BO23 Brochure En

Embed Size (px)

Citation preview

  • 8/14/2019 BO23 Brochure En

    1/24

    www.altpro.com

    AXLE COUNTER BO23

  • 8/14/2019 BO23 Brochure En

    2/24

    www.altpro.com

    1

    1. PRODUCT DESCRIPTION

    Figure 1 - BO23 conguraon sample

    1.1. GENERAL DESCRIPTION

    The axle counter BO23 is used for railway track secon occupancy control; primarily for the vital control of the

    secon occupancy. It can also be used in similar applicaons without limited safety requirements. Examples for the

    applicaon of the axle counter BO23 are:

    Occupancy control of the staon secons within the staon interlocking system

    Occupancy control of the open railroad secons within the automac block system

    Occupancy control of the open railroad as a single block between staons

    Occupancy control of the several secons in wide level crossing area for the purpose of switching-on /

    switching-o the level crossing within the level crossing protecon system

    Occupancy control of a shunng staon / marshalling yard secons within the automac coach shunng

    system etc.

    The axle counter BO23 uses its sensors on each end of a given track secon to connuously control and count the

    train axles passing in and out of that secon. If the current number of axles on the secon is equal to zero, and no

    disturbance, error or fault is detected, the system will send out informaon that the secon is clear. In all other

    cases the track secon occupied informaon is sent out.

    With the BO23 equipment the track secon occupancy can be controlled on the secon with two counng points

    (on the open railroad secon or the staon track secon), on the secon with 3 counng points (switch point

    secon), on the dead end secon with one counng point, on the double slip switch point secon (4 counng

    points) or on the mulple switch points secon with maximum 8 counng points.

  • 8/14/2019 BO23 Brochure En

    3/24

    www.altpro.com2

    1.2. PRINCIPLE OF OPERATION

    Axle counter BO23 consists of the outdoor equipment on the track and the indoor equipment in the staon or in the

    block secon equipment shelter near the railroad as shown on the gure 2.

    Figure 2 - Axle counter BO23 basic structure for occupancy control of one secon with 2 counng points

    Transmission path is not considered as a part of the axle counter because the exisng railway signalling and

    telecommunicaon cables are usually used. There is a 2-wire connecon between indoor and outdoor equipment

    (single 2-wire telecommunicaon twisted pair).

  • 8/14/2019 BO23 Brochure En

    4/24

    www.altpro.com

    3

    1.3. ADVANTAGES OF AXLE COUNTERS COMPARED TO TRACK CIRCUITS

    The basic principle behind the track circuit lies in the connecon of the two rails by

    the wheels and axle of locomoves and rolling stock to short out an electrical circuit. This

    circuit is monitored by electrical equipment to detect the presence or absence of the trains.

    Wikipedia

    Figure 3 - Track circuit soluon logic diagram

    Track circuit downsides:

    Quality of electric signal from transming rail limited by sleepers and ballast insulaon resistance (mustbe as high as possible) leaking the current issue.

    This resistance is a liming factor for maximal length of track circuit. Longer secon has less resistance so

    the received signal is appropriately damped.

    The rest of the voltage on the receiver must be higher than minimal value in order for track circuit to

    funcon properly.

    Resistance can depend on hydro-meteorological circumstances and condion of top layer (sleepers and

    mud). One single roen sleeper sopped in water or one muddy pool can reduce resistance and leak too

    much current so the receiver is no longer excited and declares false occupancy.

    Funcon of track circuit depends also on the resistance of short-circuit made by axle. Problems can occur

    when small number of axles short-circuits (connects) or when resistance of the axle is too high. Poor short-

    circuit (cross rail axle connecon) can occur because of rusty lm on the rail, etc. Return current from tracon can inuence track circuit in two ways. First is saturang the transformer if

    the secon is long, return current being high and ground not ideal. The other inuence is made by higher

    harmonics close to frequency of the main signal which complicate the detecon of signal. This is enlarged

    by introducing the thyristor tracon.

