Design of Wall Footing

Embed Size (px)

Citation preview

  • 8/10/2019 Design of Wall Footing

    1/16

    Wall Thickness, t 300.00 mm

    Height of Soil above the footing, hs 740.00 mm

    Thickness of the Footing, hc 477.50 mm

    Concrete Cover 75.00 mm

    Diameter of Main Reinforcements 25.00 mmEccentricity of Lateral Loads, e 300.00 mm

    Effective depth of the Footing, d 390.00 mm

    Depth of Embedment, D 1,217.50 mm

    For Wall Footings Applied with C

    DESIGN O

    DESI

  • 8/10/2019 Design of Wall Footing

    2/16

    mm

    Effective Soil Pressure, qe 176.70 kPaRequired Width of Footing, B 2,200.00 mm

    From the Actual Soil Pressure Diagram

    Minimum Actual Soil Pressure, qumin 240.00 kPa

    Maximum Actual Soil Pressure, qumax 240.00 kPa

    Actual Soil Pressure @ Critical Section, qu1 240.00 kPa

    Actual Soil Pressure at the Face of Wall, qu2 240.00 kPa

    Check for One-Way Shear / Beam-Action Failure

    Shear Capacity, Vn 263.12 kN/m

    Actual Shear @ Critical Section, Vu1 134.40 kN/m

    FOOTING THICKNESS ADEQUACYREMARKS

    Adequate

    FOOTING DIMENSION DETERMINATIONWidth of Footing, B

    2,200.00

  • 8/10/2019 Design of Wall Footing

    3/16

  • 8/10/2019 Design of Wall Footing

    4/16

    Thickness of Wall, t

    Depth of Embedment, D

    Thickness of Footing, hcWidth of Footing, B

    Transverse Reinforcements 25.00

    Longitudinal Reniforcements 7 25.00

    Dowels 25.00

    REINFORCEMENTS

    D

    DIMENSIONS

  • 8/10/2019 Design of Wall Footing

    5/16

    DESIGN REFERENCE

    I II III IV V

    Dead Load, PDL 200.00

    Live Load, PLL 180.00

    Wind Load, PWL 0.00

    Eathquake Load, PEQ 0.00

    380.00

    I II III IV V

    Dead Load, HDL 0.00

    Live Load, HLL 0.00

    Wind Load, HWL 0.00

    Eathquake Load, HEQ 0.00

    0.00

    I II III IV V

    Dead Load, MDL 0.00

    Live Load, MLL 0.00

    Wind Load, MWL 0.00

    Eathquake Load, MEQ 0.00

    0.00

    Type of Concrete

    Compressive Strength of Footing, fc' 28.00 Mpa = 0.85

    Compressive Strength of Wall, fc' 28.00 Mpa = 0.85

    Yield Strength of Main Reinforcements 280.00 Mpa = 0.0020

    Allowable Soil Pressure, qa 200.00 kPaSurcharge, q 0.00 kPa

    Unit Weight of Concrete, c 24.00 kN/m3

    Unit Weight of Soil, s 16.00 kN/m3

    Strength Reduction Factors,

    a. Tension-contolled Sections 0.90

    b. Shear & Torsion 0.75

    c. Bearing 0.65

    oncentric Loads, Lateral Loads & Moments

    WALL FOOTING

    Moments, M (kN-m/m)

    Type of Loads LoadLoad Combination

    Mu

    0.00 0.00 0.00 0.00 0.00

    Pu

    Concentric Loads, P (kN/m)

    Total Pa

    Total Ha

    Hu

    Load

    Load

    0.00

    Lateral Loads, H (kN/m)

