43
77 CHAPTER 4 TESTING AND CORRELATION 4.1. INTRODUCTION The testing of a machine both at the work and at site is very important for a smooth operation of the machine. Tests are carried out at the work to determine whether the machine has been manufactured according to specifications of the customer and are in conformity with the design of the electrical and mechanical designers. Hence testing is essential at manufacturing works. This chapter, therefore, describes preliminary tests that have to be performed before assembling the machine in the test beds. Here, tests performed in the test beds and the site tests i.e., tests on machines before commissioning are also discussed. 4.2 OPEN CIRCUIT CHARACTERISTICS (MAGNETIZATION CURVE) The fundamental electric properties of an alternator can be well presented by its magnetization (no load) and short circuit characteristics. All the parameters characterizing the operation of the generator can be deduced from the above mentioned curves provided stator winding leakage reactance is known. i.e, basic vector diagram of the machine for every load may be constructed. The graphical relationship which exists between the exciting current and the terminal voltage of armature is called magnetization curve. It can be obtained experimentally by taking various values of exciting current

CHAPTER 4 TESTING AND CORRELATION - …shodhganga.inflibnet.ac.in/bitstream/10603/19490/11/11_chapter 4.pdf · CHAPTER 4 TESTING AND CORRELATION ... therefore the numerical difference

  • Upload
    haanh

  • View
    245

  • Download
    0

Embed Size (px)

Citation preview

77

CHAPTER 4

TESTING AND CORRELATION

4.1. INTRODUCTION

The testing of a machine both at the work and at site is very

important for a smooth operation of the machine. Tests are carried out

at the work to determine whether the machine has been

manufactured according to specifications of the customer and are in

conformity with the design of the electrical and mechanical designers.

Hence testing is essential at manufacturing works. This chapter,

therefore, describes preliminary tests that have to be performed before

assembling the machine in the test beds. Here, tests performed in the

test beds and the site tests i.e., tests on machines before

commissioning are also discussed.

4.2 OPEN CIRCUIT CHARACTERISTICS (MAGNETIZATION CURVE)

The fundamental electric properties of an alternator can be well

presented by its magnetization (no load) and short circuit

characteristics. All the parameters characterizing the operation of the

generator can be deduced from the above mentioned curves provided

stator winding leakage reactance is known. i.e, basic vector diagram of

the machine for every load may be constructed. The graphical

relationship which exists between the exciting current and the

terminal voltage of armature is called magnetization curve. It can be

obtained experimentally by taking various values of exciting current

78

and observing the corresponding armature voltages the machine being

operated on open circuit. Usually, it is necessary to insert a

considerable resistance in series with the field winding in addition to

the ordinary shunt regulator in order to bring down the exciting

currents so as to obtain points on the lower portion of the curve. The

resulting graph follows the general shape of the B-H curve.

4.2.1 OPEN CIRCUIT TEST on SRA:

1) Connections are made as per the circuit diagram as shown

in figure 4.1.

2) The M-G Set is brought to synchronous speed by varying DC

motor field.

3) By gradually varying the excitation, the corresponding open

circuit voltages are noted and tabulated as shown in table 4.1.

Graph is drawn between OC voltage and excitation as shown in

fig 4.2.

79

Fig 4.1: Circuit diagram for OCC test

80

Table 4.1 Observations of open circuit test

S.No. Field current

(If) in Amp.

Induced voltage

(V1) in Volts.

1 0 9

2 1.0 54

3 1.5 90

4 2.0 120

5 2.5 150

6 3.0 180

7 3.5 204

8 4.0 219

9 4.5 234

10 5.0 240

0 1 2 3 4 5 6

0

50

100

150

200

250

Field Current in Amp

Open

cir

cuit

vol

tage

in

Vol

ts

Fig. 4.2: open circuit characteristics

81

4.3 SHORT CIRCUIT CHARACTERISTICS

Under short circuit conditions the armature terminals of a

synchronous machine which is being driven by a prime mover at

synchronous speed are short circuited directly or through ammeter. It

has become a conventional that unless and until otherwise

mentioned, a short circuited synchronous machine is understood to

be a machine, where all the three terminals of which are short

circuited. The other short circuited conditions are those of two phase

and single phase short circuits as shown in figure , 4.3 , 4.4 and 4.5

respectively.

