    APPLICATION

    CASE STUDY

    Regd.Office & Factory: E-6, GIDC, Electronics Zone, Gandhinagar - 382 028, Gujarat (India)

    Phone : 079-23289101, 23289102, 23289103 Fax : 079-23289111 Gram : AXPERT E-Mail :[email protected]

    AMTECHDOC.NO. : AMTCS-35

    TITLE : I.D. FAN Page : 01 of 01

    HOST ORGANISATION : GRASIM INDUSTRIES, NAGDA, M.P

    PERFORMED BY : AMTECH ELECTRONICS (I) LTD.

    INDUSTRY : GRASIM POWER-HOUSE

    APPLICATION : I.D. FAN

    MOTOR DATA : 3 PHASE AC INDUCTION MOTOR

    RATING = 90KW / 125HP RPM = 742

    CURRENT = 192 Amp. VOLT = 415V, 3 PHASE.

    PREVIOUS SYSTEM : In 40 Mw power plant for maintaing 103-105 T/hr. (Tonns / Hour) steam pressure, twoboilers are used. Each having two I.D. Fan with 90 kw motor along with damper valves& IGP operated from Remote station.

    PROBLEM OBSERVED : 1. Very high starting current kick. ( About 5 to 6 times of full load current )

    2. Regular maintenance for damper valves & IGP valves.3. Steam loss due to damper & IGP valves leakages.

    PRESENT SYSTEM : Right row same steam pressure is obtain with fully opened damper valve & IGP. Andworking with three I.D. Fan (Two in boiler-1 & only one in boiler-2) with speed controtechnique through AXPERT AC Variable frequency drive control from remote station.

    SYSTEM BLOCK DIAGRAM

    :

    ADVANTAGES OF NEW SYSTEMS :

    (1) Energy saving (2) Soft-start action, limits starting current kick.

    (3) Free from mechanical maintaince of damper valves & IGP valves. (4) Inbuilt protection feature take care of motor.

    (5) Accurate steam pressure control, beacuse of fine speed control

    through AXPERT AC VFD.

    ECONOMIC ANALYSIS :

    Previous System = ID1 80 KW/h (DOL) ID1 80 KW/h (DOL)KW consumption ID2 80 KW/h (DOL) ID2 80 KW/h (DOL)

    160 KW/H IN BOILER - 1 160 KW/H IN BOILER - 2Total KW consumption = 320 KW/h

    With Axpert VFD = ID1 80 KW/h (DOL) ID1 50 KW/h ( Axpert)KW consumption ID2 50 KW/h (Axpert) ID2 OFF (DOL)

    130 KW/h 50 KW/hTotal KW consumption = 180 KW/h

    FD1

    FD2

    PA Fan-1

    PA Fan-2

    ID2 Fan-2

    ID1 Fan-1

    (DOL) 250KW

    (DOL) 250KW

    (DOL) 120KW

    (DOL) 120KW

    90KW

    (DOL) 90KW

    HT Motor

    75KWAxpert VFD

    BOILER - 1100 T/hr.

    FD1

    FD2

    PA Fan-1

    PA Fan-2

    ID2 Fan-2

    ID1 Fan-1

    250KW (DOL)

    250KW (DOL)

    120KW (DOL)

    120KW (DOL)

    90KW

    90KW (DOL) OFF

    HT Motor

    75KWAxpert VFD

    BOILER - 2100 T/hr.

    COMMONSTEAM HADDEN

    40 MWTurbine set

    105 Tonn/hour

    (steam pressure)

    NET POWER SAVING : 140KW / hr.

    MOTOR OPERATION : 7680 HRS / YEAR (Approx)

    ENERGY SAVING / YEAR : 10,75,200 KWH / YEAR

    TARIFF RATE RUPEES : 1.55 / UNIT (Minimum)

    ENERGY SAVING / MONTH : RS.1,38,880 / MONTH (Approx)

    ENERGY SAVING / YEAR : RS.16,66,560 / YEAR (Approx)

    PAYBACK PERIOD : 4 MONTHS

    +

    +