SCOPE Introduction
Current requirements
Changes
Conclusion
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
3/38
Introduction
Presentation will be in 2 parts: Skygarden then hotel
Terminology - Hotel and sky garden
OL refers to Occupant Load
Background of the review
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
4/38
- Sky garden based on 1.5 m2/ person
- QP needs to apply waiver to use higher
occupancy load factors
Current Requirements (Sky Garden)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
5/38
Types of structure at sky garden- Landscape
floor level landscape (with or without fencing)
raised landscape landscape with pebbles/stones
- Decorative features, eg statute/fountain
If roof top only
for
maintenance
purpose thenneed not
calculate OL
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
6/38
-Shallow pool / small drain / water features
-Tables/chairs
-Raised platform as seat
-playground/gym
-Jogging track
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
7/38
Type of use No Yes Remark
Purpose I Private roof
garden/terraceof residential
unit
Purpose II Roof garden /terrace belong
to a residential
unit
Common skygarden/roof
terrace
accessible to
residents &
guests
OL factorto base on
1.5 m2/
person
Calculation of Occupant Load
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
8/38
Type of use No Yes Remark
Purpose
III - VIII
Roof access
for
maintenance
only
Roof garden/roof
terrace
accessible to
other members of
public or to staff inthe building.
Occupant
load factor
to base on
1.5
m2/person
Calculation of Occupant Load
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
9/38
Planter boxes used for reducingOL calculation
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
10/38
Depth of planter box below
finished floor level
Occupant load
factor
< 300mm To base on 1.5 m2/
person
< 300 < 500mm (with full ofshrubs and trees)
Need not calculate OL
< 300 < 500mm (without full of
shrubs and trees)
To base on 3.0 m2/
person
Ht < 500mm (need not be
covered with trees/shrubs but
must be without access)
Do not need to
calculate occupant
load
Sunken Planter Box
(Permanent / fixed structure)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
11/38
Depth of planter box
below finished floor level
Occupant load
factor
< 300mm To base on 1.5 m2/
person
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
12/38
Habitable
Planter box not covered with trees/shrubs
Depth of planter box
below finished floor level
Occupant load
factor
< 300 < 500mm (with full of
shrubs and trees)
Need not calculate
OL
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
13/38
Depth of planter box
below finished floor level
Occupant load
factor
> 500mm (with or withoutshrubs and Trees
Need not calculateOL
> 500mm high
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
14/38
Height of planter box
above floor finished level
Occupant load
factor
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
15/38
Height of planter boxabove floor finished level
Occupant loadfactor
300 mm < Ht < 500mm
(planter box not coveredwith trees/shrubs)
To base on 1.5 m2/
person
Planter Box (Permanent/fixed structure)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
16/38
Height of planter box
above floor finished level
Occupant load
factor
Ht > 500mm (need not be
covered with trees/shrubs
but must be withoutaccess)
Do not need to
calculate occupant
load
Planter Box (Permanent/fixed structure)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
17/38
Not habitable
Raised planting bed with trees or shrubs between
300mm and 500mm and width of planter box not
exceeding 3m
300mm
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
18/38
>500
Raised Planter box above 500mm-must be without steps
Note: Roof level without public access (for
maintenance only) can be exempted from occupant
load calculation
Walkway
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
19/38
Unacceptable features to be considered as
Non-simultaneous Occupancy
Using cabinet or Movable container
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
20/38
Depth/height of water
feature
Occupant load factor
Less than 300mm To base on 3 m2/ person
Depth > 300mm Do not need to calculate
occupant load
Sunken/Elevated Water Feature
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
21/38
Pond - Need not calculate
OL
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
22/38
300mm
The surface area need to
allocate 3 m2/ person if any
depth exceeded 300mm
deep
Cross section of pool
Walk way
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
23/38
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
24/38
Water
features
APPLY 3 m2/ person
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
25/38
Jogging Track / foot path
(width
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
26/38
< 3 m wide 3m 2/person,
otherwise 1.5m2/person
Playground
5m2/person
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
27/38
5m
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
28/38
1.5 m2/
person
Running track
Running track
Open space
3 m2/ person
3 m2/ person
Playground
5m2/
person
3m
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
29/38
Note: QP is to submit plan
for approval if there is A/Aworks to the roof
terrace/roof garden orwhen it is affecting OL
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
30/38
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
31/38
Background
Current Requirements 4 to a room
Service apartment: 15 m2/person
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
32/38
a. Hotel/Budget Hotel
- Bedroom: will base on 15 m2/ person
(based on gross area of a room)
- Suite: to base on 15 m2/ person a room(i.e. include all areas such as living area,
toilets, etc)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
33/38
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
34/38
b. Backpacker hotel where room(s) are shared
by guests:
- To base on 3 m2/ person, subject to
max 20 pax per room (i.e. area of 60 m2)
- To base on the gross area of the unit
(i.e. includes toilets, living room,
etc)
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
35/38
For circular on Hotel and skygarden you may refer to
CORENET FSSD circular
dated 2 June 2011 and 1
August 2011, respectively.
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
36/38
Conclusion
We will continue to listen to thefeedback from the industry and fine
tune our fire safety requirements to
achieve a safe and secure
Singapore.
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
37/38
Thank you
7/27/2019 Cpt Yam OL for Hotel Roof Gdn Roof Terrace Sky Terrace
38/38
Question asked during seminar
My hotel needsd FC every year because it exceeded 200 persons. If I
apply the new calculation then I need not apply FC anymore, how
should I go about in getting exemption?
There is no exemption unless a plan submission is resubmitted and
the building has to comply with the current requirement. The
calculation shall be basing on each room not basing on the whole floorarea i.e. refers to slide 33 showing the hotel flr plan, each room shall
have the its respective area to divide by the OL factor, this includes all
usage like toilet, and with any decimal place it shall be brought forward
to the next nearest number, from there sum up every individual room
to obtain the total floor OL. Also, pls note that a minimum of 2 personsper room shall apply if the OL for each room is less than 2.