BTS Alarm Descriptions
DN7095963Issue 2-0 en
# Nokia Corporation 1 (125)
Nokia WCDMA Base Station
BTS SW WN3.0 ED1
The information in this document is subject to change without notice and describes only theproduct defined in the introduction of this documentation. This document is intended for the useof Nokia's customers only for the purposes of the agreement under which the document issubmitted, and no part of it may be reproduced or transmitted in any form or means without theprior written permission of Nokia. The document has been prepared to be used by professionaland properly trained personnel, and the customer assumes full responsibility when using it.Nokia welcomes customer comments as part of the process of continuous development andimprovement of the documentation.
The information or statements given in this document concerning the suitability, capacity, orperformance of the mentioned hardware or software products cannot be considered binding butshall be defined in the agreement made between Nokia and the customer. However, Nokia hasmade all reasonable efforts to ensure that the instructions contained in the document areadequate and free of material errors and omissions. Nokia will, if necessary, explain issueswhich may not be covered by the document.
Nokia's liability for any errors in the document is limited to the documentary correction of errors.NOKIA WILL NOT BE RESPONSIBLE IN ANY EVENT FOR ERRORS IN THIS DOCUMENTOR FOR ANY DAMAGES, INCIDENTAL OR CONSEQUENTIAL (INCLUDING MONETARYLOSSES), that might arise from the use of this document or the information in it.
This document and the product it describes are considered protected by copyright according tothe applicable laws.
NOKIA logo is a registered trademark of Nokia Corporation.
Other product names mentioned in this document may be trademarks of their respectivecompanies, and they are mentioned for identification purposes only.
Copyright © Nokia Corporation 2006. All rights reserved.
2 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Contents
Contents 3
1 About this document 7
2 Alarm handling 92.1 General 92.2 Instructions for solving problems 92.3 Blocking and locking 102.4 Identifying faulty units 10
3 Nokia UltraSite and MetroSite WCDMA BTS alarm table 25
4 Alarms 274.1 Active clock tuning fault 274.2 Antenna# connection fault 284.3 ATM, A2EA configuration error 294.4 ATM cell loss 294.5 ATM faulty 304.6 ATM processor faulty 314.7 ATM traffic overload 324.8 BS SW download or activation failed 324.9 BTS Blocked 334.10 BTS config error (all units in a cell must be of same freq) 344.11 BTS config error (different WTR variants cannot coexist in cell) 344.12 BTS config error (incorrect carrier candidates) 354.13 BTS config error (Not enough HW for LCR) 364.14 BTS config error (WAF overload, 50W not in dual WPA config) 364.15 BTS config error (WPA / WSMA version conflict in cell) 374.16 BTS config error (WSMA and WSMB cannot coexist) 384.17 BTS config error (WTR used as dual TRX behind WSMA) 384.18 BTS file error 394.19 BTS RNC interface signalling link failure 404.20 Cabinet door open 414.21 Cell blocked 414.22 Cell block rejected by RNC 424.23 Cell calibration failure 424.24 Cell power monitoring 434.25 Cell power parameter out of range 444.26 Commissioning parameter mismatch 444.27 Communication failure inside WSP 454.28 Step change of oven oscillator control over 10% of control range 464.29 Diversity branch masthead amplifier fault 484.30 DSC-bus failure 504.31 DSP failure in radiolink creation 514.32 Error in commissioning data 514.33 Error in file server during SW download 524.34 Failure in AXU initialization 534.35 Cooling fan speed has reduced from the set speed 53
DN7095963Issue 2-0 en
# Nokia Corporation 3 (125)
Contents
4.36 Fatal alarm 544.37 Fault between WAM and WSP SFN (WSP) 554.38 Fault in ATM interface 564.39 Fault in OM and DSP SW interface 564.40 File corrupted in SW download 574.41 Flash operation failure 574.42 Gain adjust alarm 584.43 Incompatible SW version detected 594.44 Wrong unit type 604.45 Initial calibration not started because other cell not cleared 604.46 Invalid carrier in WTR 614.47 Invalid frequency channel for the BTS HW 624.48 LPA faulty 624.49 LPA gain fault 634.50 LPA input signal level is too high 634.51 LPA linearization fault 644.52 LPA power supply alarm 654.53 LPA reflected power too high 654.54 LPA temperature is dangerously high 664.55 Main branch masthead amplifier fault 674.56 Mains power break, running battery backup 674.57 Major alarm 684.58 Minor alarm 694.59 Missing NBAP cell parameters, defaults are used 694.60 No connection to AXU 704.61 No connection to unit 714.62 No connection to WEA and unable to detect External alarms 724.63 Non-fatal ATM traffic overload 734.64 Not enough WAF resources in LCR 734.65 Not enough WSP resources per cell 744.66 No WSM resources 754.67 Oven oscillator clock missing 754.68 Oven oscillator heating failure 764.69 POST test failed 774.70 Power unit input voltage fault 774.71 Power unit output voltage fault 784.72 R-bus error 794.73 ROM disk corrupted during SW update 804.74 SFN synchronization failure 804.75 SFN synchronization failure 814.76 SFN synchronization failure 814.77 Smoke alarm 824.78 SW does not support commissioning file 824.79 System frame clock signal missing 834.80 T-bus error 834.81 Telecom cell enabling or disabling failed 844.82 Telecom configuration failure 854.83 Timeout, commissioned resource not ready 854.84 Too many carriers allocated for LPA 864.85 Traffic flow in a non-existent ATM connection 874.86 Transmission clock missing 87
4 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.87 TX output power measurement fault 884.88 Unit autonomous reset as a recovery action 894.89 Unit blocked 894.90 Unit has lost connection to temperature sensor 904.91 Unit initialization failure 914.92 Unit initialization failure 924.93 Unit not supported by current BTS SW version 934.94 Unit SW download failed 944.95 Unit synchronization failed 954.96 Unit temperature is high 954.97 Unknown cabinet type 964.98 Unknown HW resource 964.99 [User defined] 974.100 WAF low noise amplifier faulty 984.101 WAM SFN polling timeout 984.102 WCI baseband reference clock failure 994.103 WEA power regulator fault 1004.104 WIB unit AC line break fault 1014.105 WIB unit battery failure 1014.106 WIB unit battery temperature out of range 1024.107 WIB unit power back-up time alarm 1024.108 WMC oven oscillator fault 1034.109 WPA power level changed 1054.110 WSC oven oscillator fault 1054.111 WSC phase difference jammed to zero reading 1094.112 WSC switch unsuccessful 1114.113 WSC/WMC transmission clock missing 1114.114 WSMA ST-bus error 1124.115 WSMA T-bus error 1134.116 WSMB does not receive frame clock 1144.117 WSMB RR-bus error 1154.118 WSMB SR-bus error 1154.119 WSMB ST-bus error 1164.120 WSMB T-bus error 1174.121 WSP PCI-bus failure 1184.122 WSP unit internal failure 1194.123 WTR internal clock faulty 1194.124 WTR internal clock faulty 1204.125 WTR local oscillator not locked 1204.126 WTR loop synthesizer not locked 1214.127 WTR output power decreased 1224.128 WTR output power fault 1224.129 WTR power supply voltage fault 1234.130 WTR RT-bus fault 1234.131 WTR synthesizer is not locked 1244.132 WTR temperature is high 125
DN7095963Issue 2-0 en
# Nokia Corporation 5 (125)
Contents
6 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
1 About this document
The purpose of this document is to describe the alarms and alarm handling of theNokia UltraSite WCDMA Base Station (BTS) family, the Nokia MetroSiteWCDMA Base Station and the Nokia MetroSite 50 WCDMA Base Station. BTSsoftware (SW) uses these alarms as a basis for internal diagnosis and faultreporting through the Radio Network Controller (RNC) to the Operations SupportSystem (OSS) and BTS Site Manager.
DN7095963Issue 2-0 en
# Nokia Corporation 7 (125)
About this document
8 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
2 Alarm handling
2.1 General
Base Station (BTS) alarm handling is based on unit state information. It preventsthe sending of unnecessary alarms by checking and updating unit states. Faultmessages come either from hardware devices or software components. The faultsare system or hardware specific. The Fault Diagnosis System creates uppernetwork alarms, which are based on an analysis of the faults, and sends them tothe BTS Site Manager and RNC.
In addition to routing to the RNC, the alarms are buffered and, for example,active BTS alarms can be seen from the RNC. NetAct is used for handling theBTS alarms.
The BTS is able to maintain alarm handling after it has been commissioned and isin a configured state. During the start-up, the BTS waits for the real time clockfrom the Network Time Protocol (NTP) server, and the fault diagnosis starts afterthe time has been set or a time-out has been detected. If the BTS is unable to setthe time using the NTP server, the default time (1.1.1990) will be used.
2.2 Instructions for solving problems
When starting to solve a problem, first refer to the instructions given in theindividual alarm descriptions.
Verify the configuration of a BTS by checking the commissioning, cabling andcorrect installation of the units at the BTS. Make sure the environment does notcause the fault. For more information on implementation, normal dailyoperations, maintenance, and troubleshooting, refer to Nokia UltraSite WCDMABase Station (BTS) family, Nokia MetroSite WCDMA Base Station and NokiaMetroSite 50 WCDMA Base Station Product Documentation sets.
DN7095963Issue 2-0 en
# Nokia Corporation 9 (125)
Alarm handling
If an active alarm is a 'Start' alarm, a unit block/unblock (if supported by the unit)or site reset is required to cancel it. If the site reset or unit block/unblock does nothelp, replace the faulty unit. See the fields 'Source of the alarm' and 'Instructions'in the corresponding alarm description.
If you cannot solve the problem by yourself, contact the local Help Desk.
2.3 Blocking and locking
The 'Cancel' alarms are always sent to hosts (BTS Site Manager and RNC). Whenthe unit or cell is in a blocked state, the 'Start' alarms are only sent to the BTS SiteManager.
When a unit or cell is unblocked, all the active alarms related to the unblockedunit or cell are automatically sent to the hosts. The locked or unlocked state of acell has no effect on sending alarms to the hosts.
2.4 Identifying faulty units
This section describes how the plug-in units are identified in different WCDMABTS cabinets and how a faulty unit can be located with the NetAct system.
See below the explanations of an example 'Alarm Dialog' window for differentfields in Figure NetAct Alarms window.
. 7652 *: reported severity
. Suppl info field: fault name
. Diag info field:
(01) number of the rack where the plug-in unit is located(HEX)
(02) number of the shelf where the plug-in unit is located(HEX)
(0A) number of the slot where the plug-in unit is located(HEX)
(0010) not applicable
(WFAA 04) faulty unit and ID
10 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Unit location numbers are used in alarm information to locate a failed unit. Themain principle for numbering locations is from top to bottom and from the left tothe right. Location numbers are defined with the following parameters:
RACK Specifies the rack of the cabinet and separates BB and RFcompartments from each other
SHELF Specifies the shelf in the cabinet
SLOT Specifies the location on the shelf
The figures below indicate how the rack, shelf and slot are defined in differentWCDMA BTS cabinets.
DN7095963Issue 2-0 en
# Nokia Corporation 11 (125)
Alarm handling
Figure 1. Supreme cabinet
12 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 2. Optima cabinet
DN7095963Issue 2-0 en
# Nokia Corporation 13 (125)
Alarm handling
Figure 3. Optima Compact Outdoor (WREB) cabinet
14 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 4. Optima Compact IBBU cabinet
DN7095963Issue 2-0 en
# Nokia Corporation 15 (125)
Alarm handling
Figure 5. Optima Compact RF extension cabinet
16 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 6. Triple-mode cabinet
DN7095963Issue 2-0 en
# Nokia Corporation 17 (125)
Alarm handling
Figure 7. MetroSite cabinet
18 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 8. MetroSite 50 cabinet
The figures below indicate how the fans are defined in different WCDMA BTScabinets.
Note fan control naming: 'FAN UNIT' refers to a group of fans including the fancontrol unit. A 'fan' is a single blower.
DN7095963Issue 2-0 en
# Nokia Corporation 19 (125)
Alarm handling
Figure 9. Fan mapping in Supreme cabinet
Figure 10. Fan mapping in Optima Compact Outdoor (WREB) cabinet
WTR
WPA
53 55 57
54 56 58
153 154
HEX FAN
155
MFUAMFUA MFUA
59
WFD
WEAC
20 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 11. Fan mapping in Optima Compact IBBU cabinet
Figure 12. Fan mapping in Optima Compact RF extension cabinet
DN7095963Issue 2-0 en
# Nokia Corporation 21 (125)
Alarm handling
Figure 13. Fan mapping in Triple-mode cabinet
22 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Figure 14. Fan mapping in MetroSite cabinet
DN7095963Issue 2-0 en
# Nokia Corporation 23 (125)
Alarm handling
Figure 15. Fan mapping in MetroSite 50 cabinet
24 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
3 Nokia UltraSite and MetroSite WCDMABTS alarm table
The table below describes the fields in the alarm table:
Table 1. Description of the fields in the alarm table
Name: The name of the fault.
Product: The name of the product in question.
Detecting unit: The unit that detects the fault.
Fault source: The equipment suspected to be faulty (sub-unit in parentheses).
Note that sometimes the actual source of the alarm is different than the one thatdetects the fault.
Meaning: A description of the fault situation.
Event type: The options are:
Event (Transient or Distur). Event type alarms can be seen in the RNC in 'Alarm History'. Notification type alarm. 'Event' alarm is not cancelled, because it is never active. No recovery actions. Event type alarm is shown in the BTS Site Manager as 'Transient' and in RNC as
'Distur'
Start. Alarm, a fault situation. The alarm is not automatically cleared (without manual operation and maintenance
work), even though the problem has been solved, but requires at least blocking/unblocking the unit or site reset.
. Recovery actions depend on the reported severity
Start/Cancel. Faults can be in a start or cancel state. The alarm is automatically cleared when the problem has been solved
Unit status: The options are:
Out of order The unit does not work
DN7095963Issue 2-0 en
# Nokia Corporation 25 (125)
Nokia UltraSite and MetroSite WCDMA BTS alarm table
Table 1. Description of the fields in the alarm table (cont.)
