Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
DAC & VLF Voltage Sources Educational Session
May 26 2011
St Pete Beach, Fl
by
Henning Oetjen, Frank Petzold
HDW\
Group Company
Why do we need to talk about Voltage Sources ? (in context for field testing methods of underground power cables)
1. Suitable Voltage Sources are the prerequisite for any
type of field testing of Distribution and Transmission
type Underground Cables
2. Since DC test methods are in most situations not suitable
or permissible for testing Solid Dielectric Cables, AC Test
Methods using AC Voltage Sources are required
3
Termination
local issue Insulation
global issue
Joint
local issue
Insulation
local issue
VLF & DAC Voltage Sources are at the heart of
some of the most significant methods for
Cable Testing and Diagnostics
Selection of AC Voltage Sources
2 Criteria need to be addressed:
a. it is desirable for the AC source to generate 50/60Hz (Power
frequency range) Voltages, if the test methods requires to
replicate the same type of “effects” within the cable
insulation as are induced under operating frequency
b. AC Sources must be able to “produce” enough
power to charge not only “small” and “short” cables
(URD), but also “big” and “long” cables (Feeder, Network)
Problems associated with Selection
a. if 50/60 Hz are required, a substantial amount of
“reactive” power must be produced due to the capacitive
effect of the cable insulation (E= 1/2C x V2) [J] or [Wsec]
C = capacitance of cable in µF; V = test voltage[RMS]
b. ……worse, this reactive or “blind” power must be made
available 2 times in every cycle within a ¼ of a cycle
to raise the voltage from 0 to the desired test level
( ¼ cycle = 4 milli seconds for 60Hz!!)
c. ……even worse, this power must be also dissipated
2 times within ¼ cycle of every cycle
What are the Consequences of
E= 1/2C x V2 for 50/60 Hz?
In terms of
a. The rating of the power supply high
b. The weight and size of the power supply heavy / big
c. The capability to dissipate the energy “forced”
cooled Example Cable1 ,15kV Class, C= 0.5µF, Test voltage 25kV RMS
E = 156J or Wsec
P60Hz=40kW ( must have 40kW available every other 4 milli sec for
4 milli sec and must dissipate 40kW every other 4 milli sec
Cable2 , 35kV Class, C= 0.5µF, Test voltage 60kV RMS
E = 900J or Wsec
P60Hz =225kW(must have 225kW available every other
4 milli sec for 4 milli sec and must dissipate 225kW every 4 milli sec
E = Electrical Energy P = Electrical Power
Conclusions a. True 50/60Hz field tests of cables are to say the least for the
most part impracticle
b. Must develop AC method that requires less energy
Solutions a. Use a Very Low Frequency AC voltage VLF (0.1Hz)
b. Use a “resonant type” voltage source, which “conserves” most
of the energy and does not “dissipate” the energy
between pos. & neg. cycles
- const frequency –variable inductance
- const inductance – variable frequency,
const frequency means 50 or 60Hz,
variable frequency means power frequency range 20-300Hz (per IEC 62067, 650840)
c. Use a combination of VLF & Resonant Technologies
d. Use a combination of “Damped AC” & Resonant in a
“pulsed” application to limit the amount of energy to a few
cycles within the power frequency range
VLF Voltage Sources
2 Technologies available today
a. Sinusoidal 0.1Hz,
- makes use of the VLF technology to reduce “reactive” power
- most effective technology for small test capacitance @ fairly
modest test voltages
- only suitable wave shape to perform tan∂ measurements
- “Electrical Stress” dV/dt approx.600 x less compared to 60Hz
- Higher test capacitances are achieved by reducing the test
frequency from 0.1Hz to as low as 0.01Hz,
Caution: results not directly comparable between different frequencies!
Stress Level dV/dt very different & # of cycles different
Summary: - the only wave shape for VLF tan ∂ measurement,
- cost effective for smaller & lower voltage type cables
Time (seconds)
0 105
VLF Voltage Sources
a. Sinusoidal 0.1Hz,
State of the art Block Diagram according to
Time (seconds)
0 105
VLF Voltage Sources
sinusoidal 0.1Hz
Time (seconds)
0 105
All test voltage values in RMS!
The Growth Rate of Electrical trees depends on the Frequency
0
1
2
3
4
5
6
7
0 0.5 1 1.5 2 2.5 3
V / V 0
0.1
Hz d
issip
ati
on
fa
cto
r
Dissipation Factor tan ∂
of New and Serviced aged XLPE Cables
VLF Voltage Sources
b. Cosine rectangular 0.1Hz
Combination of VLF & Resonant Technologies
- produces equipment with high test capacitance at high voltages
(highest test capacitance 25µF @ 60kV RMS = 84kV Peak)
- only suitable wave shape to measure leakage current
(similar to DC test, due to 5 sec “plateau” phase )
- not suitable wave shape to perform tan∂ measurements
- “Electrical Stress” dV/dt approx. identical compared to 60Hz,
- Only feasible due to “energy saving resonant design”
(allows to provide the charging energy within a 2-12 milli second window)
Summary: - the only wave shape to measure leakage current
- cost effective to test larger and longer cables
- delivers the same “punch” as 60Hz dV/dt (withstand test)
T cosine shaped transition,
approx. 2 to 6 ms
Time (seconds)
0 105
T
VLF Voltage Sources
b. Cosine rectangular 0.1Hz, Block Diagram
T cosine shaped transition,
approx. 2 to 6 ms
Time (seconds)
0 105
T
13
Measurement of leakage current
approx. between 4 & 5 seconds
into the “Plateau Phase”
VLF Voltage Sources Specifics related to:
Cosine rectangular 0.1Hz
Relationship between Peak & RMS
between cos rect & sinusoidal
wave shape
T cosine shaped transition,
approx. 2 to 6 ms
Time (seconds)
0 105
T
VLF Voltage Sources Specifics related to:
Cosine rectangular 0.1Hz
T cosine shaped transition,
approx. 2 to 6 ms
Time (seconds)
0 105
T
The Initialization of Electrical Trees is a function of Frequency & Peak Voltage The Growth Rate of Electrical Trees is a function of the Frequency & Energy
DAC Voltage Source (Damped AC )
Combination of Resonant and Pulse Technologies
- DAC based field test equipment capable of High Test Capacitance @ HV
(highest test capacitance 13µF @ 350kV Peak)
- DAC wave shape to allow PD testing within power frequency range (20-300Hz)
- DAC wave shape simultaneously displays PDIV and PDEV
- DAC wave shape visualizes & estimates Dielectric Losses (tan ∂)
- DAC represents very low “risk” of cable due to short HV pulse exposure
Summary:
cost effective method to PD test larger, longer & higher voltage cables
16
Block Diagram DAC (Damped AC) Technology
DAC Voltage Source
DAC Voltage Source Specific performance characteristics
PDIV
can be detected simultaneously, because of
“pulse” application = non continuous power
PDEV
Dielectric Losses = tan∂ can be calculated
from attenuation of wave shape,
Δ indicated by “funnel”
0
Q /pC
PDEV PDIV
Ground noise level
U
U
Typical Hysteresis Effect of PD PDEV < PDIV
DAC Voltage Source
Comparison of basic PD Test parameters between
“continuous” & “pulsed” AC Voltage
Specific performance characteristics