    Track circuit requires insulated rail joints. (Even though jointless track circuits are available ,in point zones,

    high voltage impulse track circuits with joints are found more reliable)

    Track circuit requires bonding and more cabling which increases the cost of installaon, maintenance and

    error points.

    Track circuits face problems when rail head is contaminated, like rust or accumulated leafs.

    Track circuits are not reliable in wet condions, so they cannot be used for tunnel train detecon.

    Track circuits cannot be reliable on steel structures (like steel sleeper).

  • 8/14/2019 BO23 Brochure En

    5/24

  • 8/14/2019 BO23 Brochure En

    6/24

    www.altpro.com

    5

    1.4. EMC, TESTING AND CERTIFICATION

    Figure 5 - EMC Cercate for Axle Counter BO23- UNUR issued by TV Rheinland InterTrac

    Reg. No: AE 60021770 0001, Issued in: 06/2008

    Figure 6 - SIL4 Cercate for Axle Counter BO23 Issuedby TV Rheinland InterTrac

    Reg. No: ACR/B 09/241, Issued in: 10/2009

    Figure 7 - BO23 system EMC tesng Figure 8 - BO23-UNUR EMC tesng

    Figure 9 - BO23 diagnoscs Figure 10 - BO23-UNUR temperature tesng

  • 8/14/2019 BO23 Brochure En

    7/24

  • 8/14/2019 BO23 Brochure En

    8/24

  • 8/14/2019 BO23 Brochure En

    9/24

    www.altpro.com8

    2. TECHNICAL SPECIFICATION

    2.1. OUTDOOR EQUIPMENT RAIL WHEEL SENSOR ZK24-2 AND TRACKSIDE UNIT

    VUR

    Power supply (VOD1+, VOD1-): 40V DC to 100V DCSensor power supply (U+, U-): 24V DC 5%

    Power dissipaon (VUR + ZK24-2): max. 2.5W

    Total power dissipaon with

    telecommunicaon cable losses: max. 5W

    Output current of basic state of

    sensor ZK24-2: channel H: 16mA DC 8%

    channel L: 16mA DC 8%

    Output current of acve state of

    sensor ZK24-2: channel H: 10mA DC 8%

    channel L: 10mA DC 8%

    Side distance of drop-away from raildetecon of sensor ZK24-2: 5 to 15mm on the whole temperature range, for all rail types

    Operang temperature range: -40C to +80C

    Relave humidity: up to 100%

    Water and dust protecon: IP67 for trackside control unit VUR

    IP68 for sensor ZK24-2

    Vibraon and shocks resistance: tested according to EN 50125-3

    Sensor ZK24-2 - vercal axis: vibraons 5 2000Hz, 28g r.m.s., shocks 200g / 6ms

    Sensor ZK24-2 - transversal axis: vibraons 5 2000Hz, 14g r.m.s., shocks 100g / 6ms

    Sensor ZK24-2 - longitudinal axis: vibraons 5 2000Hz, 5g r.m.s., shocks 36g / 6ms

    Electrical connecon: signal screwdriver terminal blocks

    rail ground M16 screw, crimp terminal for 35 to 50 mm wire

    Minimal rail wheel diameter: 300mm

    Wheel ange height: according to UIC 510-2 (table 1)

    Wheel ange thickness: according to UIC 510-2 (table 2)

    Rail prole: S45S49UIC54UIC60 (other proles on demand)

    Dimensions of VUR case (D W H): 200 230 110 mm

    Dimensions of VUR case on column

    (D W H): 250 250 645 mm

    VUR weight without column: 5.32kg

    Column weight: 5.9kg

    Sensor ZK24-2 weight (without cable): 1.72kg

    Weight of the sensor with mounng

    bracket and cable: 6.05kgSensor shield weight: 6.78kg (UIC60); 6.3kg (S49)

    Table 1 - Wheel ange height (according to UIC 510-2)

    Wheel diameter 330mm to 630mm 630mm to 760mm >760mm

    Wheel ange heightMin. 32mm Min. 30mm Min. 28mm

    Max. 36mm Max. 36mm Max. 36mm

  • 8/14/2019 BO23 Brochure En

    10/24

    www.altpro.com

    9

    Table 2 - Wheel ange thickness (according to UIC 510-2)

