Conventional Catalogue

Embed Size (px)

Citation preview

  • 8/9/2019 Conventional Catalogue

    1/44

    ConventionalFire Alarm Systems

  • 8/9/2019 Conventional Catalogue

    2/44

    Contents

    Introduction 3-7

    Premier SX Conventional

    Fire Alarm Panel 8

    Premier Elite Conventional

    Fire Alarm Panel 9

    Premier Conventional Repeater Panel 10

    Premier M Plus 8-24 ZoneConventional Fire Alarm Panel 11

    Premier M Plus Repeater Panel 12

    Premier 48 M Plus 24-48 Zone

    Conventional Fire Alarm Panel 13

    Premier 48 M Plus Repeater Panel 14

    Premier MX ConventionalFire Alarm Panel 15

    Fyreye Extra Conventional

    Optical Smoke Detector 16

    Fyreye Extra Conventional Rate of

    Rise and Fixed Heat Detectors 17

    Fyreye Extra Conventional

    Opto-Heat Detector 18

    Fyreye Conventional

    Ultra-Violet Flame Detector 19

    Fyreye Conventional Detector Bases 20

    Zeta Remote LED Indicator 21

    Fyreye 50 & 100m Reective Beam

    Smoke Detector 22-23

    Fyreye 50 & 100m Auto-aligning Beam

    Smoke Detector Systems 50 & 100m 24-25

    Zeta UV/IR Optical Flame Detectors 26-27

    Zeta Conventional Manual Call Points 28

    Zeta Conventional

    Weatherproof Call Point 29

    Zeta Conventional Explosion Proof

    Manual Call Point 30

    Miditone ConventionalElectronic Sounder 31

    Miditone Conventional Combined

    Electronic Sounder & Flasher 32

    Securetone Conventional

    Electronic Sounder 33

    Secure Light Xenon Flasher 34

    Maxitone Conventional Sounder and

    Combined Sounder & Flasher 35

    Zeta Conventional Fire Alarm Bells 36

    Zeta Flame Proof Siren 37

    Zeta Flame Proof Gong Bell 38

    Zeta Magnetic Door Holders 39

    Zeta Duct Unit 40

    Premier Power Pack EN 54-4 Power

    Supply with LCD Screen 41

    Batteries 42

  • 8/9/2019 Conventional Catalogue

    3/44

    Introduction

    Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded

    in 1985 and is a privately held UK manufacturer of Fire Alarm, GasDetection and Emergency Systems.

    Our brand name is well known throughout the industry and is acclaimed in over forty

    countries worldwide. We are currently represented in the UK, Europe, Africa, theMiddle East, Southern Asia & South America and this list continues to grow.

    Complete System Supplier

    To meet the requirements of our ever-changing market,

    we pride ourselves on being a complete systemsupplier. This means our customers can rely on us for

    their entire system requirements.

    One of the main advantages of using a complete system

    supplier, compared with a component supplier, is that

    system wide compatibility is assured and there is one

    point of contact.

    Marketing our products as systems has played a vital

    role in our worldwide success.

    The Future

    Our continued inward investment and constant

    endeavour to offer the very best products is recognisedby our increased turnover and prot margin year-on-

    year. Our mission is to support our existing & future

    customers by providing them with the highest qualityproducts, at the most competitive prices.

    Customer Support & Product Warranty

    We value our customers greatly and to ensure they have

    the best experience we have a dedicated support team

    who are able to assist with sales, technical or logistical

    queries.

    Our products carry a full 24 month manufacturers’guarantee from the date of purchase. Our networkof authorised agents is fully trained on the use of our

    products and will provide a helpful & friendly service.

    Research & Development

    As with all electronic equipment there is an ever

    present drive to manufacture products that areincreasingly effective whilst becoming more cost

    sensitive. To meet this objective we spend a signicantpercentage of our prots on the continued development

    of products, whether it be introducing new items, or

    improving existing ones. We have a team of engineers &

    designers all of whom have vast industry knowledge &

    experience.

    As a manufacturer we always follow the market needs

    closely to evaluate how we should adapt our product

    range. This, combined with welcomed customer

    feedback, has proved to be a successful formula for

    meeting the current and future industry needs.

    Statement Of Quality Policy

    We maintain a Quality System, which conforms to BS EN

    ISO9001:2008. We are committed, where applicable,

    to manufacture in compliance with all appropriate

    legislation & regulatory requirements.

    3

  • 8/9/2019 Conventional Catalogue

    4/44

    Fire Detection &Alarm Systems BS5839

    Risk AssessmentThe ‘Fire precautions (Workplace) Regulations’ require

    any business employing ve or more persons to hold a

    written ‘Fire Risk Assessment’ and ‘Emergency Plan’.

    This must be periodically reviewed.

    The local re brigade can enforce compliance, and

    close any building that does not meet this act.

    In the event of a re in a building without a written

    ‘Fire Risk Assessment’, those responsible may face nes

    and imprisonment, and/or private litigation.

    What the law requires you to do:

     Complete a re risk assessment for your work

    place (considering all employees, the public,

    disabled people and people with special needs).

     Identify and record any signicant ndings or

    persons at risk.

     Provide and maintain re precautions.

     Provide information, instruction and training.

     Nominate persons responsible to implementyour emergency plan.

     Consult employees about the above nominations

    and your proposals to improve re precautions.

     Inform other employees who may have work

    places in the building about any signicant risks

    which may affect their safety and co-operate with

    them to reduce/control these risks.

     If you are not an employer, but control premises

    which contain more than one workplace, you are

    responsible for complying with re regulations.

     You must establish a suitable means of

    contacting the emergency services.

     Your employees must co-operate to ensure the

    workplace is safe from re and its effects.

    Introduction to FireAlarm Systems

    Fire alarm systems are used to detect are, and to signal a warning alarm to the

    appropriate source.

    In general, there are 3 types of system;

    1. Manual Fire Alarm Systems – which rely on manualcall points to signal an alarm

    2. Life Protection Fire Alarm Systems – these aredesigned to protect the occupants of a building

    3. Property Protection Fire Alarm Systems – theseare designed to protect buildings

    The warning may be simply ringing re alarm sirens,

    however if a building is likely to be unoccupied, it may

    be more appropriate to signal to a monitoring station,

    or at least send a message to the building owner via

    telephone.

  • 8/9/2019 Conventional Catalogue

    5/44

    If the total oor area is greater than300m2:

     The maximum area for a zone is 2000m2

     If a stairwell (or similar) extends beyond one oor itshould be a separate zone.

     If a zone covers more than one re compartmentthen the zone boundaries should follow thecompartment boundaries.

     The search distance within the zone in order toascertain the position of the re should not exceed60m. Remember that the use of Remote Indicatorlamps may help to reduce the distance travelled.

     If a building is divided between occupiers, zonesmust not be shared between them.

    System ZoningInformation

    60m Max.

    Manual Call PointsA ‘Manual Call Point’ is a device which enables

    personnel to raise an alarm in the event of a re

    incident by pressing a frangible element to activate the

    alarm system.

    Manual Call Points should be installed at a height of

    1.2m above oor level at easily accessible, conspicuous

    positions, on exit routes, at the entry oor landings of

    staircases and at all exits to the open air.

    Manual Call Points should be spaced so that one may

    always be found within a maximum distance of 45m

    apart or 25m for disabled person.

    1.2m - 1.4m

    45m Max. or25m Max. for disabled person

    The following guide lines should be observed:

     If the total oor area of the building is less

    than 300m2 then the building needs only one zone,

    regardless of the number of storeys.

    In order to aid identication of the source of a possible

    re, the protected building should be divided into

    ‘zones’. When deciding on a suitable zoning scheme

    for a building, consideration should be given to the

    size, any existing re routines, escape routes, zone

    accessibility, and structural re compartmentation.

    5

  • 8/9/2019 Conventional Catalogue

    6/44

    Detector Information

    Automatic Detectors

    When deciding on the type of detector to be used in any area it is important to remember that the detector has to

    discriminate between a genuine re and the normal conditions existing therein.

