106
UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS Part-1 LIST OF PROTECTIONS 1) 132 kV Ramnagar line protection a) REL 511 (distance protection terminal) b) RAICA Breaker Failure Protection 50G c) RAAAM Auto Reclose Relay d) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay 2) 132 kV Kashipur-1 line protection a) REL 511 (distance protection terminal) b) RAICA Breaker Failure Protection 50G c) RAAAM Auto Reclose Relay d) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay 3) 132 kV Kashipur-2 line protection a) REL 511 (distance protection terminal) b) RAICA Breaker Failure Protection 50G c) RAAAM Auto Reclose Relay d) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay 4) 132 kV Baspur Nagar line protection Checked by Nagendra Description UTTARANCHAL POWER CORPORATION LIMITED Prepared by Sarith Madhu Order Ref 415229 Rev 00 Sheet 1/106 Issued by Dept . Yr. Wk UASE 06 40 Drg. No. YN1M 300 624- SET Yr. wk 06 40

Best Relay Setting File ABB Perfroma

Embed Size (px)

Citation preview

Page 1: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Part-1

LIST OF PROTECTIONS

1) 132 kV Ramnagar line protection

a) REL 511 (distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay

2) 132 kV Kashipur-1 line protection

a) REL 511 (distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay

3) 132 kV Kashipur-2 line protection

a) REL 511 (distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay

4) 132 kV Baspur Nagar line protection

a) REL 511(distance protection terminal) b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet1/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 2: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

5) 400kV Rishikesh line protection

a) REL 521(distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay f) LZ96 Distance Relay

6) 400kV Moradabad line protection

a) REL 521(distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay f) LZ96 Distance Relay

7) 220kV Haldwani line protection

a) REL 521(distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay f) LZ96 Distance Relay

8) 220 kV Almora line protection

a) REL 521(distance protection terminal)b) RAICA Breaker Failure Protection 50Gc) RAAAM Auto Reclose Relayd) RXEG – 27P –Under Voltage Protection Relay e) RASC Check Synchronizing Relay f) LZ96 Distance Relay

1 (a) REL 511 (21) - RAMNAGAR FEEDER

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet2/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 3: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

System Particulars :-A)Line parameters

1)Rated line voltage - 132 kV2)Line length - 18.56 Km3)Max power flow in the line - 1301.14 MVA4)Positive sequence resistance - 0.16221744 ohms/km5)Positive sequence reactance - 0.386116 ohms/km6)Zero sequence resistance - 0.405631 ohms/km7)Zero sequence reactance - 1.622174 ohms/km

B)CT/PT details1)CT primary rating - 1000A2)CT secondary rating - 1A3)PT primary rating - 145000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.1 MVA2)Fault MVA at remote end - 1694.1 MVA(assumed)3)Source impedance angle - 80º (assumed)

D)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms (Assumed)2)Fault resistance in primary for phase-phase faults - 5 ohms (Assumed)

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/1) /(145000/110)

= 0.758621Positive sequence line resistance in secondary,R1 = 0.16221744 x 18.56 x 0.758621

= 2.2840 ohmsPositive sequence line reactance in secondary,X1 = 0.386116 x 18.56 x 0.758621

= 5.4365 ohmsZero sequence line resistance in secondary,R0 = 0.405631 x 18.56 x 0.758621

= 5.7112 ohmsZero sequence line reactance in secondary,X0 = 1.622174 x 18.56 x 0.758621

= 22.8402 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.758621= 15.1724 ohms

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet3/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 4: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.758621= 3.7931 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 2.2840

= 1.8272 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 5.4365

= 4.3492 ohms/phase Zero sequence resistance , R0PE = 0.8 x 5.7112

= 4.56896 ohms/phaseZero sequence reactance , X0PE = 0.8 x 22.8402 = 18.2722 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931, 4.3492 x 0.4663 + 1.8272) , 3 x 4.3492}= 2 x Min {3.855232 , 13.0476 }= 7.7104 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 4.3492 x 0.4663 +1.8272) , 4.5 x 4.3492}= Min { 15.1724 , 19.5714 }= 15.1724 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 2.2840 + 0.2 x 2.2840

= 2.7408 ohms/phasePositive sequence reactance , X1PP&X1PE = 5.4365+ 0.2 x 5.4365

= 6.5238 ohms/phaseZero sequence resistance , R0PE = 5.7112 + 0.2 x 5.7112

= 6.8534 ohms/phaseZero sequence reactance , X0PE = 22.8402 + 0.2 x 22.8402

= 27.4082 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 6.5238 x 0.4663 + 2.7408) , 3 x 6.5238}= 2 x Min { 5.7828 , 19.5714 }= 11.5696 ohms / loop

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet4/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 5: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 6.5238 x 0.4663 + 2.7408) , 4.5 x 6.5238}= Min { 15.1724 , 29.3571 }= 15.1724 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2.2840+2.2840

= 4.568 ohms/phasePositive sequence reactance , X1PP&X1PE = 5.4365+5.4365

= 10.873 ohms/phaseZero sequence resistance , R0PE = 5.7112+5.7112

= 11.4224 ohms/phaseZero sequence reactance , X0PE = 22.8402+22.8402

= 45.6804 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 10.873 x 0.4663 + 4.568) , 3 x 10.873}= 2 x Min { 9.6380 , 32.619 }= 19.276 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 10.873 x 0.4663 + 4.568) , 4.5 x 10.873}= Min { 15.1724 , 48.9285 }= 15.1724 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 2.2840

= 0.4568 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 5.4365

= 1.0873 ohms/phaseZero sequence resistance , R0PE = 0.2 x 5.7112

= 1.1422 ohms/phaseZero sequence reactance , X0PE = 0.2 x 22.8402

= 4.5680 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 1.0873 x 0.4663 + 0.4568) , 3 x 1.0873}= 2 x Min { 3.7931 , 3.2619 }= 6.5238 ohms / loop

Resistive reach for phase-earth,

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet5/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 6: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X } = Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 1.0873 x 0.4663 + 0.4568) , 4.5 x 1.0873}= Min { 15.1724 , 4.8928 }= 4.8928 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection, regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristic does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction, X1FwPP & X1FwPE= 2 x X3 =2 x 10.873= 21.746 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction, X1RvPP & X1RvPE= 2 x X4 =2 x 1.0873 = 2.7146 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach, RFPP= (2[2*R3 + RFPP]) = (2 [2 x 4.568 + 19.276] )= 56.824 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach, RFPE= (2[1/3(2R3 + R03) +RFPE])= (2[1/3(2x4.568+ 11.4224) +15.1724])= 44.0504 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 45.6804 =91.3608 ohms/phase

The resistive reach in the load impedance area, RLd = Max (RFPP,RFPE) = Max (19.276, 15.1724) = 19.276 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones, which are to be blocked by the PSD function. At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element, X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 10.873 = 11.9603 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element, R1IN= 1.1 (2R3 +RFPP)= 1.1 (2 x 4.568 + 19.276)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet6/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 7: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 31.2532 ohms/phaseReach multiplication for the outer reactive boundary, KX = 125 %( recommended)Reach multiplication for the outer reactive boundary, KR = 125 %( recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 1.8272X1PP & X1PE = 4.3492R0PE = 4.56896X0PE = 18.2722RFPP = 7.7104RFPE = 15.1724

2) Zone-2:-R1PP & R1PE = 2.7408X1PP & X1PE = 6.5238R0PE = 6.8534X0PE = 27.4082RFPP = 11.5696RFPE = 15.1724t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3:-R1PP & R1PE = 4.568X1PP & X1PE = 10.873R0PE = 11.4224X0PE = 45.6804RFPP = 19.276RFPE = 15.1724t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.4568X1PP & X1PE = 1.0873R0PE = 1.1422X0PE = 4.5680RFPP = 6.5238RFPE = 4.8928t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC:-X1FwPP & X1FwPE = 17.606X1RvPP & X1RvPE = 0.6212RFPP = 43.752RFPE = 26.48

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet7/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 8: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

X0FwPE & X0RvPE = 57.63RLd = 43.752ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB:-X1IN = 9.677R1IN = 24.064KX = 125RX = 125tP1 = 0.045s (Initial PSD timer for the first swing)tP2 = 0.015s (Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s (Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1, tP2, tW, tH, tEF, tR1, tR2 are recommendations and the same need to be set in accordance with the system studies.