Degraded The main functions of the unit work, but not all
Working All functions are working, but some trouble has beennotified
Info Status change information
Effect: A description of how this fault affects the operations of this unit, and how it affects theoperations of other units. The following questions are considered:
Does the status of the unit or its sub-units have any effect on the interpretation of thefault?
Does the fault have an effect on other active faults?
Reported alarms: 7650 BASE STATION FAULTY. Start, disables all cells. Cancel, causes a site reset. No new 7651, 7653 or 7654 alarms are reported when 7650 is active
7651 BASE STATION OPERATION DEGRADED. There is no limit to how many 7651 alarms can be active at the same time
7652 BASE STATION NOTIFICATION. There is no limit to how many 7652 alarms can be active at the same time
7653 CELL FAULTY. Start, the affected cell state is set disabled. Cancel, the affected cell state is set enabled
7654 CELL OPERATION DEGRADED. There is no limit to how many 7654 alarms can be active at the same time
7655 CELL NOTIFICATION. There is no limit to how many 7655 alarms can be active at the same time
LED display: The colour of the LED representing the fault level of the unit. The options are:
Stable red Major alarm
Blinking red Minor alarm
Stable yellow Unit in standby state or unit blocking
Blinking yellow Unit in self-heating state or software downloading
Stable green Unit on and working
Alternating red and greenMHA faulty
Instructions: Describes the actions required to clear the alarm.
26 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4 Alarms
4.1 Active clock tuning fault
Name Active clock tuning fault
Product Supreme; Optima; MetroSite; Triplemode
Detecting unit WAM
Fault source Active WSC, WMC
Meaning Phase measurement cannot be performedin the active WSC or WMC.
Event type Start / Cancel
Unit status Degraded
Effect If there is only one WSC or both theactive and redundant WSCs are faulty,the synchronisation does not work andthe BTS is not operational. If there is aredundant WSC and the recovery switchoperation was successful, the BTS canwork normally. If the unit is WMC and it isfaulty, the synchronisation does not workand the BTS is not operational.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (if no working WSC orWMC)
7652 BASE STATION NOTIFICATION (ifworking redundant WSC available)
LED display Stable red
Instructions 1. 1. Fast tuning (refer to BTS Manager/Fast Tuning).
2. Block/unblock the alarming unit.
3. Replace the alarming clock unit.
DN7095963Issue 2-0 en
# Nokia Corporation 27 (125)
Alarms
Note that because of a fault situation inthe active clock, the redundant clock isnot tuned. To make sure that the tuningis correct, run "Fast Tune BTS Clock"with the BTS Site Manager afterswitchover when the new WSC is takeninto use.
If there is a WMC or only one WSC, thetuning will continue but cells will remaindisabled.
4.2 Antenna# connection fault
Name Antenna# connection fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAF
Fault source WAF
Meaning The Bias-T has detected that the reflectedTX power from the antenna hasincreased. The antenna cable betweenthe WAF and MHA is faulty or theantenna is faulty. The BIAS-T may befaulty.
Event type Start
Unit status Out of order
Effect The cell is out of use.
Reported alarms 7653 CELL FAULTY (all TX/RX-BTUs inthe cell are faulty)
7654 CELL OPERATION DEGRADED(there is a working /degraded BTU in thecell)
LED display N/A
Instructions 1. Check the Bias-T and MHAcommissioning.
2. Block/unblock the WAF unit (check ifalarm reappears after 5 minutes).
3. Check the antenna line (refer to thedocument WCDMA BTSTroubleshooting Instructions).
4. Check the PITA Cable connection(RJ45).
28 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
a. Check the voltage (refer toconnector pins in the documentWCDMA BTS TroubleshootingInstructions).
b. Check the right connection (refer tothe User Manual).
c. Check by cross-connecting RJ45cables between other sectors.
4.3 ATM, A2EA configuration error
Name ATM, A2EA configuration error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The RNC A2EA transport layer addressdoes not comply with the given BTSA2EA address.
This alarm is reported to BTS SiteManager only.
Event type Start
Unit status Working
Effect If AAL2 multiplexing is not in use, BTSoperation is not affected. If the error is inthe AXC (if AAL2 multiplexing is in use),the BTS may reject AAL2 connectionestablishment requests.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions Check and re-commission the AXC (ifAAL2 multiplexing is in use), RNC or BTSwith the correct BTS A2EA addresses.
4.4 ATM cell loss
Name ATM cell loss
Product
DN7095963Issue 2-0 en
# Nokia Corporation 29 (125)
Alarms
Supreme; Optima; Optima IBBU; OtimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning ATM cells are lost. The cell loss can becaused by a traffic overload, by the WAMreceiving an invalid ATM cell or AAL5packet, or by the data corruption on Iub(that is, bad BER).
The most common causes for this alarmare transmission network problems(causing unnecessary WAM changes).
Event type Start / Cancel
Unit status Working
Effect This can result in data loss and resendingof data.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red
Instructions 1. Check that Bandwidths (that is, cells/s)are the same at BTS, AXC and RNC.
2. Check the data integrity from theincoming Iub (refer to the documentWCDMA BTS TroubleshootingInstructions).
3. Check the other transmissionelements´ active alarms (refer to AXCAlarm Manual).
4. Check the WAM, AXU and the cablingbetween them.
4.5 ATM faulty
Name ATM faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning A WAM internal failure.
Event type Start
Unit status Out of order
30 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Effect The BTS capacity decreases. If the faultyunit is the master WAM, the BTS is faulty.
Reported alarms 7650 BASE STATION FAULTY (masterWAM)
7651 BASE STATION OPERATIONDEGRADED (slave WAM)
LED display Stable red
Instructions 1. If ping to BTS is working, restart theBTS remotely.
2. If ping to BTS is not working but ping toAXC is working, then restart AXCremotely so that the BTS is alsorestarted automatically.
3. Ping the AXC. If not working, visit thesite and restart the BTS. If this does nothelp, replace the alarming WAM unit.
4.6 ATM processor faulty
Name ATM processor faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSPC, WSPD, WSPE
Meaning There is a fault in the WAM processorSFN interrupt or the SFN is not beingupdated in the WSPC/WSPD/WSPEMCU.
There is a fault in the WAM internal busor between the WAM and WSP.
There is a MCU failure in the WAM or theATM loop test at startup has failed.
Event type Start
Unit status Out of order
Effect The BTS capacity is decreased.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. If ping to BTS is working, restart theBTS remotely.
DN7095963Issue 2-0 en
# Nokia Corporation 31 (125)
Alarms
2. If ping to BTS is not working but ping toAXC is working, then restart AXCremotely so that the BTS is alsorestarted automatically.
3. Ping the AXC. If not working, visit thesite and restart the BTS. If this does nothelp, replace the alarming WAM unit.
4.7 ATM traffic overload
Name ATM traffic overload
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSPC
Meaning A buffer overflow caused by trafficoverload. The maximum capacity isexceeded and some data discarded.
Event type Start / Cancel
Unit status Degraded
Effect This alarm has variable consequences.Calls may be cut off and, in worst cases,cells may be disabled.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Check that Bandwidths (that is, cells/s)are the same at BTS, AXC and RNC.
2. Check the data integrity from theincoming Iub (refer to the documentWCDMA BTS TroubleshootingInstructions).
3. Check the other transmissionelements´ active alarms (refer to AXCAlarm Manual).
4.8 BS SW download or activation failed
Name BS SW download or activation failed
32 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WTR, WPA/WMP
Meaning The SW update to the BTS has failed.The error can be caused by a unit resetduring the SW update, a hardwareproblem in the unit or cabinet, or acorrupted flash file system.
Event type Start / Cancel
Unit status Degraded
Effect The SW update to this BTS may not bepossible without special actions. The BTScontinues its operation with the oldsoftware.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Retry the SW update.
2. If the "ROM disk corrupted during SWupdate" or other flash memory-relatedalarm is active for the faulty unit at thesame time, replace the faulty unit.
4.9 BTS Blocked
Name BTS Blocked
Product Supreme; Optima;Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source Master WAM
Meaning The BTS is blocked with the BTS SiteManager. The meaning of the fault is toavoid alarms that may rise during a BTSmaintenance task.
Event type Start
Unit status Working
Effect The BTS does not send alarms to theRNC when the BTS is blocked. Alarmcancels are sent to the RNC.
DN7095963Issue 2-0 en
# Nokia Corporation 33 (125)
Alarms
All cells are disabled.
Reported alarms 7650 BASE STATION FAULTY
LED display Stable green
Instructions To cancel the alarm, unblock the BTS.Unblocking the BTS causes a site reset.
4.10 BTS config error (all units in a cell must be of samefreq)
Name BTS config error (all units in a cell mustbe of same freq)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source CELL
Meaning A unit with an incompatible frequencytype has been detected. All units in thecell must be of the same frequency type.
Event type Start / Cancel
Unit status Out of order
Effect The capacity drops. Cell(s) may remaindown.
Reported alarms 7653 CELL FAULTY
LED display N/A
Instructions Check the unit frequency types in the celland replace the incompatible unit with acompatible one.
4.11 BTS config error (different WTR variants cannotcoexist in cell)
Name BTS config error (different WTR variantscannot coexist in cell)
Product
34 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source RX - WTR
Meaning There are different WTR variants in thesame cell.
Event type Start / Cancel
Unit status Degraded
Effect The conflicting WTR unit is marked asfaulty (not used by the Telecom), and thecell coverage may therefore decrease.For example, if the conflicting WTRA isconfigured as the transmitter for the cell,the cell may also be shut down.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red
Instructions Replace the conflicting WTR unit with acompatible unit.
4.12 BTS config error (incorrect carrier candidates)
Name BTS config error (incorrect carriercandidates)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source LCR
Meaning Carrier candidates are commissioned foreach cell (not WTR/LTX specific).
Event type Start
Unit status Degraded
Effect The BTS cannot configure the TRX to achannel that is not physically supportedby the WTR. The WTR or TRX isinoperational.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display N/A
Instructions
DN7095963Issue 2-0 en
# Nokia Corporation 35 (125)
Alarms
Recommission (Reconfigurationcommissioning) the BTS with the correctcarrier candidate values.
4.13 BTS config error (Not enough HW for LCR)
Name BTS config error (Not enough HW forLCR)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source LCR
Meaning A dual carrier WTR has been replacedwith a single carrier WTR, and it cannotserve both cells commissioned to theWTR.
Event type Start/Cancel
Unit status Out of order
Effect The BTS capacity drops.
Reported alarms 7653 CELL FAULTY
LED display N/A
Instructions Replace the single carrier WTR with adual carrier WTR.
4.14 BTS config error (WAF overload, 50W not in dualWPA config)
Name BTS config error (WAF overload, 50W notin dual WPA config)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension
Detecting unit WAM
Fault source WPA
Meaning Two 50 W WPAs are coupled to oneWAF, or one 50 W WPA and one 28 WWPA are coupled to one WAF. Only two28 W WPAs can be coupled together toone WAF unit.
36 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Event type Start / Cancel
Unit status Out of order
Effect The TX power is not turned on in the TXchain. The BTS capacity drops. Cell(s)may remain down.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Replace the 50 W WPAs with the 28 WWPAs.
4.15 BTS config error (WPA / WSMA version conflict incell)
Name BTS config error (WPA / WSMA versionconflict in cell)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source WPA
Meaning A WPAI/WPAJ with two carriers and aWOC were detected in the combinationwith a WSMA.
Event type Start / Cancel
Unit status Out of order
Effect The related cell is disabled.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Replace the WSMA with a WSMB. Orreplace the WPAI and WPAJ with aWPAA/WPAB.
DN7095963Issue 2-0 en
# Nokia Corporation 37 (125)
Alarms
4.16 BTS config error (WSMA and WSMB cannotcoexist)
Name BTS config error (WSMA and WSMBcannot coexist)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension
Detecting unit WAM
Fault source WSMA
Meaning WSMA and WSMB units are detected inthe same cabinet. They cannot coexist inthe BTS.
Event type Start / Cancel
Unit status Out of order
Effect The BTS is out of order.
Reported alarms 7650 BASE STATION FAULTY
LED display Stable red
Instructions Replace the conflicting unit WSMA withthe WSMB, or vice versa.
4.17 BTS config error (WTR used as dual TRX behindWSMA)
Name BTS config error (WTR used as dual TRXbehind WSMA)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source WTRB, WTRD
Meaning A WTR/WSM conflict is detected. Theincompatible WTR cannot operate withthe WSMA when two TRXs are used.
Event type Start
Unit status Out of order
Effect The cell capacity drops or the cell isdisabled.
38 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
The WTR capacity in the subrack remainsunused.
The incompatible WTR unit remainsunconfigured.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Replace the incompatible unit orrecommission the BTS (ReconfigurationCommissioning) with only one TRX on.
4.18 BTS file error
Name BTS file error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The BTS unit properties data is invalid ormissing.
Event type Start
Unit status Out of order
Effect The BTS does not operate.
Reported alarms 7650 BASE STATION FAULTY (masterWAM)
7651 BASE STATION OPERATIONDEGRADED (slave WAM)
7653 CELL FAULTY (WTR or WPA withno redundant unit in a cell)
7654 CELL OPERATION DEGRADED(WTR or WPA with a redundant unit in acell)
LED display Stable red
Instructions 1. Download the SW again.
2. If the fault still exists after 10 minutes,replace the alarming unit.
DN7095963Issue 2-0 en
# Nokia Corporation 39 (125)
Alarms
4.19 BTS RNC interface signalling link failureName BTS RNC interface signalling link failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, (RNC)
Meaning A common or a dedicated Node-BApplication Protocol (NBAP) or an AAL2signalling link failure. It can be causedeither by a broken WAM, the RNC, or atransmission network problem. The mostcommon reason for this alarm isfrequently-breaking transmission.
Event type Start / Cancel
Unit status Degraded
Effect The telecom SW does not operate (on theTelecom Master WAM) and therefore theWAM is not operational. The RNC NBAPstarts link re-establishment proceduresand keeps on trying until it eithersucceeds or the link is removed.Signalling and calls through the relatedcell(s) do not work.
The user data cannot be used in therelated cell(s), but the WAM can still workas a Telecom Master WAM.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Check the other transmission elements'active alarms (refer to the AXC AlarmManual).