    Smoke Detectors

    In open spaces under at horizontal ceilings, every

    point should lie within 7.5m of a smoke detector.

    Smoke detection should be generally avoided in the

    following areas to avoid unwanted alarms. They shouldbe protected by means of other detectors such as heat

    detectors.

    Contamination in dusty areas may cause unwanted

    alarms and reduce the life of the detector.

    Damp or humid conditions such as showers, bathrooms

    and external areas should be avoided as the water

    vapour may cause unwanted alarms and reduce the life

    of the detector.

    Detectors should not be mounted where gases, vapours

    or fumes are present.

    Detectors should never be used at low temperature

    where ice or condensation can affect detector

    sensitivity.

    Kitchens, garages, welding shops and boiler houses

    should generally be avoided.

    5.3m

    10.6m

    112m²

    (10.6m x

    10.6m)

    7.5m

    Room

    boundary

    Heat Detectors General

    In open spaces under at horizontal ceilings, every

    point should lie within 5.3m of a heat detector.

    Heat detectors are designed to either detect a

    rapid rise in temperature or to operate at a xedtemperature. Although they provide a slower response

    time than smoke detectors they do provide a method of

    protection for areas where smoke detectors cannot be

    used.

    Heat detectors should not be used for the protection of

    life or where extensive property loss may be expected.

    ‘Rate of Rise’ Heat Detectors

    ‘Rate of Rise’ heat detectors respond to both rapid

    increases of temperature and to xed top temperature.

    ‘Fixed Temperature’ Heat Detectors

    Fixed temperature heat detectors are available with

    different temperature settings, and are normally

    installed in kitchens, boiler rooms, etc.

    3.8m

    7.5m

    56.3m²

    (7.5m x

    7.5m)

    5.3m

    Room

    boundary

  • 8/9/2019 Conventional Catalogue

    7/44

    Fire Alarm SoundersFire Alarm Sounders should be installed throughout the

    building with an even distribution, to generally provide

    a minimum sound level of 65dB(A) or 5dB(A) above any

    background noise which is likely to persist for more

    than 30 seconds.

    Where the alarm may have to arouse sleeping persons

    e.g. Hotel bedrooms, nursing homes, etc, a minimum

    sound level of 75dB(A) is required, at the bed head with

    all the doors shut.

    All re alarm sounders in a building should produce the

    same sound, distinct from any other audible warning

    devices in the building.

    Where re alarm sounders are required in extremely

    noisy areas e.g. Machine shops, it may be necessary to

    install additional ‘Visual Indication Beacons’.

    65dB(A)@ 500Hz - 1000Hz

    +5dB(A)@ 500Hz - 1000Hz

    Background noise

    75dB(A)

    Detection In Apex RoofsIf the ceiling is pitched or sloping, smoke will tend

    to rise towards the highest point (apex) of the roof,

    therefore detection should be placed in the apex. As

    the slope tends to reduce the delay before smoke or

    heat reaches the detectors, it is permissible to use a

    greater spacing between the detectors mounted there.

    Limits of Ceiling Height

    Small Apex= Standard Spacing

    Apex

    600mm

    SmokeDetector

    Large Apex= Extended Spacing

    Cabling

    The operation of a Fire Alarm and Detection

    System’ depends on the cabling and connections

    between the components. It is essential that

    connection between Manual Call Points and

    Detectors function correctly when they are

    operated.

    Cables within the system are required to functioncorrectly for signicant periods after being

    attacked by re. These include the power supply

    cables to the control panel, the detection circuits

    and the re alarm sounder circuits. Thus the

    cables chosen must be correctly rated to withstand

    these conditions.

    7

  • 8/9/2019 Conventional Catalogue

    8/44

    Premier SX Conventional Fire Alarm Panel(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)

    The Premier SX control panel range is available

    in 1, 2, 4, 6 and 8 zones, housed in a light grey

    ame retardant ULV0 enclosure, designed to

    meet modern architectural surroundings, with

    a removable hinged door.

    The Premier SX has been designed with ease of

    installation in mind, in addition to the robust electronic

    design expected from Zeta Alarm Systems.

    Model NPSX1 NPSX2 NPSX4 NPSX6 NPSX8

    Part No. 37-050 37-051 37-052 37-053 37-054

    Mains Voltage 230V AC +10% / -15% @ 50/60Hz

    System Voltage 24V DC (nominal)

    Zone Voltage 21V DC (nominal)Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)

    Fault Relay Output 1 x relay SELV @ 1A maximum

    Fire Relay Output 1 x relay SELV @ 1A maximum

    Zone Capacity 32 devices per zone

    Remote Sounder Activation Via N/O contact (class change)

    Sounder Activation Delay 0-9 minutes in 1 minute increments

    Zone End Of Line IN4002 Diode (cathode stripe to +)

    Sounder End Of Line 10K resistor

    Charger Voltage 28.4V @ 20°C (with battery disconnected)

    Zone Short Circuit Protection 100mACharger Short Circuit Protection Battery voltage less than 20V

    Enclosure Size 355 (l) x 275 (h) x 100 (d) mm

    Weight 3.25kg (excluding batteries)

    Features

     LPCB Approved to EN54 parts 2 & 4

     One man test facility

     Disablement facility for zones & sounders

     Space for up to 7Ahr batteries

     Sounder delay option (0 – 9 min) Panel can be ush mounted

    73mm 100mm

    Wall MountFlush Mount

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    9/44

    Premier Elite Conventional Fire Alarm Panel(PE1, PE2, PE4, PE6, PE8)

    The Premier Elite 1-8 zone re alarm

    panels are ideal for small to medium sized

    installations. They meet all the requirements

    of EN54 parts 2 & 4, and come in an

    attractively styled enclosure.

    The zonal output card gives a drive voltage to operate

    zonal alarm relays, or a hardwired repeater panel.

    Model PE1 PE2 PE4 PE6 PE8

    Part No. 37-040 37-041 37-042 37-043 37-044

    Detection Zones 1 2 4 6 8

    Mains Voltage 230V AC +10%/-15% @ 50/60Hz

    System Voltage 24V DC (nominal) 29V DC (nominal)

    Zone Voltage 22V DC (nominal)

    Sounder Alarm Output 2 x 400mA @ 24V DC (nominal)

    Fault Relay Output N/A 1 x relay SELV @ 1A maximum

    Fire Relay Output 1 x relay SELV @ 1A maximum

    Zone Capacity 20 Devices 32 Devices

    Remote Sounder Activation N/A Via N/O Contacts

    Sounder Activation Delay N/A 0-9 minutes in 1 minute increments

    Zone End Of Line 10K resistor IN4002 Diode (cathode stripe to +)

    Sounder End Of Line 10K resistor 10K resistor

    Charger Voltage 27.6V DC (No Batt Connected) 28.4V @ 25°C (No Battery Connected)

    Zone Short Circuit Protection N/A 100mA

    Charger Short Circuit Protection N/A Batteries less than 21V

    Operating Temperature 0°C to 50°C

    Enclosure Size 355 x 275 x 100mm

    Weight 2.5kg (excluding batteries) 3.25kg (excluding batteries)

    Features

     Fault relay (4, 6 & 8 zone only)

     Alarm relay

    Current limited charger to prevent at batteriesdrawing too much current (4, 6 & 8 zone only)

     Built in diode base compatibility (4, 6 & 8 zoneonly)

    Sounder delay facility (4, 6 & 8 zone only)

     Connection to optional add on zonal output card

    (4, 6 & 8 zone only)

     Zone disablement facility (4, 6 & 8 zone only)

     One man test facility (4, 6 & 8 zone only)

    73mm 100mm

    Wall MountFlush Mount

    9

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    10/44

    Premier Conventional Repeater Panel(PRE-REP)

    Model PRE-REP

    Part No. 37-045

    Supply Voltage 20–35V DCSupply Voltage 29V DC (nominal)

    Connections

    A+

    0V

    GA

    CF-

    TN-

    Z1- to Z8-

    Supply +VE

    Supply –VE

    General Alarm

    Common Fault

    Tone (Buzzer Active)

    Zonal Alarm

    Operating Temperature -0°C to 50°C

    Enclosure Size 355 x 275 x 100mm

    Weight 1kg

    The Premier Repeater panel is a hard-wired

    repeater panel for use with the Premier SX (all

    sizes), and the Premier Elite (4-8 zone) panels.