1(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (1301.14 x 106) / (√3 x 132 x 103) = 5691.18 A5% of this corresponds to 0.05 x 5691.18 = 284.559 AThe secondary current is 284.559 / 1000 =2.85 A

Setting recommended = 3 ATime Delay : The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet8/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 9: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

1(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

1(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

1(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet9/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 10: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

2(a) REL 511 (21) - KASHIPUR-1 FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 132 kV2)Line length - 7.05 Km3)Max power flow in the line - 1694.61 MVA4)Positive sequence resistance - 0.16221744 ohms/km5)Positive sequence reactance - 0.386116 ohms/km6)Zero sequence resistance - 0.405631 ohms/km7)Zero sequence reactance - 1.622174 ohms/km

B) CT/PT details1)CT primary rating - 1000A2)CT secondary rating - 1A3)PT primary rating - 145000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1301.4 MVA2)Fault MVA at remote end - 1301.4 MVA(assumed)3)Source impedance angle - 80º (assumed)

D)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/1) /(145000/110)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet10/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 11: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 0.758621Positive sequence line resistance in secondary,R1 = 0.16221744 x 7.05 x 0.758621

= 0.8675 ohmsPositive sequence line reactance in secondary,X1 = 0.386116 x 7.05 x 0.758621

= 2.0650 ohmsZero sequence line resistance in secondary,R0 = 0.405631 x 7.05 x 0.758621

= 2.1694 ohmsZero sequence line reactance in secondary,X0 = 1.622174 x 7.05 x 0.758621

= 8.6758 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.758621= 15.1724 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.758621= 3.7931 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 0.8675

= 0.694 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 2.0650

= 1.652 ohms/phaseZero sequence resistance , R0PE = 0.8 x 2.1694

= 1.7355 ohms/phaseZero sequence reactance , X0PE = 0.8 x 8.6758 = 6.94064 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931, 1.652x 0.4663 + 0.694) , 3 x 1.652}= 2 x Min {3.7931 , 4.956 }= 7.5862 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 1.652 x 0.4663 +0.694) , 4.5 x 1.652}= Min { 15.1724 , 7.434 }= 7.434 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 0.8675

= 1.041 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 2.065

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet11/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 12: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 2.478 ohms/phaseZero sequence resistance , R0PE = 1.2 x 2.1694

= 2.6033 ohms/phaseZero sequence reactance , X0PE = 1.2 x 8.6758

= 10.4109 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 2.4780 x 0.4663 + 1.041) , 3 x 2.478}= 2 x Min { 3.7931, 7.434 }= 7. 5862 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 2.478 x 0.4663 + 1.041) , 4.5 x 2.478}= Min { 15.1724 , 11.151 }

= 11.151 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 0.8675

= 1.735 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 2.065

= 4.13 ohms/phaseZero sequence resistance , R0PE = 2 x 2.1694

= 4.339 ohms/phaseZero sequence reactance , X0PE = 2 x 8.6758

= 17.3516 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 4.13 x 0.4663 + 1.735) , 3 x 4.13}= 2 x Min { 3.7931 , 12.39 }= 7.5862 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 4.13 x 0.4663 + 1.735) , 4.5 x 4.13}= Min { 15.1724 , 18.585 }= 15.1724 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 0.8675

= 0.1735 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 2.065

= 0.413 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet12/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 13: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zero sequence resistance , R0PE = 0.2 x 2.1694 = 0.4338 ohms/phase

Zero sequence reactance , X0PE = 0.2 x 8.7658 = 1.7352 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 0.413 x 0.4663 + 0.1735) , 3 x 0.413}= 2 x Min { 3.7931 , 1.239 }= 2.478 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 0.413x 0.4663 + 0.1735) , 4.5 x 0.413}= Min { 15.1724 , 1.8585 }= 1. 8585 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 4.13= 8.26 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 0.413 = 0.826 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = ( 2 [2 x 1.735 + 7.5862] )= 22.1124 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 1.735+ 4.339)+15.1724])= 35.5508 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 17.3516 =34.7032 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (7.5862 ,15.1724) = 15.1724 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet13/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 14: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 4.13 = 4.543 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 1.735 + 7.5862)= 12.1618 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 0.694X1PP & X1PE = 1.652R0PE = 1.7355X0PE = 6.94064RFPP = 7.5862RFPE = 7.434

2) Zone-2 :-R1PP & R1PE = 1.041X1PP & X1PE = 2.478R0PE = 2.6033X0PE = 10.4109RFPP = 7.5862RFPE = 11.1151t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 1.735X1PP & X1PE = 4.13R0PE = 4.339X0PE = 17.3516RFPP = 7.8562RFPE = 15.1724t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.1735X1PP & X1PE = 0.413

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet14/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 15: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

R0PE = 0.4338X0PE = 1.7352RFPP = 2.478RFPE = 1.8585t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 8.26X1RvPP & X1RvPE = 0.826RFPP = 22.1124RFPE = 35.5508X0FwPE & X0RvPE = 34.7032RLd = 15.1724ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 4.543R1IN = 12.1618KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

2(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet15/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 16: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

The rated current is (1694.61 x 106) / (√3 x 132 x 103) = 7412.22 A5% of this corresponds to 0.05 x 7412.22 = 370.611 AThe secondary current is 370.611 / 1000 =0.371 A

Setting recommended = 0.4 ATime Delay: The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms2(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionization. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionization time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

2(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet16/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 17: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

2(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

3(a) REL 511 (21)- KASHIPUR – 2 FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 132 kV2)Line length - 60.09 Km3)Max power flow in the line - 1694.61 MVA4)Positive sequence resistance - 0.16221744 ohms/km5)Positive sequence reactance - 0.386116 ohms/km6)Zero sequence resistance - 0.405631 ohms/km7)Zero sequence reactance - 1.622174 ohms/km

B)CT/PT details1)CT primary rating - 1000A2)CT secondary rating - 1A3)PT primary rating - 145000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet17/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 18: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/1) /(145000/110)

= 0.758621Positive sequence line resistance in secondary,R1 = 0.16221744 x 15.615 x 0.758621

= 1.9216 ohmsPositive sequence line reactance in secondary,X1 = 0.386116 x 15.615 x 0.758621

= 4.5731 ohmsZero sequence line resistance in secondary,R0 = 0.405631 x 15.615 x 0.758621

= 4.8051 ohmsZero sequence line reactance in secondary,X0 = 1.622174 x 15.615 x 0.758621

= 19.2161 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.758621= 15.1724 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.758621= 3.7931 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 1.9216

= 1.5373 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 4.5739

= 3.6591 ohms/phaseZero sequence resistance , R0PE = 0.8 x 4.8051

= 3.8441 ohms/phaseZero sequence reactance , X0PE = 0.8 x 19.2161 = 15. 3729 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931, 3.6591x 0.4663 + 1.5373) , 3 x 3.6591}= 2 x Min {3.7931 10.9773 }= 7. 5862 ohms / loop

Resistive reach for phase-earth,

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet18/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 19: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X } = Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 3.6591 x 0.4663 +1.5373) , 4.5 x 3.6591}= Min { 15.1724 , 16.4659 }= 15.1724 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 1.9216

= 2.30592 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 4.5739

= 5.48868 ohms/phaseZero sequence resistance , R0PE = 1.2 x 4.8051

= 5.7661 ohms/phaseZero sequence reactance , X0PE = 1.2 x 19.2161

= 23.0593 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 5.48868 x 0.4663 + 2.3059) , 3 x 5.48868}= 2 x Min { 4.8653, 16.466 }= 9.7306 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 5.48868 x 0.4663 + 2.3059) , 4.5 x 5.48868}= Min { 15.1724 , 24.6990 }= 15.1724 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 1.9216

= 3. 8432 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 4.5739

= 9.1478 ohms/phaseZero sequence resistance , R0PE = 2 x 4.8051

= 9.6102 ohms/phaseZero sequence reactance , X0PE = 2 x 19.2161

= 38.4322 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 9.1478 x 0.4663 + 3.8432) , 3 x 9.1478}= 2 x Min { 8.1088 , 27.4434 }= 16.2176 ohms / loop

Resistive reach for phase-earth,

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet19/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 20: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X } = Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 9.1478 x 0.4663 + 3.8432) , 4.5 x 9.1478}= Min { 15.1724 , 27.4434 }= 15.1724 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 1.9216