Fig.4.3: Three-phase short circuited synchronous machines

Fig.4.4: Two-phase short circuited synchronous machines

82

Fig.4.5: One-phase short circuited synchronous machines

A short circuit on a synchronous machine has the internal effect

as an inductive load since in comparison to the armature leakage

reactance, the armature resistance in almost all synchronous

machines has a negligible value. The armature mmf acts directly

opposed to the field mmf in such a case. The resultant ampere-turns

inducing the armature emf are, therefore the numerical difference

between the field and armature mmfs. Since the terminals of the

machine are short circuited, the emf induced in the armature winding

by the resultant ampere-turns is equal to the voltage drop in the

winding itself. If Me, Ma be the field and armature mmf’s, the

difference Me-Ma, representing the resultant mmf Mr, induces an emf

in the armature winding. This induced voltage balances the

impedance drop IZa in the armature winding. The occ and scc

characteristics are shown in figure 4.6

In a short circuited synchronous machine the field current is

gradually increased, the current flowing in the armature winding

increases proportionally. From the results so recorded, data to

determine short circuit ratio (SCR) could be obtained.

Fig.4.6: OCC and SCC characteristics

4.3.1. SHORT CIRCUIT TEST on SRA:

1) Connections are made as per requirement as shown in fig

2) The M-G Set is brought to synchronous speed.

3) A three phase short circuit is applied to the output of the alternator

through contactor.

4) By varying the field excitation the corresponding short circuit

current readings are noted and tabulated in table 4.2.

5) A graph is drawn between short circuit current and excitation

current as shown in Fig. 4.8.

83

ionally. From the results so recorded, data to

determine short circuit ratio (SCR) could be obtained.

Fig.4.6: OCC and SCC characteristics

SHORT CIRCUIT TEST on SRA:

Connections are made as per requirement as shown in fig

G Set is brought to synchronous speed.

3) A three phase short circuit is applied to the output of the alternator

through contactor.

4) By varying the field excitation the corresponding short circuit

current readings are noted and tabulated in table 4.2.

5) A graph is drawn between short circuit current and excitation

current as shown in Fig. 4.8.

ionally. From the results so recorded, data to

Connections are made as per requirement as shown in fig 4.7.

3) A three phase short circuit is applied to the output of the alternator

4) By varying the field excitation the corresponding short circuit

5) A graph is drawn between short circuit current and excitation

84

Fig.4.7: Circuit diagram for short circuit test

85

Table 4.2: observations of short circuit test

S.No. Field current

(If) in Amp.

Short Circuit

current (Isc) in

A mp.

1 0 0

2 1.0 1.4

3 1.5 2.3

4 2.0 3.0

5 2.5 3.8

6 3.0 4.5

7 3.5 5.4

8 4.0 6.0

9 4.5 6.6

10 5.0 7.5

0 1 2 3 4 5 6

0

1

2

3

4

5

6

7

8

Field current in Amp

Sh

ort

circu

it c

urr

en

t in

Am

p

Fig. 4.8: SC characteristics

4.4 SHORT CIRCUIT RATIO:

The short circuit ratio of a synchronous machine is defined as

the ratio of the field current required to produce rated voltage at rated

86

speed and no load to the field current required to produce rated

armature current under a sustained three phase short circuit.

If there were no saturation, the short circuit ratio would be

equal to the reciprocal of the synchronous reactance. Saturation has

the effect of increasing the short circuit ratio .The short circuit ratio

has significance with respect to both the performance of the machine

and its cost. The lower the short circuit ratio, the greater is the change

in field current required to maintain constant terminal voltage for a

given change in load and lower is the steady state limit.

If there is no saturation the short circuit ratio would be

constant at all voltage or to be exact at all excitation currents or fields.

Hence the maximum power available in steady state is directly

proportional to the short circuit ratio and can be increased by

increasing the short circuit ratio .The short circuit ratio can be

increased by increasing the air gap of the machine.

An increase in air gap would mean a bigger model and hence

contain more material. The electrical and magnetic parts of the

machine need more copper and iron respectively and hence the cost of

the machine increases. An increase in short circuit ratio further

results in increase in the steady state or sustained short circuit

current and hence the designer has to find a compromise. The

maximum power in steady state condition is also dependent upon

excitation, therefore as a result of improvements in excitation systems

87

there has been a trend towards the use of lower short circuit ratio and

consequently lower cost.