    It is display only (no controls) and indicates power,

    general fault, general re & the zone in alarm. It also

    has an internal buzzer to indicate that it requires

    attention.

    It comes supplied with an interface card to connect to

    the Premier SX and Premier Elite (4-8 zone) panels.

    Features

     Zonal indication for re

     Common fault indication

     Surface or semi ush xing

    73mm 100mm

    Wall MountFlush Mount

    0

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    11/44

    Premier M Plus 8-24 Zone Conventional FireAlarm Panel (PMP8, PMP16, PMP24)

    The Premier M Plus control panels are designed

    to full the requirements of EN54 parts 2 & 4

    as well as being easy to install, operate and

    maintain.

    Being of modular construction, the basic M Plus panel

    has 8 zone capacity, expandable to 16, 20 and 24 zones.

    The Premier M Plus is suitable for surface mounting or

    semi-ush tting (with just the door protruding).

    Model PMP8 PMP16 PMP24

    Part No. 37-020 37-022 37-024

    Detection Zones 8 16 24

    Mains Voltage 230V AC +10% / -15% @ 50/60 Hz

    System Voltage 24V DC (nominal)

    Zone Voltage 21V DC

    Sounder Alarm Output 4 x 150mA @ 24V DC

    Fault Relay Output 1 x relay SELV @ 1A maximum

    Fire Relay Output 1 x relay SELV @ 1A maximum

    Zone Capacity 32 Devices

    Remote Sounder Activation N/A

    Sounder Activation Delay 0 – 9 minutes in 1 minute increments

    Zone End Of Line IN4002 Diode

    Sounder End Of Line 10KΩ Resistor

    Charger Voltage 28.4V DC (batteries disconnected)

    Zone Short Circuit Protection 100mA

    Charger Short Circuit Protection Batteries less than 20V

    Charger Size 3.0 Amp

    Operating Temperature 0°C - 50°C

    Enclosure Size 485 x 477.5 x 125mm

    Features

     4 Common sounder circuits (150mA each)

     Optional add-on zonal sounder circuits (50mAMax.)

     Serial repeater output

     Auxiliary supply (29 Volts, 250mA)

     Zone & sounder disablement facility

     Sounder delay facility

     Zonal to common timer (when tted with zonalsounder boards)

     One man test mode

    11

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    12/44

    Premier M Plus Repeater Panel(PMP-REP, PMP-REP/M)

    Model PMP-REP PMP-REP/M

    Part No. 37-026 37-027

    Functions Display & control Control only

    Supply Voltage 20-30V DC

    Max. Quantity Per System 1 5

    Connections

    Serial Repeater A

    Serial Repeater B

    +24V DC

    0V

    Operating Temperature 0°C to 50°C

    Enclosure Size 375 x 335 x 125mm

    Weight TBC

    The Premier M Plus repeater is available in 2

    versions – standard & multiple.

    The standard repeater offers display & control

    functions, however it is limited to one per system.

    The second version allows multiple repeaters on the

    same system however they do not have any control

    functions (i.e. they cannot be used to silence or reset

    the system).

    A single repeater can be powered from the panels’

    auxiliary 24V supply. If more than one repeater is to be

    used, a separate 24V is required.

    2

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    13/44

    Premier 48 M Plus 24-48 Zone ConventionalFire Alarm Panel (PMP48/24, PMP48/32, PMP48/40, PMP48/48)

    The Premier 48 M Plus control panels are designed to

    full the requirements of EN54 parts 2 & 4 as well as

    being easy to install, operate & maintain.

    Being of modular design, the basic panel has 24 zones

    built in and it can be expanded to 32, 40 & 48 zones.

    The construction of the panel is epoxy painted steel

    enclosure, with top & rear cable entries.

    Model PMP48/24 PMP48/32 PMP48/40 PMP48/48

    Part No. 37-030 37-032 37-034 37-036

    Detection Zones 24 32 40 48

    Supply Voltage 230V AC +10%/-15% @ 50/60 Hz

    System Voltage 29V DC (nominal)

    Zone Voltage 21V DC

    Sounder Alarm Output 4 X 400mA @ 24V DC

    Fault Relay Output 1 relay SELV @ 1A (normally energised)

    Fire Relay Output 1 relay SELV @ 1A maximum

    Other Connections Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)

    Zone Capacity Up to 32 devices

    Remote Sounder Activation N/A

    Sounder Activation Delay 0 to 9 minutes

    Zone End Of Line 100μF capacitor

    Sounder End Of Line 10K resistor

    Charger Voltage 28.4V DC (Batteries disconnected)

    Zone Short Circuit Protection 100mA

    Charger Short Circuit Protection Batteries less than 20V

    Charger Size 3 Amp

    IP Rating IP43

    Operating Temperature 0°C to 50°C

    Enclosure Size 675 x 480 x 135mm

    Weight 13kg

    Features

     4 common sounder circuits (400mA each) Optional add-on zonal sounder circuits (50mAMax)

     Serial repeater output

     Auxiliary supply (29 Volts, 250mA)

     Zone & sounder disablement facility

     Sounder delay facility

     Zonal to common timer (when tted with zonalsounder boards)

     One man test mode

    13

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    14/44

    Premier 48 M Plus Repeater Panel(PMP48-REP, PMP48-REP/M)

    Model PMP48-REP PMP48-REP/M

    Part No. 37-037 37-038

    Functions Display & control Control only

    Supply Voltage 20–30V DC

    Maximum Quantity Per System 1 5

    Connections

    Serial Repeater A

    Serial Repeater A

    +24V DC

    0V

    Operating Temperature 0°C to 50°C

    Enclosure Size 480 x 330 x 60mm

    Weight 4.8kg

    The Premier 48 M Plus repeater is available in

    2 versions – standard & multiple.

    The standard repeater offers display & control

    functions, however is limited to one per system.

    The second version allows multiple repeaters on the

    same system however they do not have any control

    functions (i.e. they cannot be used to silence or reset

    the system).

    A single repeater can be powered from the panels’

    auxiliary 24V supply. If more than one repeater is to be

    used, a separate 24V is required.

    4

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    15/44

    Premier MX Conventional Fire Alarm Panel(MX-16 & MX-32)

    The Premier MX ranges of panels are available

    in either 16 or 32 zone versions and have been

    approved by LPCB to EN54 parts 2 & 4.

    The panels offer an extensive range of conguration

    options whilst remaining easy to install and congure.

    Features

     LPCB Approved to EN54 parts 2 & 4

     Zonal one-man test facility

     Latching or non-latching zones

     Delayed or non delayed zone operation

     Standard or intrinsically safe zone mode

     Short circuit to re mode for compatibility withold detectors

     Zonal or common alarm operation (requiresoutput expansion PCBs)

     Latching or non-latching fault modes

     Fault routing, re routing & re protectionrelays can be programmed as 24V output(monitored) or volt free

     Fault routing, re routing & re protectionrelays can have delayed operation in anyconguration

     The panel is available as ush mount on request

     Repeater panel option (up to 5 maximum perpanel)

    Model MX-16 MX-32

    Part No. 37-140 37-142

    Detection Zones 16 32

    Supply Voltage 230V AC +/- 10%

    System Voltage 24V DC (Nominal)

    Zone Voltage 24V DC (Nominal) Relay, SELV @ 1A

    Zone End of Line 22uF, 35V Axial Capacitor

    Sounder Output 4 X 1.0A @ 24V DC

    Sounder EOL 3K9 Resistor

    Aux DC Output 24V DC (Nominal) 1A

    Repeater option Yes

    Panel Inputs

    Remote

    Evacuation

    Remote Silence

    Alarms

    Remote Reset

    Class Change

    Panel Outputs

    Fault Routing

    Relay, SELV @ 1A

    Fire Routing

    Relay, SELV @ 1A

    Fire Protection Relay,

    SELV @ 1A

    Disablement Active(Open Collector

    Output)

    Evacuation Active

    (Open Collector

    Output)

    Buzzer Active (Open

    Collector Output)

    RS 485 Repeater

    Connection

    Operating

    Temperature

    -5°C to 40°C

    Size 325 x 370 x 126mm 400 x 441 x 131mm

    Weight 7.05kg 9.35kg

    15

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    16/44

    Fyreye Extra ConventionalOptical Smoke Detector (FEOE2000)

    The Fyreye Extra optical smoke detector uses

    a pulsing IR LED & photodiode to detect IR

    scatter caused by smoke entering the chamber.