= 0.3843 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 4.5739

= 0.9148 ohms/phaseZero sequence resistance , R0PE = 0.2 x 4.8051

= 0.9610 ohms/phaseZero sequence reactance , X0PE = 0.2 x 19.2161

= 3.8432 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 0.9148 x 0.4663 + 0.3843) , 3 x 0.9148}= 2 x Min { 3.7931 , 2.7444}= 5.4888 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 0.9148 x 0.4663 + 0.3843) , 4.5 x 0.9148}= Min { 15.1724 , 4.1166 }= 4.1166 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 9.1438= 18.2876 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 0.9148 = 1. 8296 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = ( 2 [2 x 3.8432 + 16.2176] )= 47.808 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 3.8432+ 9.6102)+15.1724])= 47.8759 ohms/loop

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet20/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 21: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 38.4332=76.8664 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (16.2176,15.1724) = 16.2176 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 9.1438 = 10.0582 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 3.8432 + 16.2176)= 26.2944 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 1.5373X1PP & X1PE = 3.6591R0PE = 3.8441X0PE = 15.3729RFPP = 7.5862RFPE = 15.1724

2) Zone-2 :-R1PP & R1PE = 2.30592X1PP & X1PE = 5.48868R0PE = 5.7661X0PE = 23.0593RFPP = 9.7306RFPE = 15.1724t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 3.8432

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet21/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 22: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

X1PP & X1PE = 9.1478R0PE = 9.6102X0PE = 38.4322RFPP = 16.2176RFPE = 15.1724t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.3843X1PP & X1PE = 0.9148R0PE = 0.961X0PE = 3.8432RFPP = 5.4888RFPE = 4.1166t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 18.2876X1RvPP & X1RvPE = 1.8296RFPP = 47.808RFPE = 47.8759X0FwPE & X0RvPE = 76.8664RLd = 16.2176ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 10.0582R1IN = 26.2944KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

3(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3A

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet22/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 23: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Time delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (1694.61 x 106) / (√3 x 132 x 103) = 7412.21 A5% of this corresponds to 0.05 x 7412.21 = 370.61 AThe secondary current is 370.61 / 1000 =0.37 A

Setting recommended = 0.4 ATime Delay: The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Margini.e., the time delay = 4ms + 60ms + 12ms + 75ms (Assuming 3 cycle breaker)

= 150ms3(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

3(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet23/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 24: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

3(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

4(a) REL 511 (21) - BASPUR NAGAR FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 132 kV2)Line length - 15.615 Km3)Max power flow in the line - 1694.61 MVA4)Positive sequence resistance - 0.16221744 ohms/km5)Positive sequence reactance - 0.386116 ohms/km6)Zero sequence resistance - 0.405631 ohms/km7)Zero sequence reactance - 1.622174 ohms/km

B)CT/PT details1)CT primary rating - 1000A

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet24/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 25: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2)CT secondary rating - 1A3)PT primary rating - 145000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/1) /(145000/110)

= 0.758621Positive sequence line resistance in secondary,R1 = 0.16221744 x 15.615 x 0.758621

= 1.9216 ohmsPositive sequence line reactance in secondary,X1 = 0.386116 x 15.615 x 0.758621

= 4.5731 ohmsZero sequence line resistance in secondary,R0 = 0.405631 x 15.615 x 0.758621

= 4.8051 ohmsZero sequence line reactance in secondary,X0 = 1.622174 x 15.615 x 0.758621

= 19.2161 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.758621= 15.1724 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.758621= 3.7931 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 1.9216

= 1.5373 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 4.5739

= 3.6591 ohms/phaseZero sequence resistance , R0PE = 0.8 x 4.8051

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet25/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 26: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 3.8441 ohms/phaseZero sequence reactance , X0PE = 0.8 x 19.2161 = 15. 3729 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931, 3.6591x 0.4663 + 1.5373) , 3 x 3.6591}= 2 x Min {3.7931 10.9773 }= 7. 5862 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 3.6591 x 0.4663 +1.5373) , 4.5 x 3.6591}= Min { 15.1724 , 16.4659 }= 15.1724 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 1.9216

= 2.30592 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 4.5739

= 5.48868 ohms/phaseZero sequence resistance , R0PE = 1.2 x 4.8051

= 5.7661 ohms/phaseZero sequence reactance , X0PE = 1.2 x 19.2161

= 23.0593 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 5.48868 x 0.4663 + 2.3059) , 3 x 5.48868}= 2 x Min { 4.8653, 16.466 }= 9.7306 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 5.48868 x 0.4663 + 2.3059) , 4.5 x 5.48868}= Min { 15.1724 , 24.6990 }= 15.1724 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 1.9216

= 3. 8432 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 4.5739

= 9.1478 ohms/phaseZero sequence resistance , R0PE = 2 x 4.8051

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet26/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 27: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 9.6102 ohms/phaseZero sequence reactance , X0PE = 2 x 19.2161

= 38.4322 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 9.1478 x 0.4663 + 3.8432) , 3 x 9.1478}= 2 x Min { 8.1088 , 27.4434 }= 16.2176 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 9.1478 x 0.4663 + 3.8432) , 4.5 x 9.1478}= Min { 15.1724 , 27.4434 }= 15.1724 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 1.9216

= 0.3843 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 4.5739

= 0.9148 ohms/phaseZero sequence resistance , R0PE = 0.2 x 4.8051

= 0.9610 ohms/phaseZero sequence reactance , X0PE = 0.2 x 19.2161

= 3.8432 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (3.7931 , 0.9148 x 0.4663 + 0.3843) , 3 x 0.9148}= 2 x Min { 3.7931 , 2.7444}= 5.4888 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (15.1724 , 0.9148 x 0.4663 + 0.3843) , 4.5 x 0.9148}= Min { 15.1724 , 4.1166 }= 4.1166 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet27/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 28: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 2 x X3 =2 x 9.1438= 18.2876 ohms/ phasePositive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE

= 2 x X4 =2 x 0.9148 = 1. 8296 ohms/ phasePositive sequence resistance for ph-ph faults for forward & reverse reach , RFPP

= (2[2*R3 + RFPP]) = ( 2 [2 x 3.8432 + 16.2176] )= 47.808 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 3.8432+ 9.6102)+15.1724])= 47.8759 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 38.4332=76.8664 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (16.2176,15.1724) = 16.2176 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 9.1438 = 10.0582 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 3.8432 + 16.2176)= 26.2944 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 1.5373X1PP & X1PE = 3.6591R0PE = 3.8441X0PE = 15.3729RFPP = 7.5862RFPE = 15.1724

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet28/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 29: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2) Zone-2 :-R1PP & R1PE = 2.30592X1PP & X1PE = 5.48868R0PE = 5.7661X0PE = 23.0593RFPP = 9.7306RFPE = 15.1724t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 3.8432X1PP & X1PE = 9.1478R0PE = 9.6102X0PE = 38.4322RFPP = 16.2176RFPE = 15.1724t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.3843X1PP & X1PE = 0.9148R0PE = 0.961X0PE = 3.8432RFPP = 5.4888RFPE = 4.1166t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 18.2876X1RvPP & X1RvPE = 1.8296RFPP = 47.808RFPE = 47.8759X0FwPE & X0RvPE = 76.8664RLd = 16.2176ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 10.0582R1IN = 26.2944KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet29/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 30: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

4(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (1694.61 x 106) / (√3 x 132 x 103) = 7412.21 A5% of this corresponds to 0.05 x 7412.21 = 370.61 AThe secondary current is 370.61 / 1000 =0.37 A

Setting recommended = 0.4 ATime Delay : The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms4(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet30/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 31: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

4(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

4(e)Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

5(a) REL 511 (21) - RISHIKESH FEEDER

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet31/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 32: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

System Particulars :-A)Line parameters

1)Rated line voltage - 400 kV2)Line length - 189 Km3)Max power flow in the line - 7109.02 MVA4)Positive sequence resistance - 0.029792 ohms/km5)Positive sequence reactance - 0.332 ohms/km6)Zero sequence resistance - 0.16192 ohms/km7)Zero sequence reactance - 1.24 ohms/km

B)CT/PT details1)CT primary rating - 1000A2)CT secondary rating - 6A3)PT primary rating - 400000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/6) /(400000/110)

= 0.045833Positive sequence line resistance in secondary,R1 = 0.029792 x 189 x 0.045833

= 0.2580 ohmsPositive sequence line reactance in secondary,X1 = 0.332 x 189 x 0.045833

= 2.8759 ohmsZero sequence line resistance in secondary,R0 = 0.16192 x 189 x 0.045833

= 1.4026 ohmsZero sequence line reactance in secondary,X0 = 1.24 x 189 x 0.045833

= 10.7414 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.045833= 0.9167 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.045833= 0.2291 ohms

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet32/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 33: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 0.2580