Steam turbine driven generator i.e. turbo alternator are built

with S.C.R anywhere in the range from 0.5 to 1.1 .Most modern

generator of this type have a ratios range from 0.8 to 1.1but it

appears that 0.7 is more likely used. Water wheel generators have

been designed with short circuit ratio up to 2.How ever modern water-

wheel generators are universally designed with S.C.R from 0.9 to

1.10.Synchronous condensers have the value of S.C.R as low as 0.5.

4.4.1 Short circuit ratio of SRA

The field current required to produce an induced emf equal to

rated voltage of 230V is 4.3A ( as derived from the Fig. 4.2).

The field current required to circulate a short circuit current

equal to rated current of 7A is 4.7A (as derived from the Fig.4.8).

SCR of SRA = 4.3/4.7 = 0.91

As this designed SRA is of low rating, it does not fall into

saturation while it is shorted. Hence synchronous reactance (Xs) of

this SRA is reciprocal of SCR.

Xs = 1/ (0.91) = 1.098

88

4.5. HEAT RUN TEST ON SRA

Heat run test of a synchronous machine determines the

temperature rise which is measured by using IR THERMOMETER as

shown in figure 4.10. This of the various parts of the machine under

rated load conditions. Depending on the class of insulation used the

temperature in any part of the machine should not increase beyond

permissible limits. In the case of large machines, it is not possible to

load them for rated conditions for test bed, as loading in such cases

requires large prime movers and loading capacities.

Generally, in test beds the full load heat run test is split into

two heat run tests namely the open circuit and short Circuit heat run

tests. The final temperature rise on full load is then determined by a

superimposition of the two heat run tests. It is inferred that the

temperature rise follows very nearly an exponential function and that

the thermal-time-constant of synchronous machines vary between 60

to 240 minutes. The temperature rise in the field winding can be

watched continuously by measuring the resistance of the winding by

recording the voltage and current in the field winding. The core

temperature should in no way be above 100°C as under such

conditions the teeth which have much higher flux densities are

definitely about 20°C higher than the core.

The resistance is measured by using the micro ohmmeter

shown in figure 4.9. All the observations are tabulated in table 4.3

89

and the measured cold resistance and heat resistance are tabulated in

table 4.4.

Table4.3: Observations of heat run test conducted on 06-04-2010

Voltages in V Currents in A

S.No

Time

V1

V2

V3

I1

I2

I3

N(rpm)

1 10:30 AM

390.1 389.5 389.2 6.94 6.93 6.91 1504

2 11:00 AM

387.8 387.5 387.6 6.83 6.82 6.80 1505

3 11:30 AM

385.6 385.3 385.8 6.87 6.81 6.84 1504

4 12:00 NOON

384.3 384.5 384.8 6.78 6.75 6.79 1508

5 12:30 PM

383 384.4 385.2 6.76 6.74 6.73 1508

6 1:00 PM

382 382.8 383 6.75 6.74 6.78 1508

7 2:00 PM

384.2 382.6 383.2 6.78 6.77 6.80 1508

8 3:00 PM

386.5 383.8 382.6 6.82 6.81 6.83 1508

9 4:00 PM

384.7 385.4 384.2 6.78 6.78 6.77 1508

10 4:30 PM

383.9 384 383.5 6.70 6.77 6.76 1509

… (to be continued)

90

Table 4.3: Observations of heat run test

… (to be continued)

Armature Field

S.No

Time

D.C

(Iarm)

D.C

(Varm)

D.C

(If)

D.C

(Vf)

Power

meter

(Kw)