    Wheel diameter 330mm to 840mm >840mm

    Wheel ange thicknessMin. 27.5mm Min. 22mm

    Max. 33mm Min. 33mm

    2.2. INDOOR EQUIPMENT BO23-UNUR

    Power supply: 18V to 80V DC

    Stabilized counng point power supply: 96V DC 4%, 8W, galvanically isolated

    Total power dissipaon (8 counng

    points, power supplied): at 24V DC: 66W

    at 48V DC: 65W

    at 60V DC: 66W

    at 80V DC: 72WOperang temperature range: -30C do +70C, up to 100% RH

    Axle counng capacity: 999 axles with indicaon (internal counng up to 32767 axles)

    Microprocessor module conguraon: 2-out-of-3

    Maximal number of counng points: 8 local + 1 remote via remote indoor device (RS232)

    Maximal number of track secons: 6 secons

    Output signals: relay safety relay contacts

    serial interface RS232

    Maximal current switching on safety

    relay output contacts: 2A DC

    Maximal voltage switching on safety

    relay output contacts: 150V DC

    Maximal current on optocoupler

    output transistors: 50mA

    Maximal collector-emier voltage

    on optocoupler outputs: 75V

    Maximal saturaon voltage

    on optocoupler outputs: 1V

    Reset inputs voltage: reset acvaon: 1480V DC

    reset deacvaon:

  • 8/14/2019 BO23 Brochure En

    11/24

  • 8/14/2019 BO23 Brochure En

    12/24

  • 8/14/2019 BO23 Brochure En

    13/24

    www.altpro.com12

    3.1.3. CONFIGURATION 3 - OCCUPANCY CONTROL OF 3 INDEPENDENT SECTIONS

    Occupancy control of 3 independent secons is performed with one indoor unit BO23-UNUR whose MPU module

    runs the operaonal program BO23-3A-3B-2C. First two secons (A and B) can contain up to 3 counng points and

    third secon (C) can contain up to 2 counng points. Figure 17 shows the example of 3 independent staon secons.

    Figure 17 - Example of 3 independent secons controlled by one indoor unit BO23-UNUR with operaonal program BO23-3A-3B-2C

    Each controlled secon can have less counng points than shown on gure 17. Simultaneous train passage is allowed

    over any of two or more counng points.

    3.1.4. CONFIGURATION 4 - OCCUPANCY CONTROL OF 4 INDEPENDENT SECTIONS WITH 2

    COUNTING POINTS EACH

    Occupancy control of 4 independent secons is performed with one indoor unit BO23-UNUR whose MPU module

    runs the operaonal program BO23-2A-2B-2C-2D. Each of 4 independent secons (A, B, C and D) can have up to2 counng points. Figure 18 shows two examples of the control of 4 independent staon secons with 2 counng

    points each.

    CP1 CP2

    SECTION A

    CP3 CP4

    SECTION B

    CP5 CP6

    SECTION C

    CP7 CP8

    SECTION D

    SECTION A

    SECTION B

    CP7

    CP5

    CP8

    CP6

    CP1 CP2

    CP3 CP4

    SECTION C

    SECTION D

    Figure 18 - Two examples of 4 independent secons controlled by one indoor unit BO23-UNUR with operaonal programBO23-2A-2B-2C-2D

  • 8/14/2019 BO23 Brochure En

    14/24

  • 8/14/2019 BO23 Brochure En

    15/24

    www.altpro.com14

    Figure 20 - Two examples of two sets of 3 neighbouring secons controlled by one indoor unit BO23-UNUR with operaonal

    program BO23-2A2B2C-2D2E2F

    3.1.7. CONFIGURATION 7 - OCCUPANCY CONTROL OF 5 NEIGHBORING SECTIONS

    If the most distant counng point is sll in range of the indoor equipment (table 3), the occupancy control of5 automac block secons can be performed with one indoor unit BO23-UNUR whose MPU module runs the

    operaonal program BO23-2A2B2C2D4E. Some of these 5 secons can be used for the control of staon secons

    (e.g. entrance switch point), while the rest of the secons are used for automac block (gure 21).

