CE498 Lecture Sept 26

Embed Size (px)

Citation preview

  • 7/28/2019 CE498 Lecture Sept 26

    1/57

    ENVIRONMENTAL ENGINEERING CONCRETESTRUCTURES

    CE 498 Design Project

    September 26, 2006

  • 7/28/2019 CE498 Lecture Sept 26

    2/57

    OUTLINE

    INTRODUCTION

    PERFORMANCE CRITERIA

    DESIGN LOADS AND CONDITIONS

    STRUCTURAL DESIGN

    CONCRETE MIX DESIGN

    ADDITIONAL CRITERIA

  • 7/28/2019 CE498 Lecture Sept 26

    3/57

    INTRODUCTION

    Why concrete?

    Concrete is particularly suited for this application becauseit will not warp or undergo change in dimensions

    When properly designed and placed it is nearlyimpermeable and extremely resistant to corrosion

    Has good resistance to natural and processing chemicals

    Economical but requires significant quality control

    What type of structure?

    Our focus will be conventionally reinforced cast-in-place orprecast concrete structures

    Basically rectangular and/or circular tanks

    No prestressed tanks

  • 7/28/2019 CE498 Lecture Sept 26

    4/57

    INTRODUCTION

    How should we calculate loads?

    Design loads determined from the depth and unit weight ofretained material (liquid or solid), the external soilpressure, and the equipment to be installed

    Compared to these loads, the actual live loads are small

    Impact and dynamical loads from some equipments

    What type of analysis should be done?

    The analysis must be accurate to obtain a reasonable

    picture of the stress distribution in the structure,particularly the tension stresses

    Complicated 3D FEM analysis are not required. Simpleanalysis using tabulated results in handbooks etc.

  • 7/28/2019 CE498 Lecture Sept 26

    5/57

    PERFORMANCE CRITERIA

    What are the objective of the design?

    The structure must be designed such that it is watertight,with minimum leakage or loss of contained volume.

    The structure must be durable it must last for severalyears without undergoing deterioration

    How do you get a watertight structure?

    Concrete mix design is well-proportioned and it is wellconsolidated without segregation

    Crack width is minimized Adequate reinforcing steel is used

    Impervious protective coating or barriers can also be used

    This is not as economical and dependable as the approach of

    mix design, stress & crack control, and adequate reinforcem.

  • 7/28/2019 CE498 Lecture Sept 26

    6/57

    PERFORMANCE CRITERIA

    How to design the concrete mix?

    The concrete mix can be designed to have lowpermeability by using low water-cement ratio andextended periods of moist curing

    Use water reducing agents and pozzolans to reduce

    permeability.

    How to reduce cracking?

    Cracking can be minimized by proper design, distribution of

    reinforcement, and joint spacing. Shrinkage cracking can be minimized by using joint design

    and shrinkage reinforcement distributed uniformly

  • 7/28/2019 CE498 Lecture Sept 26

    7/57

    PERFORMANCE CRITERIA

    How to increase durability?

    Concrete should be resistant to the actions of chemicals,alternate wetting and drying, and freeze-thaw cycles

    Air-entrainment in the concrete mix helps improvedurability. Add air-entrainment agents

    Reinforcement must have adequate cover to preventcorrosion

    Add good quality fly-ash or pozzolans

    Use moderately sulphate-resistant cement

  • 7/28/2019 CE498 Lecture Sept 26

    8/57

    DESIGN LOADS AND CONDITIONS

    All the loads for the structure design can be obtained from

    ASCE 7 (2006), which is the standard for minimum designloads for building structures endorsed by IBC

    Content loads

    Raw Sewage 63 lb/ft3

    Grit from grit chamber .. 110 lb/ft3

    Digested sludge aerobic. 65 lb/ft3

    Digested sludge anerobic 70 lb/ft3

    For other numbers see ACI 350.

