Upload
anand-dudheliya
View
262
Download
3
Embed Size (px)
Citation preview
8/20/2019 Distillation Column Control Design
1/22
Strategy
for
Distillation-Column
Control
i chemical plants and petroleum refineries, there
are, today,
many distillation
columns that
are
working well. There are also many others tha t are not working
well,
and
at least a few that function very poorly, or not a t all.
Failure
to obtain
performance specified by the column design engineer is due, in many cases,
to
faulty or inadequate control system design. Troubleshooting of columns that
are already in operation is frequently necessary, but practical considerations
usually
limit
corrective measures to relatively minor items. Proper original
design is by far the best way to guarantee satisfactory operation and control.
Therefore, in this book we will approach the design of integrated distillation-
column control systems as a systems problem in process design. The application
of feedforward, feedback, and protective controls wdl be coordinated with the
sizing and proper location of process holdups
to
achieve both automatic start-
up and shutdown and smooth, noninteracting control of column product
compositions.
1
.i DISTILLATION CONTROL OBJECTIVES
The starring point of any design project is a definition of objectives. For
distillation there are many possible approaches, but the one chosen here is one
the authors have found broadly
useful
in virtually
all
kinds of processes.’ It
has three main facets: 1)material-balance control, (2) product quality control,
and
3)
satisfaction of constraints.
As
applied specifically
to
distillation columns,
this philosophy suggests the following:
1. Material-balance control”
This term is sometimes used by others”
to
mean a control system in which reflux is
set
by reflux drum level control, and distillatelfeedratio is set manually
o r
by a com position (temperature)
controller. The authors of this book have been unable to find any special merit for this scheme
except for some high reflux ratio
columns.
8/20/2019 Distillation Column Control Design
2/22
4 StrMeD
J -
Dthdktim-Column Control
-The column control system must
cause
the average
sum
of the product
streams
to be
exactly equal
to
the average feed rate.
Harbed4
has called
this requirement that of keeping the column
in
“balance.”
-The resulting adjustments in process flows must
be
smooth and gradual
to
avoid upsetting either the column or downstream process equipment
fed by the column.
--Column holdup and overhead and
bottoms
inventories should
be
maintained between maximum and
minimum
l i mts
It is important
to
note that the material-balance controls on any
given column must be consistent with the material-balance controls on
adjacent process equipment. In most cases material balance will
be
con-
trolled by so-called “averaging” liquid-level or pressure controls.
2.
Product quality control
The control system for a binary distillation in most cases must:
-Maintain the concentration of one component
in
either the overhead
or bottoms at a specified value.
-Maintain the composition at the other end of the column as close as
possible
to
a desired composition.
t
It
is
usually true
that
minimum
operating cost
is
achieved when the
products are controlled at
minimum
acceptable purities.
This is
so
because
the
relationship between thermodynamic work of separation and purity
is nonlinear.” For some columns compositions
are
allowed
to
vary at
one end, and sometimes both ends, to satisfjr cert in economic constraints.
Both material-balance and composition controls must function sat-
isfactorily
in the
face
of
possible disturbances
in:
-Feed flow rate
-Feed composition
-Feed thermal condition
-Steam supply pressure
--Coohg-water supply temperature
--Cooling-water header pressure
-Ambient temperature, such
as
that caused by rainstorms
3. Satisfaction of constraints
For
safe,
satisfactory operation of the column, certain constraints
must be observed. For example:
-The column shall not
flood.
--Column pressure drop should be high enough to maintain effective
column operation, that
is
to
prevent serious
weeping
or dumping.
t
For
multicomponent columns subjected
to
feed composition changes, it is not
possible
to
hold exactly constant the compositions
at
both ends of the column;
the
composition at one end
must change
a little.
If feed variations are in the nonkey components, composition may
vary
somewhat at
both
ends of
the
column.With only two drawoffs, we can conml two keys, but
not the nonkey components.
8/20/2019 Distillation Column Control Design
3/22
1
I
Distillutk
Control O&jem’ves
5
-The temperature difference in the reboiler should not exceed the
critical temperature difference.
--Column feed rate should not be
so
high as to overload reboiler or
condenser heat-transfer capacity.
-Boilup should not be
so
high that an increase will cause
a
decrease
in product purity at the top of the column.
--Column pressure should not exceed a maximum permissible value.
There are, in addition, several other facets of column control.
Startup and Shutdown
Column controls should facilitate startup and shutdown and, by implication,
Transitions
When it is desired to change product compositions, the column controls
should facilitate doing
so.
This is particularly important when feed stock com-
position varies widely and it is desired to optimize column o r train operation,
as, for example, with a computer.
Heat Recovery
Increasingly there is an interest in recovering as much heat as possible. The
petroleum industry has frequently used the sensible heat in a column bottom
product to preheat column feed. Recently more ambitious schemes have been
employed in which the reboiler for one column is used as tha condenser for
another. Such schemes magnify control problems and sometimes limit process
turndown.
Testing
There should be enough instrumentation so that testing may be carried out
Miscellaneous
In addition to the above, column control should be designed with human
engineering in mind. For example:
-The operator‘s work station, whether a cathode ray tubekeyboard console
or a panelboard with gages, switches, recorders, and so on, should be carefully
designed according to human engineering principles for easy
use.
-The controls should be
so
designed as to require minimum maintenance.