    Figure 21 - Example of 5 neighbouring secons controlled by one indoor unit BO23-UNUR with operaonal program BO23-2A2B2C2D4E (automac block / staon)

    3.1.8. CONFIGURATION 8 - OCCUPANCY CONTROL OF 6 NEIGHBORING SECTIONS

    If the most distant counng point is sll in range of the indoor equipment (table 3), the occupancy control of

    6 automac block secons can be performed with one indoor unit BO23-UNUR whose MPU module runs the

    operaonal program BO23-2A2B2C2D2E3F. Some of these 6 secons can be used for the control of staon secons

    (e.g. entrance switch point), while the rest of the secons are used for automac block (gure 22).

  • 8/14/2019 BO23 Brochure En

    16/24

    www.altpro.com

    15

    Figure 22 - Example of 6 neighbouring secons controlled by one indoor unit BO23-UNUR with operaonal program BO23-2A2B2C2D2E3F (automac block / staon)

    3.1.9. CONFIGURATION 9 - OCCUPANCY CONTROL OF 3 INDEPENDENT STATION SECTIONS AND

    ONE BLOCK SECTION BETWEEN STATIONS USING SERIAL RS232 LINK

    By preseng the operaonal program BO23-3A-2B-2C-2D, one indoor unit BO23-UNUR can control the occupancy

    of 3 independent staon secons (secon A with 3, secon B with 2 and secon C with 2 counng points), and

    simultaneously one block secon between staons (secon D) with 2 counng points using the serial RS232

    connecon with neighbouring staon. Schemac diagram of the occupancy control of block secon between

    staons (secon D) is shown on gure 23.

    Figure 23 - Control of the block secon between staons using serial connecon RS232 between indoor units BO23-UNURwith operaonal program BO23-3A-2B-2C-2D

    The main goal for using the principle of controlling the block secon between staons is to avoid the wire connecon

    to the distant counng point when it is out of range of the indoor equipment (in the case of large distance between

    staons), or if the wire connecon between staons is simply undesirable (e.g. if there is not enough twisted pairs forthe whole signalling system), so the bre opc cable is preferred. The closer counng point is in this case connected

    via 2-wire twisted pair directly to the indoor unit BO23-UNUR (to the terminal of eight counng point, receiving

    module UP8) as in previous examples. The indoor unit receives informaon from the distant counng point of the

    block secon via RS232 link between the indoor unit BO23-UNUR in the staon and the indoor unit BO23-UNUR

    in the neighbouring staon that controls the more distant counng point directly and runs the same operaonal

    program BO23-3A-2B-2C-2D. This link is on both indoor units connected to MPU LINK connector on the front plate

    of processing module MPU. Communicaon between two indoor units is performed on the safety principle for

    closed transmission systems according to EN50159-1.

    The length of the block secon between staons is limited only by the telecommunicaon parameters of used

    transmission system (ber opc cable with appropriate converters, type of modem for 2-wire connecon etc.); the

    secon can be a few dozen of kilometres long.

  • 8/14/2019 BO23 Brochure En

    17/24

    www.altpro.com16

    3.2. LEVEL CROSSING APPLICATIONS

    3.2.1. TWO INDEPENDENT SECTIONS WITH OVERLAPPING OVER THE ROAD

    Figure 24 - Train detecon with axle counter BO23 for level crossing on single track open line (basic conguraon) variantwith two overlapping secons

    The train presence on the complete level crossing area is controlled using two independent secons (gure 24);secon A between counng point 1 and counng point 2, and secon B between counng point 3 and counng

    point 4. Secons A and B are overlapping over the road. Counng points 1 and 4 are located on calculated distances

    for switching the level crossing on.

    Basic state of the train detecon unit on level crossing (axle counter BO23) is as follows:

    Secon A clear, secon B clear (both secons clear).