    Live loads

    Catwalks etc 100 lb/ft2

    Heavy equipment room 300 lb/ft2

  • 7/28/2019 CE498 Lecture Sept 26

    9/57

    DESIGN LOADS AND CONDITIONS

    When using the LRFD (strength or limit states design

    approach), the load factors and combinations from ACI 318can be used directly with one major adjustment

    The load factors for both the lateral earth pressure H and thelateral liquid pressure F should be taken as 1.7

    The factored load combination U as prescribed in ACI 318must be increased by durability coefficients developed fromcrack width calculation methods:

    In calculations for reinforcement in flexure, the required

    strength should be 1.3 U In calculations for reinforcement in direct tension, including

    hoop tension, the required strength should be 1.65 U

    The required design strength for reinforcement in shearshould be calculated as fVs> 1.3 (Vu-fVc)

    For compression use 1.0 U

  • 7/28/2019 CE498 Lecture Sept 26

    10/57

    STRUCTURAL DESIGN

    Large reinforced concrete reservoirs on compressible soil

    may be considered as beams on elastic foundations. Sidewalls of rectangular tanks and reservoirs can be

    designed as either: (a) cantilever walls fixed at the bottom,or (b) walls supported at two or more edges.

    Circular tanks normally resist the pressure from contentsby ring tension

    Walls supporting both interior water loads and exterior soilpressure must be designed to support the full effects of

    each load individually Cannot use one load to minimize the other, because

    sometimes the tank is empty.

  • 7/28/2019 CE498 Lecture Sept 26

    11/57

    STRUCTURAL DESIGN

    Large diameter tanks expand and contract appreciably as

    they are filled and drained. The connection between wall and footing should either

    permit these movements or be strong enough to resist themwithout cracking

    The analysis of rectangular wall panels supported at threeor four sides is explained in detail in the PCA publicationthat is available in the library and on hold for the course

    It contains tabulated coefficients for calculating stressdistributions etc. for different boundary conditions and canbe used directly for design

    It also includes some calculation and design examples

  • 7/28/2019 CE498 Lecture Sept 26

    12/57

    STRUCTURAL DESIGN

    Reinforced concrete walls at least 10 ft. high that are in

    contact with liquids should have a minimum thickness of12 in.

    The minimum thickness of any minor member is 6 in., andwhen 2 in. cover is required then it is at least 8 in.

    For crack control, it is preferable to use a large number ofsmall diameter bars for main reinforcement rather than anequal are of larger bars

    Maximum bar spacing should not exceed 12 in.

    The amount of shrinkage and temperature reinforcement isa function of the distance between joints in the direction

    Shrinkage and temperature reinforcement should not be lessthank the ratios given in Figure 2.5 or ACI 350

    The reinforcement should not be spaced more than 12 in.and should be divided equally between the two surfaces

  • 7/28/2019 CE498 Lecture Sept 26

    13/57

    STRUCTURAL DESIGN

    Figure showing minimum shrinkage reinforcement andtable showing minimum cover for reinforcement required

  • 7/28/2019 CE498 Lecture Sept 26

    14/57

    STRUCTURAL DESIGN

    In order to prevent leakage, the strain in the tension

    reinforcement has to be limited The strain in the reinforcing bars is transferred to the

    surrounding concrete, which cracks.

    Hence, minimizing the stress and strain in the reinforcing bar

    will minimize cracking in the concrete. Additionally, distributing the tension reinforcement will

    engage a greater area of the concrete in carrying the strain,which will reduce cracking even more.

    The strength design requires the use of loads, loadcombinations and durability coefficients presented earlier

  • 7/28/2019 CE498 Lecture Sept 26

    15/57

    STRUCTURAL DESIGN

    Serviceability for normal exposures

    For flexural reinforcement located in one layer, thequantity Z (crack control factor of ACI) should not exceed115 kips/in.

    The designer can use the basic Gergley-Lutz equation for

    crack width for one way flexural members. The reinforcement for two-way flexural member may be

    proportioned in each direction using the aboverecommendation too.

    Alternate design by the working stress method withallowable stress values given and tabulated in ACI 350. Donot recommend this method for us.