= 0.2064 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 2.8759

= 2.3007 ohms/phaseZero sequence resistance , R0PE = 0.8 x 1.4026

= 1.1221 ohms/phaseZero sequence reactance , X0PE = 0.8 x 10.7414 = 8.5931 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291, 2.3007 x 0.4663 + 0.2064) , 3 x 2.3007}= 2 x Min {1.2792, 6.9021 }= 2.5584 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 2.3007 x 0.4663 +0.2064) , 4.5 x 2.3007}= Min { 1.2792 , 10.3532 }= 1.2792 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 0.2580

= 0.3096 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 2.8759

= 3.4511 ohms/phaseZero sequence resistance , R0PE = 1.2 x 1.4026

= 1.6831 ohms/phaseZero sequence reactance , X0PE = 1.2 x 10.7414

= 12.8897 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 3.4511 x 0.4663 + 0.3096) , 3 x 3.4511}= 2 x Min { 1.9188, 10.3533 }= 3.8376 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet33/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 34: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 3.4511 x 0.4663 + 0.3096) , 4.5 x 3.4511}= Min { 1.9188 , 15.5299 }= 1.9188 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 0.2580

= 0.516 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 2.8759

= 5.7518 ohms/phaseZero sequence resistance , R0PE = 2 x 1.4026

= 2.8052 ohms/phaseZero sequence reactance , X0PE = 2 x 10.7414

= 21.4828 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 5.7518 x 0.4663 + 0.516) , 3 x 5.7518}= 2 x Min { 3.1981 , 17.2554 }= 6.3962 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 5.7518 x 0.4663 + 0.516) , 4.5 x 5.7518}= Min { 3.1981, 25.8831 }= 3.1981 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 0.2580

= 0.0516 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 2.8759

= 0.5752ohms/phaseZero sequence resistance , R0PE = 0.2 x 1.4026

= 0.2805ohms/phaseZero sequence reactance , X0PE = 0.2 x 10.7414

= 2.1483 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 0.5752 x 0.4663 + 0.0516) , 3 x 0.5752}= 2 x Min { 0.3198 , 1.7256}= 0.6396 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 0.5752 x 0.4663 + 0.0516) , 4.5 x 0.5752

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet34/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 35: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= Min { 0.9167 , 2.5884 }= 0.9167 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 5.7518= 11.5036 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 0.5752 = 1. 1504 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = (2 [2 x 0.516 + 6.3962])= 14. 8564 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 0.516+ 2.8052) + 3.1981])= 8.9541 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 21.4828=42.9656 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (6.3962,3.1981) = 6.3962 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 5.7518 = 6.3270 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 (2 x 0.516 + 6.3962)= 8.168 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet35/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 36: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 0.2064X1PP & X1PE = 2.3007R0PE = 1.1221X0PE = 8.5931RFPP = 2.5584RFPE = 1.2792

2) Zone-2 :-R1PP & R1PE = 0.3096X1PP & X1PE = 3.4511R0PE = 1.6831X0PE = 12.8897RFPP = 3.8376RFPE = 1.9188t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 0.516X1PP & X1PE = 5.7518R0PE = 2.8052X0PE = 21.4828RFPP = 6.3962RFPE = 3.1981t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.0516X1PP & X1PE = 0.5752R0PE = 0.2805X0PE = 2.1483RFPP = 0.6396RFPE = 0.9167t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 11.5036X1RvPP & X1RvPE = 1.1504RFPP = 14.8564RFPE = 8.9541X0FwPE & X0RvPE = 42.9656RLd = 6.3962ARGLd = 25º

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet36/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 37: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

tPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 6.3270R1IN = 8.168KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

5(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 6A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (7109.02 x 106) / (√3 x 400 x 103) = 10261.29 A5% of this corresponds to 0.05 x 10261.29 = 513.06 AThe secondary current is 513.06 x 6 / 1000 =3.0786 A

Setting recommended = 3.1 ATime Delay : The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms5(c) Auto reclose RAAAM

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet37/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 38: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

5(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

5(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet38/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 39: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

5(f) LZ96 Distance Relay

System Particulars :-A)Line parameters

1)Rated line voltage - 400 kV2)Line length - 189 Km3)Max power flow in the line - 7109.02 MVA4)Positive sequence resistance - 0.029792 ohms/km5)Positive sequence reactance - 0.332 ohms/km6)Zero sequence resistance - 0.16192 ohms/km7)Zero sequence reactance - 1.24 ohms/km

B)CT/PT details1)CT primary rating - 1000 A2)CT secondary rating - 6 A3)PT primary rating - 400000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/6) /(400000/110)

= 0.045833Positive sequence line resistance in secondary,R1 = 0.029792 x 189 x 0.4

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet39/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 40: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 0.258073 ohmsPositive sequence line reactance in secondary,X1 = 0.332 x 189 x 0.4

= 2.87595 ohmsZero sequence line resistance in secondary,R0 = 0.16192 x 189 x 0.4

= 46.81152 ohmsZero sequence line reactance in secondary,X0 = 1.24 x 189 x 0.4

= 93.744 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance R1 = 0.8 x 0.258073

= 0.206459 ohms/phasePositive sequence reactance X1 = 0.8 x 2.87595

= 2.30076 ohms/phase Z1 = 0.206459+j 2.30076 ohms/phase │Z1│= 2.31 ohms/phase Zone-2 settingPositive sequence resistance R1 = 1.2 x 0.258073

= 0.309668 ohms/phasePositive sequence reactance X1 = 1.2 x.2.87595

= 3.45114 ohms/phase Z2 = 0.309668+j3.45114 ohms/phase

│Z2│ = 3.46501 ohms/phaseZone-3 settingPositive sequence resistance , R1 = 2 x 0.258073

= 0.516146 ohms/phasePositive sequence reactance , X2 = 2 x 2.87595

= 5.7519 ohms/phase Z3 = 0.516146+j5.7519 ohms/phase │Z3│ = 5.77501 ohms/phaseZone-4 settingPositive sequence resistance , R1 = 0.2 x 0.258073

= 0.05162 ohms/phasePositive sequence reactance , X1 = 0.2 x 9.74175

= 0.5752 ohms/phase Z4 = 0.05162+j0.5752 ohms/phase

│Z4│ = 0.5723 ohms/phase

Setting of Distance ZonesThe values of Zi (i=1,2,3) for the zones can be set using the formula : Zi = ZM * mi * 100/Ni Ohms/phase m = 1,10,100 m1/N1 = Z1/(100*ZM)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet40/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 41: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 6.9543/(100*0.1) m1/N1 = 0.84782 m1= 100 N1 = 87 m2/N2 = Z2/(100*Zm) = 10.4433/(100*0.1) m2/N2 = 1.04433 m2 = 100 N2= 58 m3/N3 = Z3/(100*Zm) = 17.4055/(100*0.1) m3/N3 = 1.74055 m3= 100 N3= 35 REPLICA IMPEDANCE (ZM)= 0.02 REPLICA ANGLE (PHI-M) = 85

Setting Of Under Impedance Starter

ZA= (0.258073+j*2.87595)+(1.2*(0.029792+j*0.332)*189*0.045833) Load Impedance = 400*400/ 7109.02 ZA= 0.567761 +j 6.32709

ZA is less than 0.65 * Load Impedance. ZA is set according to the formula : ZA = 50 * ZM * 100/NA NA = 50*100*0.02/6.35251 Reverse to forward reach ratio kB = ZB/ZA = 0.3

Setting Of Zero Seq. Compensation Factor: ko= Z0-Z1/3*Z1 =((0.16192+j*1.24)-(0.029792+j*0.332))/(3*(0.029792+j*0.332)) =0.3

The Recommended Settings m1 = 100

N1 = 87

m2 = 100

N2 = 58

m3 = 100

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet41/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 42: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

N3 = 35

ZM = 0.02

6(a) REL 511 (21) - MORADABAD FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 400 kV2)Line length - 92.26 Km3)Max power flow in the line - 17084.91 MVA4)Positive sequence resistance - 0.029792 ohms/km5)Positive sequence reactance - 0.332 ohms/km6)Zero sequence resistance - 0.16192 ohms/km7)Zero sequence reactance - 1.24 ohms/km

B)CT/PT details1)CT primary rating - 1000A2)CT secondary rating - 6A3)PT primary rating - 400000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/6) /(400000/110)

= 0.045833Positive sequence line resistance in secondary,R1 = 0.029792 x 92.26 x 0.045833

= 0.1259 ohmsPositive sequence line reactance in secondary,X1 = 0.332 x 92.26 x 0.045833