    Condion for switching the level crossing onis any of the following:

    Occupancy (release of the Track Clearrelay on the axle counter BO23) of any of the secons (A or B)

    during the regular train passage from any direcon, or caused by eventual disturbance/failure

    Occupancy (release of the Track Clear relay) of both secons simultaneously caused by disturbance/failure

    Some other way of switching-on if provided, independently from axle counter (e.g. manually by switch/

    pushbuons), as well as in case of failure detected in the level crossing system.

    Condion for switching the level crossing ois any of the following:

    Occupancy (release of the Track Clearrelay and picking of the Track Occupiedrelay) of both secons (A

    and B) and clearance (release of the Track Occupiedrelay and picking of the Track Clearrelay) of at least

    one secon (A or B) regular train passages including shunng

    Occupancy (release of the Track Clearrelay and picking of the Track Occupiedrelay) of only one secon (A

    or B) and clearance (release of the Track Occupiedrelay and picking of the Track Clear relay) of the same

    secon, in case the other secon is clear all the me shunng train movement with change in direcon,without crossing the road

    Seng both secons into the basic (clear) state using the reset manual (locally or remotely) or automac

  • 8/14/2019 BO23 Brochure En

    18/24

    www.altpro.com

    17

    Some other way of switching-o if provided, independently from axle counter (e.g. manually by switch/

    pushbuons, aer the me-out for automac switch-o ).

    3.2.2. THREE ADJACENT SECTIONS

    Figure 25 - Train detecon with axle counter BO23 for level crossing on single track open line (basic conguraon) variantwith 3 adjacent secons

    The train presence on the complete level crossing area is controlled using 3 adjacent secons (gure 25). Counng

    points 1 and 4 are located on calculated distances for switching the level crossing on. Secon B that controls the

    occupancy of the road area (island secon) is minimally 20m long, i.e. must be longer than the greatest distance

    between two neighbouring axles on the railway vehicles.

    For the double track open line 3 more secons on the axle counter BO23 (D, E and F) can be used for the other

    track, i.e. 4 more counng points. There is sll only one indoor unit BO23-UNUR in the level crossing house; only

    the addional modules (cards) are plugged into it according to the applicaon. One indoor unit BO23-UNUR can

    control up to 8 counng points, which can be congured on up to 6 secons (see the User Documentaon of BO23).

    Basic stateof the train detecon unit on level crossing (axle counter BO23) is as follows:

    Secon A clear, secon B clear, secon C clear (all 3 secons clear).

    Condion for switching the level crossing onis any of the following:

    Occupancy (release of the Track Clearrelay on the axle counter BO23) of secon A or secon C during

    the regular train passage from any direcon or caused by eventual disturbance/failure

    Occupancy (release of the Track Clearrelay) of secon B or 2 or 3 any of the secons simultaneously

    caused by disturbance/failure

    Some other way of switching-on if provided, independently from axle counter (e.g. manually by switch/

    pushbuons), as well as in case of failure detected in the level crossing system.

  • 8/14/2019 BO23 Brochure En

    19/24

    www.altpro.com18

    Condion for switching the level crossing ois any of the following:

    Occupancy (release of the Track Clear relay and picking of the Track Occupied relay) of secon B and

    clearance (release of the Track Occupiedrelay and picking of the Track Clearrelay) of secon B regular

    train passages including shunng

    Occupancy (release of the Track Clearrelay and picking of the Track Occupiedrelay) of secon A only or

    secon C only and clearance (release of the Track Occupiedrelay and picking of the Track Clearrelay) of

    the same secon, in case the other two secons are clear all the me shunng train movement with

    change of direcon, without crossing the road

    Seng all 3 secons into the basic (clear) state using the reset manual (locally or remotely) or automac

    Some other way of switching-o if provided, independently from axle counter (e.g. manually by switch/push

    buons, aer the me-out for automac switch-o ).