  • 7/28/2019 CE498 Lecture Sept 26

    16/57

    STRUCTURAL DESIGN

    Impact, vibration, and torque issues

    When heavy machines are involved, an appropriate impactfactor of 1.25 can be used in the design

    Most of the mechanical equipment such as scrapers,clarifiers, flocculators, etc. are slow moving and will not

    cause structural vibrations Machines that cause vibration problems are forced-draft

    fans and centrifuges for dewatering clarifier sludge ordigester sludge

    The key to successful dynamic design is to make sure thatthe natural frequency of the support structure issignificantly different from frequency of disturbing force

  • 7/28/2019 CE498 Lecture Sept 26

    17/57

    STRUCTURAL DESIGN

    To minimize resonant vibrations, ratio of the natural

    frequency of the structure to the frequency of thedisturbing force must not be in the range of 0.5 to 1.5.

    It should preferably be greater than 1.5

    Methods for computing the structure frequency are

    presented in ACI 350 (please review if needed)

    Torque is produced in most clarifiers where the entiremechanism is supported on a central column

    This column must be designed to resist the torque shearwithout undergoing failure

  • 7/28/2019 CE498 Lecture Sept 26

    18/57

    MATERIAL DESIGN

    The cement should conform to:

    Portland cement ASTM C150, Types I, IA, II, IIA, .

    Blended hydraulic cement ASTM C595

    Expansive hydraulic cement ASTM C845

    They cannot be used interchangeably in the same structure

    Sulfate-resistant cement must have C3A content notexceeding 8%. This is required for concrete exposed tomoderate sulfate acctak (150 to 1000 ppm)

    Portland blast furnace slab cement (C595 may be used)

    Portland pozzolan cement (C595 IP) can also be used

    But, pozzolan content not exceed 25% by weight ofcementitous materials

  • 7/28/2019 CE498 Lecture Sept 26

    19/57

    MATERIAL DESIGN

    The air entraining admixture should conform to ASTM C260

    Improves resistant to freeze-thaw cycles

    Improves workability and less shrinkage

    If chemical admixtures are used, they should meet ASTMC494. The use of water reducing admixtures is

    recommended The maximum water-soluble chloride ion content,

    expressed as a % of cement, contributed by all ingredientsof the concrete mix should not exceed 0.10%

  • 7/28/2019 CE498 Lecture Sept 26

    20/57

    MATERIAL DESIGN

    Mix proportioning all material should be proportioned to

    produce a well-graded mix of high density and workability 28 day compressive strength of 3500 psi where the concrete

    is not exposed to severe weather and freeze-thaw

    28 day compressive strength of 4000 psi where the concrete

    is exposed to severe weather and freeze-thaw Type of cement as mentioned earlier

    Maximum water-cement ratio = 0.45

    If pozzolan is used, the maximum water-cement + pozzolan

    ratio should be 0.45 Minimum cementitious material content

    1.5 in. aggregate max 517 lb/yd3

    1 in. aggregate max 536 lb/yd3

    0.75 in. aggregate max 564 lb/yd3

  • 7/28/2019 CE498 Lecture Sept 26

    21/57

    MATERIAL DESIGN

    Air entrainment requirements

    5.5 1 % for 1.5 in. aggregate

    6.0 1 % for 1.0 or 0.75 in. aggregate

    Slump requirements

    1 in. minimum and 4 in. maximum

    Concrete placement according to ACI 350 (read when youget a chance)

    Curing using sprinkling, ponding, using moisture retainingcovers, or applying a liquid membrane-forming compoundseal coat

    Moist or membrane curing should commence immediately

    after form removal

  • 7/28/2019 CE498 Lecture Sept 26

    22/57

    ADDITIONAL CRITERIA

    Concrete made with proper material design will be dense,

    watertight, and resistant to most chemical attack. Underordinary service conditions, it does not require additionalprotection against chemical deterioration or corrosion

    Reinforcement embedded in quality concrete is well

    protected against corrosive chemicals There are only special cases where additional protective

    coatings or barriers are required

    The steel bars must be epoxy coated (ASTM A775)

    In special cases, where H2S evolves in a stagnantunventilated environment that is difficult or uneconomical tocorrect or clean regularly, a coating may be required

  • 7/28/2019 CE498 Lecture Sept 26

    23/57

    REFERENCES

    ACI 350 (1989)

    Books on reserve in the library

    Emails from Jeffrey Ballard, structural engineer, HNTB. Hewill visit to talk with us soon.