= 1.4039 ohmsZero sequence line resistance in secondary,R0 = 0.16192 x 92.26 x 0.045833

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet42/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 43: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 0.6847 ohmsZero sequence line reactance in secondary,X0 = 1.24 x 92.26 x 0.045833

= 5.2434 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.045833= 0.9167 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.045833= 0.2291 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 0.1259

= 0.10072 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 1.4039

= 1.1231 ohms/phaseZero sequence resistance , R0PE = 0.8 x 0.6847

= 0.5478 ohms/phaseZero sequence reactance , X0PE = 0.8 x 5.2434 = 4.1947 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291, 1.1231 x 0.4663 + 0.10072) , 3 x 1.1231}= 2 x Min {0.6244, 3.3693 }= 1.2488 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 1.1231 x 0.4663 + 0.10072) , 4.5 x 1.1231}= Min { 0.9167 , 5.0539 }= 0.9167 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 0.1259

= 0.1511 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 1.4039

= 1.6847 ohms/phaseZero sequence resistance , R0PE = 1.2 x 0.6847

= 0.8216 ohms/phaseZero sequence reactance , X0PE = 1.2 x 5.2434

= 6.2921 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet43/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 44: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 1.6847 x 0.4663 + 0.1511) , 3 x 1.6847}= 2 x Min { 0.9377, 5.0541 }= 1.8754 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 1.6847 x 0.4663 + 0.1511) , 4.5 x 1.6847}= Min { 0.9377 , 7.5812 }= 0.9377 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 0.1259

= 0.2518 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 1.4039

= 2.8078 ohms/phaseZero sequence resistance , R0PE = 2 x 0.6847

= 1.3694 ohms/phaseZero sequence reactance , X0PE = 2 x 5.2434

= 10.4868 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 2.8078 x 0.4663 + 0.2518) , 3 x 2.8078}= 2 x Min { 1.5611 , 5.6156 }= 3.1222 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.2291 , 2.8078 x 0.4663 + 0.2518) , 4.5 x 5.7518}= Min { 1.5611, 25.8831 }= 1.5611 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 0.1259

= 0.0252 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 1.4039

= 0.2808ohms/phaseZero sequence resistance , R0PE = 0.2 x 0.6847

= 0.1369ohms/phaseZero sequence reactance , X0PE = 0.2 x 5.2434

= 1.0487 ohms/phase

Resistive reach for phase-phase faults,

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet44/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 45: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X } = 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (0.2291 , 0.2808 x 0.4663 + 0.0252) , 3 x 0.2808}= 2 x Min { 0.2291 , 0.8424}= 0.4582 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (0.9167 , 0.2808 x 0.4663 + 0.0252) , 4.5 x 0.2808}= Min { 0.9167 , 1.2636 }= 0.9167 ohms / loop

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 2.8078= 5.6156 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 0.2808 = 0.5616 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = ( 2 [2 x 0.2518 + 3.1222] )= 7.2516 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 0.2518+ 1.3694)+1.5611])= 1.3709 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 10.4868=20.9736 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (3.1222.1.5611) = 3.1222 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet45/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 46: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 2.8078 = 3.08858 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 0.2518 + 3.1222)= 3.9084 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 0.10072X1PP & X1PE = 1.1231R0PE = 0.5478X0PE = 4.1947RFPP = 1.2488RFPE = 0.9167

2) Zone-2 :-R1PP & R1PE = 0.1511X1PP & X1PE = 1.6847R0PE = 0.8216X0PE = 6.2921RFPP = 1.8754RFPE = 0.9377t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 0.2518X1PP & X1PE = 2.8078R0PE = 1.3694X0PE = 10.4868RFPP = 1.3222RFPE = 1.5611t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.0252X1PP & X1PE = 0.2808

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet46/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 47: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

R0PE = 0.1369X0PE = 1.0487RFPP = 0.4582RFPE = 0.9167t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 5.6156X1RvPP & X1RvPE = 0.5616RFPP = 7.2516RFPE = 1.3709X0FwPE & X0RvPE = 20.9736RLd = 3.1222ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 3.08858R1IN = 3.9084KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

6(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 6 A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet47/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 48: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

The rated current is (17084.91 x 106) / (√3 x 400 x 103) = 24660.67 A5% of this corresponds to 0.05 x 24660.67 = 1233.03 AThe secondary current is 1233.03 x 6 / 1000 =7.398 A

Setting recommended = 7.4 ATime Delay : The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms6(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

6(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet48/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 49: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

6(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

6(f) LZ96 Distance Relay

System Particulars :-A)Line parameters

1)Rated line voltage - 400 kV2)Line length - 92.26 Km3)Max power flow in the line - 17084.91 MVA4)Positive sequence resistance - 0.029792 ohms/km5)Positive sequence reactance - 0.332 ohms/km6)Zero sequence resistance - 0.16192 ohms/km7)Zero sequence reactance - 1.24 ohms/km

B)CT/PT details1)CT primary rating - 1000 A2)CT secondary rating - 6 A3)PT primary rating - 400000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet49/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 50: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (1000/1) /(400000/110)

= 0.275Positive sequence line resistance in secondary,R1 = 0.029792 x 107.794x 0.275

= 0.883 ohmsPositive sequence line reactance in secondary,X1 = 0.332 x 107.794 x 0.275

= 1.40389 ohmsZero sequence line resistance in secondary,R0 = 0.16192 x 92.26 x 0.045833

= 0.6847 ohmsZero sequence line reactance in secondary,X0 = 1.24 x 92.26 x 0.045833

= 5.2434 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance R1 = 0.8 x 0.125978

= 0.100782 ohms/phasePositive sequence reactance X1 = 0.8 x 1.40389

= 1.12311 ohms/phase Z1 = 0.100782+j 1.12311 ohms/phase │Z1│= 1.12762 ohms/phase Zone-2 settingPositive sequence resistance R1 = 1.2 x 0.125978

= 0.151174 ohms/phasePositive sequence reactance X1 = 1.2 x 1.40389

= 1.68467 ohms/phase Z2 = 0.151174+j1.6847 ohms/phase

│Z2│ = 1.69144 ohms/phaseZone-3 settingPositive sequence resistance , R1 = 2 x 0.125978

= 0.251976 ohms/phasePositive sequence reactance , X2 = 2 x 1.40389

= 2.80778 ohms/phase Z3 = 0.251976+j2.80778 ohms/phase │Z3│ = 2.81906 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet50/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 51: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zone-4 settingPositive sequence resistance , R1 = 0.2 x 0.125978

= 0.0251976 ohms/phasePositive sequence reactance , X1 = 0.2 x 1.40389

= 0.280778 ohms/phase Z4 = 0.0251976+j0.280778 ohms/phase

│Z4│ = 0.2819 ohms/phase

Setting of Distance ZonesThe values of Zi (i=1,2,3) for the zones can be set using the formula : Zi = ZM * mi * 100/Ni Ohms/phase m = 10 m1/N1 = Z1/(100*ZM) = 6.9543/(100*0.1) m1/N1 = 0.84782 m1= 10 N1 = 18 m2/N2 = Z2/(100*Zm) = 10.4433/(100*0.1) m2/N2 = 1.04433 m2 = 10 N2= 12 m3/N3 = Z3/(100*Zm) = 17.4055/(100*0.1) m3/N3 = 1.74055 m3= 100 N3= 71 REPLICA IMPEDANCE (ZM)= 0.02 REPLICA ANGLE (PHI-M) = 85

Setting Of Under Impedance Starter

ZA= (0.125978+j*1.40389)+(1.2*(0.029792+j*0.332)*92.26*0.0458333) Load Impedance = 400*400/ 17084.91 ZA= 1.60232 +j 18.7968

ZA is less than 0.65 * Load Impedance. ZA is set according to the formula : ZA = 50 * ZM * 100/NA NA = 50*100*0.02/3.10097 Reverse to forward reach ratio kB = ZB/ZA = 0.3

Setting Of Zero Seq. Compensation Factor: ko= Z0-Z1/3*Z1 =((0.16192+j*1.24)-(0.029792+j*0.332))/(3*(0.029792+j*0.332)) = 0.3

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet51/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 52: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

The Recommended Settings m1 = 10

N1 = 18

m2 = 10

N2 = 12

m2 = 100

N1 = 71

ZM = 0.02

PHI-M = 85

kB = 0.3

7(a) REL 511 (21) - HALDWANI FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 220 kV2)Line length - 53.5 Km3)Max power flow in the line - 2870.56 MVA4)Positive sequence resistance - 0.0748748 ohms/km5)Positive sequence reactance - 0.399252 ohms/km6)Zero sequence resistance - 0.219978 ohms/km7)Zero sequence reactance - 1.339228 ohms/km

