Click here to load reader
Upload
layzinesskillsyahoo
View
217
Download
0
Embed Size (px)
Citation preview
8/11/2019 ASHRAE Chilled 22
http://slidepdf.com/reader/full/ashrae-chilled-22 1/1
56 ASHR AE Journa l ash rae .o rg Februar y 2010
By James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE
ASHRAE Guideline 22-2008, Instrumentation for Monitoring Central Chilled-
Water Plant Efficiency, is the result of years of work to come up with a
meaningful procedure for determining the overall energy rate for the total electric
motor-driven, chilled water plant. The overall efficiency of central chiller plants is
important, as they consume many megawatts; it is estimated that their energy
use is around 30% of the entire HVAC industry.
This guideline was developed for con-
ducting a test on a specific chiller plant to
determine its coef ficient of performance
(COP). The data collected included many
values that would be needed for such a test.
This article’s goal is to assist designers and
operators in using this guideline in the con-
tinuous measurement and recording of the
energy rate of an operating chilled water
plant. It is limited to electric motor-driven
plants (as is the guideline), but includes
chiller plants with heat recovery chillers
and water-side economizers.
Measured kW/ton can be trended
against plant load in tons of cooling,
outdoor temperatures and condenser
water temperature. The resultant informa-
tion can be a useful tool in maintenance
programming; an increase in kW/ton may
signal a need for maintenance or an im-
minent equipment failure. For example,
an increase in kW/ton may indicate dirty
condenser tubes in the chillers, a partially
clogged strainer for tower pumps, or a
leaking coil valve as theT for the chilled
water drops below design.
Harvard University was an early pro-
ponent of using kW/ton as a means of
measuring the improvement of chiller
plant ef ficiency. For years, they displayed
it in large numerals on the wall of one of its
chiller plants. It proved to be an effective
tool in the operation and maintenance of
that plant. Today, they show it prominently
on their chiller plant computer screens as
shown in Figure 1.
Most of the central chiller plants in the
United Sates use I-P instrumentation and
measure the energy rate in kW/ton. Sincethis is a practical document rather than a
theoretical one, COP and SI procedures
will not be covered. Likewise, uncertainty
of measurement will not be addressed.
Anyone who wishes to determine this can
use the guideline for assistance in mak-
ing this evaluation. The instrument error
expressed in this article should result in
an uncertainty of around 2.2%. This is
derived from Table 5-2 of the guideline.
Derivation of the Basic kW/ton EquationThe basic kW/ton equation is derived
in Paragraph B1.3 of the guideline. It is
Equation B-3 in the guideline; it is re-
peated here with a different designation
for flow as Equation 1.
kW = kW× 24 (1)
Q×(T 2 – T 1)
About the Author
James B. (Burt) Rishel, P.E., is director of me-
chanical systems for tekWorx, LLC.
Guideline for Instrumentation for Monitoring Central Chilled-Water Plant Efficiency
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-ConditioningEngineers, Inc. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permissionof ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org.