Upload
sam
View
217
Download
0
Embed Size (px)
Citation preview
7/31/2019 Circuit Breaker Presentation
1/56
SWITCH
7/31/2019 Circuit Breaker Presentation
2/56
FUSE
NOT USED IN A TRANSMISSION
NETWORK AS IT WOULD FAIL TOINTERRUPT.
7/31/2019 Circuit Breaker Presentation
3/56
7/31/2019 Circuit Breaker Presentation
4/56
Power
plantTransformer Transformer
Local
distribution
net work
Transmission
line
Switch
Yards
Switch
Yard
Power Transmission system
7/31/2019 Circuit Breaker Presentation
5/56
CLASIFICATIONN OF CIRCUIT BREAKERS
Based on VoltageLow- less than 1kV
Medium - 1kV to 52kV
High/Extra High- 66kV to 765kV
Ultra High -above 765kV
Based on location
Indoor
Outdoor
Based on External design
dead tank
Live tank
Based on Interrupting media
Air break
Air blast
Bulk oil
Minimum oil
SF6 gas insulated
vacuum
7/31/2019 Circuit Breaker Presentation
6/56
DEAD TANK TYPELIVE TANK TYPE
CLASIFICATION OF AIS BREAKERS
7/31/2019 Circuit Breaker Presentation
7/56
ACB
AIR
ABCB
BOCB
OIL
MOCB
DOUBLE PRESSURE
SF6
SINGLE PRESSURE
VACUUM
7/31/2019 Circuit Breaker Presentation
8/56
7/31/2019 Circuit Breaker Presentation
9/56
MOCB
7/31/2019 Circuit Breaker Presentation
10/56
Axial blast - Contraction chamber principle in MOCB
7/31/2019 Circuit Breaker Presentation
11/56
Cross blast in MOCBs
7/31/2019 Circuit Breaker Presentation
12/56
7/31/2019 Circuit Breaker Presentation
13/56
SF6 GAS PROPERTIES
7/31/2019 Circuit Breaker Presentation
14/56
SF6 - DOUBLE PRESSURE
7/31/2019 Circuit Breaker Presentation
15/56
First generation interrupter-Double pressure type
Closed Position
Opening Position
Open Position
7/31/2019 Circuit Breaker Presentation
16/56
DOUBLE PRESSURE SYSTEM
SINGLE PRESSURE SYSTEM
7/31/2019 Circuit Breaker Presentation
17/56
7/31/2019 Circuit Breaker Presentation
18/56
Normal Puffer Interrupterfor 145-800kV voltage class
7/31/2019 Circuit Breaker Presentation
19/56
VACUUM
7/31/2019 Circuit Breaker Presentation
20/56
72.5kV Minimum Oil Circuit
Breaker type HLC
7/31/2019 Circuit Breaker Presentation
21/56
145kV Minimum Oil Circuit
Breaker type HLD
7/31/2019 Circuit Breaker Presentation
22/56
7/31/2019 Circuit Breaker Presentation
23/56
7/31/2019 Circuit Breaker Presentation
24/56
7/31/2019 Circuit Breaker Presentation
25/56
7/31/2019 Circuit Breaker Presentation
26/56
Arc interruption in duel flow conducting nozzle interrupter
7/31/2019 Circuit Breaker Presentation
27/56
Arc quenching process
7/31/2019 Circuit Breaker Presentation
28/56
7/31/2019 Circuit Breaker Presentation
29/56
7/31/2019 Circuit Breaker Presentation
30/56
145kV hydraulic mechanism operated SF6 gas breaker
7/31/2019 Circuit Breaker Presentation
31/56
245kV SF6 Circuit Breaker type
3AV1
7/31/2019 Circuit Breaker Presentation
32/56
7/31/2019 Circuit Breaker Presentation
33/56
420kV SF6 Circuit Breaker type
3AT2/3
7/31/2019 Circuit Breaker Presentation
34/56
7/31/2019 Circuit Breaker Presentation
35/56
800kV SF6 Circuit Breaker type
3AT4/5
800kV Type 3AT4/5 SF6 gas circuit breaker
7/31/2019 Circuit Breaker Presentation
36/56
800kV Type 3AT4/5 SF6 gas circuit breaker
7/31/2019 Circuit Breaker Presentation
37/56
7/31/2019 Circuit Breaker Presentation
38/56
7/31/2019 Circuit Breaker Presentation
39/56
7/31/2019 Circuit Breaker Presentation
40/56
Hydraulic operating mechanism
7/31/2019 Circuit Breaker Presentation
41/56
7/31/2019 Circuit Breaker Presentation
42/56
Spring operated mechanisms
7/31/2019 Circuit Breaker Presentation
43/56
Pneumatic mechanism
COMPARISON OF ELECTROHYDRAULIC - PNEUMATIC - SPRING
MECHANISMS
7/31/2019 Circuit Breaker Presentation
44/56
MECHANISMS
Electro Hydraulic Pneumatic Spring
1. No compressor is required Hydraulic pump ismaintenance free and directly coupled to motor.
Compressor is required, which needs routinemaintenance (at least once a year). Compressors arenormally coupled to motor by belt, which is a weak
link. Also intake air filters of compressors requirefrequent change (Every Six months in pollutedatmosphere)
No compressor is required Hence no associatedmaintenance problems.