2. Check the BTS and RNC transmissionsettings.
3. Reset the AXC.
4. Change the WAM unit.
Note
BTS and AXC can be restarted remotely.
40 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.20 Cabinet door openName Cabinet door open
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;MetroSite 50
Detecting unit WEA
Fault source WEA
Meaning The cabinet door is open or the cabinetdoor sensor is faulty.
Event type Start / Cancel
Unit status Working
Effect No direct effect on the BTS operation.Note that the WHX fan does not stopeven when the door is open.
Reported alarms 7651 BASE STATION DEGRADED(MetroSite, MetroSite 50)
7652 BASE STATION NOTIFICATION(other products)
LED display N/A
Instructions 1. Ensure that the cabinet door(s) areproperly closed.
2. Check that the door switches functioncorrectly and that they have beenadjusted correctly.
4.21 Cell blocked
Name Cell blocked
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning The user has blocked the cell with theBTS Site Manager.
Event type Start / Cancel
Unit status Working
Effect
DN7095963Issue 2-0 en
# Nokia Corporation 41 (125)
Alarms
The BTS does not send to the RNC anyalarms related to the blocked cell or theunits commissioned to the blocked cell.Alarm sending to the BTS Site Manageris always enabled. Alarm cancels arealways sent to the RNC.
Calls through the blocked cell aretransferred to another cell. It is notpossible to establish new calls throughthe blocked cell.
Reported alarms 7653 CELL FAULTY
LED display Stable green
Instructions To cancel the alarm, unblock the cell.
4.22 Cell block rejected by RNC
Name Cell block rejected by RNC
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source LCR
Meaning The cell has been disabled due to BTSinternal reasons, for example if the RNChas rejected the normal cell blockingduring the Intelligent Shutdown.
Event type Start / Cancel
Unit status Working
Effect The cell is disabled.
Reported alarms 7653 CELL FAULTY
LED display N/A
Instructions 1. Check the other active alarms.
2. Check the mains power supply.
4.23 Cell calibration failure
Name Cell calibration failure
Product
42 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning TX power calibration failure: a CPICHsetup failure, a CPICH release failure or ageneral initial calibration failure.
Event type Start
Unit status Out of order
Effect If the initial calibration fails, the cell isfaulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Check the commissioning (LCRcablings).
2. Block/unblock the alarming unit or theWPA connected to the alarming WTR.
The unit needs to be blocked/unblocked to get initialized/configuredagain if there was an internal failure.
3. Start a looptest with BTS Manager tocheck WSM cablings.
4. Check the RF and WSM cablings.
5. Replace the alarming unit.
4.24 Cell power monitoring
Name Cell power monitoring
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WPA
Meaning The WPA/Radio output power hasdropped. There is a fault in the downlinktransmission path.
Event type Start
Unit status Out of order
Effect The cell is disabled.
DN7095963Issue 2-0 en
# Nokia Corporation 43 (125)
Alarms
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WPA. The unit needsto be blocked/unblocked to get itinitialised/configured again if there wasan internal failure.
2. Block/unblock the WTR belonging tothe same LCR.
3. Check the RF TX cabling.
4. The fault may be in the WTR or WPA(refer to the document WCDMA BTSTroubleshooting Instructions).
4.25 Cell power parameter out of range
Name Cell power parameter out of range
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source LCR
Meaning The power values in the cell configurationdata sent by the RNC are out of range.
Event type Start / Cancel
Unit status Degraded
Effect In a cell set-up, the cell is set inactiveuntil valid cell configuration data has beenreceived. In a cell reconfiguration, the cellcontinues operating with the previousconfiguration data.
Reported alarms 7655 CELL NOTIFICATION
LED display N/A
Instructions Set the correct power values to the RNC.
4.26 Commissioning parameter mismatch
Name Commissioning parameter mismatch
44 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning A commissioning parameter does nothave a valid value (the parameter ismissing or it has a value outside thevalue range) or there are errors in thecommissioning file.
Event type Start
Unit status Degraded
Effect The BTS capacity may decrease or theremay be interference in calls.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions Reconfigure the BTS with CommissioningWizard.
4.27 Communication failure inside WSP
Name Communication failure inside WSP
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSP
Fault source WSP
Meaning An internal communication failurebetween the DSP processors.
Event type Start / Cancel
Unit status Out of order
Effect The BTS capacity possibly decreases.The Digital Signal Processing (DSP) doesnot work correctly.
Reported alarms 7650 BASE STATION FAULTY (all WSPsare faulty)
7651 BASE STATION OPERATIONDEGARDED (at least one working WSP)
DN7095963Issue 2-0 en
# Nokia Corporation 45 (125)
Alarms
LED display Stable red
Instructions 1. Block/unblock the alarming WSP.
2. The fault may be in the WTR or WPA(refer to the document WCDMA BTSTroubleshooting Instructions).
Also check for other alarms. If the “Unitautonomous reset as a recovery action”alarm has occurred for the alarmingWSP, replace the alarming WSP unit.
4.28 Step change of oven oscillator control over 10% ofcontrol range
Name Step change of oven oscillator controlover 10% of control range
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSC/WMC
Meaning The reference frequency that the BTSmaster clock receives from the transportpart has changed by about 0.2 ppm ormore (which equals the changemagnitude of 204 DAC steps or more)during the measurement period (about 20minutes), compared to the BTS masterclock frequency.
The cause of the alarm can be:
1. The Iub reference frequency haschanged due to a fault in thetransmission network synchronisation(which in turn is caused by anequipment fault or a setting error). Notethat if the network synchronisationmalfunction lasts a long time, the alarmis cancelled when the BTS frequencyreaches the faulty Iub synchronisation.The alarm can also be activated if thefaulty Iub synchronisation is correctedand there is again the difference of 0.2ppm or more. The alarm is cancelledwhenever the difference becomessmaller than 0.2 ppm.
46 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
2. The Iub reference frequency fluctuatescontinuously due to a great deal of jitter/wander in the transmission network.The alarm is continuously activated/cancelled (however, the alarming statemay predominate). There is alwayssome jitter/wander in the transmissionnetwork; the limits are defined in ITU-TG.823/824/825.
3. If the BTS integrated transport partreceives the synchronisationinformation via the 2.048 MHzsynchronisation input (external clocksource), the alarm situation may becaused by a fault of that signal. In thatcase, the alarm behaviour notificationslisted with the Iub signal (see above)are also valid in this case.
4. There is an equipment fault in the BTS.The equipment fault is, however, notthe most common reason. Normally thereason can be found in the Iub/reference signal behaviour (see thedescriptions above).
Note that if the alarm 7651 BASESTATION OPERATION DEGRADED:'WSC oven oscillator fault' becomesactive, it may cause the alarm 7652BASE STATION NOTIFICATION:'Difference between BTS master clockand reference frequency' to cancel.
Event type Start / Cancel
Unit status Degraded
Effect This fault does not immediately affect theoperations of the BTS, but it is anotification that the BTS frequencydeviates from the Iub reference. The BTSmaster clock tuning continues in spite ofthe alarm, but because the BTS masterclock adjustment is quite slow in order tofilter the instabilities of the Iub interface, ittakes some time (even several hours)before the BTS operations start to beaffected.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red (WSC/WMC)
Instructions Because there are several possibilities forthe alarm activation, a BTS ClockFrequency History feature has beendeveloped. The stored history data canbe accessed via the BTS Site Manager.
DN7095963Issue 2-0 en
# Nokia Corporation 47 (125)
Alarms
The history data can be used as a tool forfinding out the reason for the fault/alarmsituation (for further instructions about thehistory feature, see the online Help of theBTS Site Manager). Depending on thepossible reason, follow the instructionsbelow:
1. In case of fault in the transmissionnetwork synchronisation, the networksynchronisation must be corrected. Thelong-term accuracy of the Iub signalmust be 0.015 ppm or better (check thecorrect Iub accuracy by measuring it).No actions on the BTS are necessarilyneeded.
2. If the basic accuracy of the Iub signal isin order but there is too much instability,that is, the jitter/wander is outside theacceptable limits, the synchronisationof the transmission network must becorrected. The limits for the jitter/wander are defined in the ITU-T G.823/824/825. No actions on the BTS areneeded.
3. In case of BTS equipment fault, thelocation may be:
a. Transport part. First check the alarms of the
AXC node with the AXCManager and act accordingly.
. If there are no alarms, check theAXC synchronisation settings.
b. WSC unit. If both the Iub reference signal
accuracy and the AXC node arein order but the WSC unit is stillalarming, run the fast tuning withthe BTS Site Manager.
. If the alarm is still active after thefast tuning is finished, reset thesite.
. If that does not help, replace theWSC unit.
Note that if the reason is in thetransmission networksynchronisation, replacing theWSC unit does not correct thesituation. Furthermore, thealarm activity (frequent alarms/cancels) points to instability inthe transmission network, not toa fault in the unit.
48 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4. After the fault situation has beencleared, the BTS master clock may alsorequire tuning because the BTS masterclock adjustment is quite slow. Thetuning may be done:. manually by changing the DAC
word (during a site visit). or with fast tuning, in which the BTS
master clock is tuned in a fewminutes automatically near the Iubreference (normal tuning takes careof the fine tuning). Note, however,that the fast tuning should only beused in case the Iub referencesignal is known as a good one.Otherwise the BTS frequency maybe tuned into a totally incorrectvalue, causing serious problems inthe network performance.
Background information:
The principle is that in the mobilenetwork, the synchronisation goes fromMSC => RNC => BTS. But in reality thatchain might be broken somewhere and,for example, when using leased lines, theBTS may take the referencesynchronisation from the transmissionnetwork of another operator. This doesnot harm the system if thesynchronisation of the leased line serviceprovider is also accurate/stabile enough.The BTS uses the incomingsynchronisation signal as a reference forthe Air interface, the accuracyrequirement of which is set by 3GPP.
4.29 Diversity branch masthead amplifier fault
Name Diversity branch masthead amplifier fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAF
Fault source (WAF), MHA
Meaning The operating voltage of the Mast HeadAmplifier (MHA) is supplied through theBias-T from the WAF. The WAF monitorsthe consumption of the current and
DN7095963Issue 2-0 en
# Nokia Corporation 49 (125)
Alarms
generates an alarm if it deviates from thenormal consumption. The cable betweenthe MHA and WAF is faulty, the Bias-T isfaulty, the MHA is faulty or the MHA doesnot exist.
Event type Start
Unit status Out of order
Effect If the MHA is faulty, the RX performanceis degraded. The size of the cell may bereduced.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Alternating red and green
Instructions 1. Check the MHA commissioningparameters.
2. Block/unblock the WAF in belongingLCR.
3. Check the RF cabling and Bias-T.
4. The fault can be in WAF, Bias-T orMHA. Refer to the document WCDMABTS Troubleshooting Instructions.
4.30 DSC-bus failure
Name DSC-bus failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSP
Meaning There is a failure in the bus between theWAM and WSP (DSC bus), which meansthat messages do not get through via thatDSC bus.
Event type Start
Unit status Out of order; Degraded
Effect If the source of the fault is at the WSPend of the bus, the DSP capacitydecreases. If the source of the fault is atthe WAM end of the bus, it is possiblethat calls will not get through at all.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
50 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
LED display Blinking red (WAM), Stable red (WSP)
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.31 DSP failure in radiolink creation
Name DSP failure in radiolink creation
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSP
Meaning Radiolink creation has failed repeatedlydue to DSP rejection or no response fromthe DSP CPU.
Event type Start
Unit status Out of order
Effect The BTS capacity may decrease.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.32 Error in commissioning data
Name Error in commissioning data
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning The WTR initialisation parameters arefaulty. The error can be caused by amissing parameter in the commissioningfile: the cabling information (main,diversity), feeder loss, local cellresources, for example.
DN7095963Issue 2-0 en
# Nokia Corporation 51 (125)
Alarms
Event type Start
Unit status Working
Effect The WTR is initialised with the defaultvalues.
The BTS capacity may decrease or theremay be interference in calls.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable green
Instructions 1. Check that the cell parameters, RXcabling, feeder loss and MHA gain arecorrect in the commissioning file.
2. Update the information if needed.Reconfiguration commissioning isrequired for correcting the values.
4.33 Error in file server during SW download
Name Error in file server during SW download
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The BTS is unable to obtain a file fromthe file server (error in FTP open or FTPget). The file server is down, the file ismissing, or the path is incorrect. Apossible error in the DCN and Iub, or auser administration error (invalidusername or password, or the user doesnot have access rights for the files).
Event type Start / Cancel
Unit status Degraded
Effect The BTS continues its operation with theold software.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red
Instructions 1. Try to repeat the SW download a fewtimes.
2. Check the FTP account user settings.
52 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
3. Check the file and path names.
4. Check the administration log on the fileserver.
4.34 Failure in AXU initialization
Name Failure in AXU initialization
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The BTS has lost connection to the AXUor the AXU SW is incompatible. The AXUdoes not respond to requests from theBTS.
Event type Start / Cancel
Unit status Degraded
Effect The RNC connection and the remote BTSSite Manager connection will not work.The CNBAP will stay down. The BTS isnot operational.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Check the AXC configuration.
2. Reset AXC unit remotely. This will alsocause a BTS restart.
4.35 Cooling fan speed has reduced from the set speed
Name Cooling fan speed has reduced from theset speed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit UltraSite, MetroSite, MetroSite 50, Triple-mode: WAM
Fault source Supreme: WFA, WPA and WHX fans
DN7095963Issue 2-0 en
# Nokia Corporation 53 (125)
Alarms
Optima family: WFA, WPA and WHX fans
Triple-mode: WFA, WMP/WTR and WHXfans
MetroSite, MetroSite 50: WFA fans
Meaning A fan does not rotate or rotates slowerthan at the requested speed, or the RPMinfo is not available for the fan.
Event type Start / Cancel
Unit status Degraded
Effect If the redundant fans cannot cool thecabinet sufficiently, a unit overheatingmay occur. For example, a temperaturealarm from the WPA/WMP or WTR maybe generated.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable red
Instructions 1. Check the fan ID from the alarm textand locate the problematic fan. See theFan mapping figures.