    Type of Loads

    0.00

    Load Combination

    Total Ma

    GN CRITERIA

    0.00 0.00

    Normal-Weight Concrete

    0.00

    280.00 528.00 420.00 420.00 0.00 528.00

    0.00 0.00

    NSCP 2010

    Load CombinationType of Loads

  • 8/10/2019 Design of Wall Footing

    6/16

    Modification Factor, 1.00

    Spacing of Bars 350.00

    No. of Long Bars 7

    From the Actual Soil Pressure Diagram

    Actual Moment @ Critical Section, Mu 108.30 kN-m

    Coeffiecient of Resistance, Ru 0.79 Mpa

    Required Steel Ratio, req 0.0029

    Minimum Steel Ratio Requirements

    Approach

    Minimum Steel Ratio, min 0.0020

    Remarks Use req 0.0029

    Area of Steel @ Transverse Direction 1,372.39 mm2

    Actual Spacing 357.67 mm

    Actual Clear Spacing 332.67 mm

    Provided Spacing 350.00 mm

    Spacing Requirements

    Maximum Spacing, Smax 450.00 mm

    3hc 1,432.50 mm

    450 mm 450.00 mm

    Conservative

    For the Transverse Reinforcements

    FLEXURAL REINFORCEMENTS

  • 8/10/2019 Design of Wall Footing

    7/16

    Remarks, Use S 350.00 mm

    Minimum Clear Spacing, Smin 25.40 mm

    db 25.00 mm

    4/3(Max. Aggregate) 25.40 mm

    25mm 25.00 mm

    Remarks, Use S 350.00 mm

    Spacing, S 350.00 mm

    Required No. of Longitudinal Bars 7.00 pcs

    Spacing, S 350.00 mm

    Wall

    Footing

    Development for Tension (Transverse Bars)

    Coating of BarsFactors,

    t 1.30

    e 1.00

    s 1.00

    Checking of Factors

    t e 1.30

    Required t e 1.30

    Cb 87.50 mm

    Distance from the nearest concrete surface 87.50 mm

    Half of Spacing, S 175.00 mm

    Minimum Development Length (ld) 300.00 mm

    Basic Development Length (ldb) 446.69 mm

    Development Length (ld) 437.11 mm

    Actual Development Length (ld) 875.00 mm

    Remarks

    Development for Compression (Dowels)

    At Wall

    Minimum Basic Development Length (ldb) 200.00 mm

    Basic Development Length (ldb) 317.49 mm

    (0.24fydb)/(fc') 317.49 mm

    0.043dbfy 301.00 mm

    Development Length (ld) 873.19 mm

    Remarks

    At Footing

    Basic Development Length (ldb) 317.49 mm

    DEVELOPMENT LENGTH

    Uncoated or Galvanized

    Adequate

    Adequate

    For the Longitudinal Reinforcements

    Adequate

    Adequate

  • 8/10/2019 Design of Wall Footing

    8/16

    (0.24fydb)/(fc') 317.49 mm

    0.043dbfy 30.10 mm

    Development Length (ld) 873.19 mm

    Actual Development Length (ld) 352.50 mm

    Remarks

    If Bending of Bars are Considered

    Bend Diameter 150.00 mmActual Splice 465.32 mm

    Maximum Length of Bend 950.00 mm

    Remarks

    mm

    mm

    mmmm

    mm dia. @ 350.00 mm

    mm dia. @ 350.00 mm

    mm dia. @ 900.00 mm

    300.00

    1,217.50

    477.502,200.00

    ETAILING

    Adequate

    Inadequate: Increase hc or Requires Bending

  • 8/10/2019 Design of Wall Footing

    9/16

  • 8/10/2019 Design of Wall Footing

    10/16

    mm

    pcs

  • 8/10/2019 Design of Wall Footing

    11/16

  • 8/10/2019 Design of Wall Footing

    12/16

  • 8/10/2019 Design of Wall Footing

    13/16

  • 8/10/2019 Design of Wall Footing

    14/16

    - -

    1.00 0.75 0.85

    1.00 0.75 0.85

    Modification Factors

  • 8/10/2019 Design of Wall Footing

    15/16

    GENERAL NOTES

    1 Text in GREEN is the design input. This where you must type/input the values accordin

    2 Text in BLUE is the result of values you have typed/selected.

    3 Text in BLACK is for general instructions.

  • 8/10/2019 Design of Wall Footing

    16/16

    g to your design specifications