B)CT/PT details1)CT primary rating - 800 A2)CT secondary rating - 1 A3)PT primary rating - 220000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet52/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 53: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (800/1) /(220000/110)

= 0.4Positive sequence line resistance in secondary,R1 = 0.0748748 x 53.50 x 0.4

= 1.6023 ohmsPositive sequence line reactance in secondary,X1 = 0.399252 x 53.50 x 0.4

= 8.5440 ohmsZero sequence line resistance in secondary,R0 = 0.219978 x 53.50 x 0.4

= 4.7075 ohmsZero sequence line reactance in secondary,X0 = 1.339228 x 53.50 x 0.4

= 28. 6595 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.4= 8 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.4= 2 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 1.6023

= 1.2818 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 8.5440

= 6.8352 ohms/phaseZero sequence resistance , R0PE = 0.8 x 4.7075

= 3.766 ohms/phaseZero sequence reactance , X0PE = 0.8 x 28.6595 = 22.9276 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2, 6.8352 x 0.4663 + 1.28184) , 3 x 6.8352}= 2 x Min {4.4691, 20.5056 }= 8.9382 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet53/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 54: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 6.8352 x 0.4663 + 1.28184) , 4.5 x 6.8352}= Min { 8 , 30.8754 }= 8 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 1.6023

= 1.9228 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 8.554

= 10.2648 ohms/phaseZero sequence resistance , R0PE = 1.2 x 4.7075

= 5.649 ohms/phaseZero sequence reactance , X0PE = 1.2 x 28.6595

= 34.3914 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 10.2648 x 0.4663 + 1.9228) , 3 x 10.2648}= 2 x Min { 6.7093, 30.7944 }= 13. 4186 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 10.2648 x 0.4663 + 1.9228), 4.5 x 10.2648}= Min { 8 , 46.1916 }= 8 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 1.6023

= 3.2046 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 8.554

= 17.108 ohms/phaseZero sequence resistance , R0PE = 2 x 4.7075

= 9.415 ohms/phaseZero sequence reactance , X0PE = 2 x 28.6595

= 57. 319 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 17.108 x 0.4663 + 3.2046) , 3 x 17.108 }= 2 x Min { 11.1821 , 51.324 }= 22.3642 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet54/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 55: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8, 17.108 x 0.4663 + 3.2046) , 4.5 x 17.108 }= Min { 11.1821, 76.986 }= 11.1821 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 1.6023

= 0.3205 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 8.554

= 1.7108ohms/phaseZero sequence resistance , R0PE = 0.2 x 4.7075

= 0.9415 ohms/phaseZero sequence reactance , X0PE = 0.2 x 28.6595

= 5.7319 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 1.7108 x 0.4663 + 0.3205) , 3 x 1.7108}= 2 x Min { 2 , 5.1324}= 4 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 1.7108 x 0.4663 + 0.3205) , 4.5 x 1.7108 }= Min { 8 , 7.6986 }= 7. 6986 ohms/km

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 17.108= 34.216 ohms/ phase

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 1.7108 = 3.4216 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = ( 2 [2 x 3.2046 + 22.3642] )= 57. 5468 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 3.2046 + 9.415)+11.1821])= 34. 391 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet55/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 56: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

= 2 x X03= 2 x X0PE= 2 x 51.319 = 102.638 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (22.3642,11.1821) = 22.3642 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 17.108 = 18.8188 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 3.2046 + 22.3642)= 31.6507 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 1.2818X1PP & X1PE = 6.8352R0PE = 3.766X0PE = 22.9276RFPP = 8.9382RFPE = 8

2) Zone-2 :-R1PP & R1PE = 1.9228X1PP & X1PE = 10.2648R0PE = 5.649X0PE = 34.3914RFPP = 13.4186RFPE = 8t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 3.2046X1PP & X1PE = 17.108

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet56/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 57: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

R0PE = 9.415X0PE = 57.319RFPP = 22.3642RFPE = 11.1821t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.3205X1PP & X1PE = 1.7108R0PE = 0.9415X0PE = 5.7319RFPP = 2.2364RFPE = 1.1182t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 34.216X1RvPP & X1RvPE = 3.4216RFPP = 57.5468RFPE = 32.9031X0FwPE & X0RvPE = 102.638RLd = 22.3642ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 18.8188R1IN = 31.6507KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

7(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3A

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet57/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 58: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Time delay: 20 ms - 99 hrs

System Particulars:CT ratio = 800 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (2780.56 x 106) / (√3 x 220 x 103) = 7297.29 A5% of this corresponds to 0.05 x 7297.29 = 364.86 AThe secondary current is 364.86 / 800 =0.4561 A

Setting recommended = 0.5 ATime Delay : The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms7(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionisation. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionisation time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

7(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet58/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 59: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

7(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

7(f) LZ96 Distance Relay

System Particulars :-A)Line parameters

1)Rated line voltage - 220 kV2)Line length - 53.5 Km3)Max power flow in the line - 2870.56 MVA4)Positive sequence resistance - 0.0748748 ohms/km5)Positive sequence reactance - 0.399252 ohms/km6)Zero sequence resistance - 0.219978 ohms/km7)Zero sequence reactance - 1.339228 ohms/km

B)CT/PT details1)CT primary rating - 800 A

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet59/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 60: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2)CT secondary rating - 1 A3)PT primary rating - 220000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (800/1) /(220000/110)

= 0.4Positive sequence line resistance in secondary,R1 = 0.0748748 x 53.50 x 0.4

= 1.6023 ohmsPositive sequence line reactance in secondary,X1 = 0.399252 x 53.50 x 0.4

= 8.5440 ohmsZero sequence line resistance in secondary,R0 = 0.219978 x 53.50 x 0.4

= 4.7075 ohmsZero sequence line reactance in secondary,X0 = 1.339228 x 53.50 x 0.4

= 28. 6595 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance R1 = 0.8 x 1.6023

= 1.2818 ohms/phasePositive sequence reactance X1 = 0.8 x 8.5440

= 6.8352 ohms/phase Z1 = 1.2818+j6.8352 ohms/phase │Z1│= 6.9543 ohms/phase Zone-2 settingPositive sequence resistance R1 = 1.2 x 1.6023

= 1.9228 ohms/phasePositive sequence reactance X1 = 1.2 x 8.554

= 10.2648 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet60/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 61: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Z2 = 1.9228+j10.2648 ohms/phase │Z2│ = 10.4315 ohms/phase

Zone-3 settingPositive sequence resistance , R1 = 2 x 1.6023

= 3.2046 ohms/phasePositive sequence reactance , X2 = 2 x 8.554

= 17.108 ohms/phase Z3 = 3.2046+j17.108 ohms/phase │Z3│ = 17.1629 ohms/phaseZone-4 settingPositive sequence resistance , R1 = 0.2 x 1.6023

= 0.3205 ohms/phasePositive sequence reactance , X1 = 0.2 x 8.554

= 1.7108ohms/phase Z4 = 0.3205+j1.7108 ohms/phase

│Z4│ = 1.7056 ohms/phase

Setting of Distance ZonesThe values of Zi (i=1,2,3) for the zones can be set using the formula : Zi = ZM * mi * 100/Ni Ohms/phase m = 10 m1/N1 = Z1/(100*ZM) = 6.9543/(100*0.1) m1/N1 = 0.84782 m1= 10 N1 = 14 m2/N2 = Z2/(100*Zm) = 10.4433/(100*0.1) m2/N2 = 1.04433 m2 = 100 N2= 96 m3/N3 = Z3/(100*Zm) = 17.4055/(100*0.1) m3/N3 = 1.74055 m3= 100 N3= 58 REPLICA IMPEDANCE (ZM)= 0.1 REPLICA ANGLE (PHI-M) = 85

Setting Of Under Impedance Starter

ZA= (1.60232+j*8.54399)+(1.2*(0+j*0.399252)*53.5*0.4) Load Impedance = 220*220/ 2870.56 ZA= 1.60232 +j 18.7968

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet61/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 62: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

ZA is less than 0.65 * Load Impedance. ZA is set according to the formula : ZA = 50 * ZM * 100/NA NA = 50*100*0.1/18.865 Reverse to forward reach ratio kB = ZB/ZA = 0.3