2. Check the fan and cabling.
3. If that does not help, replace the WFA,WFD or MFU module or the fancontrolled by the WFA, WFD or MFU.
Fan control: 'FAN UNIT' refers to agroup of fans including the fan controlunit. A 'fan' is a single blower.
4.36 Fatal alarm
Name Fatal alarm
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension
Detecting unit WAM
Fault source WOU
Meaning ARIO has detected a Fatal level alarm.Some ARIO alarms can be cancelledwithout reset, but most ARIO alarmsrequire a WOU block/unblock to cancel.
Event type Start / Cancel
Unit status Out of order
Effect The related cell is faulty.
54 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Check the WOU or WRUs. Use the ARIOLocal Management Tool and NokiaAdvanced Indoor Radio userdocumentation to diagnose the errorcause.
4.37 Fault between WAM and WSP SFN (WSP)
Name Fault between WAM and WSP SFN(WSP)
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSP
Fault source WSP, (WAM)
Meaning Synchronisation between the WAM andWSP is lost.
Event type Start
Unit status Out of order
Effect The BTS capacity possibly decreases.The Digital Signal Processing (DSP) doesnot work correctly.
Reported alarms 7650 BASE STATION FAULTY (all WSPsare faulty)
7651 BASE STATION OPERATIONDEGARDED (at least one working WSP)
LED display Stable red
Instructions 1. If only one WSP in the cabinetgenerates this alarm, the WSP is faulty.
2. If all WSPs in a subrack generate thisalarm, the WAM is faulty.
3. If all WSPs generate this alarm, theWSC/WMC is faulty.
Otherwise, check for other alarms. Ifthe "Unit autonomous reset as arecovery action" alarm has occurred forthe alarming WSP, replace the alarmingWSP unit.
DN7095963Issue 2-0 en
# Nokia Corporation 55 (125)
Alarms
4.38 Fault in ATM interfaceName Fault in ATM interface
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning WAM ATM interface, AXC or CIF busfailure. The AXC may have been reset.
A WAM processor failure.
Event type Start
Unit status Out of order
Effect Communication to other WAMs is notfunctioning.
The BTS capacity decreases. The BTS isfaulty if the BTS configuration has onlyone WAM or all WSPs are under thefaulty WAM.
Reported alarms 7650 BASE STATION FAULTY (withoutslave WAM recovery)
7651 BASE STATION OPERATIONDEGRADED (several WAMs with WSPs)
LED display Stable red
Instructions 1. Block/unblock the faulty unit (this willreset the BTS).
2. Swap the WAM units between subracksand check if the alarm follows the unit.Replace the faulty WAM unit.
3. Check the AXU.
4. Check the backplane connectionbetween the WAM and AXU.
4.39 Fault in OM and DSP SW interface
Name Fault in OM and DSP SW interface
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSPA, WSPC
56 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Meaning A communication failure between theWAM and DSP.
Event type Start
Unit status Out of order
Effect The Digital Signal Processing (DSP) doesnot work correctly. The BTS capacitypossibly decreases.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.40 File corrupted in SW download
Name File corrupted in SW download
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The SW being downloaded is corruptedor incorrectly formed.
Event type Start / Cancel
Unit status Working
Effect The BTS continues its operation with theold software.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions 1. Retry the SW update.
2. Fetch BTS log files and check thedownload status from the BTS SWDLreport.
4.41 Flash operation failure
Name Flash operation failure
DN7095963Issue 2-0 en
# Nokia Corporation 57 (125)
Alarms
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM, WTR, WPA/WMP, WSPC
Fault source WAM, WTR, WPA/WMP, WSPC
Meaning The flash memory operation failure. If thisalarm appears continuously, the flash chipmay be broken.
Event type Start
Unit status Degraded
Effect BTS memory operations are not stable,for example the software download andparameter updates.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (if unit is WAM, WSPC)
7654 CELL OPERATION DEGRADED (ifunit is WPA/WMP or WTR)
LED display Blinking red
Instructions 1. Check the other active alarms. If theROM disk is corrupted, change thealarming unit.
2. Block/unblock the faulty unit.
There are no recovery actions and dueto that the block/unblock can be triedonce. If that does not help, replace thefaulty unit.
4.42 Gain adjust alarm
Name Gain adjust alarm
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning The WTR cannot adjust the TX outputpower.
Event type Start / Cancel
Unit status Degraded
Effect
58 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
The WTR gain fluctuations cannot beadjusted, which affects the cell outputpower accuracy. The operation of therelated cell is degraded and there may bedisturbances or cutoffs in calls.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red (WTR)
Instructions 1. Block/unblock the WTR. The unit needsto be blocked/unblocked to get itinitialised/configured again if there wasan internal failure.
2. Check the WTR RF TX cabling.
3. If that does not help, replace thealarming unit.
4.43 Incompatible SW version detected
Name Incompatible SW version detected
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WTR, WPA/WMP
Meaning A new unit with an incompatible SW hasprobably been inserted in the BTS.
Event type Start / Cancel
Unit status Out of order
Effect The resources provided by the unitcannot be used.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WAM (or undefined))
7653 CELL FAULTY (WPA/WMP or theonly WTR in the cell)
7654 CELL OPERATION DEGRADED(WTR)
LED display Stable green
Instructions Update the compatible SW to the BTS(check the SW versions to see the activeSW version, and update the active SWversion), unless it is automaticallyupdated by the NetAct.
DN7095963Issue 2-0 en
# Nokia Corporation 59 (125)
Alarms
4.44 Wrong unit type
Name Wrong unit type
Product Supreme; Optima IBBU; Optima CompactRF Extension; MetroSite 50
Detecting unit WAM
Fault source WSMA, (WTRA, WSPA), WMCMMetroSite 50/WN3.0: WMCM12, WTRB
Meaning An unsupported unit (for example aWSMA, WTRA, WSPA, WMCM or WTRB)has been detected in the cabinet.
Event type Start
Unit status Out of order
Effect The BTS is faulty or the capacity isdecreased.
Reported alarms 7650 BASE STATION FAULTY (WMC)
7651 BASE STATION OPERATIONDEGRADED (WSP, MetroSite 50)
7653 CELL FAULTY (WSM, WTR)
LED display Stable red
Instructions Replace the unsupported unit with a unitof the correct type.
4.45 Initial calibration not started because other cell notcleared
Name Initial calibration not started becauseother cell not cleared
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning
60 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
There is a shared WPA/WMP in theconfiguration (WPA serves two cells). Thefirst cell needs to be calibrated andtherefore the second active cell needs tobe cleared, but the clearing fails.
Event type Start / Cancel
Unit status Degraded
Effect The initial power level of the cell isinaccurate. Continuous calibration is notperformed. The cell size may differ fromthe planned coverage.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red
Instructions 1. Block/unblock the WPA/WMP unitbelonging to the same LCR as alarmingWTR. The unit needs to be blocked/unblocked to get it initialized/configuredagain if there was an internal failure.
2. Reset the site.
4.46 Invalid carrier in WTR
Name Invalid carrier in WTR
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning There was an attempt to set the WTR toa channel not supported by the WTR (ona different frequency band).
Event type Start / Cancel
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Make sure that correct carrier numbersare in use in the RNC.
2. Commission the BTS with the correctWCDMA carrier values for the WTR.
DN7095963Issue 2-0 en
# Nokia Corporation 61 (125)
Alarms
4.47 Invalid frequency channel for the BTS HWName Invalid frequency channel for the BTS HW
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR, WPA, WIC, WAF, WMP
Meaning The requested channel in the cell set-upis not acceptable, that is, the frequencyband and/or the carrier spacing and/or thenumber of carriers is/are not acceptablefor the BTS HW.
Event type Transient
Unit status Working
Effect The BTS capacity possibly decreases.
Reported alarms 7655 CELL NOTIFICATION
LED display Stable green
Instructions Check the RNC cell parameters againstthe BTS HW configuration. The cellfrequency is out of the minimum/maximum limit of the HW, or the numberof carriers for the HW type is exceeded,or the carrier spacing limit is exceeded.There are different type variations of theHW that may have limitations in thesupported frequency range andbandwidth.
4.48 LPA faulty
Name LPA faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WPA/WMP
Fault source WPA/WMP
Meaning The unit is broken, because the startupself-test fails, the FPGA file downloadingfrom flash fails, or the synthesiser ismalfunctioning. This fault can only occurin the self-test phase.
Event type Start
62 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Unit status Out of order
Effect The unit does not operate. The relatedcell becomes faulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WPA/WMP.
2. Replace the alarming WPA/WMP.
4.49 LPA gain fault
Name LPA gain fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPA/WMP
Fault source WPA/WMP
Meaning A malfunction in some part of theamplifier, which therefore cannot performthe specified gain.
Event type Start / Cancel
Unit status Degraded
Effect The BTS capacity possibly decreases.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red
Instructions 1. Block/unblock the WPA/WMP.
2. Replace the alarming WPA/WMP.
4.50 LPA input signal level is too high
Name LPA input signal level is too high
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPA/WMP, WOU
Fault source WPA/WMP, (WTR), WOU
Meaning
DN7095963Issue 2-0 en
# Nokia Corporation 63 (125)
Alarms
The input signal level from the WTR iscritically high. The LPA gain is too low.
Event type Start
Unit status Out of order
Effect There is no RF output from the WPA/WMP, WOU. The related cell becomesfaulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WTR and WPA/WMPor WOU.
2. Check PTx Target value with NEMUand HSDPA power parameters (refer tothe Technical NoteTN_3GBTS_SW_2006_0035).
3. Replace the faulty unit.
4.51 LPA linearization fault
Name LPA linearization fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPA/WMP
Fault source WPA/WMP
Meaning The quality of the output signal is poor, orthe synthesizers are not locked.
Event type Start
Unit status Out of order
Effect There is no RF output from the WPA/WMP. The related cell becomes faulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WPA/WMP.
2. Check RF TX cabling (refer to thedocument WCDMA BTSTroubleshooting Instructions).
3. Replace the alarming unit.
64 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.52 LPA power supply alarmName LPA power supply alarm
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WPA/WMP, WOU
Fault source WPA/WMP, WOU
Meaning The internal power supply of the unit ismalfunctioning.
Event type Start
Unit status Out of order
Effect There is no RF signal at the WPA/WMPor WOU output. The related cell becomesfaulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WPA/WMP, WOU.
2. Check the power supply and WPAcablings and connectors from thebackplane (refer to the documentWCDMA BTS TroubleshootingInstructions.
3. Replace the alarming unit.
4.53 LPA reflected power too high
Name LPA reflected power too high
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPA/WMP
Fault source WPA/WMP, WAF, (cable)
Meaning A serious increase in the outputimpedance. A cable may be broken or acable connection may be faulty.
Event type Start
Unit status Out of order
Effect There is no RF output from the WPA/WMP. The related cells are disabled.
DN7095963Issue 2-0 en
# Nokia Corporation 65 (125)
Alarms
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the WPA.
2. Check the RF cabling between theWPA and WAF.
3. Check the WOC (in the redundantconfiguration) installation inaccordance with the installationinstructions (that is, check that cablelengths and codes are right betweenWTR, WIC and WPA).
4. Check the WAF, the antenna cablingand cables.
5. Replace the WPA.
4.54 LPA temperature is dangerously high
Name LPA temperature is dangerously high
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPA/WMP, WOU
Fault source WPA/WMP, WOU
Meaning The temperature of the unit is critical. Ithas reached its maximum acceptablelevel.
It is also possible that the temperaturesensor is broken.
Event type Start
Unit status Out of order
Effect There is no output from the WPA/WMP orWOU. The related cell becomes faulty.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Check the other active alarms related totemperature or cooling fan.
2. Block/unblock WPA if no other alarmingunit is present.
If block/unblock does not help, replacethe alarming unit.
66 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.55 Main branch masthead amplifier faultName Main branch masthead amplifier fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAF
Fault source (WAF), MHA
Meaning The operating voltage of the MHA issupplied through the Bias-T from theWAF. The WAF monitors the consumptionof the current and generates an alarm if itdeviates from the normal consumption.The cable between the MHA and WAF isfaulty, the Bias-T is faulty, the MHA isfaulty, or the MHA does not exist.
Event type Start
Unit status Out of order
Effect If the MHA is faulty, the RX performanceis degraded. The size of the cell may bereduced.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Alternating red and green (WAF)
Instructions 1. Check the MHA commissioningparameters.
2. Block/unblock the WAF in belongingLCR.
3. Check the RF cabling and Bias-T.
4. The fault can be in WAF, Bias-T orMHA. Refer to the document WCDMABTS Troubleshooting Instructions.
4.56 Mains power break, running battery backup
Name Mains power break, running batterybackup
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;MetroSite 50
Detecting unit WAM.
Fault source O&M master WAM
Meaning
DN7095963Issue 2-0 en
# Nokia Corporation 67 (125)
Alarms
There is a fault in the mains powersupply. The BTS has received a BatteryBackup alarm and the IntelligentShutdown procedure has been started.
Event type Start / Cancel
Unit status Degraded
Effect The battery backup unit is partly orcompletely in use. The intelligentshutdown operation is started. If themains power does not return, the cells areshut down according to the predefinedparameters.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable green
Instructions Check the mains power supply.
4.57 Major alarm
Name Major alarm
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension
Detecting unit WAM
Fault source WOU
Meaning ARIO has detected a Major level alarm.Some ARIO alarms can be cancelledwithout reset, but most ARIO alarmsrequire a WOU block/unblock to cancel.
Event type Start / Cancel
Unit status Degraded
Effect The functionality of the specific cell isdegraded.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red
Instructions Check the WOU or WRUs. Use the ARIOLocal Management Tool and NokiaAdvanced Indoor Radio userdocumentation to diagnose the errorcause.
68 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.58 Minor alarmName Minor alarm
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension
Detecting unit WAM
Fault source WOU
Meaning ARIO has detected a Minor level alarm.Some ARIO alarms can be cancelledwithout reset, but most ARIO alarmsrequire a WOU block/unblock to cancel.
Event type Start / Cancel
Unit status Degraded
Effect The functionality of the specific cell isdegraded.
Reported alarms 7654 CELL OPERATION DEGRADED
LED display Blinking red
Instructions Check the WOU or WRUs. Use the ARIOLocal Management Tool and NokiaAdvanced Indoor Radio userdocumentation to diagnose the errorcause.