2. All parts permanently immersed in oil - No scope forinternal corrosion or rusting.
All parts exposed to atmosphere. In addition,atmospheric air is compressed and releasedduring closing / opening operation. Duringexpansion, traces of moisture present in air inspiteof purification / drying of air, condense on metal
parts of the mechanism causing corrosion andrusting.
All parts exposed to atmosphere Heaters providedto prevent condensation of moisture on parts ofmechanism
3. Minimal piping Oil flow is through ducts in valveblock assembly No scope for external leakage Internal leakage, if any, would only cause morefrequent operation of motor at worst.
Piping is involved - Scope for leakage. No piping - No leakage.
4. No mechanical latches.The differential piston principle used clearly definesthe switching condition and ensures that this ismaintained should there be a fall in pressure and that"creeping" trip out is prevented.
Latches are to be checked for disturbances in settings
after specified no. of operations
Latches are to be checked for disturbances in settings
after specified no. of operations.
5. Small in size, compact and robust construction.Reliability very high.
Complex construction with many componentsand moving parts - Reliability very low.
Simple in design and construction. Less componentsand moving parts, hence reliable.
6. Two Close-Open operations are possible after failureof supply to motor.
One Open-Close-Open or Close-Open-Close
operation is possible after failure of supply to motor.
One Open-Close-Open operation is possible after
failure of supply to the motor.
COMPARISON OF ELECTROHYDRAULIC - PNEUMATIC - SPRING
MECHANISMS
7/31/2019 Circuit Breaker Presentation
45/56
MECHANISMS
Electro Hydraulic Pneumatic Spring
7 No additional damping system The damping requiredfor both closing and opening is provided by the
hydraulics of the operating mechanism.
Additional damping system is required which is to beroutinely checked and maintained.
Additional damping system is required which is to beroutinely checked and maintained.
8 No inter-posing mechanism. The piston systemtransmits the operating energy direct to the operatingrod.
Inter-posing mechanism with linkages is required fortransmission of operating energy to the movingcontact system.
Inter-posing mechanism with linkages is required fortransmission of operating energy to the movingcontact system.
9 Low noise level High noise level Low noise level
T ti f i it b k
7/31/2019 Circuit Breaker Presentation
46/56
Testing of circuit breaker
Type tests
High power tests
Direct tests
synthetic tests
Short circuit tests
Switching performance tests
High voltage tests
Mechanical and environmental tests
Temperature rise test
Routine tests
Mechanical operations test
Measurement of contact resistance
Voltage withstand test on control circuit
Power frequency withstand test on main circuit
High pressure test on Hydraulic mechanism
SF6 gas tightness test
Pump charging time for operations
Leak testing hydraulic mechanism
N2 leak test on accumulator
Thermal Assist Interrupter
7/31/2019 Circuit Breaker Presentation
47/56
Thermal Assist Interrupterfor 72.5-170kV voltage class
Thermal Assist Interrupter
7/31/2019 Circuit Breaker Presentation
48/56
Thermal Assist Interrupterfor 72.5-170kV voltage class
7/31/2019 Circuit Breaker Presentation
49/56
SF6 gas circuit breaker SF6 gas operated mechanism
7/31/2019 Circuit Breaker Presentation
50/56
SF6 gas operated mechanism
7/31/2019 Circuit Breaker Presentation
51/56
SF6 gas operated mechanism
7/31/2019 Circuit Breaker Presentation
52/56
Compact switchgear
7/31/2019 Circuit Breaker Presentation
53/56
Circuit breakers with composite insulators
Explosion proof
Light weight
Single piece of any length
No L/D constraint
Higher creapage can be achieved
Comparatively costly
No of joints can be reduced
7/31/2019 Circuit Breaker Presentation
54/56
SF6 gas insulated substation
SB6 offer extension : MCI the Integrated Compact Module
7/31/2019 Circuit Breaker Presentation
55/56
Functions :
-INTERRUPTION
-ISOLATION
-MEASURING
-CONTROL (& PROTECTION)
Up to 170kV 2000A 40kA
7/31/2019 Circuit Breaker Presentation
56/56