1 10:30 AM

3.1 198 3.59 141 4.64

2 11:00 AM

3.0 202 3.72 152 4.57

3 11:30 AM

3.0 202 3.68 151 4.54

4 12:00 PM

2.9 200 3.71 152 4.48

5 12:30 NOON

2.9 201 3.71 153 4.46

6 1:00 PM

2.9 207 3.71 144 4.49

7 2:00 PM

2.9 197 3.71 134 4.49

8 3:00 PM

3.0 195 3.71 134 4.49

9 4:00 PM

3.0 193 3.71 134 4.49

10 4:30 PM

3.0 191 3.71 134 4.45

91

Table 4.3: Observations of heat run test

Temperatures in degree centigrade

S.No

Time

Room

Body

Driving

end

Non-

driving

end

1 10:30 AM

34.4 34.4 -- 37

2 11:00 AM

34.9 47.2 -- 39

3 11:30 AM

34.9 51.1 38 41

4 12:00 AM

34.9 55.3 40 42

5 12:30 NOON

34.9 56 42 44

6 1:00 PM

36.3 61 43 44

7 2:00 PM

36.9 64 45 45

8 3:00 PM

36.9 65 45 45

9 4:00 PM

36.9 66 46 46

10 4:30PM 37.7 66 46.5 46.5

92

Fig.4.9: Resistance is measured by Micro ohm meter LR-2045

Fig.4.10: Temperature measured by

FLUKE IR THERMOMETER

93

Table 4.4: Cold resistance and heat resistance

Beginning ( 10 : 30 AM) Ending ( 4 : 30 PM)

Line Resistance Line Resistance

RY = 96.6mΩ YB = 96.9.mΩ BR = 96.4mΩ

RY = 105.3mΩ YB = 105.4mΩ BR = 105.1mΩ

Phase resistances Phase resistances

RN = 47.6mΩ YN = 47.9mΩ

BN = 47.7mΩ .

RN = 51.7mΩ YN = 51.1mΩ BN = 51.4mΩ

Field Resistance Field Resistance

0.017 kΩ

0.018 kΩ

It is inferred from the table 4.3 that the thermal time constant of this

SRA is approximately 90 minutes.

4.6. LOAD CHARACTERISTICS:

The load characteristic of an alternator is obtained by

determining the relationship between the terminal voltage and the

load current, while the exciting current and the speed is kept

constant.

As the armature current is increased, the terminal voltage drops

due to many reasons, but when The power factor is leading the load

characteristic curve may raise at first. Each curve is nearly straight at

the beginning but tends to droop because, with the increase in load

94

current, the angle of lag between current and emf, owing to the

original field increases.

In modern alternators the steady short circuit current is not

much greater than full load rated current .This is purposely arranged

to prevent excessive current in the event of short circuit.

4.6.1 Load Test on SRA:

In order to obtain the relation between terminal voltage and load

current and also to determine the efficiency, load test [25] is

conducted.

The MG set is made to run at synchronous speed, the resistive

load bank is gradually applied on the machine and the corresponding

readings are tabulated as shown in the table 4.5 and graph is drawn

as shown in Fig. 4.11.

95

Table 4.5: Observations of load test

Power

meter

readings

In Kw

Terminal

voltage

(VL) in V

Load

Current

(IL) in A

Field

Current

(If) in A

0.8 392 1.2 3.8

1.22 392 1.8 3.8

1.6 385 2.4 3.8

1.8 384 2.8 3.8

2.18 382 3.3 3.8

2.4 382 3.7 3.8

2.82 378 4.3 3.8

3.2 378 4.9 3.8

3.5 378 5.4 3.8

3.7 376 5.8 3.8

4.2 375 6.6 3.8

4.6 374 7.2 3.8

96

0 1 2 3 4 5 6 7 8

0

50

100

150

200

250

300

350

400

Ter

min

al V

olta

ge in

Vol

ts

Load current in Amp

Fig. 4.11: Load characteristics

4.6.2 Efficiency

The input of the alternator is the mechanical torque of the D.C

motor which is measured by the TORQUE SENSOR as shown in figure

4.12. and its corresponding block diagram is shown in

figure 4.13

Fig.4.12 Torque Sensor

97

Fig. 4.13 Block diagram to find torque

Efficiency of the SRA = Output of SRA/ Input of SRA

Output of SRA is nothing but electrical power =

3 cos

3 378 5.4 1

3535.46

out l l

out

P VI

P W

φ= ×

= × × ×

=

Input to SRA is nothing but output of DC motor which is mechanical

power

Generally power is defined as torque (T) × angular velocity (ω )=

2

60

2 150026.275

60

4127.25

in

in

in

NP T

P

P W

π

π

= ×

× = ×

=

Shaft torque 26.275 is read by torque sensor

Efficiency of the SRA is

D.C MOTOR

TORQUE

SENSOR

S.R.A

98

3535.46

100 1004127.25

85.66%

out

in

P

η

= × = ×

=

Taking the efficiency of the prime mover i.e., DC motor as 86.5%

Efficiency of the MG-set = Efficiency of DC motor × Efficiency of SRA

= 0.865×0.8566 =0.7409

=74.09%

4.7 CONCEPT OF BALANCED AND UNBALANCED LOAD

CONDITIONS

A synchronous machine operating under balanced and

unbalanced conditions can be analyzed on the basis of two basic

concepts viz. The method of symmetrical components and Blondel’s

two reaction theory.