Setting Of Zero Seq. Compensation Factor: ko= Z0-Z1/3*Z1 =((0.219978+j*1.33923)-(0.0748748+j*0.399252))/(3*(0.0748748+j*0.399252)) =0.3

The Recommended Settings m1 = 10

N1 = 14

m2 = 100

N2 = 96

m3 = 100

N3 = 58

ZM = 0.1

PHI-M = 85

ko = 0.3

kB = 0.3

8(a) REL 511 (21) – ALMORA FEEDER

System Particulars :-A)Line parameters

1)Rated line voltage - 220 kV2)Line length - 61 Km3)Max power flow in the line - 3783.99 MVA4)Positive sequence resistance - 0.0748748 ohms/km5)Positive sequence reactance - 0.399252 ohms/km6)Zero sequence resistance - 0.219978 ohms/km7)Zero sequence reactance - 1.339228 ohms/km

B)CT/PT details1)CT primary rating - 800 A

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet62/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 63: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

2)CT secondary rating - 1 A3)PT primary rating - 220000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR = (800/1) /(220000/110)

= 0.4Positive sequence line resistance in secondary,R1 = 0.0748748 x 61x 0.4

= 1.8269 ohmsPositive sequence line reactance in secondary,X1 = 0.399252 x 61x 0.4

= 9.7417 ohmsZero sequence line resistance in secondary,R0 = 0.219978 x 61x 0.4

= 5.3675 ohmsZero sequence line reactance in secondary,X0 = 1.339228 x 61x 0.4

= 32.6772 ohms

Fault resistance in secondary for phase-earth faults , Rfe = 20 x 0.4= 8 ohms

Fault resistance in secondary for phase-phase faults , Rfp = 5 x 0.4= 2 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance , R1PP&R1PE = 0.8 x 1.8269

= 1.4615 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.8 x 9.7417

= 7.79336 ohms/phaseZero sequence resistance , R0PE = 0.8 x 5.3675

= 4.294 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet63/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 64: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zero sequence reactance , X0PE = 0.8 x 32.6772 = 26.1418 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2, 7.79336 x 0.4663 + 1.4615) , 3 x 7.79336}= 2 x Min {5.0955, 23.3801 }= 10.191 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 7.79336 x 0.4663 + 1.4615) , 4.5 x 7.79336}= Min { 8 , 35.0701 }= 8 ohms / loop

Zone-2 settingPositive sequence resistance , R1PP&R1PE = 1.2 x 1.8269

= 2.1923 ohms/phasePositive sequence reactance , X1PP&X1PE = 1.2 x 9.7417

= 11.69004 ohms/phaseZero sequence resistance , R0PE = 1.2 x 5.3675

= 6.441 ohms/phaseZero sequence reactance , X0PE = 1.2 x 32.6772

= 39.2126 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 11.69 x 0.4663 + 2.1923) , 3 x 11.69}= 2 x Min { 7.6433, 35.07 }= 15.2866 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 11.69 x 0.4663 + 2.1923), 4.5 x 11.69}= Min { 8 , 52.61 }= 8 ohms/ loop

Zone-3 settingPositive sequence resistance , R1PP&R1PE = 2 x 1.8269

= 3.6538 ohms/phasePositive sequence reactance , X1PP&X1PE = 2 x 9.7417

= 19.4834 ohms/phaseZero sequence resistance , R0PE = 2 x 5.3675

= 10.735 ohms/phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet64/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 65: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zero sequence reactance , X0PE = 2 x 32.6772= 65.3544 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 19.4834 x 0.4663 + 3.6538) , 3 x 19.4834 }= 2 x Min { 12.7389 , 58.4502 }= 25.4778 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8, 19.4834 x 0.4663 + 3.6538) , 4.5 x 19.4834 }= Min { 12.7389, 87.6753 }= 12.7389 ohms / loop

Zone-4 setting (reverse)Positive sequence resistance , R1PP&R1PE = 0.2 x 1.8269

= 0.3654 ohms/phasePositive sequence reactance , X1PP&X1PE = 0.2 x 9.7417

= 1.9483ohms/phaseZero sequence resistance , R0PE = 0.2 x 5.3675

= 1.0735 ohms/phaseZero sequence reactance , X0PE = 0.2 x 32.6772

= 6.5354 ohms/phase

Resistive reach for phase-phase faults, RFPP = 2 x Min { Max (Fault resistance, X tan 25 +R) , 3X }

= 2 x Min { Max (Rfp , X1PP tan 25 +R1PP) , 3X1PP } = 2 x Min { Max (2 , 1.9483 x 0.4663 + 0.3564) , 3 x 1.9843}

= 2 x Min { 2 , 5.9529}= 4 ohms / loop

Resistive reach for phase-earth, RFPE = Min { Max (Fault resistance, X tan 25 +R) , 4.5X }

= Min { Max (Rfe , X1PE tan 25 +R1PE) , 4.5X1PE } = Min { Max (8 , 1.9483 x 0.4663 + 0.3564) , 4.5 x 1.9483 }= Min { 8 , 8.7674 }= 8 ohms/km

General Fault Criteria (GFC)

GFC is an overall impedance-measuring element with a very high reach and long time delay for its tripping function. The GFC characteristics should in general cover all the impedance measuring zones used for distance protection ,regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Positive sequence reactance for ph-ph & ph-e elements in the forward direction ,X1FwPP & X1FwPE= 2 x X3 =2 x 19.4834= 38.9668 ohms/ phase

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet65/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 66: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction ,X1RvPP & X1RvPE= 2 x X4 =2 x 1.9483 = 3.8966 ohms/ phase

Positive sequence resistance for ph-ph faults for forward & reverse reach , RFPP= (2[2*R3 + RFPP]) = ( 2 [2 x 3.6538 + 25.4778] )= 65.5708 ohms/loop

Positive sequence resistance for ph-e faults for forward & reverse reach , RFPE= (2[1/3(2R3 + R03)+RFPE])= (2[1/3(2 x 3.6538 + 10.735)+12.7389])= 37.5062 ohms/loop

Zero sequence reactance for ph-e elements in the forward & reverse direction, X0FwPE & X0RvPE = 2 x X03= 2 x X0PE= 2 x 65.3544 = 130.7088 ohms/phase

The resistive reach in the load impedance area , RLd = Max(RFPP,RFPE) = Max (25.4778,12.7389) = 25. 4778 ohms/loop

Load Angle, ARGLd = 25º (Assumed)

Power Swing Block FunctionThe reach of the inner characteristic in the resistive and reactive direction is set so that the inner

characteristics covers completely all the distance protection zones,which are to be blocked by the PSD function.At least 10% of additional safety margin is considered.

Reactive reach of the inner characteristics of the power swing blocking element , X1IN= 1.1 x X3= 1.1 x X1PP= 1.1 x 19.4834 = 21.4317 ohms/phase

Resistive reach of the inner characteristics of the power swing blocking element , R1IN= 1.1 (2R3 +RFPP)= 1.1 ( 2 x 3.6538 + 25.4778)= 36.0639 ohms/phase

Reach multiplication for the outer reactive boundary, KX = 125%(recommended)Reach multiplication for the outer reactive boundary, KR = 125%(recommended)

Setting Recommendations:-

1) Zone-1:-R1PP & R1PE = 1.4615X1PP & X1PE = 0.7934R0PE = 4.294X0PE = 26.1418RFPP = 10.191RFPE = 8

2) Zone-2 :-

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet66/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 67: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

R1PP & R1PE = 2.1923X1PP & X1PE = 11.69004R0PE = 6.441X0PE = 39.2126RFPP = 15.2866RFPE = 8t2PP & t2PE = 0.400 s (time delay for trip)

3) Zone-3 :-R1PP & R1PE = 3.6538X1PP & X1PE = 19.4834R0PE = 10.735X0PE = 65.3544RFPP = 25.47`78RFPE = 12.7389t3PP & t3PE = 0.800 s(time delay for trip) 4) Zone-4:- (reverse)R1PP & R1PE = 0.3654X1PP & X1PE = 1.9483R0PE = 1.0735X0PE = 6.5354RFPP = 4RFPE = 8t4PP & t4PE = 0.250 s (time delay for trip)

5) GFC :-X1FwPP & X1FwPE = 38.9668X1RvPP & X1RvPE = 3.8966RFPP = 65.5708RFPE = 37.5062X0FwPE & X0RvPE = 130.7088RLd = 25.4778ARGLd = 25ºtPP & tPE = 2s(time delay for trip)

6) PSB :-X1IN = 21.4317R1IN = 36.0639KX = 125RX = 125tP1 = 0.045s(Initial PSD timer for the first swing)tP2 = 0.015s(Fast PSD timer for the consecutive swings within tW)tW = 0.250s(Hold timer for the activation of fast PSD timer)tH = 0.5s (Hold Timer for PSD detected)tEF = 60s(Timer overcoming 1-Ph reclosing dead time)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet67/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 68: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

tR1 = 0.300s(Timer to time delay block by the residual current)tR2 = 2.00s (On delay timer for blocking of output signal at very slow swings

The time delays tP1,tP2,tW,tH,tEF,tR1,tR2 are recommendations and the same need to be set in accordance with the system studies.