    The detector is particularly suitable for detecting

    optically dense smoke, involving materials such as soft

    furnishings, PVC, plastic, foam and all similar materials

    which produce small visible particles (0.5 to 10μm).

    The detector will work with most modern re alarm

    control panels and comes supplied with a locking grub

    screw to prevent unauthorised head removal.

    The Fyreye Extra range of detectors has an extra LED to

    improve detector identication in an alarm condition.

    Features

     Designed to meet EN54 requirements

     Attractive design

     Dual LEDs for 360° visibility

     Lockable base to stop unauthorised removal

     Compatible with all Fyreye bases

    Model FEOE2000

    Part No. 80-022

    Detector Class Optical Smoke

    Design Standard EN54 part 7

    Approval DIFTOperating Voltage 9-33V DC

    Quiescent Current 65μA

    Alarm Current @ 24V DC 53mA MAX

    Operating Temperature -10°C to +50°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH non-condensing

    Alarm Condition 2.4% obscuration per metre

    Coverage 100m2

    IP Rating IP43

    Start-up Time 10 SecondsSize (with Base) 100 x 37mm (101 x 53mm)

    Weight (with Base) 95g (153g)

    37mm100mm

    6

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    17/44

    Fyreye Extra Conventional Rate of Rise andFixed Heat Detectors (FEHE2000 & FEFHE2000)

    The Fyreye Rate of Rise heat detector

    (FEHE2000) uses a thermistor arrangement

    to sense a quick rise in temperature and also

    a nal threshold temperature of 57°C. The

    Fyreye xed heat detector (FEFHE2000) has a

    single thermistor arrangement that gives an

    alarm at a temperature of 90°C.

    The detectors will work with most modern re alarm

    control panels and comes supplied with a locking grub

    screw to prevent unauthorised head removal.

    The Fyreye Extra range of detectors has an extra LED to

    improve detector identication in an alarm condition.

    Model FEHE2000 FEFHE2000

    Part No. 80-038 80-039

    Detector Class Rate of Rise & Fixed Heat Detector Fixed Heat Only

    Design Standard EN54 part 5

    Approval DIFTOperating Voltage 9-33V DC

    Quiescent Current 40μA

    Alarm Current @ 24V DC 34mA

    Operating Temperature -10°C to +50°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH non-condensing

    Alarm Condition Rate of rise or xed heat trigger @ 57°C Fixed heat trigger @90°C

    Coverage 50m²

    IP Rating IP43

    Start-up Time 10 SecondsSize (with Base) 100 x 48 mm (101 x 64 mm)

    Weight (with Base) 75g (133g)

    Features

     Designed to meet EN54 requirement

     Lockable to base to stop unauthorised removal

     Remote LED output

     Dual LEDs for 360° visibility

    Compatible with all Fyreye bases

    48mm100mm

    17

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    18/44

    Fyreye Extra ConventionalOpto-Heat Detector (FEOH2000)

    The Fyreye Extra opto-heat detector

    incorporates both an optical chamber and

    heat sensing element with advanced detection

    technology & discrimination algorithms. This

    multisensor is the perfect replacement for

    ionisation detectors.

    The detector will work with most modern re alarm

    control panels and comes supplied with a locking grub

    screw to prevent unauthorised head removal.

    The Fyreye Extra range of detectors has an extra LED to

    improve detector identication in an alarm condition.

    Features

     Advanced electronic technology used tominimise false alarms

     Designed to meet EN54 requirement

     Built-in 10 seconds alarm verication

     Lockable to base to stop unauthorised removal

     Remote LED output

     Dual LEDs for 360° visibility

    Compatible with all Fyreye bases

    Model FEOH2000

    Part No. 80-025

    Detector Class Optical / Heat

    Design Standard EN54

    Approval DIFTOperating Voltage 17-20V DC

    Quiescent Current 100μA

    Alarm Current @ 24V DC 70mA MAX

    Operating Temperature -20°C to +60°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH non-condensing

    Alarm Condition 3% obscuration per metre

    Coverage 100m²

    IP Rating IP43

    Start-up Time 10 SecondsSize (with Base) 100 x 50mm (100 x 66mm)

    Weight (with Base) 95g (153g)

    50mm100mm

    8

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    19/44

    Fyreye ConventionalUltra-Violet Flame Detector (FEUV2000)

    Model FEUV2000Part No. 80-045

    Detector Class Ultra Violet Flame Detector

    Operating Voltage 12-28V DC

    Quiescent Current 320μA

    Alarm Current @ 24V DC 45-50mA

    Operating Temperature 0°C to 45°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH non-condensing

    Alarm Condition 10 seconds for 30mm ame @ 4 metres

    Detection Angle 120°UV Sensitivity 185-260nm

    Size (with Base) 98 x 36mm (98 x 52mm)

    Weight (with Base) 85g (143g)

    The Fyreye ultra-violet am detector is

    particularly suited to applications where

    ames can be expected to develop initially

    rather than smoke. This is typically due to the

    nature of the materials being protected for

    instance camera lm, computer, audio & video

    tapes or disks.

    The detector is for indoor use only and should not

    be exposed to spurious sources of UV, such as sparks,

    uncovered halogen lights, lightening, etc. as these maytrigger a false alarm.

    Due to the operational nature of ame detectors it is

    generally recommended to t just one detector per

    zone.

    Features

     Low prole shape

     The detector is solar blind and incorporates an

    electronic lter to eliminate unwanted alarmsfrom naturally occurring phenomena

     Fast response time

     High immunity to electrical noise & RFinterference

    UV EMISSIONPOINT

    VERTICAL VIEWING

    (top fig.)

    HORIZONTAL

    VIEWING

    (bottom fig.)

    90°90°

    60°60°

    30°30°

    ANODE

    CATHODE

    90°90°

    60°60°

    30°30°

    ANODE

    CATHODE

    Horizontal & Vertical Detector Field Of View

    19

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    20/44

    Fyreye Conventional Detector Bases(FE-CB, FE-DB, FE-RB)

    Model FE-CB FE-CB/S FE-CB/D FE-DB FE-DB/S FE-DB/D FE-RB

    Part No. 80-050 80-050S 80-050D 80-052 80-052S 80-052D 80-054

    Type Common base Diode base Relay base

    Supply Voltage 9-33V DC 24V DC

    Quiescent Current @ 24V 0μA

    Alarm Current @ 24V 0mA 15mA

    Relay Max Switching Power N/A 30W, 50VA

    Relay Max Switching Power N/A 30W, 50VA

    Relay Max Switching Current N/A 1A resistive

    Relay Max Switching Voltage N/A 50V AC

    Relay Minimum Capability N/A 10μA, 10mV

    Relay Dropout Voltage N/A

  • 8/9/2019 Conventional Catalogue

    21/44

    Zeta Remote LED Indicator(ZT-RL)

    Model ZT-RL

    Part No. 48-023

    Input Voltage 5 – 30vdc

    Quiescent Current 0mA

    Alarm Current 12mAOperating Temperature 0°C - 50°C

    Max Humidity 95% Relative Humidity Non-condensing

    IP Rating IP41

    Size 85 x 85 x 70mm

    Weight 113g

    Remote LEDs indicators are used in

    installations where a detector going to alarm is

    likely to occur out of sight (for instance behind

    a locked door or in a ceiling void). In these

    instances the indicator will then show the

    location of the alarm.