4.59 Missing NBAP cell parameters, defaults are used
Name Missing NBAP cell parameters, defaultsare used
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning An alarm is generated if even one cellparameter is missing from the RNCconfiguration data and BTScommissioning file.
Event type Start
Unit status Degraded
Effect Default values are used for the cell. Thecell operation may become degraded.
Reported alarms
DN7095963Issue 2-0 en
# Nokia Corporation 69 (125)
Alarms
7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. If the parameters are configured toNokia RNC, delete and recreate BTSObject in NEMU.
2. Reconfigure the BTS withCommissioning Wizard, if the defaultvalues for the cell parameters (such ascell radius, rampdown time/step) arenot appropriate.
4.60 No connection to AXU
Name No connection to AXU
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source AXU
Meaning The master WAM detected that the AXUdoes not respond to polling messages.
Event type Start / Cancel
Unit status Out of order
Effect Links to the RNC will not work and callsare not possible.
Note
The recovery time between AXC and WAMis 15 minutes, and the O&M connectiondoes not work then.
The site is reset after the alarm iscancelled.
Reported alarms 7650 BASE STATION FAULTY
LED display Stable red
Instructions 1. Check for alarms on the AXC.
2. Restart the AXC remotely. This will alsocause a BTS restart.
3. Replace the alarming AXC unit.
70 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.61 No connection to unitName No connection to unit
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSC, WTR, WPA, WSP, WAF,WSM, WMC, WMP, WIB, WPS, WHX,WCI, WIC, WID, IFU, AXU, MHA, WEA,WFA, WOU, WFD, WCC
Meaning The connection to a unit that belongs tothe BTS configuration has been lost.
Event type Start / Cancel
Unit status Out of order
Effect If the WSC is lost, the redundant WSC isbrought into use automatically.
Depending on whether the WAM is thecabinet master, subrack primary orsecondary WAM, the cell(s) or cell group(s) are lost or their capacity decreases, orthe whole BTS is faulty.
If the alarm source is the WMC or WCI,the BTS is faulty.
If the alarm source is the WTR, WAF,WSM, WOU or WPA, the cell is blocked.
If the alarm source is the WIC, it may notbe possible to read WAF alarms.
Furthermore, additional 'No connection tounit' alarms may be issued from otherunits (WAM, WPA, WTR).
If a cancellation of the alarm 'Noconnection to unit' of the WSM or primaryWAM is sent, a site reset occurs as arecovery action.
This alarm cancels all active alarms forthe same unit.
Reported alarms 7650 BASE STATION FAULTY (O&Mmaster WAM, no redundant WSC, WMC,WCI)
7651 BASE STATION OPERATIONDEGRADED (WAM, WSP, WPS,WPS_EXT, WPS_TR, WIC)
7652 BASE STATION NOTIFICATION (Ifredundant WSC available, WID, BB_WFA,TR_WFA, WFA WHX, WIB)
DN7095963Issue 2-0 en
# Nokia Corporation 71 (125)
Alarms
7653 CELL FAULTY (TX/RX-WTR orWAF (all TX/RX WAFs in cell are broken),WSM_TR, WSM, WPA/WMP/WOU (oneWPA/WMP in a cell))
7654 CELL OPERATION DEGRADED(RX-WTR or WAF (a working TX/RX WAFexists in a cell), WPA/WMP (other workingWPA/WMP in a cell)
LED display Stable red
Instructions 1. Check the alarm history, alarming unitand subrack.
2. If SW updates have been donerecently, reload the SW.
3. If WAF or WIC is alarming, try re-commissioning the site.
4. Check that the unit is properlyconnected. If the unit LED does notlight up, the unit is faulty. The fault mayalso be in the WPS unit or backplane.
5. Check the power cables andconnectors, and I2C bus cables.
Cancel alarms: Removing and insertingthe WIC, WSM or primary WAM causes asite reset. If both WSCs are removed,inserting the first removed WSC back intothe cabinet causes a site reset.
If the 7650 BASE STATION FAULTYalarm is issued, reset the site. First try toreset the site by the software. If that doesnot help, replace the faulty unit.
4.62 No connection to WEA and unable to detectExternal alarms
Name No connection to WEA and unable todetect External alarms
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WEA
Meaning The WEA unit is missing from the BTS orit cannot be detected.
Event type Start / Cancel
72 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Unit status Out of order
Effect The external alarms will not be detected.There are problems with reporting doorand smoke alarms, for example.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable red
Instructions 1. Check the WEA and cabling.
2. If that does not help, replace thealarming unit.
To check units behind a same bus, referto the document WCDMA BTSTroubleshooting Instructions.
4.63 Non-fatal ATM traffic overload
Name Non-fatal ATM traffic overload
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning Traffic load is approaching the maximumcapacity. However, no data is discardedyet.
Event type Start / Cancel
Unit status Working
Effect Quality of service may be degraded.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red
Instructions Check that the ATM configurations in theBTS, AXC and RNC match.
4.64 Not enough WAF resources in LCR
Name Not enough WAF resources in LCR
Product
DN7095963Issue 2-0 en
# Nokia Corporation 73 (125)
Alarms
Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR
Meaning There are not enough WAF units in a cell.
Event type Start / Cancel
Unit status Out of order
Effect Some cells are inactive.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Refer to sections No connection toWAF alarms and No connection to unitin the document WCDMA BTSTroubleshooting Instructions.
2. Increase the number of WAF units inthe BTS.
MetroSite 50: Change the WAF.
4.65 Not enough WSP resources per cell
Name Not enough WSP resources per cell
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source Master WAM
Meaning The number of WSP units in the BTS istoo small. For every three cells, theremust be at least one WSP present.
Event type Start / Cancel
Unit status Working
Effect The BTS capacity drops, cell(s) may beinactive.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable green
74 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Instructions 1. Check possible WSP, WSM and WAMalarms. If Base Band pooling is in use,check LCG (Local Cell Group)commissioning. Check that all subracksare in working state.
2. Increase the number of WSP units inthe BTS.
4.66 No WSM resources
Name No WSM resources
Product Optima IBBU; Optima Compact RFExtension
Detecting unit WAM
Fault source WSM
Meaning There should be two WSM units in thesubrack 1. The WSM2 must always beconnected when the WSM1 is used. Ifthere is no connection to the WSM2, thisfault is generated for the WSM1.
Event type Start
Unit status Out of order
Effect The cell is disabled.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Insert the WSM2.
4.67 Oven oscillator clock missing
Name Oven oscillator clock missing
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSC/WMC
Fault source WSC/WMC
Meaning The WSC cannot deliver the clock signalsrequired by the other units.
DN7095963Issue 2-0 en
# Nokia Corporation 75 (125)
Alarms
Event type Start / Cancel
Unit status Out of order
Effect If there is only one clock in the cabinet,the BTS is not operational.
UltraSite: If there is an operating WSC inthe BTS, the redundant clock is broughtinto operation in case the active clockgenerates an alarm.
Reported alarms 7650 BASE STATION FAULTY (Noredundant WSC)
7652 BASE STATION NOTIFICATION(redundant WSC available)
LED display Stable red (WSC/WMC )
Instructions Replace the clock unit.
4.68 Oven oscillator heating failure
Name Oven oscillator heating failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSC/WMC
Fault source WSC/WMC
Meaning The heating of oven oscillator fails andthe unit is broken. The ambienttemperature can also be too low orchange too fast.
Event type Start / Cancel
Unit status Degraded
Effect If there is only one clock in the cabinet,the BTS can function properly for a fewdays without an external reference, butthe network performance may start todecrease gradually.
UltraSite: If there is an operating WSC inthe BTS, the redundant clock is broughtinto operation in case the active clockgenerates an alarm.
Reported alarms 7651 BASE STATION DEGRADED (noredundant WSC)
7652 BASE STATION NOTIFICATION(redundant WSC available)
76 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
LED display Blinking red (WSC/WMC)
Instructions 1. Check the active fan alarms.
2. Replace the clock unit.
4.69 POST test failed
Name POST test failed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSP
Meaning The unit or module has been testedduring the BTS power-on self test (POST)and a failure has been detected.
Event type Start
Unit status Out of order
Effect The faulty WSP is not configured, so theBTS capacity decreases.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Remove/reinsert the alarming unit.
3. Replace the alarming unit.
4.70 Power unit input voltage fault
Name Power unit input voltage fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPS
Fault source WPS (AC/DC line)
Meaning The input voltage of the BTS hasdecreased.
Event type Start / Cancel
DN7095963Issue 2-0 en
# Nokia Corporation 77 (125)
Alarms
Unit status Degraded
Effect If the voltage continues to decrease, theBTS stops functioning.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red (WPS)
Instructions 1. Check the other MAINS related activealarms.
2. Check the power supply voltage. If it isOK, replace the power cable.
3. Check the power unit.
4.71 Power unit output voltage fault
Name Power unit output voltage fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WPS
Fault source WPS
Meaning The output voltage is too low or too high.
Usually the reason for the fault is the unititself, but in some cases the reason canbe the unit that the WPS feeds.
If a short circuit occurs in the fed unit, itmay affect the WPS and the "OutputVoltage Fault" alarm is generated.
Event type Start / Cancel
Unit status Out of order
Effect The subrack and cell under the WPS unitmay become degraded or faulty.
A single faulty power unit will notadversely affect the operation of otherpower units in the system.
Reported alarms 7650 BASE STATION FAULTY (when thisfault is active for all WPS units)
7651 BASE STATION OPERATIONDEGRADED (single WPS)
LED display Stable red (WPS)
Instructions 1. Check the other active alarms.
78 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
2. Check the units that are supplied by thealarming WPS.
3. Check the backplane connectors andcables.
4. Replace the alarming WPS unit.
4.72 R-bus error
Name R-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSP
Fault source WTR
Meaning The bus between the WSP and WTRdoes not work. The R bus errors areprobably caused by a faulty WSM orWTR.
Event type Start / Cancel
Unit status Out of order; Degraded
Effect The BTS capacity possibly decreases.Calls in the affected cell may not bepossible.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WSP)
7653 CELL FAULTY (WTR/TRX)
7654 CELL OPERATION DEGRADED(WTR/TRX)
LED display Stable red
Instructions 1. If the WSM/WMC also generates analarm from a WTR unit, check the WTRand WSM cable.
2. If there are no active WSM/WMCalarms, the reason for the alarm is afaulty WSM/WMC or WSP.
3. Run a WCDMA BTS loop test to locatethe faulty unit.
4. If the WSP is faulty, block/unblock it.
5. Replace the faulty unit.
DN7095963Issue 2-0 en
# Nokia Corporation 79 (125)
Alarms
4.73 ROM disk corrupted during SW updateName ROM disk corrupted during SW update
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM, WTR, WMP, Nokia WPA
Fault source WAM, WTR, WMP, Nokia WPA
Meaning The file storing to flash fails because of acorrupted file system.
Event type Start
Unit status Working
Effect The SW update does not work.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions Replace the alarming unit.
4.74 SFN synchronization failure
Name SFN synchronization failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSPC
Meaning The WSP is not synchronised with theWAM.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases and callsmay be dropped.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. If that does not help, replace thealarming unit.
80 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.75 SFN synchronization failureName SFN synchronization failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source WAM
Meaning WAM internal synchronisation failure.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases, some cellsmay become disabled.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Check and correct the ATMconfiguration.
2. Replace the WAM.
4.76 SFN synchronization failure
Name SFN synchronization failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source Slave WAM
Meaning The slave WAM is not synchronised withthe master WAM.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases, some cell(s) may become faulty.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
DN7095963Issue 2-0 en
# Nokia Corporation 81 (125)
Alarms
2. If that does not help, replace thealarming unit.
4.77 Smoke alarm
Name Smoke alarm
Product Supreme; Optima IBBU; Optima CompactRF Extension
Detecting unit WEA
Fault source WEA
Meaning The internal smoke detector has detectedsmoke in the cabinet.
Event type Start / Cancel
Unit status Working
Effect None
Reported alarms 7652 BASE STATION NOTIFICATION
LED display N/A
Instructions 1. Check the root cause.
2. If the alarm was false, replace thealarming smoke detector.
4.78 SW does not support commissioning file
Name SW does not support commissioning file
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The software does not support the newcommissioning file loaded to the BTS.
Event type Start
Unit status Out of order
Effect The BTS is not commissioned oroperational.
Reported alarms 7650 BASE STATION FAULTY
82 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
LED display Stable red
Instructions 1. Check and correct the contents of thecommissioning file. Load the correctcommissioning file to the BTS.
2. Update the BTS software.
4.79 System frame clock signal missing
Name System frame clock signal missing
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WCI
Meaning The WAM does not receive a systemframe clock (SFCLK) from the WCI/WMC,because of the transceiver circuit in theWCI, the receiver circuit in the WAM, orthe system frame clock bus is faulty.
Event type Start
Unit status Degraded
Effect Calls via the faulty sector(s) are notpossible.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red (WAM)
Instructions 1. Block/unblock the alarming unit (WAM).This ensures that nothing unexpectedhas happened in the unit start-upphase.
2. If that does not help, replace thealarming unit (WAM).
4.80 T-bus error
Name T-bus error
Product MetroSite
Detecting unit WMC
DN7095963Issue 2-0 en
# Nokia Corporation 83 (125)
Alarms
Fault source WSP
Meaning The WMC has detected parity orsynchronisation errors in the TX samplesof the incoming T-bus from the WSP unit.
Event type Transient
Unit status Working
Effect The capacity drops.
The WTR and WSP capacity in thesubrack remains unused.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions 1. Check the WSP in the same subrack.
2. Check the alarm history. If the alarmoccurs frequently, replace the WMC orWSP.
4.81 Telecom cell enabling or disabling failed
Name Telecom cell enabling or disabling failed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source LCR
Meaning The cell enabling (the set-up of CPICHand BCH) failed, or the cell disabling (therelease of common channels) failed. Thereason could be a hardware or a busproblem, or a lack of DSP or ATMresources.
Event type Start / Cancel
Unit status Working
Effect The affected cell state remainsunchanged.