The set of three equal stator currents which produce a flux wave

rotating at synchronous speed with the rotor forms positive phase

sequence currents and they are designated as Ia1,Ib1 and Ic1.

The set of three equal stator currents which produce a flux wave

rotating at synchronous speed against the rotor forms negative phase

sequence currents and they are designated as Ia2,Ic2 and Ib2.

The set of three equal stator currents which produce no net

fundamental air gap flux (because the three currents are in time

phase under displaced by 120 elec degrees apart) identified as zero

sequence currents and they are designated as Ia0,Ib0 and Ic0.

99

Positive, negative and zero sequence currents may exist not only

as fundamental frequency currents but also as harmonics. For

example, under balanced conditions all triple harmonic currents are

zero sequence.

Blondel’s two reaction theory deals mainly with positive

sequence currents [26]. Unbalanced loading of a generator effects

heating of solid iron and damping circuits which is due to rotor

currents induced at twice the supply frequency. This abnormal

heating of solid iron limits the negative sequence capability of machine

[27].

The additional losses due to negative phase sequence stator

currents will exist on the surface of the rotor for solid rotor turbo

generators [28]. The study of unbalanced currents reveals significance

of rotor design features and practices.

4.7.1 BALANCED LOAD TEST

In order to observe the variations in the voltage and currents

while the SRA is subjected to phase loading, balanced load test is

conducted.

Rheostat load has been connected to the SRA and the load

setting across each branch is done by selector switches. The

corresponding readings captured by power meter are tabulated in

table 4.6 and 0ne of the reading is shown in the fig: 4.14.

100

Table 4.6: Observations of balanced load test

Fig: 4.14 power meter reading depicting balanced loads

DC MOTOR

SIDE

ALTERNATOR SIDE

S.No

Input

voltage

Input

current

V1

V2

V3

I1

I2

I3

Power

(kW)

1

195.2

2.12

102.5

102.0

103.0

0.56

0.56

0.56

0.17

2

193.2

2.52

180.1

180.3

180.1

4.3

4.3

4.3

2.32

3

192.7

2.95

232.2

231.1

232.2

5.9

5.9

5.9

4.11

101

4.7.2 UNBALANCED LOAD TEST

In order to observe the variations in the voltage and currents

while the SRA is subjected to asymmetrical loads [29], unbalanced

load test is conducted.

Rheostat load has been connected to the SRA and the load

setting across each branch is done by selector switches. The

corresponding readings captured by power meter are tabulated in

table 4.7 and 0ne of the reading is shown in the fig: 4.15.

Table 4.7: Observations of unbalanced load test

DC MOTOR SIDE

ALTERNATOR SIDE

S.No

Input

voltage

Input

current

V1

V2

V3

I1

I2

I3

P

(Kw)

1

195.4

2.13

102.3

103.1

104.6

0.55

0.57

0.56

0.17

2

194.4

2.32

58.2

50.9

40.8

1.45

1.56

2.74

0.27

3

192.2

2.51

81.5

67.3

64.2

0.98

1.61

2.72

0.35

102

Fig.4.15: Readings captured by power meter CW-140

The inverse currents [30] caused by unbalanced load in the

rotor pulsate with twice the grid frequency. Therefore, the associated

eddy currents in the solid rotor iron flow in a thin layer under the iron

surface specified by the penetration depth. Besides the skin effect

forcing them to flow in a thin layer under the iron surfaces the eddy

currents are subjected to a second skin effect. It becomes obvious

when encircling both the currents in the damper and the slot walls.

Together they built up a resultant ampere turn value which drives a

common leakage flux across the slot. It is well known that the damper

is subjected to a skin effect that displaces this currents towards the

slot openings. Without any additional reasoning it can be stated that

the same applies to the eddy currents in the slot walls. Thus, the

currents in the iron are not only limited by the impedances built up by

the iron but also by the common leakage reactance attributed to the

damper and iron currents.

103

The additional losses of the SRA due to negative sequence

currents [31] is calculated based on the readings recorded in the

above table 4.6 & 4.7. In other words, the additional losses [32] due to

negative sequence currents is nothing but the difference in power

input to the DC motor while the MG set subjected to both the

balanced and unbalanced loads.

The input power drawn by the DC motor while the MG set is

connected to the balanced load = 195.2*2.12

= 413.824 W

The input power drawn by the DC motor while the MG set is

connected to unbalanced load = 195.4*2.13

= 416.202 W

Additional loss of the SRA is nothing but the difference of above two

inputs

i.e., 416.202 - 413.824 = 2.378 W

∴ Additional losses due to Negative-seq. currents = 2.378 W

Total losses of SRA =output – input

= 3876.14-3320.3

= 555.84W

The percentage of additional losses = 2.378/555.8 = 0.43%

104

As this designed SRA is of low rating and the wedges are made of

Glass laminates, the additional losses due to negative sequence

currents are very small. In large machines the wedges are metallic and

the rotor is made of solid iron forging. Hence the negative sequence

capability is limited to 10 % in order to limit negative sequence losses

and rotor heating.

4.8 THREE PHASE SHORT CIRCUIT FAULT ON A

SYNCHRONOUS GENERATOR:

A sudden short circuit [34] in a synchronous machine takes place

if the machine is running at synchronous speed and having been

excited is suddenly short circuited on its terminals. This may take

place either when the machine is running on no-load or when it is

loaded. The loading may either be direct-loading at the terminals of

the machine or the machine may be synchronized to a grid supplying

power to the grid therewith. Modern synchronous machines are star-

connected. Synchronous machines with isolated neutrals and as such

conditions of a 3-phase or a 2-phase sudden short-circuit are the only

ones, which are of importance from a practical point of view. As a

result of sudden short-circuits, large currents flow in the machines.

Knowledge of these currents is essential in order to design the support

of the winding-head and the foundation of the machines.

In no-load operation of the synchronous machine, the total flux

linking the rotor windings consists of the useful flux Φ and field

leakage flux Фel.

105

. .po cΦ = elΦ+Φ

In steady state 3-phase short circuit operation of the machine, the

total flux linking the rotor windings consists of the effective useful flux

effΦ and the field leakage flux.

. .ps cΦ = eff el

Φ +Φ

The effective useful flux depends upon the effective field current

and can be determined with the help of the equivalent circuit diagram

of the synchronous machine in three-phase steady state short-circuit

condition. Since both the field and the armature reaction m.m.f have

their axes in the direct-axis, only the direct-axis equivalent circuit

diagram is considered. Since the steady state 3-phase short-circuit

corresponds to a purely inductive loading, the effect of the field

current is partly neutralized by the armature reaction. For a given

field current the induced e.m.f in the armature is .e adi x

The armature current I = al ad

E

x x+ =

.e ad

al ad

i x

x x+

Hence the effective field current = ei I− = .

e ad

e

al ad

i xi

x x−

+

. al

eeff e

d

xi i

x=

Therefore

106

. al

eff

d

x

xΦ = Φ

and hence

. . . al

ps c el

d

x

xΦ = Φ + Φ

The total flux linking the rotor under short-circuit conditions . .ps cΦ is

smaller than . .po cΦ which is the total flux linking the rotor under open-

circuit conditions. In case a three-phase sudden short-circuit occurs

on the terminals of an unloaded synchronous machine, the flux . .po cΦ

cannot suddenly change its value to . .ps cΦ due to the magnetic inertia.

The only difference between a sudden and a steady state short-circuit

is called for by the transients which come into play because of

magnetic inertia. Due to magnetic inertia, not only the rotor links total

flux but also the flux values linked with the three stator phases at the

instant of the sudden short circuit, have tendencies to retain their

values.

It is needless to say that a sudden short-circuits of the three

terminals of an excited synchronous machine causes large short-

circuit currents to flow in the armature of the synchronous machine.

These sudden short-circuit currents decay down to the steady state

value within a few seconds. The sudden short-circuit test is carried

out in order to determine the various constants mentioned and also to

107

see whether the machine is capable to withstand the mechanical

stresses developed by the sudden short circuit currents.