    Features

     Twin LED’s

     Surface or ush mounting

    21

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    22/44

    Fyreye 50 & 100m Reective BeamSmoke Detector (ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)

    The Fyreye reective beam detectors comprise

    of a single unit incorporating an infrared

    transmitter & receiver. The signal is reected

    by a prism and analysed for smoke presence.

    Should a predetermined level be reached then

    the detector will signal an alarm.

    The system is designed to be mounted so that the beam

    will project between 0.3 and 0.6 metres below the

    ceiling and parallel to it. Lateral detection may be up to

    7.5 metres either side of the beam.

    Features

     50 or 100 metre reective beam smoke detector

     VdS approved

     Complies fully to;

     BS 5839 part 5

     EN54 part 12

     Single compact housing

     Horizontal or vertical mounting

     12-24V DC operation

     Low current consumption

     Latching or non latching alarm

     Reector targeting mode to ease set-up

     Microprocessor controlled

     Automatic contamination compensation

     Selectable sensitivity

     Robust construction

    126mm 120mm

         1     4     0    m    m

         2     1     0    m    m

    70mm

    100mm

         1     0     0    m

        m

    9.5mm

    2

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    23/44

    Model ZT-50RZ ZT-100RZ ZT-50RV ZT-100RV

    Part No. 47-050 47-051 47-050A 47-051A

    Range 5-50m 50-100m 5-50m 50-100m

    Number of Wires 2 4

    Supply Voltage 10.2V to 30V DC

    Quiescent Current

  • 8/9/2019 Conventional Catalogue

    24/44

    Fyreye 50 & 100m Auto-aligning Beam SmokeDetector Systems 50 & 100m (ZT-5000R & ZT-5000R/100)

    Features Worldwide approvals including EN54:12 andUL268

     Up to 4 detectors per system controller

     Each detector congurable from 8m to 100m

     Integral LASER

     Auto-align fast automatic beam alignment

     Auto-optimise building movement andcontamination compensation

     Low level system controller 20mm cable gland knockouts on systemcontroller

     2-wire interface from system controller todetector

    Additional System Components

      ZT-5000R/DH - 47-072 - Fyreye Auto-aligning SingleBeam Detector Head 50m

     ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligningSingle Beam Detector Head 100m

     ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning BeamDetector Long Range Kit

    The system consists of 2 parts; the beam detector itself

    and a low level control unit.

    The system can be fully customised, according to local

    conditions and installation guidelines; alarm thresholds

    (sensitivity) and time to alarm/fault can be set from the

    low level system controller.

    Each detector head is independently congurable from

    8m through to 100m and has its own individual re

    threshold. The system controller retains one set of re

    and fault relays that is common to all detectors that are

    installed.

    The system is supplied as either a 50 or 100 metreversion with a single detector head. Additional heads

    and a long range kit (additional prisms to allow the

    detector head to reach 100m) are available separately.

    Based on the proven technology of the

    standard Fyreye reective beam detectors, the

    Fyreye auto-aligning beam detector has been

    designed to help improve ease of installation.

    The system is ideally suited for the protection of

    large areas where the use of traditional detection

    technologies would prove to be too difcult and/or

    costly to install.

    The system combines an infrared transmitter and

    receiver in the same discrete unit and operates by

    projecting a well-dened beam to a reective prism,

    which returns the beam to the receiver for analysis.

    Smoke in the beam path causes a drop in power, which,

    if below a pre-determined level, results in an alarm

    signal.

    4

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    25/44

    Model ZT-5000R ZT-5000R/100

    Part No. 47-070 47-071

    Range 50m 100m

    Number of Wires 4

    Supply Voltage 14-28V DC

    Operating Current8-12mA (low current mode with 1 detector)48-52mA (high current mode with 1-4 detectors)

    Operating Temperature -20°C to 55°C

    Storage Temperature -40°C to 85°C

    Max Humidity 85% RH non-condensing

    Max Wind Speed Not affected

    Alarm Current 35mA (typical)

    Fire Output Volt free relay contact

    Fault Output Volt free relay contact

    Beam Misalignment Tolerance @ 35% Detector ± 0.8°, Prism ± 5.0°

    Alarm Thresholds 2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)

    Optical Wavelengths 850nm

    Construction Flame Retardant ABS (Grey / Black)

    IP Rating IP54

    Detector Size 135 x 135 x 135mm

    Detector Weight 0.5kg

    Controller Size 202 x 230 x 81mm

    Controller Weight 0.9kg

    135mm 135mm

    202mm 81mm

    2   3   0  mm

    1   3   5  mm

    25

  • 8/9/2019 Conventional Catalogue

    26/44

    Zeta UV/IR Optical Flame Detectors(VS-200P & VS-200EX)

    Features

     UV/IR spectrum for medium distance detectionand high false alarm immunity

     Compact & lighter design

     User selectable sensitivity & functions

     Multiple output options (relays for alarm & fault,0-20mA (stepped) and RS-485/RS-232 spectrummonitoring)

     ATEX approved by DNV for explosion-proof (VS-

    200EX UV/IR only)

     CE certied

    TypicalApplications

    Non-hazardous (VS-200P)

     Parking buildings

     Warehouse

     Waste disposal facilities

     Culture centres

    Hazardous (VS-200EX)

     Offshore oil & gasinstallations

     Onshore oil & gasinstallations andpipelines

     Petrochemical plants

     Chemical plants

     Shipbuilding facility

     Automotive industry

     Storage tank farms

     Power generationfacility

     Petrochemical plants

     Painting industry

     Warehouse

    Waste disposal facility

     Explosive & munitions

    The VS-200P & VS-200EX UV/IR ame detectors

    detect fuel & gas res at long distances with

    the highest immunity to false alarms. The

    detectors can detect a 0.1m² gasoline pan reat 30m in less than 5 seconds.

    VS-200P VS-200EX

    6

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    27/44

    Model VS-200P VS-200EX

    Part No. 47-150 47-151

    Spectrum Response UV /IR (Dual Bands)

    Spectrum Response

    (at highest sensitivity settingfor 0.1m² pan re)

    Fueln-Heptane

    Gasoline

    Diesel

    LPG*

    Distance30m

    30m

    20m

    20m

    FuelEthanol

    IPA

    Methanol

    Distance20m

    25m

    20m

    *0.5m high / 0.2m width plume re

    Response Time Typically 5 seconds

    Adjustable Time Delay Up to 20 seconds

    Sensitivity Range 4 sensitivity ranges for 0.1m² n-Heptane pan re from 15m to 65m

    Field of View Horizontal 90°, Vertical 90°

    Built-in-Test Manual (optionally Automatic)

    Temperature Range Operating/Storage: -40°C to 75°C

    Humidity Up to 95% non-condensing

    Operating Voltage 24VDC norminal (17-31VDC)

    Power Consumption Standby: max. 35mA, Alarm: max. 75mA

    Cable Entry 1 x M20 (ISO)

    Wiring AWG 16-26 (Str 1.5mm² to 0.13mm²)

    Electromagnetic Compatibility EMI/RFI protected to EN61000 series

    Electrical Interface The detector includes twelve(12) terminals with four(4) wiring options

    Relays Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC

    0-20mA (stepped)

    Non-isolated “Source” conguration

    Fault:Normal:

    Alarm:

    0 +1mA4mA±10%

    20mA±10%

    Bit Fault:

    Warning:Resistance

    Loop:

    2mA±10%16mA±10%

    Max. 800Ω

    Materials Polycarbonate Enclosure

    Heavy duty copper free aluminium (less than 1%) with bright grey

    anodizing nish

    Enclosure options - Stainless Steel 316L with electro polish nish

    Mounting (Tilt Mount) Stainless Steel

    Heavy duty copper free aluminium (less than 1%) with grey epoxy

    enamel nish

    Options - Stainless Steel 316L with electro polish nish

    DimensionsDetector: 80 x 82 X 86

    mmDetector: 83(d) x 126(l) mm

    Weight

    Detector : 0.3kg (1.0kg

    with cable gland /

    1m-length cable / TiltMount)

    Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland /

    1m-length

    Detector (St. SUS316L): 2.0 kg

    Tilt mount (aluminium/ St.): 0.3kg / 0.7kg

    Water and Dust IP66 per EN60529 IP66 and IP67 per EN60529

    EMI/RFI CE MarkingATEX Ex II 2 G

    Exd IIC T6, -40°C to +75°C (DNV 09 ATEX 0000)

    PerformanceEN54-10 (designed tomeet)

    KFI (Korea)

    EN54-10 (designed to meet)

    27

  • 8/9/2019 Conventional Catalogue

    28/44

    Zeta Conventional Manual Call Points(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)

    The Zeta conventional manual call point has

    a modern design and has been approved by

    BSI to EN54 part 11. It is a resettable call

    point that signals an alarm with a yellow ag

    entering the window area and a red alarm LED.

    There are two versions available; the ZT-CP2 call points

    comes complete with a protective Perspex cover as

    well as a “snaplatch” catch that needs to be broken off

    before the call point cover can be lifted (this acts as a

    deterrent to malicious activations and forms a Type B

    call point). Alternatively the ZT-CP1 is supplied withoutthe Perspex cover & “snaplatch” and is single action or

    Type A call point.

    The recommended colour for these call points is red

    however white is also available to meet architectural

    requirements.

    Model ZT-CP2 ZT-CP2/W ZT-CP1 ZT-CP1/W

    Part No. 43-300 43-314 43-301 43-317

    Type Type B Type A

    Element Type Resettable

    Alarm ActivationBreak “snaplatch”, lift Perspex cover, press

    elementPress element

    Colour Red White Red White

    Input Voltage 9-33V DC

    Quiescent Current 0mA

    Alarm Current Typical 35mA (maximum 51mA)

    Alarm Load 470 Ω resistor

    Operating Temperature -20°C to 50°C

    Max Humidity 95% RH non-condensing

    IP Rating IP43

    Size 111 x 100 x 67mm 105 x 100 x 58mm

    Weight 198g 175g

    Features

     BSI approved to EN54 part 11

     Attractive design

    8

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    29/44

    Zeta Conventional Weatherproof Call Point(ZT-CP2/WP)

    Model ZT-CP2/WP

    Part No. 43-350

    Type Type B

    Element Type Resettable

    Alarm Activation Break “snaplatch”, lift Perspex cover, press element

    Colour Red

    Input Voltage 9-33V DC

    Quiescent Current 0mA

    Alarm Current Typical 35mA (maximum 51mA)

    Alarm Load 470 Ω resistor

    Operating Temperature -20°C to 50°C

    Max Humidity 95% RH non-condensing

    IP Rating IP65Size 87 x 87 x 70mm

    Weight 198g

    The Zeta conventional weatherproof manual

    call point is an IP65 rated call point which

    complies with EN54 part 11. It is resettable

    and signals an alarm with a yellow ag

    entering the window area and a red alarm LED.

    The call point comes complete with a protective Perspex

    cover as well as a “snaplatch” catch that needs to be

    broken off before the call point cover can be lifted (this

    acts as a deterrent to malicious activations and forms a

    Type B call point).

    Features

     Complies with EN54 part 11

     Attractive design

     Resettable element

     Protective cover

    29

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    30/44

    Zeta Conventional Explosion ProofManual Call Point (ZT-BGU/WP/R & ZT-BGU/WP)

    The Zeta conventional explosion proof manual

    call point is manufactured from aluminium

    with a built-in push button activator. The call

    point is nished with red anti-corrosive epoxy

    powder coating with 2 x 20mm cable entries.

    This unit is equipped with a stainless steel

    hammer and chain.

    Two models are available; the ZT-BGU/WP/R with 470Ω

    built-in resistor for connection to a standard re alarm

    system or the ZTBGU/WP for mains connection.

    Model ZT-BGU/WP/R ZT-BGU/WP

    Part No. 43-300/WP 43-305/WP

    Contact Rating 10 Amp

    Voltage Rating 500V AV

    Build-in Resistor 470Ω N/A

    IP Rating IP65

    Earthling 2No M6 eternal & 1No M5 internal

    Size TBC

    Weight 1.5kg

    2 Nos.0.75″ET

    B    R   E    A 

    K    G  L

     A    S

         S

         I   N 

     C ASE  O  F     

    F I RE185mm

    105mm

    4 Holes - ø7

    Hammer

    Chain

    0

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    31/44

    Miditone Conventional Electronic Sounder(ZMDD/8R & ZMDD/8W)

    The Miditone sounder is a small, high output

    conventional sounder which designed to meet

    the requirements of EN54 part 3 and is CE

    marked.

    The sounder is a compact unit that ts a standard

    European back box and can be either surface or ush

    mounted. It has a choice of 8 tone patterns, selectable

    by an internal dip switch and a sound output of 95dB @

    1m with volume control.

    It is available in red or white to meet architectural

    requirements.

    Features

     Complies to EN54 part 3

     95dB @ 1m sound output

     8 Tone patterns

    Flush or surface xing

    Model ZMDD/8R ZMDD/8W

    Part No. 42-040 42-040A

    Sound Output See current consumption table

    Colour Red White

    Operating Voltage 9-30V DC

    Quiescent Current 0mA

    Alarm Current @ 24V See current consumption table

    Operating Temperature -10°C to 50°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH Non Condensing

    IP Rating IP43

    Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)

    Weight (with Back Box) 100g (150g)

    DIL Switch Settings (SW4 N/A)

    1 2 3 Tone Description dB Level Current (mA)

    Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 97 (+/- 2dB) 21

    On Off Off Alternating 554 and 440Hz 0.5s Each 95 (+/- 2dB) 17

    Off On Off Continuous 660Hz 96 (+/- 2dB) 22

    On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 94 (+/- 2dB) 17

    Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 8-24

    On Off On Continuous 970Hz 95 (+/- 2dB) 25.5Off On On Sweep Positive 800-970Hz 99 (+/- 2dB) 25

    On On On Alternating 800 and 970Hz @ 0.25s Each 100 (+/- 2dB) 25

    31

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    32/44

    Miditone Conventional Combined ElectronicSounder & Flasher (ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)

    The Miditone combined sounder & asher is a small, high

    output conventional sounder & asher which is designed

    to meet the requirements of EN54 part 3 and is CE

    marked.

    The device is a compact unit that ts a standard

    European back box and can be either surface or ush

    mounted. It has a choice of 8 tone patterns, selectable

    by an internal dip switch and a sound output of 95dB

    @ 1m with volume control. This is an ideal solution to

    upgrade an existing sounder to a combined sounder &

    asher.

    It is available with either a red, amber, blue, clear or

    green lens to meet architectural requirements.