8(b) Breaker Failure Protection - 50 - RAICA

Relay Detail:RXIB range: 0 .2-3ATime delay: 20 ms - 99 hrs

System Particulars:CT ratio = 1000 / 1A

Calculations:Setting of LBB should be as sensitive or more sensitive than the most sensitive protection of the unit. The most sensitive protection of the unit is Reverse power protection which is set at 5%. Hence the setting recommended is 5% of the rated current

The rated current is (3783.99 x 106) / (√3 x 220 x 103) = 9930.69 A5% of this corresponds to 0.05 x 9930.69 = 496.53 AThe secondary current is 496.53 / 800 =0.6207 A

Setting recommended = 0.62 ATime Delay: The time delay should include RXIB pickup time + Breaker opening time + Reset time of RXIB24 + Marginie., the time delay = 4ms + 60ms + 12ms + 75ms ( Assuming 3 cycle breaker)

= 150ms

8(c) Auto reclose RAAAM

Dead Time: A time between the fault clearing and the reclosing shot is necessary to allow for the arc de-ionization. The dead time setting corresponds to the time between the auto reclosing start and the reclosing shot. In the event of a single phase fault and single phase tripping in long lines, the de-ionization time will be longer than with three phase tripping due to capacitive coupling to the healthy phases.Single phase dead time is recommended to be set to 1secThree phase dead time is recommended to be set to 600msecReclaim Time: The reclaim time is the time during which a new start of the auto-reclosing is blocked. It is chosen considering the breaker duty cycle, which

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet68/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 69: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

specifies the minimum allowed time between successive breaker reclosing attempts, so that an eventual tripping and reclosing on to permanent faults, will neither deteriorate the breaker capacity nor damage the breaker. Typical value = 30 sec.

8(d) Under Voltage Protection – 27P - RXEG

Relay Details:RXEG range: 40 - 120 V

Calculations:Under voltage 1st stage is set to 85% of the rated voltage.Setting of RXEG = 0.85 x 110 = 93.5 VTime delay 1st stage – 3 sec.Under voltage 2nd stage is set to 80% of the rated voltage.Setting of RXEG = 0.8 x 110 = 88 VTime delay 2nd stage – 1 sec.

Recommended Settings:RXEG 1st stage setting = (2.34 x 40)RXEG 2nd stage setting = (2.2 x 40)Timers Stage I = 3 secStage II = 1 sec

8(e) Check Synchronizing Relay RASC:

Relay Details:Voltage difference: 7.5 - 67.5 % in steps of 7.5%Phase angle difference: 5 - 75 in steps of 5

Calculations:Check synchronizing relay for line is set to voltage difference of 30 % and phase angle difference of 30

.

Recommended SettingsVoltage setting: 4 * 7.5 %Phase angle setting: 6 * 5

Connect 110 V if phase to phase voltage is connected

8(f) LZ96 Distance Relay

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet69/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 70: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

System Particulars :-A)Line parameters

1)Rated line voltage - 220 kV2)Line length - 61 Km3)Max power flow in the line - 2870.56 MVA4)Positive sequence resistance - 0.0748748 ohms/km5)Positive sequence reactance - 0.399252 ohms/km6)Zero sequence resistance - 0.219978 ohms/km7)Zero sequence reactance - 1.339228 ohms/km

B)CT/PT details1)CT primary rating - 800 A2)CT secondary rating - 1 A3)PT primary rating - 220000 V4)PT secondary rating - 110 V

C)Source Impedance1)Fault MVA at local end - 1694.61MVA2)Fault MVA at remote end - 1694.61 MVA(assumed)3)Source impedance angle - 80º (assumed)

E)Fault resistance 1)Fault resistance in primary for phase-earth faults - 20 ohms 2)Fault resistance in primary for phase-phase faults - 5 ohms

Relay details:-In=1A,Un=110V

Calculations :-

Impedance ratio = CTR/PTR= (800/1) /(220000/110)

= 0.4Positive sequence line resistance in secondary,R1 = 0.0748748 x 61 x 0.4

= 1.82695 ohmsPositive sequence line reactance in secondary,X1 = 0.399252 x 61 x 0.4

= 9.74175 ohmsZero sequence line resistance in secondary,R0 = 0.219978 x 61 x 0.4

= 5.3675 ohmsZero sequence line reactance in secondary,X0 = 1.339228 x 61 x 0.4

= 32.6772 ohms

Zone-1 is set to protect 80% of the lineZone-2 is set to protect (120% of the line)Zone-3 is set to protect (200% of the line)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet70/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 71: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Zone-4 is set to protect 20% of the Line in the reverse direction

Zone-1 settingPositive sequence resistance R1 = 0.8 x 1.82695

= 1.46156 ohms/phasePositive sequence reactance X1 = 0.8 x 9.74175

= 7.7934 ohms/phase Z1 = 1.46156+j 7.7934 ohms/phase │Z1│= 7.92926 ohms/phase Zone-2 settingPositive sequence resistance R1 = 1.2 x 1.82695

= 2.19233 ohms/phasePositive sequence reactance X1 = 1.2 x 9.74175

= 11.6901 ohms/phase Z2 = 2.19233+j11.6901 ohms/phase

│Z2│ = 11.8939 ohms/phaseZone-3 settingPositive sequence resistance , R1 = 2 x 1.82695

= 3.2046 ohms/phasePositive sequence reactance , X2 = 2 x 9.74175

= 17.108 ohms/phase Z3 = 3.2046+j17.108 ohms/phase │Z3│ = 19.8232 ohms/phaseZone-4 settingPositive sequence resistance , R1 = 0.2 x 1.82695

= 0.36539 ohms/phasePositive sequence reactance , X1 = 0.2 x 9.74175

= 1.94835 ohms/phase Z4 = 0.36539+j1.94835 ohms/phase

│Z4│ = 1.9823 ohms/phase

Setting of Distance ZonesThe values of Zi (i=1,2,3) for the zones can be set using the formula : Zi = ZM * mi * 100/Ni Ohms/phase m = 10 m1/N1 = Z1/(100*ZM) = 6.9543/(100*0.1) m1/N1 = 0.84782 m1= 10 N1 = 13 m2/N2 = Z2/(100*Zm) = 10.4433/(100*0.1) m2/N2 = 1.04433 m2 = 100 N2= 84 m3/N3 = Z3/(100*Zm) = 17.4055/(100*0.1)

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet71/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 72: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

m3/N3 = 1.74055 m3= 100 N3= 50 REPLICA IMPEDANCE (ZM)= 0.1 REPLICA ANGLE (PHI-M) = 85

Setting Of Under Impedance Starter

ZA= (1.82695+j*9.74175)+(1.2*(0.0748748+j*0.399252)*61*0.4) Load Impedance = 220*220/ 3783.99 ZA= 1.60232 +j 18.7968

ZA is less than 0.65 * Load Impedance. ZA is set according to the formula : ZA = 50 * ZM * 100/NA NA = 50*100*0.1/21.8055 Reverse to forward reach ratio kB = ZB/ZA = 0.3

Setting Of Zero Seq. Compensation Factor: ko= Z0-Z1/3*Z1 =((0.219978+j*1.33923)-(0.0748748+j*0.399252))/(3*(0.0748748+j*0.399252)) =0.3

The Recommended Settings m1 = 10

N1 = 13

m2 = 100

N2 = 84

m3 = 100

N3 = 50

ZM = 0.1

PHI-M = 85

ko = 0.3

kB = 0.3

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet72/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40

Page 73: Best Relay Setting File ABB Perfroma

UTTARANCHAL POWER CORP.LTD / SETTING CALCULATIONS

Checked by Nagendra Description

UTTARANCHAL POWER CORPORATION LIMITEDPrepared by Sarith Madhu Order Ref

415229Rev00

Sheet73/73

Issued by Dept . Yr. Wk

UASE 06 40

Drg. No.

YN1M 300 624-SETYr. wk

06 40