Before performing the test the machine should be carefully

inspected to see that the bracing of the stator coil ends is satisfactory

and that the foundation is in good condition and the holding down

bolts are tight. The rotor should also be inspected to see that all keys

and bolts are in place and properly tightened. Generally oscilloscope

readings are taken to determine reactances. It is, therefore, necessary

to short-circuit the machine by a circuit-breaker which closes all three

circuits at almost exactly the same instant to avoid errors due to

single phase action at the beginning of the short-circuit. Precision

shunts are used for recording the currents on an oscilloscope. It must

not be forgotten that the shunts have to be earthed.

The major effects of short circuit are increase in armature

current which in term result in large electro dynamic forces. These

forces may either be between the winding head and iron are the

between the winding heads are different phases. The large electro

dynamo forces can result in a displacement of the end portions of the

stator coils against one another. These displacements can result in an

injury to the insulation of the winding and hence shut down of the

machine. The end portions of the coils must, therefore, be specially

braced. Besides the forces in the end portions of the coils, sudden

short circuits by a synchronous machine result in torque pulsation.

108

As a result of these torques of high magnitude the casing, the

shaft and the foundation must be designed to withstand the stresses.

The very high values of armature currents cause I2R losses in

the machine which in turn result increased heating of the machine.

since the sudden short circuits are switched off with in a very

short time, the heating in the machines due to them is generally not

appreciable.

4.8.1 Three phase Short circuit Fault on SRA:

Fig 4.16: Experimental setup for 3

After assimilating the procedure of a three phase short circuit and its

effects as mentioned in the section 4.8, a t

experiment is performed on the SRA as shown in Fig.4.16

corresponding circuit diagram in

109

Three phase Short circuit Fault on SRA:

TRANSIENT RECORDER

Experimental setup for 3-phase short circuit fault

After assimilating the procedure of a three phase short circuit and its

effects as mentioned in the section 4.8, a three phase short circuit

experiment is performed on the SRA as shown in Fig.4.16

corresponding circuit diagram in Fig. 4.17

TRANSIENT RECORDER

phase short circuit fault

After assimilating the procedure of a three phase short circuit and its

hree phase short circuit

experiment is performed on the SRA as shown in Fig.4.16 and the

110

Fig: 4.17 Circuit diagram of SRA under three phase SC fault

1) The connections are made as per the circuit diagram shown in Fig

4.17

2) The MG setup is made to run at synchronous speed

3) By varying excitation the output of the SRA is brought to the 50% of

rated voltage.

4) The output terminals of SRA are short circuited through contactor

and the supply to the prime mover is disconnected instantaneously.

5) The contactor is open immediately and the transient currents are

captured by Transcoder DL –750 as shown in Fig.4.17

111

Fig. 4.18 Voltage and current of SRA during 3phase short circuit

As the damper windings are absent in the designed SRA and the

height of wedges has been machined during redesigning process. The

sub transient current is not noticeable which is evident from figure

4.18.

The behavior of the voltage before, during and after short

circuit can be well understood from Fig. 4.19.

112

Fig 4.19 Voltage: Before, during and after three phase SC fault

Fig 4.20 The currents in all three phases during three phase SHORT CIRCUIT

As the three phase short circuit is a symmetrical fault, the

currents in all the three phases will be equal in magnitude which is

depicted in Fig. 4.20.

113

4.8.2 Determination of Reactances from 3phase sudden short

circuit test

The direct-axis sub-transient and transient reactances are

determined from the current waves of a three-phase short-circuit

suddenly applied to the machine operating at no-load and rated

speed.The current peaks in one of the three phases are plotted on a

graph paper. In plotting the current values from the oscillogram, the

first peak should be plotted at abscissa 1 and subsequent peaks

numbered consequently. The positive peaks are therefore given odd

numbers and the negative even numbers.

The current values from the oscillograms should be plotted

first and then the median line and the a.c. component. The curves are

usually plotted on standard rectangular co-ordinates and most

conveniently analyzed if the currents are expressed in p.u. values,

with the unit value equal to the peak value of the rated current wave.

The a.c. component of the current is then replotted on the semi-

log scales with the current on the logarithmic scale. Since the first

peak is plotted at abscissa 1, the abscissa for the time of application

of the short-circuit is usually not at zero, but at a time which can be

readily determined from the oscillogram. The zero time line should be

drawn on the semi-log plot and extrapolations of the current curves

are extended to this line. Since the plot of the current on a semi-log

paper is represented by a straight line together with a curve of several

114

cycles at the beginning of the short-circuit, it is important to choose

such time and current scales that will avoid a steep slope during the

first three or four cycles.