  • 7/28/2019 CE498 Lecture Sept 26

    24/57

    ENVIRONMENTAL ENGINEERING CONCRETESTRUCTURES

    CE 498 Design Project

    November 16, 21, 2006

  • 7/28/2019 CE498 Lecture Sept 26

    25/57

    OUTLINE

    INTRODUCTION

    LOADING CONDITIONS

    DESIGN METHOD

    WALL THICKNESS

    REINFORCEMENT

    CRACK CONTROL

  • 7/28/2019 CE498 Lecture Sept 26

    26/57

    INTRODUCTION

    Conventionally reinforced circular concrete tanks have

    been used extensively. They will be the focus of ourlecture today

    Structural design must focus on both the strength andserviceability. The tank must withstand applied loads

    without cracks that would permit leakage. This is achieved by:

    Providing proper reinforcement and distribution

    Proper spacing and detailing of construction joints

    Use of quality concrete placed using proper constructionprocedures

    A thorough review of the latest report by ACI 350 isimportant for understanding the design of tanks.

  • 7/28/2019 CE498 Lecture Sept 26

    27/57

    LOADING CONDITIONS

    The tank must be designed to withstand the loads that it

    will be subjected to during many years of use. Additionally,the loads during construction must also be considered.

    Loading conditions for partially buried tank.

    The tank must be designed and detailed to withstand the

    forces from each of these loading conditions

  • 7/28/2019 CE498 Lecture Sept 26

    28/57

    LOADING CONDITIONS

    The tank may also be subjected to uplift forces from

    hydrostatic pressure at the bottom when empty. It is important to consider all possible loading conditions on

    the structure.

    Full effects of the soil loads and water pressure must be

    designed for without using them to minimize the effects ofeach other.

    The effects of water table must be considered for thedesign loading conditions.

  • 7/28/2019 CE498 Lecture Sept 26

    29/57

    DESIGN METHODS

    Two approaches exist for the design of RC members

    Strength design, and allowable stress design.

    Strength design is the most commonly adopted procedure forconventional buildings

    The use of strength design was considered inappropriate

    due to the lack of reliable assessment of crack widths atservice loads.

    Advances in this area of knowledge in the last two decadeshas led to the acceptance of strength design methods

    The recommendations for strength design suggest inflatedload factors to control service load crack widths in therange of 0.004 0.008 in.

  • 7/28/2019 CE498 Lecture Sept 26

    30/57

    Design Methods

    Service state analyses of RC structures should include

    computations of crack widths and their long term effectson the structure durability and functional performance.

    The current approach for RC design include computationsdone by a modified form of elastic analysis for composite

    reinforced steel/concrete systems. The effects of creep, shrinkage, volume changes, and

    temperature are well known at service level

    The computed stresses serve as the indices of performanceof the structure.

  • 7/28/2019 CE498 Lecture Sept 26

    31/57

    DESIGN METHODS

    The load combinations to determine the required strength

    (U) are given in ACI 318. ACI 350 requires twomodifications

    Modification 1 the load factor for lateral liquid pressure istaken as 1.7 rather than 1.4. This may be over conservative

    due to the fact that tanks are filled to the top only duringleak testing or accidental overflow

    Modification 2 The members must be designed to meet therequired strength. The ACI required strength U must beincreased by multiplying with a sanitary coefficient

    The increased design loads provide more conservative designwith less cracking.

    Required strength = Sanitary coefficient X U

    Where, sanitary coefficient = 1.3 for flexure, 1.65 for directtension, and 1.3 for shear beyond the capacity provided by the

    concrete.

  • 7/28/2019 CE498 Lecture Sept 26

    32/57

    WALL THICKNESS

    The walls of circular tanks are subjected to ring or hoop

    tension due to the internal pressure and restraint toconcrete shrinkage.