Reported alarms 7655 CELL NOTIFICATION
LED display N/A
Instructions 1. Check the other active alarms if WSPcapacity has been decreased.
2. Check if there are enough WSP units.
84 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.82 Telecom configuration failure
Name Telecom configuration failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSP, WTR, WPA/WMP
Meaning A Telecom slave configurations orregistrations failure. A unit RNWconfiguration failure. A Telecom RNWreconfiguration failure. Or a WSP unit toWAM allocation failure.
Event type Start
Unit status Out of order
Effect The affected WAM unit is not operational.In case of a WSP fault, the channelcapacity is lost and cell(s) may becomeunavailable. In case of a WTR or WPA/WMP, the associated cell(s) becomefaulty.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (if unit is WAM, WSP)
7653 CELL FAULTY (TX/RX-WTR, WPA/WMP with no redundancy)
7654 CELL OPERATION DEGRADED(RX-WTR or WPA/WMP with redundancy)
LED display Stable red
Instructions 1. Block/unblock the alarming unit. Theunit needs to be blocked/unblocked toget it initialised/configured again if therewas an internal failure.
4.83 Timeout, commissioned resource not ready
Name Timeout, commissioned resource notready
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;MetroSite 50
DN7095963Issue 2-0 en
# Nokia Corporation 85 (125)
Alarms
Detecting unit WAM
Fault source WAM, WPA, WTR, WSM
Meaning The faulty unit has not been configured orinitialised.
Event type Start
Unit status Out of order
Effect The BTS capacity is decreased.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WAM)
7653 CELL FAULTY (WPA, TX WTR/TRX)
7654 CELL OPERATION DEGRADED(RX WTR/TRX)
LED display Stable red
Instructions Recommission the site.
4.84 Too many carriers allocated for LPA
Name Too many carriers allocated for LPA
Product Supreme; Optima;Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WPA/WMP
Meaning Too many carriers have been allocated tothe WPA/WMP.
Event type Start
Unit status Out of order
Effect The WPA/WMP remains unconfigured.The affected cell stays inactive.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions Remove the additional carrier in theReconfiguration commissioning.
86 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.85 Traffic flow in a non-existent ATM connectionName Traffic flow in a non-existent ATM
connection
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, (AXC)
Meaning Traffic flow in a non-existent ATMconnection, for example due to anincorrect configuration.
Event type Start / Cancel
Unit status Degraded
Effect The BTS capacity may be decreased.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Check and correct the ATMconfiguration in the BTS, AXC andRNC.
4.86 Transmission clock missing
Name Transmission clock missing
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WCI
Fault source WCI, (AXU, IFU)
Meaning The clock of the BTS, the WSC/WMCunit, uses the Iub or the signal receivedfrom an external clock as a clockreference. The signal is routed throughthe AXC and WCI to the WSC. This alarmis generated if the WCI does not receivethe clock reference signal.
Event type Start / Cancel
Unit status Working
Effect Tuning does not follow the externalreference.
DN7095963Issue 2-0 en
# Nokia Corporation 87 (125)
Alarms
The BTS continues its operation with itsown oven oscillator.
The BTS can function properly for a fewdays without an external reference, butthe network performance may start todecrease gradually.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Check the other transmission-relatedalarms, example: link breaks.
2. Check the AXC settings.
3. Check the transmission cabling.
4. Replace the WCI unit.
4.87 TX output power measurement fault
Name TX output power measurement fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WTR, WPA/WMP/WOU
Meaning The WTR or WPA/WMP/WOU outputpower measurement has failed.
Event type Start / Cancel
Unit status Out of order
Effect The gain control feature is lost and it maygenerate interference to the network.
The NBAP common measurementmessage is incorrect due to missingmeasurement data from the WTR, WPA/WMP/WOU or RF module.
Reported alarms 7653 CELL FAULTY (TX/RX-WTR, WPA/WMP with no redundancy.)
7654 CELL OPERATION DEGRADED(RX-WTR or WPA/WMP withredundancy.)
LED display Stable red
Instructions
88 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
1. Block/unblock the alarming unit. Theunit needs to be blocked/unblocked toget it initialised/configured again if therewas an internal failure.
2. Check the units and the RF cablingbetween the WPA/WMP/WOU andWTR units (refer to the documentWCDMA BTS TroubleshootingInstructions).
4.88 Unit autonomous reset as a recovery action
Name Unit autonomous reset as a recoveryaction
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSP, WAM, WTR
Meaning There are problems in a unit. The BTStries to correct the situation by performinga recovery reset to the faulty unit.
Event type Transient
Unit status Working
Effect The faulty unit is reset.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions Check the alarm history and other activealarms of the unit.
Note
This alarm does not require any (special)actions.
4.89 Unit blocked
Name Unit blocked
Product
DN7095963Issue 2-0 en
# Nokia Corporation 89 (125)
Alarms
Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source Supreme: slave WAM, WTR, WPA, WSP,WAF, WSC
MetroSite: WTR, WMP, WSP, WAF
Optima: slave WAM, WTR, WPA, WSP,WAF, WSC
Triple-mode: slave WAM, WTR, WMP,WSP, WAF
MetroSite 50: WTR, WMP, WSP, WAFARIO: WOU
Meaning A unit is blocked with the BTS SiteManager.
The purpose of the fault is to avoidalarms that may rise during the unitmaintenance task.
Event type Start / Cancel
Unit status Out of order
Effect The BTS does not send alarms related tothe blocked unit to the RNC. Alarmsending to the BTS Site Manager isalways enabled. The alarm cancels arealways sent to the RNC.
It is not possible to establish phone callsthrough the blocked unit.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WAM, WSP)
7653 CELL FAULTY (TX/RX-WTR orWAF (all TX/RX WAFs in a cell arebroken), WPA/WMP (one WPA/WMP in acell))
7654 CELL OPERATION DEGRADED(RX-WTR or WAF (a working TX/RX WAFexists in a cell), WPA/WMP (other workingWPA/WMP in a cell))
LED display Stable red
Instructions To cancel the alarm, unblock the unit.
4.90 Unit has lost connection to temperature sensor
90 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Name Unit has lost connection to temperaturesensor
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSP, WPS, WSC/WMC, WPA/WMP, WTR, WFA
Meaning The temperature sensor may be brokenor the temperature value from thetemperature sensor is unavailable,unreliable or outside the defined limits.
Event type Start / Cancel
Unit status Working
Effect Temperature control tries to stabilize thetemperature according to the correlatedtemperature information from the adjacentunits.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions Replace the alarming unit.
4.91 Unit initialization failure
Name Unit initialization failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSP
Meaning Connection to the WSP fails due to aWSP internal failure.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases, cell(s) mayremain down.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
DN7095963Issue 2-0 en
# Nokia Corporation 91 (125)
Alarms
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.92 Unit initialization failure
Name Unit initialization failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSM, WSC/WMC, WAM, WTR, WSP,WPA/WMP, (AXU)
Meaning A unit or an IP address initialisation hasfailed.
Event type Start
Unit status Out of order; Degraded
Effect If the fault source is WSC/WMC, the BTSis not operational. If the fault source isAXU, connections to the RNC and BTSare not working. If the fault source isWAM, either the ATM or Telecom in thatunit is not working.
Reported alarms 7650 BASE STATION FAULTY (unit isWSC (non redundant), WMC, masterWAM)
7651 BASE STATION OPERATIONDEGRADED (WAM, WSM, WSP,redundant WSC available)
7653 CELL FAULTY (TX/RX-WTR, WPA/WMP)
7654 CELL OPERATION DEGRADED(RX-WTR)
LED display Blinking red (WAM)
Stable red (other faulty units)
Instructions 1. Block/unblock the alarming unit.
2. Check if the non-commissioned WAMis Master WAM. If so, this causes thealarm. Check the alarm history to knowwhy WAMs´ switchover occurred.
92 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
3. If the WAM is the alarm source, checkthe RNC IP address in thecommissioning file and modify the file ifneeded. If that does not help, perform apower-off reset.
4. If the previous step does not help,replace the alarming unit.
4.93 Unit not supported by current BTS SW version
Name Unit not supported by current BTS SWversion
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source All possible units.
Meaning An unsupported unit was found in theBTS. Typically this happens when a newunit version is installed and there is anolder BTS SW in use that does notsupport the new unit version.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases.
Reported alarms 7650 BASE STATION FAULTY (O&Mmaster WAM, no redundant WSC, WMC,WCI)
7651 BASE STATION OPERATIONDEGRADED (other WAM, WSP, WPS,WPS_EXT, WPS_TR, WIC)
7652 BASE STATION NOTIFICATION (ifredundant WSC available, WID, BB_WFA,TR_WFA, WFA WHX, WIB, WEA)
7653 CELL FAULTY (TX/RX-WTR orWAF (all TX/RX WAFs in the cell arebroken), WSM_TR, WSM, WPA/WMP(one WPA/WMP in the cell))
7654 CELL OPERATION DEGRADED(RX-WTR or WAF (a working TX/RX WAFexists in the cell), WPA/WMP (otherworking WPA/WMP in the cell))
LED display Stable red
Instructions Replace the unit or upgrade the BTS SW.
DN7095963Issue 2-0 en
# Nokia Corporation 93 (125)
Alarms
4.94 Unit SW download failed
Name Unit SW download failed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM (ATM SW), WSP (DSP SW), WSPC(MCU SW), WPA (WPA SW)
Meaning The software update to the unit or subunithas failed.
Event type Start
Unit status Out of order
Effect If the ATM SW update to an O&M masterWAM fails or the ATM Post fails, the BTSis not operational.
If the ATM SW update to slave WAMsfails or the ATM Post fails, the subrack isnot operational. If the DSP SW or WSPC(MCU SW) update fails, the BTS capacitydrops. If the WPA SW update fails, thecell is faulty. If the optical interface FPGASW update fails, communication to radiomodules does not work and the BTS isnot operational.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WAM or WSP)
7653 CELL FAULTY (WPA (one WPA inthe cell))
7654 CELL OPERATION DEGRADED(WPA (other working WPA in the cell))
LED display Stable red
Instructions 1. Block/unblock the WSP.
2. If Step 1 does not help, replace thealarming unit.
OR
Download the BTS SW again.
94 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.95 Unit synchronization failedName Unit synchronization failed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSPC
Meaning The WAM/WSPC synchronisation hasfailed.
Event type Start
Unit status Out of order
Effect The BTS capacity possibly decreases.Some cells may become disabled.
Reported alarms 7650 BASE STATION FAULTY (O&Mmaster WAM)
7651 BASE STATION OPERATIONDEGRADED (WSPC)
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.96 Unit temperature is high
Name Unit temperature is high
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM, WSP, WPS, WSC/WMC
Meaning The temperature of a unit exceeds thethreshold value.
Event type Start / Cancel
Unit status Working
Effect The operation of the BTS possiblydecreases.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable green
Instructions
DN7095963Issue 2-0 en
# Nokia Corporation 95 (125)
Alarms
Check the active fan alarms, and theairflow of the BTS.
4.97 Unknown cabinet type
Name Unknown cabinet type
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WAM
Meaning The cabinet cannot be identified by itsproduct code (or object ID). The problemis probably in the WID id.
Event type Start
Unit status Degraded
Effect The BTS starts up as a previouslydetected cabinet type. If the previouscabinet type cannot be determined, theBTS starts up as a Supreme cabinet.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Check the WID connection and replaceWID.
4.98 Unknown HW resource
Name Unknown HW resource
Product Supreme; Optima IBBU; Optima CompactRF Extension; MetroSite; Triplemode;MetroSite 50
Detecting unit WAM
Fault source All possible units according to the unit id.
Meaning A unit cannot be identified by its productcode or by its physical device address(object ID).
Event type Start
96 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Unit status Out of order
Effect The BTS capacity decreases.
Reported alarms 7650 BASE STATION FAULTY
7651 BASE STATION OPERATIONDEGRADED (WAM, WSP, WPS, WIC,WSC, WMC, WCI, WID, WFA, WHX,WIB, WEA)
7653 CELL FAULTY (TX/RX-WTR orWAF (all TX/RX WAFs in cell are broken),WSM, WPA/WMP (one WPA/WMP incell).)
7654 CELL OPERATION DEGRADED(RX-WTR or WAF (a working TX/RX WAFexists in cell), WPA/WMP (other workingWPA/WMP in cell).)
LED display Blinking red
Instructions Replace the alarming unit.
4.99 [User defined]
Name [User defined]
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;MetroSite 50
Detecting unit WEA
Fault source WEA
Meaning High or low voltage on the external alarmline.
The user specifies the fault text duringcommissioning.
Event type Start / Cancel
Unit status Working
Effect For example, with the intelligentshutdown, the WPA/WMP and the localcell resources are blocked to minimize thepower consumption. Therefore, thebattery backup can keep the AXU unit upand running longer than the other BTSunits.
Reported alarms 7401 - 7424 (EAC1=7401, EAC2=7402and so on)
LED display N/A
DN7095963Issue 2-0 en
# Nokia Corporation 97 (125)
Alarms
Instructions [User defined]
4.100 WAF low noise amplifier faulty
Name WAF low noise amplifier faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAF
Fault source WAF
Meaning One of the two RX preamplifiers (one inthe main branch and the other in thediversity branch) is faulty. The LEDindicates the faulty unit.
MetroSite 50: One, some or all of the RXpreamplifiers (max 6) are faulty. The LEDindicates the faulty unit.
Event type Start
Unit status Out of order; Degraded
Effect There are up to six antennas in a cell andif one of the antennas is functioning, thecell is operational. However, the cell andRX performance are degraded.
Reported alarms 7653 CELL FAULTY (UltraSite, MetroSite,Triple-mode: both branches are faulty.MetroSite 50: all branches are faulty)
7654 CELL OPERATION DEGRADED(UltraSite, MetroSite, Triple-mode: singlebranch. MetroSite 50: one or morebranches)
LED display Stable red
Instructions 1. Block/unblock the WAF unit. This ismost likely a HW fault, but blocking/unblocking the unit ensures that beforea site visit.
2. If that does not help, replace the faultyunit.
4.101 WAM SFN polling timeout
98 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Name WAM SFN polling timeout
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source Slave WAM
Meaning The slave WAM is not synchronised withthe master WAM.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases. Cells maybecome faulty.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
Note
After a WAM bloc/unblock, the BTS will berestarted.
2. If that does not help, replace thealarming unit.
4.102 WCI baseband reference clock failure
Name WCI baseband reference clock failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WCI
Fault source Master/Redundant WSC
Meaning The master or redundant WSC does notgenerate Baseband Reference Clock(BRCLK) to the WCI because of aninternal failure or a clock driver failure inthe WSC unit.
Event type Start / Cancel
Unit status Out of order
Effect If there is only one clock in the cabinet,the BTS is not operational.
DN7095963Issue 2-0 en
# Nokia Corporation 99 (125)
Alarms
UltraSite: If there is an operating WSC inthe BTS, the redundant clock is broughtinto operation in case the active clockgenerates an alarm.
Reported alarms 7650 BASE STATION FAULTY (if bothWSCs are faulty)
7652 BASE STATION NOTIFICATION(else)
LED display N/A
Instructions 1. Block/unblock the active WSC unit.
2. Replace the WCI unit.
3. Replace both WSC units.
4.103 WEA power regulator fault
Name WEA power regulator fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WEA
Fault source WEA
Meaning The WEA unit external interfaceconnectors are connected incorrectly, orthere is a shot circuit in the +5 VCD.
Event type Start / Cancel
Unit status Working
Effect The external connectors are notfunctioning.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Stable red
Instructions 1. Disconnect the external cables andcheck whether the alarm disappears.
2. Check the external cables andconnection.
3. If the alarm does not disappear, checkthe WEA and replace it if faulty.
100 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.104 WIB unit AC line break faultName WIB unit AC line break fault
Product MetroSite
Detecting unit WIB
Fault source WIB, (AC Line)
Meaning There is a mains break. The BTS powersupply is cut off.
Event type Start / Cancel
Unit status Working
Effect The WIB starts to supply voltage to theWPSM and continues the power supplyfor 10 s.
If the mains power does not recoverduring the 10 seconds, the BTS will shutdown due to the lack of power.
Reported alarms 7650 BASE STATION FAULTY
LED display Stable green
Instructions Check the power supply to the BTS.
4.105 WIB unit battery failure
Name WIB unit battery failure
Product MetroSite
Detecting unit WIB
Fault source WIB
Meaning WIB unit battery failure:. Several battery blocks (cells) are dead
and the back-up system is out of order.. Some of the battery blocks (cells)
reached an overcharge or a dischargevoltage in a stand-by condition.
. The voltage of one cell is notcompatible with the other cell voltages.
Event type Start / Cancel
Unit status Degraded
Effect The WIB does not work at all, or it cannotsupply sufficient power to the WPS.
Reported alarms 7652 BASE STATION NOTIFICATION
DN7095963Issue 2-0 en
# Nokia Corporation 101 (125)
Alarms
LED display Blinking red
Instructions 1. Check the battery cablings and cellvoltage levels.
2. Replace the WIB unit or battery.
4.106 WIB unit battery temperature out of range
Name WIB unit battery temperature out of range
Product MetroSite
Detecting unit WIB
Fault source WIB
Meaning Because the heater or heater control unitdoes not work correctly, the temperaturemeasured inside the unit is out of normaltemperature range.
Event type Start / Cancel
Unit status Working
Effect If the WIB is still used, the battery will runout much sooner than expected.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red (WIB)
Instructions 1. Check the temperature of the batteryspace.
2. Check the battery temperature sensor.
4.107 WIB unit power back-up time alarm
Name WIB unit power back-up time alarm
Product MetroSite
Detecting unit WIB
Fault source WIB
Meaning The WIB cannot supply nominal power for10 seconds and/or the estimated batterylife is 26 weeks or less.
Event type Start / Cancel
Unit status Degraded
102 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Effect If the WIB is still used, the battery runsout as shown in the Remaining BatteryLife Indicator.
If the battery life has ended, the "WIB unitbattery failure" alarm is generated.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Blinking red (WIB, battery life still left)
Stable red (WIB, no battery left)
Instructions Replace the WIB unit.
4.108 WMC oven oscillator fault
Name WMC oven oscillator fault
Product MetroSite
Detecting unit WAM
Fault source WMC
Meaning The oven oscillator adjusting area isreaching its limit value. The alarm isactivated if the WMC tunes the ovenoscillator so that the DAC word(parameter to control the oven oscillatoroutput frequency) value becomes lowerthan 205 or greater than 3891 (5% of thetotal adjustment area). The range for theDAC word is 0 - 4095. The cause of thealarm can be:. The Iub reference frequency has been
incorrect for a long time (up to severaldays) due to a fault in the transmissionnetwork synchronisation (which in turnis caused by an equipment fault or asetting error).
Before activating this alarm, the alarm7652 BASE STATION NOTIFICATION:'Difference between BTS master clockand reference frequency' may havebeen active.
. If the BTS-integrated transport partreceives the synchronisationinformation via the 2.048 MHzsynchronisation input (external clocksource), the alarm situation may be
DN7095963Issue 2-0 en
# Nokia Corporation 103 (125)
Alarms
caused by a fault in that signal. In thatcase the alarm behaviour notificationslisted with the Iub signal (see above)are also valid here.
. The fast tuning action of the BTSmaster clock may have been executedwithout checking if the reference signalis correct or not. If the reference signalis incorrect during the fast tuningexecution, it may result in adjusting theBTS master clock frequency far fromthe nominal value, which causesserious problems in the networkperformance.
. There is an equipment fault in the BTS.
. Due to the oven oscillator (OCXO)aging inside the WSC unit, the unit maybe approaching the end of its lifetime. Insuch a case, after the alarm activation,the DAC value is quite stable, while inthe other fault cases it may be veryunstable or at the edge of theadjustment area (0 or 4095).
Note that if the alarm 7651 BASESTATION OPERATION DEGRADED:'WMC oven oscillator fault' becomesactive, it may cause the alarm 7652BASE STATION NOTIFICATION:'Difference between BTS master clockand reference frequency' to cancel.
Event type Start / Cancel
Unit status Degraded
Effect The severity of the fault depends on thesituation:. If the WMC unit (OCXO) is approaching
the end of its lifetime but the referencefrequency is still correct, the BTS andsystem performance may be normal formonths or even one year after thealarm activation (given that the DAC isnot at the edge of the adjustment area).
. The other faults may cause the BTSand system performance to collapsedue to an incorrect air interfacefrequency.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable green
Instructions Background information:
104 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
The principle is that in a mobile network,the synchronisation goes from MSC =>RNC => BTS. But in reality, that chainmight be broken and, for example, whenusing leased lines, the BTS may take thereference synchronisation from thetransmission network of another operator.This does not harm the system if thesynchronisation of the leased line serviceprovider is accurate or stable enough.The BTS uses the incomingsynchronisation signal as a reference forthe Air interface, the accuracyrequirement of which is set by 3GPP.
1. In case of fault in the transmissionnetwork synchronisation, the networksynchronisation must be corrected. Thelong-term accuracy of the Iub signalmust be 0.015 ppm or better.
2. In case of BTS equipment fault, thelocation may be:
a. Transport part
- Check the alarms of the AXC nodewith the AXC Manager and actaccordingly.
- If there are no alarms, check theAXC synchronization.
b. WMC unit
- If both the Iub reference signalaccuracy and the AXC node are inorder but the WMC unit is stillalarming, run the fast tuningprocedure with the BTS SiteManager.
- If there is no cure in a few minutes,reset the site.
- If that does not help, replace theWMC unit.
3. After the fault situation has beencleared, the BTS master clock may alsorequire tuning, because the BTSmaster clock adjustment is quite slow.The tuning may be done:
- Manually, by changing the DAC word(during a site visit).
- With fast tuning, by which the BTSmaster clock is tuned in a few minutesautomatically near the Iub reference(normal tuning takes care of the finetuning).
DN7095963Issue 2-0 en
# Nokia Corporation 105 (125)
Alarms
Note
The fast tuning should only be used in casethe Iub reference signal is known to be agood one. Otherwise the BTS frequencymay be tuned into a totally incorrect value,causing serious problems in the networkperformance.
4.109 WPA power level changed
Name WPA power level changed
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WAM
Fault source WPA
Meaning The power level of a replaced WPA unitdiffers from the original WPA unit.
Event type Start / Cancel
Unit status Out of order
Effect The capacity drops. Cell(s) may remaindown.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions If the WPA is accidentally changed to adifferent power level type of WPA, replacethe WPA unit to the correct power leveltype of WPA.
4.110 WSC oven oscillator fault
Name WSC oven oscillator fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
106 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Detecting unit WSC
Fault source WSC
Meaning The oven oscillator adjusting area isreaching its limit value. The alarm isactivated if the WSC tunes the ovenoscillator so that the DAC word(parameter to control the oven oscillatoroutput frequency) value becomes lowerthan 205 or greater than 3891 (5% of thetotal adjustment area). The range for theDAC word is 0 - 4095. The cause of thealarm can be:. The Iub reference frequency has been
incorrect for a long time (up to severaldays) due to a fault in the transmissionnetwork synchronisation (which in turnis caused by an equipment fault or asetting error). Before activating thisalarm, the alarm 7652 BASE STATIONNOTIFICATION: 'Difference betweenBTS master clock and referencefrequency' may have been active.
. If the BTS integrated transport partreceives the synchronisationinformation via the 2.048 MHzsynchronisation input (external clocksource), the alarm situation may becaused by a fault in that signal. In thatcase the alarm behaviour notificationslisted with the Iub signal (see above)are also valid in this case.
. The fast tuning action of the BTSmaster clock may have been executedwithout checking if the reference signalis correct or not. If the reference signalis incorrect during the fast tuningexecution, it may result in adjusting theBTS master clock frequency far fromthe nominal value, which causesserious problems in the networkperformance.
. There is an equipment fault in the BTS.
. Due to the oven oscillator (OCXO)aging inside the WSC unit, the unit maybe approaching the end of its lifetime. Insuch case, after the alarm activation,the DAC value is quite stable, whereasin the other fault cases it may be veryunstable or at the edge of theadjustment area (0 or 4095).
DN7095963Issue 2-0 en
# Nokia Corporation 107 (125)
Alarms
Note that if the alarm 7651 BASESTATION OPERATION DEGRADED:'WSC oven oscillator fault' becomesactive, it may cause the alarm 7652BASE STATION NOTIFICATION:'Difference between BTS master clockand reference frequency' to cancel.
Event type Start / Cancel
Unit status Degraded
Effect The severity of the fault depends on thesituation:. If the WSC unit (OCXO) is approaching
the end of its lifetime but the referencefrequency is still correct, the BTS andsystem performance may be normal formonths or even a year after the alarmactivation (if the DAC word is not at theedge of the adjustment area).
. The other faults may cause the BTSand system performance to collapsedue to incorrect air interface frequency.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WMC or only one WSC)
7652 BASE STATION NOTIFICATION (ifredundant WSC available)
LED display Stable red (WSC)
Instructions Background information:
The principle is that in a mobile network,the synchronisation goes from MSC =>RNC => BTS. But in reality that chainmight be broken somewhere and, forexample, when using leased lines, theBTS may take the referencesynchronisation from the transmissionnetwork of another operator. This doesnot harm the system if also thesynchronisation of the leased line serviceprovider is accurate/stable enough. TheBTS uses the incoming synchronisationsignal as a reference for the Air interface,the accuracy requirement of which is setby 3GPP.
1. In case of fault in the transmissionnetwork synchronisation, the networksynchronisation must be corrected. Thelong-term accuracy of the Iub signalmust be 0.015 ppm or better.
2. In case of BTS equipment fault, thelocation may be:
a. Transport part
108 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
. First check the alarms of theAXC node with the AXCManager and act accordingly.
. If there are no alarms, check theAXC synchronisation settings.
b. WSC unit. If both the Iub reference signal
accuracy and the AXC node arein order but the WSC unit is stillalarming, run the fast tuningprocedure with the BTS SiteManager.
. If there is no cure in a fewminutes, reset the site.
. If that does not help, replace theWSC unit.
Note: In case the BTS isequipped with two WSCs, theredundant unit takes over theoperation of the faulty unit. But ifthe fault situation is caused byan incorrect reference signal,both the WSC units may startalarming sooner or later.
3. After the fault situation has beencleared, the BTS master clock may alsorequire tuning, because the BTSmaster clock adjustment is quite slow.The tuning may be done:. Manually, by changing the DAC
word (during a site visit).. Or with fast tuning, by which the
BTS master clock is tuned in a fewminutes automatically near the Iubreference (normal tuning takes careof the fine tuning).
Note, however, that the fast tuningshould only be used in case the Iubreference signal is known to be agood one. Otherwise the BTSfrequency may be tuned into atotally incorrect value, causingserious problems in the networkperformance.
4.111 WSC phase difference jammed to zero reading
Name
DN7095963Issue 2-0 en
# Nokia Corporation 109 (125)
Alarms
WSC phase difference jammed to zeroreading
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSC, WMC
Meaning The WSC phase measurement is jammedand the tuning operation is degraded.
The problem can be caused by a WSCfault or a too fast frequency change onthe Iub.
Event type Start / Cancel
Unit status Degraded
Effect The BTS master clock (OCXO) is in thehold-over mode because it cannot use thesynchronisation reference information.The BTS air interface stability is notaffected, but the accuracy starts to driftslowly. It may take even several weeksbefore the BTS/RAN operations start tobe affected.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED (WMC or only one WSC)
7652 BASE STATION NOTIFICATION (ifredundant WSC available)
LED display Blinking red (WCS)
Instructions 1. If the basic accuracy of the Iub signal isin order but there is too much instability(the jitter/wander is outside theacceptable limits), the synchronisationof the transmission network must becorrected. The limits for the jitter/wander are defined in the ITU-T G.823.No actions on the BTS are needed.
2. Reset the site and wait about 10minutes.
3. Try a power-on reset. If the alarmreappears, replace the unit.
If the alarm reappears during the nextfew weeks or the clock seems unstable,replace the unit.