    Model ZMDF/8R ZMDF/8A ZMDF/8B ZMDF/8C ZMDF/8G

    Part No. 42-024 42-024A 42-024B 42-02C 42-024G

    Sound Output See current consumption table

    Lens Colour Red Amber Blue Clear Green

    Operating Voltage 17-30V DC

    Quiescent Current 0mA

    Alarm Current @ 24V See current consumption table

    Operating Temperature -10°C to 50°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH non condensing

    IP Rating IP43

    Size (with Back Box) 85 x 85 x 35mm (85 x 85 x 67mm)

    Weight (with Back Box) 112g (162g)

    Features

     Complies to EN54 part 3

     95dB @ 1m sound output

     8 tone patterns

     Flush or surface xing

    DIL Switch Settings (SW4 N/A)

    1 2 3 Tone Description dB LEVEL CURRENT (mA)

    Off Off Off Sweep Negative 1200- 500 Hz In 1 Second 102 (+/- 2dB) 35

    On Off Off Alternating 554 and 440Hz 0.5s Each 100 (+/- 2dB) 27

    Off On Off Continuous 660Hz 100 (+/- 2dB) 33

    On On Off Alternating 554Hz @ 0.1s/440Hz @ 0.4s 98 (+/- 2dB) 26

    Off Off On Intermittent 970Hz @ 0.5s On/Off 93 (+/- 2dB) 13 - 35

    On Off On Continuous 970Hz 103 (+/- 2dB) 37

    Off On On Sweep Positive 800-970Hz 103 (+/- 2dB) 45

    On On On Alternating 800 and 970Hz @ 0.25s Each 103 (+/- 2dB) 42

    2

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    33/44

    Securetone Conventional Electronic Sounder(ZST/8R & ZST/8W)

    The Securetone sounder is designed to be

    aesthetically pleasing and unobtrusive. It has

    an elegant round design and ts to its supplied

    mounting plate with a bayonet action to avoid

    unsightly screws.

    It has 8 selectable tones with a volume adjust screw to

    set the required sound level.

    This product is designed to meet the requirements of

    EN54 part 3 and is CE marked.

    Features

     8 selectable tones

     Volume control

    Model ZST/8R ZST/8W

    Part No. 42-004 42-004A

    Sound Output 100dBA @ 1 metre

    Colour Red White

    Operating Voltage 10-30V DC

    Quiescent Current 0mA

    Alarm Current @ 24V 35mA MAX

    Operating Temperature -0°C to 50°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH Non Condensing

    IP Rating IP43

    Size (including Plate) 100 x 100 x 75mm (100 x 100 x 85mm)

    Weight (including Plate) 230g (260g)

    85mm

    1   0   0  mm

    33

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    34/44

    Secure Light Xenon Flasher(ZTSL6/R & ZTSL6/A)

    The Secure Light Xenon Flasher range is

    designed to provide a visual warning at alarm

    condition.

    Both red and amber versions are available with the

    lenses constructed of high-Impact and heat resistant

    ACRYREX. The case is made of high-impact resistant ABS

    plastic.

    Features

     Available in Red & Amber

     Fits onto a standard outlet box

    Model ZST/8R ZST/8W

    Part No. 42-035 42-038

    Colour Red AmberFlash Energy 3 Watt

    Flash Frequency 60 times per minute

    Operating Voltage 20-30V DC

    Quiescent Current 0mA

    Alarm Current @ 24V 100mA MAX

    Operating Temperature -30°C to 60°C

    Minimum Continuous Temperature 0°C

    Maximum Humidity 95% RH Non Condensing

    IP Rating IP54

    Size 97 x 100mmWeight (including Plate) 231g

    97mm

    1   0   0  mm

    4

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    35/44

    Maxitone Conventional Sounder andCombined Sounder & Flasher (ZMT/8R, ZMT/8W & ZMTF/8R)

    The Maxitone sounder is an ideal alternative

    to re bells and for external use. It is housed

    in an attractive horn comprises of ame

    retardant ABS. Eight selectable tones and

    volume control are featured to meet most

    requirements.

    The Maxitone is also available with transparent

    polycarbonate front which will provide both visual and

    audible alarm.

    Model ZMT/8R ZMT/8W ZMTF/8R

    Part No. 42-001 42-001A 42-032

    Sound Output See current consumption table

    Colour Red White Red

    Operating Voltage 17-30V DCQuiescent Current 0mA

    Alarm Current @

    24VSee current consumption table

    Operating

    Temperature-20°C to 60°C

    MinimumContinuous

    Temperature

    0°C

    Maximum Humidity 95% RH non condensing

    IP Rating IP65

    Size 124 x 130 x 100mmWeight 357g

    120mm

    126mm

    107mm

    DIL SWITCH SETTINGS (SW4 N/A)

    1 2 3 Tone Description dB LevelCurrent

    (mA)

    Off Off Off  Sweep Negative 1200-500 Hz In 1 Second

    101 (+/-2dB)

    27

    On Off Off  Alternating 554 and

    440Hz 0.5s Each

    98 (+/-

    2dB)20

    Off On Off Continuous 660Hz101 (+/-

    2dB)27

    On On Off  Alternating 554Hz @0.1s/440Hz @ 0.4s

    98 (+/-2dB)

    19

    Off Off OnIntermittent 970Hz @

    0.5s On/Off 

    98 (+/-

    2dB)20

    On Off On Continuous 970Hz103 (+/-

    2dB)29.3

    Off On OnSweep Positive 800-

    970Hz

    103 (+/-

    2dB)38

    On On OnAlternating 800 and

    970Hz @ 0.25s Each

    102 (+/-

    2dB)35

    Features

     High output

     8 selectable tones

     Volume control

    35

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    36/44

    Zeta Conventional Fire Alarm Bells(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)

    The Zeta motorised re alarm bells combine

    styling and functional efciency. They

    incorporate a low power rotary centrifugal

    mechanism, which gives a high sound output

    with low current consumption at 24V dc.

    The bells are available in 2 sizes; 6″ (152mm) and 8″

    (203mm). These sizes suit a wide variety of installations.

    There is a 230V ac version of the 6″ bell, and a 24V dc

    Weatherproof version of the 8″ bell.

    Features

     Low current

     Universally accepted re evacuation signal

    Model ZTB6B ZTB8B/230 ZTB8B ZTB8B/WP

    Part No. 41-003 41-004 41-005 41-006

    Supply Voltage 18-30V dc 200-250V AC 18-30V dc

    Diameter 6″ (152mm) 8″ (203mm)

    Quiescent Current 25mA 28mA

    Nominal Output @ 1M 95dB(A) 97dB(A)

    Dimensions 152 x 152 x 55mm 203 x 203 x 55mm

    Weight 860g 960g 1700g 1800g

    ZTB6B ZTB8B

    152mm 55mm

    55mm

         1     5     2    m    m

    203mm

         2     0     3    m    m

    6

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    37/44

    Zeta Flame Proof Siren(ZTSR/EXD24 & ZTSR/EXD230)

    The Zeta ame proof siren is an explosion

    proof siren available in either 24V or 230V

    versions.

    An intrinsically safe circuit is housed in the main

    chamber and it is duly wired up to terminal chamber

    through sealed bushes. The horn unit is placed on the

    main chamber cover and the output signals are takenthrough sealed coils. Neoprene ‘0’ rings are provided for

    the weather proof protection.

    Model ZTSR/EXD24 ZTSR EXD230

    Part No. 42-100/24 42-105/230

    Type Of Protection Flame proof – Exd T6 IP 65

    Area Classication Zone 1 & 2

    Gas Groups Group I, II A, II B, II C

    Apparatus

    StandardIS - 2148

    CMRI Certicate CMRI / TC / S / H388

    Approvals CCE, DGFAS

    Materials Cast Aluminium LM 6

    Weight 5 Kg (approx.)

    Size 170 (w) x 390 (h) x 240 (d) mm

    IP Protection IP 65 to IS 13947 / 93

    Finish Anti corrosive Epoxy – Powder Coated

    Cable Entry 2 x ¾″ ETGasket Neoprene

    Hardware Stainless Steel

    Terminals4 x 2.5 sq. mm (standard) 6 x 2.5 sq.

    mm (for looping)

    Voltage 24 V DC 230 V AC – 50 Hz

    Output Current 600mA Peak. Galvanically Isolated

    Power Rating 18 Watts

    Sound Output106 db 900 Hz On & Off alternativelyat 1C/s

    EarthingExternal: 2 Nos.

    - M6

    Internal: 1 No. -

    M5

    170mm 240mm

     3   9   0  mm

    37

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    38/44

    Zeta Flame Proof Gong Bell(ZTB8B/EXD/24)

    The Zeta ame proof gong bell is an explosion

    proof gong bell with a terminal chamber.

    A highly reliable electric circuit is housed inside to

    control the frequency of the gong operating spindle.