The need for frequent or critical “tuning” should be avoided. The hardware
should be designed and arranged for convenient access and quick repair or
replacement.
-The control system design engineer should use the simplest possible
design procedures, not only to hold design costs down, but also so that the
work can be readily discussed with other design and plant personnel. This will
facilitate, at a later date, any necessary minor redesign a t the plant site. Failure
should make it easy to achieve total reflux operation when desired.
for tray efficiency, heat and material balances, flooding, and so on.
8/20/2019 Distillation Column Control Design
4/22
6 tratemfw
Didhttim-Column
Control
of design and plant personnel
to
achieve a mutual understanding of design
objectives, concepts, and methods is one of the frequent causes of unsatisfactory
plant operation.
1.2 ARRANGEMENTS FOR MATERIAL-BALANCE CONTROL
As
shown elsewhere,’ the size and location of
tanks
and the concept of
overall material-balance control used
can
have a great influence on plant investment
and process control. If the design engineer
uses
the concept of
control
in
the
directwn opposite t o w tanks
may
be
smaller and plant fned investment and
working capital can be lower than if
umtroZ in the directwn
es used. The
meaning of these expressions is illustrated, for simple tanks with level controllers,
in
Figures 1.1 and
1.2.
For the last tank in a series (final product storage), the demand flow is
always the shipments to a customer. As shown by Figures 1 . 3 and 1.4, the
choice in control strategy is between adjusting the flow into the last tank (control
in direction opposite to flow) or adjusting flow into the first process step
(control
in
direction of flow). In the first case, we can easily
use
simple automatic
controls.
In
the second case,
it
is more common to have an operator make the
adjustment.
When more than one tank
is
involved, other advantages of control in the
direction opposite
to
flow
are
(1)
less difficulty with stability problems, and
(2) reduced internal turndown requirements. “Turndown,”
as
used here, is the
ratio of maximum required flow rare to minimum required flow rate. In this
instance the meaning is that, in response
to
a given change in demand flow,
the required change in the manipulated flows will be smaller in one case than
in the other.
Once
the
basic concept of material-balance control
has
been selected for a
process, one must apply the same concept to
all
process steps. It is for this
reason
t h a t
the first step in designing column controls is
to
determine the
material-balance control arrangement. Control in the direction of flow is the
most commonly used concept (although the least desirable), and a frequently
encountered arrangement is shown on Figure 1.5. Here level in the condensate
receiver (also commonly called reflux
dr um
or accumulator)
sets
the top product,
or distillate flow, while the level in the base of the column sets the bottom
product flow; in other columns base level sets steam or other heat-transfer
media
to
the reboiler, in which case the condensate receiver level
sets top
product flow.
Generally speaking the direction of material-balance control is determined
by the demand stream. In recycle systems we may find some material-balance
controls in the direction of flow while others are in the direction opposite
to
Material-balance control, in the direction opposite to flow, can lead
to
many
interesting level-control and flow-ratio options.
These are
discussed in derail
in Chapter 6 .
8/20/2019 Distillation Column Control Design
5/22
1 2 A w a q m ~
m
M a t d - B a l a n c e
Control 7
FIGURE 1.1
Material balance control in direction opposite
to
flow
FIGURE 1 2
Material
balance
control in direction of
flow
8/20/2019 Distillation Column Control Design
6/22
3
G
c
Q
c
sa
a
c a
U
C
E
L
2
m
k
@
?
E
a
3
2
c
C
sB
W
E
8/20/2019 Distillation Column Control Design
7/22
C
Q
3
L
3
C
8
2
8
z
E
3
m
C
I
-
c
.
3
8
8
-
c
m
m
-
?
E
z
=
3
o
i
U
8/20/2019 Distillation Column Control Design
8/22
10
Strategy for
Dljtillatwn-Column Control
FIGURE 1.5
Distillation column with material balance control in direction
of
flow
8/20/2019 Distillation Column Control Design
9/22
1.3
Funahmentnls ofComposition Control 11
1.3
F U N D M E N T L S O F C O M P O S IT IO N C O N TR O L
Let us consider briefly what must be done to
a
column to keep terminal
compositions constant on
a
steady-state basis when the column is subjected
to
sustained changes in feed flow rate or feed composition. Methods of handling
other disturbances will be discussed later.
To simpl@ the analysis, let us limit
our
attention to an ideal, binary distillation.
This is somewhat restrictive, although the results will be applicable in
a
general
way
to
multicomponent systems, particularly those that may be treated as quasi-
b&ary or pseudobinary systems.
As will
be
shown in Chapter
2,
if feed composition and feed thermal
condition are constant, then we want the “operating lines” on
a
McCabe-
Thiele diagram to remain constant when feed flow changes. The operating lines
(defined in the next chapter) will not change as long as the distillate-to-feed,
reflux-to feed, boilup-to-feed, and bottom-product-to-feed ratios
are
held constant.
Practically speaking one may hold
all
four ratios constant by fixing anv one of
the three pairs: (1) the reflux-to-feed ratio and
the
boilup-to-feed
ratio,
(2)
the reflux-to-feed ratio and
the
bottom-product-to-feed ratio, and
(3)
the boilup-to-feed ratio and the distillate-to-feed ratio. In considering case
( 1 ) ,
for example, we see tha t if the rectification section vapor-to-feed ratio is
fixed (and it will be if the boilup-to-feed ratio is fixed) and the reflux-to-feed
ratio is fixed, then the distillate-to-feed ratio will be fixed, since the distillate
flow is the difference between the reflux flow
and
the vapor flow. Similarly,
the bottom-product-to-feed ratio will be fixed, since the bottom product flow
is the difference between
the
stripping section liquid and the boilup.
If feed rate and feed composition are not constant, Rippin and Lamb’ have
shown that, for small perturbations, one should change the boilup and reflux
according to the following equations:
A V = K ~ A z F
KfzAF
ALR
=
Kf3AzF
Kf4A.F
where
V = vapor flow from the reboiler
LR = internal reflux flow at
the
top of the column
The A’s represent departures from average operating conditions. The constants
KO
Kf4
may be calculated approximately by the column designer. Luyben6
has shown that it is necessary to be quite careful in designing feedforward
compensation for feed composition changes, particularly when the column is
not making a sharp separation.
Visualization of column operation,
in
terms of reflux-to-feed and boilup-
to-feed ratios, was suggested by Uitti7 and has since been proposed in varying
degrees bv many others. Throughout the rest of this book, it will be used as
the primar). basis for column composition control.
8/20/2019 Distillation Column Control Design
10/22
12
StrateBy
fmDirtillatMn Column Control
It should be noted, however, that this feedforward approach
to
column
control has a particular limitation: In general one cannot calculate the constants
Kfl -.
Kf4
with great accuracy. For columns that are not operating
too
close
to either upper dr lower h i t s of capacity, small changes in feed rate, and
consequent changes in boilup and reflux, will not change tray efficiency appreciably.
The terms Kf nd
Kf4
therefore will be constants. If the feed composition
changes are not too large (as will usually be the case), then Kflnd Kf3 ay
also be treated as constants. To determine the control accuracy obtainable by
this approach, one should make the necessary calculations or tests for each
individual column. Where really close control is required, one must supplement
feedforward control with measurement of the column terminal compositions
and subsequent feedback control,
a t
least
a t
one end of the column. The usual
philosophy will be to
use
feedforward for fast, approximate control and feedback
for long-term, accurate control of composition.
It should be noted,
too,
that feedforward from feed composition may not
be needed if the feed comes from
a
process step with discharge composition
control. Feedfonvard compensation for other process variables, such as bottom
product or distillate demand flow, is discussed in Chapter
6.
As will be shown later (Chapters 5 and 20), a properly designed column
feed system can play
a
very important role in filtering out hsturbances in feed
rate, feed composition, and feed enthalpy, thereby making composition control
much easier.
1.4
COMPENSATION FOR VARIOUS DISTURBANCES
Feed Thermal Condition
Feed should enter the column with a constant enthalpy. When significant
changes are anticipated, a heat exchanger and feed-enthalpy control system
should be provided. This is discussed in more detail in Chapters
5
and
11.
Steam
Supply
Pressure
Changes here can cause changes in boiling rate. The best preventive is a
steam-to-feed ratio control system combined with temperature and pressure
compensation of steam flow. A high pressure drop across the steam valve favors
smooth control but velocity-limiting trim may be required
to
minimize noise
and plug and seat wear. A high pressure drop is also undesirable for energy
conservation. If the pressure drop is high enough, sonic flow through
the
valve
results, and reboiler steam-side pressure has no effect on flow rate. The design
should avoid having sonic flow corresponding to low feed rates and nonsonic
flow corresponding
to
high feed rates, since required controller gain changes
make tuning v ry difficult.
8/20/2019 Distillation Column Control Design
11/22
1.5
Startup and Shutdown 13
Cooling-Water Supply Temperature
Cmling-water temperature
changes
are
usually
seasonal, and will require
n o specific correction.
If, for
some reason,
they are
large
and rapid, then it
may
be
desirable
to
provide an enthalpy control system for the condenser.
By
measuring the temperature rise of the cooling water across the condenser, and
multiplying
i t
by
the
cooling-water flow rate, one has a measure of the heat
transferred, 4.. This calculated value of qc can
serve
as the measured variable
in an enthalpy control system. For column pressure control, the enthalpy control
system can serve as the secondary loop in a cascade system.
Cooling-Water Header Pressure
One
of
the best ways
to
make a flow system immune
to
pressure changes
is
to
provide a high system pressure drop. This, however, is costlv. Another
way, which should be satisfactory for some distillation columns, is to
use
a
cooling-water flow control system. It does, however, have limitations, which
will be discussed later.
Ambient Temperature
If the column, auxiliaries, and piping are properly insulated, and if the
column is properly controlled, ambient changes should cause little difficulty
unless
the condenser is of
the
air-cooled type. In this event it may be desirable
to
use an internal reflux computer, discussed in Chapter 11. If, as is often the
case, the vapor piping from the top of the column to the condenser is both
uninsulated and long, ambient temperature changes mav cause fluctuations in
pressure and the rate of condensation.
1.5
STARTUP AND SHUTDOWN
Startup and shutdown are often dismissed as relatively unimportant, since
they happen
so
seldom that
i t
is not economical to spend much time and monev
on improvements. This may be true in a petroleum refinery where shutdowns
may occur at intervals of two or three years. In the chemical industry, however,
where process equipment is often plagued by severe corrosion or by plugging
process materials, startups and shutdowns are far more common- perhaps
monthly, weekly, or even daily. Further, elaborate heat and material recycle
schemes may require inmcate startup/shutdown procedures as part of the original
design. To put it another way, columns and their control systems may have
to be designed specifically
to
accommodate
a
particular startup/shutdown
procedure.
Columns are commonly started up in
total
reflux-no product is taken off
at top or bottom. Limited experience, however, suggests that faster and smoother
8/20/2019 Distillation Column Control Design
12/22
14
Stratgy for Dtddhtkfi-Cul~mnuntrui
startups may be achieved by recycling top and bottom products back to feed
during part of the startup sequence.
Startup/shutdown will be discussed in more detail in Chapter 9.
1.6
CONTROL SYSTEM DESIGN PHILOSOPHY
Current
Design
Practices
In
the
preface we noted that we would try, in this book,
to
present
a
multivariable control approach to distillation column control. Before discussing
this, however, let
US
look a t typical controls in existing plants.
There is a traditional pattern of what is called “instrumentation” in the
chemical and petroleum industries based on single-loop control (sometimes
called SISO-single input, single output). Each process operation has a number
of independent or single loops for feedback control of temperatures, pressures,
flows, liquid levels, and sometimes compositions. The term “single loop” means
there is one measurement, one controller, and one final control element, usually
a
valve. Many, but not all, of these loops are represented in the central control
room (CCR)
by control stations.
The controllers usually have neither antireset windup nor automatic tracking,
and there is little or no logic circuitry
to
tie the many loops together. This
statement is true for both analog
and
some digital hardware. As a consequence
the operators must perform startup operations with the control stations switched
to “manual,” and must implement process logic by switching in and out of
automatic.” Since the original design procedures are usually qualitative and
intuitive, with heavy emphasis on conformity to past practices, it is not surprising
that some loops never work in “automatic.” Others, although stable in “automatic,”
are
so
sluggish that they are ineffective in dealing with typical ‘disturbances.
For newer plants with higher throughputs, operation closer to hard constraints,
smaller and fewer holdups, energy-recovery systems, and elaborate material-
recycle systems, the traditional “instrumentation” approach to control is often
seriously inadequate.
For some years now, progress in single-loop design has been essentially at
a standstill.
As
recently as 1950, process control was hardware limited. Since
then primary measuring elements, controllers, computing devices, control stations,
and control valves have improved greatly in reliability, sensitivity, and speed
of response. Consequently these characteristics
less
and less frequently pose
limitations
to
the single-loop designer. Further,
the
quality
of
control achieved
by single-loop systems is not greatly affected by type of hardware; it makes
little difference, for a given algorithm, whether one uses analog pneumatic or
electronic gear, microprocessor controls, or
a
digital computer.* In addition,
Digital computers and microprocessor controls, however, usually offer a wider range of
controller parameter adjustments and facilitate the design of control systems more sophisticated
than most of those discussed in this
book.
8/20/2019 Distillation Column Control Design
13/22
1 6
Control System Des
Philosop@
15
optimized tuning procedures for unaided feedback controllers have limited
practical value for continuous processes; they yield results that are far inferior
to
those obtainable with well-damped feedback controls with simple feedforward
and override control.*
For plants being designed today (late 1983), it is increasingly common
to
use
microprocessor controls instead of analog
see
discussion under “Hardware
Conventions and Considerations”).
Multivariable Control
To avoid the limitations of single-loop design and to provide a more flexible
and sophisticated process operating logic than can be implemented by human
operators, we use an approach we call multivariable control.’ Many definitions
of this term may be found in the literature, but most of them are expressed
in mathematical terms rather than
in
terms of process hctions. For our purposes
we define a multivariable control svstem as one that has the built-in intelligence
to look simultaneously at two or more process variables and to choose, in a
given situation, the best of several preprogrammed strategies (algorithms) for
manipulating one or more control valves (or other final control elements).
For example, the steam valve for a distillation column reboiler, depending
on circumstances, may respond to controllers for:
Steam flow rate
Column
AP
Column pressure
Base temperature
Column feed rate
Column base level
Column bottom-product rate
The seven variables listed may also
exert
control on five or
six
other valves.
To
provide automatic control of this sort, we make extensive use of “variable
configuration” controls that
are
usually implemented by overrides.
I f
for instance,
base composition is normally controlled by steam flow that can be taken over
or overriden by high column AP, this is a variable configuration. If base level
control is normally achieved bv a PI controller that can be overridden by high
or low base level proportion&-only controls, we call that “variable structure.”
Multivariable control may involve both variable configuration and variable
structure
controls. Hardware permits us
to
automate this kind of control with a speed,
precision, and reliabilinr that are completely beyond the capabilities of human
operators.
It is common to think of process control fimctions stacked one above another
in
a pyramid or hierarchic arrangement as with traditional business or military
organization structures, particularly when computers are involved. Multivariable
control structures, however, with their extensive lateral and diagonal crossovers,
are functionally more like the modern “matrix” concept of management. From
8/20/2019 Distillation Column Control Design
14/22
16 Strategy
fm
Distillation-Column
Control
a control engineering standpoint, the shorter lines of communication
and
de-
centralized control functions permit more rapid and stable control, and more
reliable, troublefree operation.
By now it is probably apparent tha t we are striving for control system
designs whose performance and design parameters are specified in advance of
plant startup. In practice we furnish calibration data for controller parameters
and computational devices for the majority of control loops prior
to
startup.