    Any significant cracking in the tank is unacceptable.

    The tensile stress in the concrete (due to ring tension from

    pressure and shrinkage) has to kept at a minimum to preventexcessive cracking.

    The concrete tension strength will be assumed 10% fc in thisdocument.

    RC walls 10 ft. or higher shall have a minimum thickness of12 in.

    The concrete wall thickness will be calculated as follows:

  • 7/28/2019 CE498 Lecture Sept 26

    33/57

    WALL THICKNESS

    Effects of shrinkage

    Figure 2(a) shows a block of concretewith a re-bar. The block height is 1 ft, tcorresponds to the wall thickness, thesteel area is As, and the steel percentageis r.

    Figure 2(b) shows the behavior of theblock assuming that the re-bar is absent.The block will shorten due to shrinkage.Cis the shrinkage per unit length.

    Figure 2(c) shows the behavior of theblock when the re-bar is present. The re-bar restrains some shortening.

    The difference in length between Fig.2(b) and 2(c) is xC, an unknown quantity.

  • 7/28/2019 CE498 Lecture Sept 26

    34/57

    WALL THICKNESS

    The re-bar restrains shrinkage of the concrete. As a result,

    the concrete is subjected to tension, the re-bar tocompression, but the section is in force equilibrium

    Concrete tensile stress is fcs = xCEc

    Steel compressive stress is fss= (1-x)CEs

    Section force equilibrium. So, rfss=fcs Solve for x from above equation for force equilibrium

    The resulting stresses are:

    fss=CEs[1/(1+nr)] and fcs=CEs[r/(1+nr)]

    The concrete stress due to an applied ring or hoop tensionof T will be equal to:

    T * Ec/(EcAc+EsAs) = T * 1/[Ac+nAs] = T/[Ac(1+nr)]

    The total concrete tension stress = [CEsAs + T]/[Ac+nAs]

  • 7/28/2019 CE498 Lecture Sept 26

    35/57

    WALL THICKNESS

    The usual procedure in tank design is to provide horizontal

    steel As for all the ring tension at an allowable stress fs asthough designing for a cracked section.

    Assume As=T/fs and realize Ac=12t

    Substitute in equation on previous slide to calculate tensionstress in the concrete.

    Limit the max. concrete tension stress to fc= 0.1 fc

    Then, the wall thickness can be calculated as

    t = [CEs+fsnfc]/[12fcfs]* T

    This formula can be used to estimate the wall thickness

    The values of C, coefficient of shrinkage for RC is in therange of 0.0002 to 0.0004.

    Use the value of C=0.0003

    Assume fs= allowable steel tension =18000 psi

    Therefore, wall thickness t=0.0003 T

  • 7/28/2019 CE498 Lecture Sept 26

    36/57

    WALL THICKNESS

    The allowable steel stress fs should not be made too small.

    Low fs will actually tend to increase the concrete stress andpotential cracking.

    For example, the concrete stress = fc = [CEs+fs]/[Acfs+nT]*T

    For the case of T=24,000 lb, n=8, Es=29*106 psi, C=0.0003

    and Ac=12 x 10 = 120 in3

    If the allowable steel stress is reduced from 20,000 psi to

    10,000 psi, the resulting concrete stress is increased from266 psi to 322 psi.

    Desirable to use a higher allowable steel stress.

  • 7/28/2019 CE498 Lecture Sept 26

    37/57

    REINFORCEMENT

    The amount size and spacing of

    reinforcement has a great effecton the extent of cracking.

    The amount must be sufficientfor strength and serviceability

    including temperature andshrinkage effects

    The amount of temperature andshrinkage reinforcement isdependent on the length

    between construction joints

  • 7/28/2019 CE498 Lecture Sept 26

    38/57

    REINFORCEMENT

    The size of re-bars should be chosen recognizing that

    cracking can be better controlled by using larger number ofsmall diameter bars rather than fewer large diameter bars

    The size of reinforcing bars should not exceed #11.Spacing of re-bars should be limited to a maximum of 12

    in. Concrete cover should be at least 2 in. In circular tanks the locations of horizontal splices should

    be staggered by not less than one lap length or 3 ft.

    Reinforcement splices should confirm to ACI 318

    Chapter 12 of ACI 318 for determining splice lengths. The length depends on the class of splice, clear cover, clear

    distance between adjacent bars, and the size of the bar,concrete used, bar coating etc.

  • 7/28/2019 CE498 Lecture Sept 26

    39/57

    CRACK CONTROL

    Crack widths must be minimized in tank walls to preventleakage and corrosion of reinforcement

    A criterion for flexural crack width is provided in ACI 318.This is based on the Gergely-Lutz equation z=fs(dcA)

    1/3

    Where z = quantity limiting distribution of flexural re-bar

    dc = concrete cover measured from extreme tension fiber tocenter of bar located closest.

    A = effective tension area of concrete surrounding theflexural tension reinforcement having the same centroid asthe reinforcement, divided by the number of bars.

  • 7/28/2019 CE498 Lecture Sept 26

    40/57

    CRACK CONTROL

    In ACI 350, the cover is taken equal to 2.0 in. for any cover

    greater than 2.0 in. Rearranging the equation and solving for the maximum bar

    spacing give: max spacing = z3/(2 dc2 fs

    3)

    Using the limiting value of z given by ACI 350, the maximumbar spacing can be computed

    For ACI 350, z has a limiting value of 115 k/in.

    For severe environmental exposures, z = 95 k/in.

  • 7/28/2019 CE498 Lecture Sept 26

    41/57

    ANALYSIS OF VARIOUS TANKS

    Wall with fixed base and free top; triangular load

    Wall with hinged base and free top; triangular load andtrapezoidal load

    Wall with shear applied at top

    Wall with shear applied at base

    Wall with moment applied at top

    Wall with moment applied at base

  • 7/28/2019 CE498 Lecture Sept 26

    42/57

    CIRCULAR TANK ANALYSIS

    In practice, it would be rare that a base would be fixed

    against rotation and such an assumption would lead to animproperly designed wall.

    For the tank structure, assume

    Height = H = 20 ft.

    Diameter of inside = D = 54 ft. Weight of liquid = w = 62.5 lb/ft3

    Shrinkage coefficient = C = 0.0003

    Elasticity of steel = Es = 29 x 106 psi

    Ratio of Es/Ec = n = 8 Concrete compressive strength = fc = 4000 psi

    Yield strength of reinforcement = fy = 60,000 psi

  • 7/28/2019 CE498 Lecture Sept 26

    43/57

    It is difficult to predict the behavior of the subgrade and its

    effect upon restraint at the base. But, it is more reasonableto assume that the base is hinged rather than fixed, whichresults in more conservative design.

    For a wall with a hinged base and free top, the coefficients

    to determine the ring tension, moments, and shears in thetank wall are shown in Tables A-5, A-7, and A-12 of theAppendix

    Each of these tables, presents the results as functions ofH2/Dt, which is a parameter.

    The values of thickness t cannot be calculated till the ringtension T is calculated.

    Assume, thickness = t = 10 in.

    Therefore, H2/Dt = (202)/(54 x 10/12) = 8.89 (approx. 9 in.)

    CIRCULAR TANK ANALYSIS

  • 7/28/2019 CE498 Lecture Sept 26

    44/57

    Table A-5 showing the ring tension values

  • 7/28/2019 CE498 Lecture Sept 26

    45/57

    Table A-7, A-12 showing the moment and shear

  • 7/28/2019 CE498 Lecture Sept 26

    46/57

    CIRCULAR TANK ANALYSIS

    In these tables, 0.0 H corresponds to the top of the tank,

    and 1.0 H corresponds to the bottom of the tank. The ring tension per foot of height is computed by

    multiplying wu HR by the coefficients in Table A-5 for thevalues of H2/Dt=9.0

    wu for the case of ring tension is computed as: wu = sanitary coefficient x (1.7 x Lateral Forces)

    wu = 1.65 x (1.7 x 62.5) = 175.3 lb/ft3

    Therefore, wu HR = 175.3 x 20 x 54/2 = 94, 662 lb/ft3

    The value of wu HR corresponds to the behavior where thebase is free to slide. Since, it cannot do that, the value ofwu HR must be multiplied by coefficients from Table A-5

  • 7/28/2019 CE498 Lecture Sept 26

    47/57

    CIRCULAR TANK ANALYSIS A plus sign indicates tension, so there is a slight

    compression at the top, but it is very small.

    The ring tension is zero at the base since it is assumed thatthe base has no radial displacement

    Figure compares the ring tension for tanks with free slidingbase, fixed base, and hinged base.

  • 7/28/2019 CE498 Lecture Sept 26

    48/57

    CIRCULAR TANK ANALYSIS

    Which case is conservative? (Fixed or hinged base)

    The amount of ring steel required is given by:

    As = maximum ring tension / (0.9 Fy)

    As = 67494/(0.9 * 60000) = 1.25 in2/ft.

    Therefore at 0.7H use #6bars spaced at 8 in. on center intwo curtains.

    Resulting As = 1.32in2/ft.

    The reinforcement along the height of the wall can bedetermined similarly, but it is better to have the same barand spacing.

    Concrete cracking check The maximum tensile stress in the concrete under service

    loads including the effects of shrinkage is

    fc = [CEsAs + Tmax, unfactored]/[Ac+nAs] = 272 psi < 400 psi

    Therefore, adequate

  • 7/28/2019 CE498 Lecture Sept 26

    49/57

    CIRCULAR TANK ANALYSIS

    The moments in vertical wall strips

    that are considered 1 ft. wide arecomputed by multiplying wuH

    3 bythe coefficients from table A-7.

    The value of wu for flexure =

    sanitary coefficient x (1.7 x lateralforces)

    Therefore, wu = 1.3 x 1.7 x 62.5 =138.1 lb/ft3

    Therefore wuH3 = 138.1 x 203 =

    1,104,800 ft-lb/ft

    The computed moments along theheight are shown in the Table.

    The figure includes the moment for

    both the hinged and fix conditions

  • 7/28/2019 CE498 Lecture Sept 26

    50/57

    CIRCULAR TANK ANALYSIS

    The actual restraint is somewhere in between fixed and

    hinged, but probably closer to hinged. For the exterior face, the hinged condition provides a

    conservative although not wasteful design

    Depending on the fixity of the base, reinforcing may be

    required to resist moment on the interior face at the lowerportion of the wall.

    The required reinforcement for the outside face of the wallfor a maximum moment of 5,524 ft-lb/ft. is:

    Mu/(ffc bd2) = 0.0273 (where d = t cover dbar/2)

    From the standard design aid of Appendix A, take the valueof 0.0273 and obtain a value for w from the Table.

    Obtain w=0.0278

    Required As = wbdfc/fy = 0.167 in2

  • 7/28/2019 CE498 Lecture Sept 26

    51/57

    CIRCULAR TANK ANALYSIS

    r=0.167/(12 x 7.5) = 0.00189

    rmin = 200/Fy = 0.0033 > 0.00189 Use #5 bars at the maximum allowable spacing of 12 in.

    As = 0.31 in2 and r = 0.0035

    The shear capacity of a 10 in. wall with fc=4000 psi is Vc= 2 (fc)

    0.5 bwd = 11,384 kips

    Therefore, f Vc = 0.85 x 11,284 = 9676 kips

    The applied shear is given by multiplying wu H2 with the

    coefficient from Table A-12 The value of wu is determined with sanitary coefficient = 1.0

    (assuming that no steel rft. will be needed)

    wuH2 = 1.0 x 1.7 x 62.5 x 202 = 42,520 kips

    Applied shear = Vu = 0.092 x wuH2

    = 3912 kips < fVc

  • 7/28/2019 CE498 Lecture Sept 26

    52/57

    RECTANGULAR TANK DESIGN

    The cylindrical shape is structurally best suited for tank

    construction, but rectangular tanks are frequentlypreferred for specific purposes

    Rectangular tanks can be used instead of circular tanks whenthe footprint needs to be reduced

    Rectangular tanks are used where partitions or tanks withmore than one cell are needed.

