20 diameter bars as well as 10mm diameter bars for stirrups. The steel provides tensile reinforcement so as to prevent cracking and defections.Masonry Concrete versus clay blocks

Concrete blocks have higher compressive strength than clay blocks

Concrete blocks have lower water absorption rates than clay blocks

Clay blocks react more with a humid environment, that is, they tend to swell.Ferro-cement

This a thin composite made with a cement based mortar matrix reinforced with closely spaced layers of relatively smaller diameter mesh (Antoine E. Naaman 2000). The basic parameters which characterise ferrocement are the specific sruface area of reinforcement, the volume fraction of the reinforcement, the surface cover of the mortar over the reinforcement and the relatively high quality of the mortar. Ferrocement behaves like reinforced concrete in its load bearing characterisitcs, with the essential difference being that crack development is retarded by the dispersion of the reinforcement in fine form throughout the mortar. Advantages of ferrocement:

Low weight compared to RCC Cheaper in construction

Less thermal conductivity as compared to RCC

Long lifetime in comparison to steel structures

Ease of construction

Disadvantages

Labour intensive

References Websites

1. 9th International Symposium on Ferrocement, Bali 2009-01

http://ferro9.unila.ac.id./latest/about-ferrocement.html (Accessed 10, 01, 2009)

2. Raft Foundation Solutions

www.raftsolutions.co.za(Accessed 15,01,2009)

3. Earthquake Resistant Design

http://www.Richardpclarke.tripod.com(Accessed 10,01,2009)

4. Advantages and disadvantages of moment resisting frames

http://www.scholar.google.com/scholar?q=advantages+disadvantages+of+momnet+resisting+frames(Accessed 19,01,2009)

BOOKS

5. Reinforced Concrete Designers Handbook , Tenth Edition Charles E Reynolds and James C Steedman - Chapter 20, Design of Beams and Slabs.6. Design of Structural Elements Concrete, steelwork, masonry and timber design to British Standards and Eurocodes Chanakya Arya Page 76, design of pad footing.

7. Structural Design -Extracts from British Standards for Students of Structural design- 5th Edition BSI.

Proposal for Alternative 1: Reinforced Concrete Control TowerDesign Philosophy for Control TowerThe design of the control tower takes into account two primary considerations which are elegance and structural stability. The control tower in any airport should be able to carry out its functions while at the same time be attractive. In this conceptual design the tower was created from a number of different ideas all bearing in mind simplicity and dynamic performance. The tower was designed to be able to withstand earthquake and wind loading as well the foundation was designed to prevent overturning of the tall structure. With dynamic performance taken care of, the group was left to make the tower aesthetically pleasing. The domed shape roof of the structure provides beauty as well as an air of elegance to the high rise building.

The cab was designed with a total 3600 view port fitted with glass facades which amplifies the appearance of the cab. The shaft of the tower being structurally stable will be painted and groove pointed with glass windows present on each side of the shaft per floor. This gives the tower a sophisticated finish as well as it lends to natural lighting of the shaft. The design keeps true to the wishes of the client since it is distinctive, highly sculpted as well as it represents an iconic landmark. W3

W2

W1

W4

W0

Footing 2.25 x 2.25m 3m

Continuous beam 1500 x600mm

backfill

Hardcore

Sand blinding

Polythene

BRC

4 inch thick Floor Slab

SOIL