We calculate these from simulations or simple linear models. For microprocessor
computer controls, we calculate scaling parameters for computation blocks
(either in software or hardware). Our design procedures are accurate enough
that only a modest amount of empirical controller tuning is required at startup.
Stability Speed
of
Response, and Interactions
Most existing literature on automatic control is concerned with the stability
and speed of response of single loops. The traditional objectives of feedback
control system design are:
1.
To
get
the
fastest possible response to set point changes.
2.
To
compensate for or
to
attenuate disturbances as much and as quickly
as possible. These must be accomplished with a reasonable degree of closed-
loop stability.”
In process control the objectives are often quite different. The objectives
of averaging level control, for example, clearly are different from those just
mentioned. A typical chemical
plant
o r refinery has hundreds of single loops
with many interactions among them. It is usually far more important to design
for
a
dynamic balance among these loops with
a
minimum of interaction than
to
strive for maximum speed of response. Further, it
is
usually undesirable
to
make rapid changes in manipulated variables since these may upset the process.
For example, distillation column reflux flow and boilup should not be changed
too rapidly since these might cause transient flooding or weeping in part of
the column. Our preferred philosophy of controller tuning is discussed in a
book’ and a paper.”
There are five simple methods by which to make a system noninteracting:
1. Design material-balance control loops
to
be at least a factor of 10 slower
than related composition control loops. Similarly, in cascade systems, make the
secondary or slave loop at least a factor of
10
faster than the master loop.
2
Avoid designs
that
are intrinsically interacting,
such
as pressure control
and
flow control at the same point in a pipeline. One of the two controllers
must be detuned.
3.
Select process designs that eliminate or minimize interaction. For example,
Some processes are open-loop unstable,
which
means that controls must be added and
must
be
kept in “automatic” for stable operation.
8/20/2019 Distillation Column Control Design
15/22
1 6 ontrol
System
Des@
Philosqphy
17
if a tubular reactor is fed at several points along its length from a common
header, flow-rate interactions may be reduced to an arbitrary level by providing
a very high pressure drop across each feed valve in comparison with the reactor
pressure drop.
4
Use
override circuits. Although not specifically intended for this purpose,
override circuits, by permitting only one controller at
a
time to control a given
valve, eliminate interactions.
5. Use interaction compensators (decouplers). If two control loops, such
as top and bottom temperature controls on
a
distillation column, interact, we
can eliminate the interactions by installing
two
compensators. One compensates
for the action of the top temperature controller on the bottom loop while the
other compensates for the action of the bottom temperature control loop on
the top one. This is discussed in Chapter 20.
In
addition, there are some very sophisticated mathematical methods for
dealing with
interaction^.^^,^^ ^^
Some are intended for noninteracting design
while others seek a design that provides an optimum amount of interaction.
Hardware Conventions and Considerations*
For control loops represented in
the
CCR (central control room), it is
normal practice (as mentioned earlier)
to
furnish “control stations.” These may
be analog pneumatic, analog electronic, or microprocessor based. In the last
case, the station may be physically distinct, like an analog station, or may be
represented on
a
CRT display as a “faceplate.” Each provides an indication
of
the process variable (flows, level, temperature, etc.), the desired value (set point),
and the valve loading signal (controller output, really). There is also a “manual-
automatic” switch, which some vendors label “hand-automatic.” In the “manual”
mode, the feedback controller is disconnected and there is a knob that enables
the operator remotely
to
set the valve position. This may or may not be subject
to
restrictions imposed bv feedforward compensation, overrides, and
so
on,
depending on the design philosophy for a particular project.
If
cascade control is involved, as, for example, liquid level control cascaded
to flow control, the secondary station not only has manual-automatic switching,
but
also
another fUnction-“remote-locaI.”
In
the “remote” position, the secondary
controller set point comes from the output of the primary controller. In the
c‘loca”’ position, valve position may be set manually or the controller set point
may be set by the operator (c‘local-auto”).Although cascade functions are
sometimes combined into one station (or CRT “faceplate”) for space and
money-saving reasons, we recommend dual stations. Most single-station designs
with which we are familiar are very inflexible and complicated; they do not
permit ready implementation of feedforward, overrides, and
so
forth.
Much
of this
section may seem superfluous
to
instrument and
plant
personnel.Our experience
however with process design engineers column designers and so
for& is
that this discussion
may be very helpfid.
8/20/2019 Distillation Column Control Design
16/22
18 Strategyfm Dirtillation-Column Control
As of this writing (late 1983),the two biggest hardware needs appear to
1.
Better measurements, especially of compositions.
2.
Better control valves. With regard to these, more progress has been made
in
the design of valve bodies and trim than in the design of actuators. Valve
positioners should always be used (it is assumed in this book that they will
be)
. Piston actuators with double-acting, two-stage positionersare recommended.
As far as CCR hardware is concerned, we have
a
decided preference for
microprocessor controls. They
are
technically more versatile and
are
less expensive
(some versions) than analog. As of late 1983, many are featuring satisfactory
antireset windup and override capabilities. In adchion, they provide more
advanced logic capability, dead-time simulation, and adaptive tuning. Some of
the last named achieve self-tuning via stochastic techniques or by pattern rec-
ognition. Others have gain scheduling, where reset time and proportional gain
are functions of some process variable or the controller error signal.
Microprocessor controls usually have a sampling time of a fraction of a
second. Although slightly slower than analog controls, their performance can
generdy be approximated by analog control algorithms.
Other advantages include freedom from drift, and the fact that they can be
calibrated more precisely, can be reconfigured or restructured without wiring
changes, have a larger range of tuning parameters, and contain more control
algorithms.
For most projects today, it is possible
to
find worthwhile applications for
a
supervisory digital computer with
a
good data historian, regardless of the
type
of basic controls selected (pneumatic, electronic, or microprocessor). Digital
readouts for important variables are worthwhile because they permit seeing
their magnitudes with sensitivity approaching that of the original analog mea-
surements. Most typical analog measurements have a sensitivity ranging from
one part per 1000 to one part per
10,000.
Most analog readout devices,
however, are limited to
0.5-2
percent.
For maximum advantage a supervisory computer should be programmed
to have the control algorithms discussed in Chapter 12. These are position
rather than velocity algorithms.
It
is our opinion that using such
a
computer
to imitate unenhanced two nd three-mode analog controls is poor practice.
Some worthwhile applications for computers will be discussed later.
Computer consoles were originally provided in the
CCR
for the convenience
of
the
operators. Sometimesa consolidated console is also provided for production
supervision. Engineers’ consoles, perhaps
at
another location, facilitate technical
studies. Separate consoles for maintenance personnel
(the
computer can be a
powerful maintenance tool) are highly desirable.
Most control valves today are either single-seated global types
or
rotary types.
For both
there are substantial, coercive stem forces when the valves are in flowing streams. Positioners
compensate
for
this and maintain the valve’s inherent flow characteristic expressed as a function
of
controller output signal.
It
should be noted, however, that some users prefer not
to
use
positioners.
be:
8/20/2019 Distillation Column Control Design
17/22
1.8 Column Des@ Philosophy
and
Control System Des@ 19
PROCEDURE FOR OVERALL CONTROL SYSTEM DESIGN
We now have enough information to suggest a sequence of design steps
to follow that will lead to a quantitative definition of column and hardware
performance.
1. After careful discussion with the process engineer and column designer,
and after careful review of the overall process flow sheet, prepare a simplified
flow sheet that defines the control concepts:
a. Select the overall material-balance control scheme first, preferably
proceeding from final product inventory
to
raw material inventory.
ll
individual equipment-piece material-balance controls must be consistent
with this scheme.
b. Select composition control schemes.
c. Add feedforward and interaction compensators as required.
d. Add protective controls and automatic startup/shutdown circuits.
e .
Add miscellaneous temperature and pressure controls.
2. Prepare material-balance and composition-control signal flow diagrams.
3. Determine holdup volumes required for smooth material-balance control
4.With holdups determined calculate column-composition transfer
functions.
5. Select measurement spans and calculate control valve sizes.
6 .
Calculate feedforward and interaction compensators.
7. Calculate
all
other overrides.
8. Calculate feedback-controller gain and reset settings and control-loop
natural frequencies. Check feed-tank material balance and mixing time constants
for adequacy.
9. Use simulation for some columns, particularly those in critical service
or with a new untested control system
o r
process configuration. Simulation of
the column and its control system will be usefd in confirming control concepts
and controller tuning parameters.
It
may also save startup time.
Hardware vendors may now be selected and the measurement and control
equipment may be ordered.
Part
I1
of this book deals with the qualitative and heuristic aspects of steps
1 and
3.
Quantitative information for the other steps is presented in Part 111.
1 7
and for liquid-level override controls at each end of the column.
1.8
COLUMN DESIGN
PHILOSOPHY
AND CONTROL SYSTEM DESIGN
Experience on many projects shows that even small, simple columns benefit
from a modest application of feedforward compensation and overrides. This is
due to the trend toward increasinglv tight column design. The number of trays
is held down because smaller allowan&
are
made for uncertainty in tray efficiency.
Column diameter and tray spacing are now kept
to
smaller values, with the
8/20/2019 Distillation Column Control Design
18/22
2 StrategyfmDljtillatwn-Column Control
result that columns typically operate closer to flooding. The combined effect
of these design policies is to make columns much touchier and harder to control.
Experience indicates that typical incremental instrument investment over
that required for unenhanced feedback controls is
5-10
percent (large projects
tend toward the lower figure). This incremental investment not only provides
better normal control, but it also helps
to
avoid inadvertent shutdowns.
It
is,
therefore, our opinion that these controls should be used
to
some extent on
almost every column.
Suppose, however, that the customer insists on minimum application of
feedback controls with
no
feedfonvard compensation or overrides. What column
design philosophy should be followed?Having had considerable adverse experience
with columns with primitive controls, particularly sidestream drawoff columns,
and columns with heat recovery schemes, we suggest the following:
1. Design for normal operation
a t
60 percent of the rate for flooding.*
2.
Provide five extra trays or increase the number of trays by
10
percent,
3.
Provide increased tray spacing.
4.
Provide larger condensers. If water cooled,
use
tempered water.
5.
Provide larger reboilers (lower heat flux).
6.
Control column
Al’
by boilup, or
flow
control steam.
7.
Provide
100
percent reserve capacity in heat-recovery schemes or avoid
8.
Avoid sidestream drawoff designs.
9. Provide surge tanks between columns with at least 30-60 minutes of
whichever is larger.
them altogether.
holdup each.
1 9
EXISTING COLUMNS-TYPICAL PRACTICES
AN D TROUBLESHOOTING
Although
ths
book deals primarily with &stillation control in design projects,
it is pertinent to consider briefly the controls of typical, existing columns, the
opportunities for their improvement, and how to troubleshoot them when
necessary. Frequently encountered problems include unstable or ineffective con-
trols, off-specification product or products, and f l d g r dumping. In addition,
it is fairly common practice to use excessive boilup and reflux to make sure of
meeting
or exceeding product specifications. This not only wastes energy; it
also reduces column capacity.
To
provide
a
perspective
on
energy savings, one
may note that
100
Ibm/hr of steam is
worth $3200
per year (basis
$4.00/1000
pounds, 8000 hours per year). To save this amount of steam would probably
be only a modest accomplishment for most columns.
If composition control of each product stream is desired (and this is
usually
In some companies
columns
are designed by
the
probabilistic methods recommended
by
Fractionation Research, Incorporated.
8/20/2019 Distillation Column Control Design
19/22
1
IO Cunventwns Followed
in thlj
Book 21
the
case), the most obvious deficiency of most exisring columns is the lack of
appropriate composition measurements. Most commonly temperature in the
upper or lower section of the column (or both) is used
in
lieu of true composition
measurements. Frequently composition control is attempted at only one end
of the column, and sometimes
at
neither end.
Another shortcoming frequently observed is the use of fixed flow controls
for steam, reflux, or product drawoff. Any such unaided flow control should
be regarded with suspicion. With rare exceptions flow-control set points must
be changed to accomplish either composition control or material balance control.
In view of the preceding comments about problem areas and likely op-
portunities for improvement of composition control and reduction in energy
consumption, the following guidelines are suggested:
1.
Make sure that column material-balance controls are properly designed
and tuned, and that hardware, especially level and flow transmitters and control
valves,
is in
good working condition. If
PI
level controllers are’used, follow
the
tuning procedures of Chapter 16; auto overrides or nonlinear controllers
should be used.
It
is usually desirable
to
cascade level control to flow control,
in which case flow measurement should be linear.
2.
Provide averaging level control of column feed. Column feed rate should
also be held between maximum and minimum limits.
3.
Provide a linear flow measurement for steam flow control.
Also
provide
temperature and pressure compensation.
4. If condenser controls are
a
problem, review the control schemes in
Chapter
3.
5.
At this point with flows established, smoothed, and in some cases limited,
it will probably be possible to see some improvement in composition control,
at least for part of the time. For further improvement provide steam-to-feed
ratio control, internal reflux-to-feed or distillate-to-feed ratio control, high
A P
override on steam to protect against flooding, and a minimum steam flow
ltmiter
to
protect against dumping.
6.
If composition is measured and
is
cascade controlled via reflux or boilup,
or both, ratio controls should be replaced by impulse feedforward compensation
see Chapter 12) if feed flow turndown is greater than 2:
1.
7.
For pressurized or vacuum columns, make sure an adequate scheme is
provided for maintaining an inert balance.
8. If temperature
by
itself is not an adequate measure of composition,
consider one of the schemes in Chapter 10 for using temperature, pressure,
and,
in some cases,
flow
measurements
to
deduce compositions.
.
1
I
CONVENTIONS FOLLOWED IN THIS
BOOK
Throughout the remainder of this book, we will frequently illustrate control
schemes with pneumatic components. This is done for convenience. Pneumatics,
8/20/2019 Distillation Column Control Design
20/22
22
Strategy
fm
Dirtillation Column Control
with few exceptions, features a standard signal span of 3- 15psig. LL pneumatic
controllers, as far as we know, can achieve antireset windup by the same external
reset feedback method. This appears
to
be the most universally usell method
(we use it extensively), and has been adopted by one manufacturer of analog
electronic instruments and by several vendors of microprocessor-based distributed
controls. Other vendors of electronic analog and digital controls feature a wide
variety of techniques; some of these work fairly well, while some are quite
inflexible. A brief discussion is presented in Chapter 12.
Units used
in this
book are those commonly employed in chemical engineering:
pounds, feet, degrees Celsius, mols, and
so
on. To facilitate the calculation of
control engineers’ “time constants,” we have mostly used time units of minutes
or seconds [e.g., Ibm/sec, Ibm/min, (pcu/sec>/”C fi’]. For projects that make
partial
use
of metric or SI units,
we
found it convenient
to
convert them
to
the above units. Generally speaking, we have found no advantage in writing
equations with SI units. Instead, in programs for computers or programmable
calculators, we mostly write the equations in the older units and add subroutines
for going back and forth to metric or SI units.
The most common type of controller used in the chemical and petroleum
industries
was
once called “proportional plus automatic reset,” later shortened
to
“proportional reset.” Today it is more common to
use
“PI,” which stands
for proportional-integral. It is also becoming common today to speak of iontroller
gain rather than proportional band
(PB
=
100/Kc).
We
will also
use
“reset
time,” usually in minutes, rather than its older reciprocal, “repeats per minute.”
For drawings in which we are trying to present a perspective of control
concepts (configurations), we
use
very simplified symbols. In drawings where
we are trying to illustrate concepts of structure (overrides, feedfonvard, etc.),
we use a more detailed symbolism that we have found useful in our design
work.