Background information:
The principle in the mobile network is thatthe synchronisation goes from MSC =>RNC => BTS. But in reality that chainmight be broken somewhere and, for
110 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
example, when using leased lines theBTS may take the referencesynchronisation from the transmissionnetwork of another operator. This doesnot harm the system if also thesynchronisation of the leased line serviceprovider is accurate/stable enough. TheBTS uses the incoming synchronisationsignal as a reference for the Air interface,the accuracy requirement of which is setby 3GPP.
4.112 WSC switch unsuccessful
Name WSC switch unsuccessful
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WAM
Fault source Redundant WSC
Meaning The WSC recovery switch over failed.
Event type Start
Unit status Working
Effect The BTS is not operational because theactive WSC was removed or it is faultyand the recovery switch wasunsuccessful. There is no working WSCunit and the synchronisation does notwork.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display Green
Instructions 1. Fast tune the active unit.
2. Block/unblock the alarming unit. Thismay cause a BTS reset.
4.113 WSC/WMC transmission clock missing
Name WSC/WMC transmission clock missing
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
DN7095963Issue 2-0 en
# Nokia Corporation 111 (125)
Alarms
Detecting unit WSC/WMC
Fault source WSC/WMC
Meaning The clock of the BTS, the WSC/WMCunit, uses the Iub or the signal receivedfrom an external clock as a clockreference. The signal is routed throughthe AXC and WCI to the WSC. This alarmis generated if the WCI does not receivethe clock reference signal.
Event type Start / Cancel
Unit status Degraded
Effect Tuning does not follow the externalreference.
The BTS continues its operation with itsown oven oscillator.
The BTS can function properly for a fewdays without an external reference, butthe network performance may start todecrease gradually.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red (set by the WSC/WMC itself)
Instructions 1. Check the other transmission-relatedalarms, example, link-breaks.
2. Check the AXC settings.
3. Check the transmission cablings.
4. Replace the WCI unit.
4.114 WSMA ST-bus error
Name WSMA ST-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WSM
Fault source Alarming WSM, (cable)
Triple-mode: WTR (cable)
Meaning
112 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
The TX signal is transported from theWSP unit to all WTR units via the WSMs.The WSM units in different subracks areconnected to each other via the STbuses. This alarm is generated when theWSM unit detects errors in the incomingST bus from the adjacent WSM unit.
The reason for the failure is the cablebetween the WSM front panels or theWSM units indicated in the alarm.
Event type Transient
Unit status Working
Effect The capacity drops. The cell is lost.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display N/A
Instructions 1. Run the WCDMA BTS loop test.
2. Check the WSM cables.
3. Replace the units indicated in the alarmone by one and check whether theproblem is cleared. Refer to thedocument WCDMA BTSTroubleshooting Instructions.
4.115 WSMA T-bus error
Name WSMA T-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WSM
Fault source WSP
Meaning The signal is transported from the WSPunit to the WTR unit via the WSM. Thisalarm is generated when the WSM unitdetects errors in the incoming T-bus fromthe WSP unit.
The reason for the failure is probably theWSP or WSM unit. The unit may havebeen installed incorrectly or the backplanecabling is faulty.
Event type Transient
Unit status Working
Effect The capacity drops.
DN7095963Issue 2-0 en
# Nokia Corporation 113 (125)
Alarms
The WTR and WSP capacity in thesubrack remains unused.
Reported alarms 7652 BASE STATION NOTIFICATION
LED display N/A
Instructions 1. Replace the units indicated in the alarmone by one and check whether theproblem is cleared.
Refer to the document WCDMA BTSTroubleshooting Instructions.
4.116 WSMB does not receive frame clock
Name WSMB does not receive frame clock
Product Supreme; Optima; Triplemode
Detecting unit WSMB
Fault source WCI
Meaning The WSMB does not receive the SystemFrame Clock (SFCLK) correctly from theWCI unit.
This fault may appear, if the only clockunit (WSC) is removed.
Event type Start / Cancel
Unit status Degraded
Effect The BTS capacity is degraded.
The WTR and WSP capacity in thesubrack is not used.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Block/unblock the alarming WSM.
Note
This will cause BTS reset.
2. Replace the WCI unit and checkwhether the alarm is cleared.
3. Check the backplane cables andconnectors.
114 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.117 WSMB RR-bus errorName WSMB RR-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode;MetroSite 50
Detecting unit WSMB/WMC
Fault source WTR
Meaning The signal is transported from the WTR tothe WSP via the WSM. This alarm isgenerated when the WSM/WMC unitdetects errors in the incoming RR busfrom the WTR unit.
The reason for the failure is probably theWTR or WSMB/WMC unit. The unit mayhave been installed incorrectly or thebackplane cabling is faulty.
Event type Start
Unit status Out of order
Effect The capacity drops. The cell is lost. Inmost cases, this generates an R bus erroralarm and the cell is blocked.
Reported alarms 7653 CELL FAULTY (TX/RX-WTR)
7654 CELL OPERATION DEGRADED(RX-WTR)
LED display Stable red
Instructions 1. Run the WCDMA BTS loop test.
2. Replace the units indicated in the alarmone by one and check whether theproblem is cleared.
3. Check the backplane cables andconnectors. Refer to the documentWCDMA BTS TroubleshootingInstructions.
4.118 WSMB SR-bus error
Name WSMB SR-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WSM
Fault source Adjacent/alarming WSM, (cable)
DN7095963Issue 2-0 en
# Nokia Corporation 115 (125)
Alarms
Triple-mode: WTR (cable)
Meaning UltraSite:
The RX signal is transported from theWTR unit to all WSP units via the WSMs.The WSM units in different subracks areconnected to each other via the SRbuses. This alarm is generated, when theWSM unit detects errors in the incomingSR bus from the adjacent WSM unit. Thereason for the failure is the cable betweenthe WSM front panels or the WSM unitsindicated in the alarm.
Triple-mode:
The RX signal is transported from theWTR30 and WRT20 units (connected tothe SR bus) to the WSP units via the SRbus. This alarm is generated, when theWSM detects errors in the incoming SRbus from the WTR unit.
The reason for the failure is the WSM orWTR unit or the cable between the WSMfront panel and the backplane.
Event type Start
Unit status Degraded
Effect The capacity drops. The cell is lost. In themost cases, this generates an R bus erroralarm and the cell is blocked.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Run the WCDMA BTS loop test.
2. Check the WSM cables.
3. Replace the units indicated in the alarmone by one and check whether theproblem is cleared. Refer to thedocument WCDMA BTSTroubleshooting Instructions.
4.119 WSMB ST-bus error
Name WSMB ST-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode
Detecting unit WSM
116 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Fault source Alarming WSM, (cable)
Triple-mode: WTR (cable)
Meaning The TX signal is transported from theWSP unit to all WTR units via the WSMs.The WSM units in different subracks areconnected to each other via the STbuses. This alarm is generated when theWSM unit detects errors in the incomingST bus from the adjacent WSM unit.
The reason for the failure is the cablebetween the WSM front panels or theWSM units indicated in the alarm.
Event type Start
Unit status Degraded
Effect The capacity drops. The cell is lost.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Blinking red
Instructions 1. Run the WCDMA BTS loop test.
2. Check the WSM cables.
3. Replace the units indicated in the alarmone by one and check whether theproblem is cleared. Refer to thedocument WCDMA BTSTroubleshooting Instructions.
4.120 WSMB T-bus error
Name WSMB T-bus error
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; Triplemode;MetroSite 50
Detecting unit WSM/WMC
Fault source WSP
Meaning The signal is transported from the WSPunit to the WTR unit via the WSM. Thisalarm is generated when the WSM unitdetects errors in the incoming T-bus fromthe WSP unit.
The reason for the failure is probably theWSP or WSM unit. The unit may havebeen installed incorrectly or the backplanecabling is faulty.
DN7095963Issue 2-0 en
# Nokia Corporation 117 (125)
Alarms
Event type Start
Unit status Out of order
Effect The BTS capacity is decreased.
The WTR and WSP capacity in thesubrack remains unused.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Run the WCDMA BTS loop test.
2. Check the WSM cables.
3. Replace the units indicated in the alarmone by one and check whether theproblem is cleared. Refer to thedocument WCDMA BTSTroubleshooting Instructions.
4.121 WSP PCI-bus failure
Name WSP PCI-bus failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WSPC
Fault source WSPC
Meaning There is a fault in the internal WSP PCIbus target (DSP) connections. Some ofthe WSP DSP processors may be brokenand out of use.
Event type Start
Unit status Out of order
Effect The WSP unit resources are notavailable. The BTS capacity decreases.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions Replace the alarming unit.
118 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.122 WSP unit internal failureName WSP unit internal failure
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WAM
Fault source WSP
Meaning The WAM and WSP are notsynchronised.
Event type Start
Unit status Out of order
Effect The BTS capacity decreases.
Reported alarms 7651 BASE STATION OPERATIONDEGRADED
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.123 WTR internal clock faulty
Name WTR internal clock faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The WTR internal system clock ismissing. This can be caused by a missingor bad quality reference clock signal fromthe WSC, or a WTR unit HW failure. Thetransmitted and received frequencies areincorrect.
Event type Start
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY (TX/RX-TRX)
7654 CELL OPERATION DEGRADED(RX-TRX)
DN7095963Issue 2-0 en
# Nokia Corporation 119 (125)
Alarms
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
3. Check the backplane cables andconnectors.
4.124 WTR internal clock faulty
Name WTR internal clock faulty
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The WTR VCXO PLL is not locked. Thiscan be caused by a missing or badquality reference clock signal from theWSC or a WTR unit HW failure. Thetransmitted and received frequencies areincorrect.
Event type Start
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY (TX/RX-WTR)
7654 CELL OPERATION DEGRADED(RX-WTR)
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
3. Check the backplane cables andconnectors.
4.125 WTR local oscillator not locked
Name WTR local oscillator not locked
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
120 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Detecting unit WTRB
Fault source WTRB
Meaning The TX IF synthesizer (common to bothTX chains) cannot lock to the definedfrequency.
Event type Start / Cancel
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY (TX-WTR)
7654 CELL DEGRADED (RX-WTR)
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.126 WTR loop synthesizer not locked
Name WTR loop synthesizer not locked
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The RF loop does not function. Thetransmitter output signal is not down-converted to the receiver frequency.
Event type Start / Cancel
Unit status Working
Effect The RF loop tests do not function. Thenormal RX and TX functionality of theWTR can continue undisturbed.
Reported alarms 7655 CELL NOTIFICATION
LED display Stable green
Instructions 1. Try to perform the loop test again.
2. Block/unblock the alarming unit.
3. Replace the alarming unit.
DN7095963Issue 2-0 en
# Nokia Corporation 121 (125)
Alarms
4.127 WTR output power decreasedName WTR output power decreased
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WTR
Fault source WTR
Meaning The TX1 RF and/or TX2 RF signal levelof the main RF output is lower than thepredetermined level.
Event type Start
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.128 WTR output power fault
Name WTR output power fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WTRB
Fault source WTRB
Meaning An amplifier stage is out of order in theTX chain. The TX is out of order andneeds to be shut down. The downlinktransmission of the TX must be stopped.
Event type Start
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
122 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
4.129 WTR power supply voltage faultName WTR power supply voltage fault
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode
Detecting unit WTRA
Fault source WTRA
Meaning There is a fault in the power feed or RFcabling, or there is external interference.
One or more critical power supplyvoltages or BIAS currents are outside theallowed range.
Event type Start / Cancel
Unit status Out of order
Effect The WTR does not transmit.
One or both of the WTR receivers are notreceiving. If either of the receivers isreceiving, the cell is operational, but thecell performance is degraded due to amissing diversity receiver.
Reported alarms 7653 CELL FAULTY (TX/RX-TRX)
7654 CELL OPERATION DEGRADED(RX-TRX)
LED display Stable red
Instructions 1. Block/unblock the WTR unit belongingto the alarming cell.
2. Block/unblock the WAF unit belongingto the alarming cell.
3. Check the RF cabling, connectors,WTR backplane connectors, externaldevices in the antenna line (forexample, MHAs), and externalinterference of RX band (with aspectrum analyser). Refer to thedocument WCDMA BTSTroubleshooting Instructions.
4.130 WTR RT-bus fault
Name WTR RT-bus fault
Product
DN7095963Issue 2-0 en
# Nokia Corporation 123 (125)
Alarms
Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The bus clock signal is corrupted ormissing in the RT bus. The signalfrequency should be exactly half of thesystem clock frequency.
Event type Start / Cancel
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY (TX/RX-TRX)
7654 CELL OPERATION DEGRADED(RX-TRX)
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Check the WSM, WSP and WTR.
Note
The problem can be in the unit connector orbackplane cablings.
4.131 WTR synthesizer is not locked
Name WTR synthesizer is not locked
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The TX & RX RF synthesizer or the RXIF synthesizer is not locked (or the RFsynthesizer buffer amplifier is faulty). Theoutput frequency of the transmitter can bewrong or missing, or the receiver mightreceive a wrong frequency or is notreceiving.
Event type Start
Unit status Out of order; Degraded
124 (125) # Nokia Corporation DN7095963Issue 2-0 en
BTS Alarm Descriptions
Effect The WTR cannot transmit and/or receiveanything depending on which synthesizer(TX/RX) is faulty.
Reported alarms 7653 CELL FAULTY (TX/RX-TRX)
7654 CELL OPERATION DEGRADED(RX-TRX)
7655 CELL NOTIFICATION (RX-TRX)
LED display Stable red
Instructions 1. Block/unblock the alarming unit.
2. Replace the alarming unit.
4.132 WTR temperature is high
Name WTR temperature is high
Product Supreme; Optima; Optima IBBU; OptimaCompact RF Extension; MetroSite;Triplemode; MetroSite 50
Detecting unit WTR
Fault source WTR
Meaning The internal temperature of the WTR isdangerously high.
Event type Start / Cancel
Unit status Out of order
Effect The related cells are disabled.
Reported alarms 7653 CELL FAULTY (TX/RX-WTR)
7654 CELL OPERATION DEGRADED(RX-WTR)
LED display Stable red
Instructions 1. Check the other active temperature orcooling fan-related alarms.
2. If no reason can be found, the sensor isprobably broken. Replace the unit.
DN7095963Issue 2-0 en
# Nokia Corporation 125 (125)
Alarms