The straight line in the current-time plot on a semi-log paper is

extrapolated to zero time and

dX ' = dI

E

'

Where

E = the open circuit voltage of the machine immediately before

the sudden short-circuit expressed in p.u

dI' = per unit current from the current in the transient state

dX" = dI

E

"

dI" is the per unit current from the a.c. component curve at t=0

and E has already been defined.

NOTE: It is not essential that the sudden short-circuit should be

performed to determine the values of dX" , dX ' . The method for the

determination of dX" in standstill has already been described. The

difficulty, however, arises in the determination of dX ' . The modern

practice is to determine dX" and dX ' with the help of suddenly

115

switching off the three-phase sustained short-circuit. A record of the

recovery voltage with time helps us to determine dX" and dX ' .

The following machine parameters [35] have been determined from the

Fig4.17 and 4.19.

Base KVA = 5

Base KVLL =O.400

Base Current,A = 5/(√3 * 0.400) = 6.95

Base Impedance = (Base KVLL )2* 1000/ Base KVA

= 32 Ω

Actual Impedance(Za) = Rated Voltage/Rated current

= 400/(√3 * 7.5) =30.33

Per unit Impedance =[(Za)* (KVA)B]/[ (KV)2B * 1000]

= (30.33 * 5 )/ [(0.415)*1000]

= 0.881

Sub-transient Current(Id′′) = 10 p.u

Sub-transient Reactance( Xd′′) =1.0/10= 0.1

Transient Current( Id′) = 4.5 p.u

Transient Reactance( Xd′) = 1/4.5 = 0.22

Steady state Current(Id) =0.9 p.u

116

Steady state reactance(Xd) = 1/0.9 = 1.1

Sub transient reactance, Xd″ = 0.1

Transient Reactance, Xd′ = 0.22

Steady state reactance Xd = 1.1

4.9 L – L FAULT ON SYNCHRONOUS GENERATOR

An experiment to illustrate a three phase L-L fault is performed on

the SRA as shown in Fig.4.21.

1. The MG setup is made to run at synchronous speed.

2. By varying excitation the output of the SRA is brought to the 50% of

rated voltage.

3. The two phases of output terminals of SRA are short circuited

through contactor and the supply to the prime mover is

disconnected instantaneously [36].

4. The contactor is opened immediately and the transient voltages and

currents are captured by Transcoder DL-750 as shown in

Fig.4.22and its enlarged form is shown in Fig.4.23

117

Fig 4.21 Circuit diagram for LL- Fault Experiment

Fig 4.22 Voltage and current at the instant of LL-fault

118

Fig 4.23 Enlarged wave form of V and I during L-L fault

4.9.1 Determination of Reactances from L-L fault on SRA

The direct-axis sub-transient and transient reactances are

determined from the current waves of a L-L fault suddenly applied to

the machine operating at no-load and rated speed. The procedure to

calculate the various reactances for L-L fault condition is same as

mentioned in section 4.8.2. The machine parameters for L-L fault

condition [37] have been determined from the Fig 4.22 & Fig 4.23

Sub-transient Current(Id″) = 6.4 p.u

Sub-transient Reactance( Xd″) =1.0/6.4= 0.156

Transient Current( Id′) = 4.2 p.u

Transient Reactance( Xd′) = 1/4.2 = 0.238

Steady state Current(Id) = 0.8 p.u

119

Steady state reactance(Xd) = 1/0.8 = 1.25

Sub transient reactance, Xd″ = 0.156

Transient Reactance, Xd′ = 0.238

Steady state reactance Xd = 1.25

4.10 CONCLUSIONS

1. The short circuit ratio of SRA is calculated from OC and SC

tests and found as 0.91.

2. The synchronous reactance of SRA is determined as 1.098.

3. The percentage change in resistance for a rise in temperature of

32°C is found as 10% approximately.

4. The thermal time constant of SRA is observed as 90min

5. The value of efficiency of SRA is calculated as 85.66%

6. The additional losses of the SRA due to negative sequence

currents is found 2.378W which is 0.43% of total losses

7. The machine reactances for three phase short circuit and L-L

fault are calculated from the respective graphs.

CHAPTER 5

HARMONIC COMPENSATION