    The behavior of rectangular tanks is different from thebehavior of circular tanks

    The behavior of circular tanks is axisymmetric. That is thereason for our analysis of only unit width of the tank

    The ring tension in circular tanks was uniform around thecircumference

  • 7/28/2019 CE498 Lecture Sept 26

    53/57

    RECTANGULAR TANK DESIGN

    The design of rectangular tanks is very similar in concept

    to the design of circular tanks The loading combinations are the same. The modifications

    for the liquid pressure loading factor and the sanitarycoefficient are the same.

    The major differences are the calculated moments, shears,and tensions in the rectangular tank walls.

    The requirements for durability are the same for rectangularand circular tanks. This is related to crack width control,which is achieved using the Gergely Lutz parameter z.

    The requirements for reinforcement (minimum or otherwise)are very similar to those for circular tanks.

    The loading conditions that must be considered for thedesign are similar to those for circular tanks.

  • 7/28/2019 CE498 Lecture Sept 26

    54/57

    RECTANGULAR TANK DESIGN

    The restraint condition at the base is needed to determine

    deflection, shears and bending moments for loadingconditions.

    Base restraint conditions considered in the publicationinclude both hinged and fixed edges.

    However, in reality, neither of these two extremes actuallyexist.

    It is important that the designer understand the degree ofrestraint provided by the reinforcing that extends into thefooting from the tank wall.

    If the designer is unsure, both extremes should beinvestigated.

    Buoyancy Forces must be considered in the design process

    The lifting force of the water pressure is resisted by the

    weight of the tank and the weight of soil on top of the slab

  • 7/28/2019 CE498 Lecture Sept 26

    55/57

    RECTANGULAR TANK BEHAVIOR

    x

    y

    y

    z

    Mx= moment per unit width about the x-axisstretching the fibers in the y direction when theplate is in the x-y plane. This momentdetermines the steel in the y (vertical direction).

    My= moment per unit width about the y-axisstretching the fibers in the x direction when the

    plate is in the x-y plane. This momentdetermines the steel in the x (horizontaldirection).

    Mz= moment per unit width about the z-axisstretching the fibers in the y direction when the

    plate is in the y-z plane. This moment determinesthe steel in the y (vertical direction).

    RECTANGULAR TANK BEHAVIOR

  • 7/28/2019 CE498 Lecture Sept 26

    56/57

    RECTANGULAR TANK BEHAVIOR

    Mxy or Myz = torsion or twisting moments for plate or wall in the x-y and

    y-z planes, respectively.

    All these moments can be computed using the equations

    Mx=(Mx Coeff.) x q a2/1000

    My=(My Coeff.) x q a2/1000

    Mz=(Mz Coeff.) x q a2/1000

    Mxy=(Mxy Coeff.) x q a2/1000

    Myz=(Myz Coeff.) x q a2/1000

    These coefficients are presented in Tables 2 and 3 for rectangular

    tanks

    The shear in one wall becomes axial tension in the adjacent wall.Follow force equilibrium - explain in class.

    RECTANGULAR TANK BEHAVIOR

  • 7/28/2019 CE498 Lecture Sept 26

    57/57

    RECTANGULAR TANK BEHAVIOR

    The twisting moment effects such as Mxy may be used to

    add to the effects of orthogonal moments Mx and My forthe purpose of determining the steel reinforcement

    The Principal of Minimum Resistance may be used fordetermining the equivalent orthogonal moments for design

    Where positive moments produce tension: Mtx = Mx + |Mxy|

    Mty = My + |Mxy|

    However, if the calculated Mtx < 0,

    then Mtx=0 and Mty=My + |Mxy2/Mx| > 0

    If the calculated Mty < 0

    Then Mty = 0 and Mtx = Mx + |Mxy2/My| > 0

    Similar equations for where negative moments producetension