In pneumatics it is c o m o n to refer to most signal-conditioning devices
other than controllers as “relays.” Included are adders, subtractors, multipliers,
and
so
on. For electronic analog and digital controls, it is more common to
use terms such as signal
scalers
and mult@lien.
A table of nomenclature and symbols will be found at the end of this book.
1 .I I LITERATURE
For anyone seriously interested in distillation control, two books are highly
recommended. The first is an easy-to-read, nontheoretic (as far as control is
concerned) work by F. G. Shinskey.” The treatment of energy conservation
alone
is
worth the price of the book. The second book is by Rademaker,
Rijnsdorp, and Maarleveld.12It relies heavily on conventional, single-loop control
theory, and explores painstalungly a large number of possible control systems.
It also contains an extensive bibliography.
8/20/2019 Distillation Column Control Design
21/22
Refevences 3
For basic reference books on distillation, we have made much use of those
Treybal,l6
and
Hengstebeck”
y Van Winkle13 and King.14Others by
also have been
useful.
one by Harriott,” and one bv Murri11.28 For more advanced treatments, we
suggest texts by Koppel,20 Douglas,21 and Gould.22 The last contains some
perceptive comments about
the
difficulties of applving advanced control t heo ry
developed by electrical and mechanical engineers to chemical processes. Recent
books bv Rav”3 and by S te phanopol~ us~~iscuss applications of “modern control
theor .” ’in chemical processes. M c A v o ~ ~as addressed the specific subject of
interaction analysis.
Nonchemical engineers with no background in distillation may find an
introductonr text
bi
Nisenfeld and Seemann
useful.24
t is clearly written and
easv to read.
For basic books on control, we recommend two written by the
1. Buckley,
P.
S., Techniques of Process
Control, Wiley, New York, 1964.
2. Harbert, W. D., Pet. R$27(4): 106-
109
(1948).
3. Harbert, W. D.,
Pet.
Ref 29(10): 117-
122 (1950).
4.Harbert, W. D., Pet. Ref 35(11): 151-
159 (1956).
5. R~ppin,D. W.
T.,
and D. E. Lamb,
“A Theoretical Study of the Dy-
namics and Control of Binan Dis-
tillation Columns,” Bulletin from
the Universitv of Delaware,
1960.
6.
Luyben, W. L., Chem. End.
P q .
61(8): 74-78 (1965).
7. Uitti, K. D., ISA Paper no. 49-9-2.
8. Buckle?,
P.
S., “Override Controls on
a Chemical Reactor,” in Proceedings
of Texas A M Instrumentation
Symposium, Jan. 1970.
9. Buckley,
P. S. ,
“Multivariable Control
in
the Process Industries,” presented
at Purdue University, Apr. 1975.
10. Buckley, P.
S.,
“A
Modem
Perspective
on Controller Tuning,” presented
at Texas A M University, Jan. 17,
1973.
11. Shinskey, F. G., DljtiLLatwn Control,
McGraw-Hill, New York, 1977.
12. Rademaker, O., J.
E.
Rijnsdorp, and
REFERENCES
A. Maarleveld, DynamicJ and Control
of Continuous Distillation Units, El-
sevier, New York, 1975.
13.
Van
Winkle, M.,
DG-tilhim,
McGraw-
Hill. New York, 1967.
14. King, C. J., Separation Processes,
McGraw-Hdl, New York, 1971.
15. Holland, C.
D.,
Fundamentals and
Modelling of Separation Processes,
Prentice-Hall, Englewood Cliffs,
N.J., 1975.
15A. Holland, C. D., and A.
I.
Liapis,
Computer Methodr fm Soltin8 Dy-
u
eparmim
P r o b h
McGraw-
Hill, New York, 1983.
16. Trevbal, R.
E.,
Mms-Tran er Opera-
twns, McGraw-Hill, New York,
1968.
17. Hengstebeck, R. J., Distillation, Rein-
hold, New York,
1961.
18.
Luyben, W.
L.,
ProcessMod.ellin8,Sim-
ulation, and Control f i Chemical
Enginem, McGraw-Hdl, New York,
1973.
19. Harriott,
P.,
Process Control,McGraw-
Hill, New York, 1964.
20. Koppel, L. B., Introduction to Control
T b e o q . . . Prentice-Hd, Engle-
wood Cliffs, N.J., 1968.
21. Douglas, J. M., Process Dynamics and
8/20/2019 Distillation Column Control Design
22/22
24 Stratgy
fm
Dirtillation-Column Control
Control ( 2vols. , Prentice-Hall, En-
glewood Cliffs, N.J., 1972.
22. Gould, L. A., Chemical Process Control,
Addson-Wesley, Reading, Mass.,
1969.
23. Ray,
W.
H.,Advanced Process Control,
McGraw-Hd,
New York, 1981.
24. Nisenfeld, E. I., and R. C. Seemann,
Dictdlation Columns, ISA, Research
Triangle Park, N.C., 1981.
25. Buckley,
P.
S., Materral Balance Control
in Recycle Systems INTECH, May
1974, pp 29-34.
26. McAvoy,
T.,
InteractwnAnalysir In-
strument Society of America,
1983.
27. Stephanopolous,
G.,
Chemical Process
Control, Prentice-Hall, Englewood
Cliffs, N.J., 1983.
28. Murrill,
P.
W., Fundumntals Process
Control Theory, Instrument Society
of America, 1981.