    3.2.3. TRAIN DETECTION WITH AXLE COUNTER BO23 FOR LEVEL CROSSING WHICH IS

    SWITCHED-ON FROM ONE DIRECTION BY THE STATION INTERLOCKING (FROM THE

    STATION)

    Figure 26 - Train detecon with axle counter BO23 for level crossing which is switched-on from one direcon by the staon

    interlocking (from the staon)

    Such a conguraon of the axle counter BO23 is used when the level crossing is switched-on automacally for the

    train direcon towards the staon and for the train direcon from the staon the level crossing is switched-on by

    seng the exit train routes on the staon interlocking. This is usually the case when the level crossing is located

    between the entrance signal and associated distant-signal. Secon B that controls the occupancy of the road area

    (island secon) is minimally 20m long, i.e. must be longer than the greatest distance between two neighbouring

    axles on the railway vehicles.

    Basic stateof the train detecon unit on level crossing (axle counter BO23) is as follows:

    Secon A clear, secon B clear (both secons clear).

  • 8/14/2019 BO23 Brochure En

    20/24

  • 8/14/2019 BO23 Brochure En

    21/24

    www.altpro.com20

    long, i.e. must be longer than the greatest distance between two neighbouring axles on the railway vehicles.

    Basic stateof the train detecon unit on level crossing (axle counter BO23) is as follows:

    Secon A clear.

    Condion for switching the level crossing on (although the primary funcon of the axle counter is in this case

    switching-o) is as follows:

    Occupancy (release of the Track Clearrelay) of the secon A caused by disturbance/failure or possible

    non-regular train passages from the staon.

    Condion for switching the level crossing ois any of the following:

    Occupancy (release of the Track Clearrelay and picking of the Track Occupied relay) of the secon A and

    clearance (release of the Track Occupied relay and picking of the Track Clearrelay) of the secon A

    regular train passages including shunng

    Seng the secon A into the basic (clear) state using the reset manual (locally or remotely) or automac

    Some other way of switching-o if provided, independently from axle counter (e.g. manually by switch/

    pushbuons, aer the me-out for automac switch-o ).

    3.2.5. TRAIN DETECTION WITH AXLE COUNTER BO23 FOR LEVEL CROSSING ON A SINGLE

    TRACK LINE EQUIPPED WITH AUTOMATIC BLOCK

    Figure 28 - Train detecon with axle counter BO23 for level crossing on a single track line equipped with automac block

    In case the line is equipped with automac block (more than one secon between staons) and dependency

    between the level crossing and automac block system should be provided, the switch-on secon between the

    switch-on point and the road that has the block signal in direcon towards the level crossing is split on two secons,

    and the addional counng point is located behind the block signal. In example on gure 28, block signals are

    located in the level crossing area on both sides regarding the road, so the whole level crossing area is divided into

    the 5 secons (AE).

    This way the level crossing control system can provide the required dependency with automac block system; e.g. if

    the signal Block 1 (gure 28.) shows the stop aspect (red), the level crossing will not switch-on immediately aer

    occupaon of the secon A, but only aer signal Block 1 changes the aspect to allow the movement or when thesecon B occupies too etc.

  • 8/14/2019 BO23 Brochure En

    22/24

    www.altpro.com

    21

    3.3. OCCUPANCY CONTROL IN STATION

    Figure 29 - Example of opmal connecon of axle counters BO23 for small staon control

    Figure 29 shows an example of a small staon that uses axle counters BO23 for occupancy control of all staon

    secons, between entry signals on both sides. Such a staon with 11 secons / 14 counng points can be controlledby 3 indoor units BO23-UNUR placed in the relay room of the staon, designated in dierent colours on gure

    29, together with related secons controlled by appropriate unit. Each counng point (wheel sensor ZK24-2 with

    trackside unit VUR) is connected to relay room using only one 2-wire twisted pair, no maer if it belongs to only one

    secon (terminal counng point) or two neighbouring secons. Further interconnecons of signals from common

    counng points are made among indoor units in the relay room.

  • 8/14/2019 BO23 Brochure En

    23/24

  • 8/14/2019 BO23 Brochure En

    24/24