    The operating spindle and dish are made out of stainless

    steel thereby ensuring a long life.

    The electric circuits are connected to terminals in

    the terminal chamber through nipple. The covers are

    provided with neoprene gaskets for weatherproof

    protection.

    Model ZTB8B/EXD

    Part No. 41-075

    Type Of Protection Flame proof – Exd T6 IP 65

    Area Classication Zone 1 & 2

    Apparatus Standard IS - 2148

    Material Cast Aluminium LM 6

    Weight 3 Kg (approx.)

    Size 225(w) x 285(h) x 160(d) mm

    IP Protection IP 65 to IS 13947 / 93

    FinishAnti Corrosive Epoxy –

    Powder coated

    Cable Entry 1 X 3/4″ ET

    Gasket Neoprene

    Hardware Stainless steel

    Voltage24V DC or 110V / 230V AC –

    50 Hz

    Power Rating 12 Watt

    Sound Output 112db

    Terminals 4 x 4 mm²

    EarthingExternal: 2 Nos – M6 Internal:1 No. - M5

    225mm 160mm

    2   8   5  mm

    8

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    39/44

    Zeta Magnetic Door Holders(ZT-DR24 & ZT-DR240)

    Model ZT-DR24 ZT-DR240

    Part No. 50-001 50-002

    Rated Voltage 24V DC 230V AC

    Rated Current 65mA 6mA

    Switch Through Aux Yes No

    Needs Back EMF Diode Yes No

    Holding Force 400 N

    Size (Main Unit) 110 x 85 x 38mm

    Dimensions (Keeper Plate) 55 x 55 x 50mm

    Weight (Main Unit) 404g

    Weight (Keeper Plate) 153g

    The Zeta magnetic door holders are designed

    to retain a re door open against the force of

    its own closing device. In the event of a re,

    the door holder magnet can be turned off bythe re alarm, allowing the door to shut.

    The manual release button is changeable from the base

    side to left or right. Cable entry is possible from rear

    side by means of enclosed exits from the base side, left

    or right.

    An optional bracket is also available for oor or wall

    mounting (ZT-BR).

    Features

     Tested according to EN1155

    ZT-BR

    39

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    40/44

    Zeta Duct Unit(ZT-DU, ZT-DU/12 & ZT-DU/230)

    The Zeta duct unit allows air in a ventilation

    duct to be monitored for smoke via a smoke

    detector mounted externally in a sealed

    chamber. The unit comes supplied with 2

    sampling probes (one in & one out) which are

    mounted through the duct in the centre of the

    air ow.

    There are 3 versions of the unitavailable which are as follows;

    ZT-DU – enclosure supplied with a Fyreye common base(FE-CB) allowing either a conventional or addressable

    Fyreye detector to be connected and wired as part a

    system.

    ZT-DU/12 – enclosure c/w Fyeye base and relay boardwith form C relay outputs for alarm and for fault which

    requires 12V power supply.

    ZT-DU/230 - enclosure c/w Fyeye base and relay boardwith form C relay outputs for alarm and for fault which

    requires 230V power supply.

    Please note for reliable smoke detection the air speed in

    the duct must be at least 2.5m/s.

    Features

     Fire and Fault relays

     Option for latching or non-latching

     Manual reset (latching option)

    Model ZT-DU ZT-DU/12 ZT-DU/230

    Part No. 48-011A 48-011B 48-011C

    Supply Voltage N/A 12V 230V

    Stand by current N/A 46mA (From 12v supply)

    Alarm current N/A 86mA (From 12v supply)

    Fault current N/A 26mA (From 12v supply)

    Indications N/A Power, fault & alarm

    Outputs N/A 1 x fault relay & 1 x alarm relay

    Size 190 x 227 x 70mm

    Weight 728g 989g

    Direction of Airflow

    Duct Wall

    Test Point

    0

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    41/44

    Premier Power Pack EN 54-4 Power Supplywith LCD Screen (PP-2/12, PP-5/17)

    The Premier Power Pack Power supply uses an

    innovative design that allows the engineer to

    view system status through the on board LCD

    screen. The screen can display several power

    supply parameters, including output voltage,

    and output current.

    The power supply itself uses a 3 state charger which

    uses BOOST, FLOAT, and PULSE modes, depending on the

    state of the battery.

    The PSU will disconnect the batteries under mains failcondition, when the batteries are fully discharged to

    prevent damage to the batteries.

    The PSU will also monitor the battery for high internal

    resistance, and signal a fault if that condition is

    detected.Screen Information

    System Normal Screen

    Z E T A A L A R M S Y S T E M S

    P R E M I E R P O W E R - P A C K

    R A T I N G 3 0 V D C 2 . 0 A

    S Y S T E M N O R M A L

    Screen 1 - Main Information

    M A I N S : O K B A T T S : O K

    V ( A ) = 2 9 . 5 V ( B ) = 2 9 . 5

    C U R R E N T 0 . 1 2 A M P S

    Screen 2 - Battery Info

    B A T T E R Y I M P : 0 . 0 0 3 7

    C H A R G E R V O L T : 2 5 . 4 5 V

    C H A R G E T Y P E : B O O S T

    B A T T E R Y S T A T E : G O O D

    Screen 3 - Misc.

    E A R T H : 2 . 4 4 7 V G O O D

    C H A R G E R C I R C U I T : O K

    B A D B A T T E R Y L V L X . X R

     

    Screen 4 - Software Information

     

    S o f t w a r e P S U : 2 V 0 0

    S o f t w a r e L C D : 2 V 0 0

    Model PP-2/12 PP-5/17

    Part No. 46-300 46-305

    Input Voltage 170-264V AC 47-63 Hz

    Output Voltage 28V DC Nominal 28V DC Nominal

    Power Rating 75W 150W

    Efciency 79% 86%

    Total Power

    Output2.0 Amp 5.0 Amp

    Power Supply

    Outputs2 Fused Outputs 2 Fused Outputs

    Maximum Current

    Per Output0.625mA 2.0 Amps

    Battery Charging

    Current750mA 920mA

    Fault Relay Rating SELV 1A SELV 1A

    IP Rating IP30 IP30

    Size 375 x 335 x 128mm 375 x 403 x 128mm

    41

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    42/44

    Batteries(Z20201, Z20301, Z20651, Z21251 & Z21751)

    As re alarm systems are life safety systems,

    they must have a battery backup to ensure full

    functionality is maintained in the event of a

    mains failure. All parts of the system (including

    auxiliary power supplies) must have a battery

    backup.

    All the batteries stocked are 12V meaning that 2

    batteries are required for a 24V systems. The standard

    capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and

    17Ah.

    It is important to choose the correct battery size for the

    system load to give the required standby time (usually

    24 or 48 hours).

    Model Z20201 Z20301 Z20651 Z21251 Z21751

    Part No. 46-002 46-100 46-003 46-105 46-004

    Type Sealed lead acid

    Voltage 12V DC

    Capacity 2.2 Ah 3.2 Ah 7.2 Ah 12 Ah 17 Ah

    Size 178 x 34 x 65mm 132 x 59 x 65mm 151 x 65 x 98mm 150 x 98 x 103mm 178 x 75 x 168mm

    Weight 1.0kg 1.25kg 2.5kg 3.5kg 5.8kg

    Battery Calculation

    To calculate the required battery backup, we use the equation:-

    Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x ISBY)]

    Where:

    TALM

     = Maximum time in hours required for the alarm [½ hour is most common time]

    IALM

     = Total Alarm Current in amps for all alarm devices connected to the alarm

    circuits

    TSBY

     = Standby time in hours for the system after mains failure [normally 24, 48 or 72

    hr]

    ISBY

     = Quiescent current in amps of control panel in fault condition [because of mains

    failure] PLUS all loop devices

    2

    Conventional Fire Alarm Systems /

  • 8/9/2019 Conventional Catalogue

    43/44

  • 8/9/2019 Conventional Catalogue

    44/44

    Available now from: