Moisture Migration Control Moisture Migration Control with 100% Dedicated with 100% Dedicated Outdoor Air Systems Outdoor Air Systems ASHRAE 2005 Winter Meeting ASHRAE 2005 Winter Meeting Orlando, Florida Orlando, Florida Presented by Presented by Boggarm S. Setty, P.E., FASHRAE Boggarm S. Setty, P.E., FASHRAE Setty & Associates, Ltd. Setty & Associates, Ltd. ASHRAE TC 9.8 Seminar ASHRAE TC 9.8 Seminar

ASHRAE TC 9.8 Seminar - Setty & Associates Final.pdf · ASHRAE 62n Positive Pressure ... Existing Classroom Unit Ventilators with Chilled Water Cooling Coils and Hot Water Heating

Embed Size (px)

Citation preview

Moisture Migration ControlMoisture Migration Controlwith 100% Dedicatedwith 100% DedicatedOutdoor Air SystemsOutdoor Air Systems

ASHRAE 2005 Winter MeetingASHRAE 2005 Winter MeetingOrlando, FloridaOrlando, Florida

Presented byPresented byBoggarm S. Setty, P.E., FASHRAEBoggarm S. Setty, P.E., FASHRAE

Setty & Associates, Ltd.Setty & Associates, Ltd.

ASHRAE TC 9.8 SeminarASHRAE TC 9.8 Seminar

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

IntroductionIntroduction

Mold/Mildew Growth are Issues in SchoolsMold/Mildew Growth are Issues in Schools High Humidity Levels Encourage Fungi/Fungal GrowthHigh Humidity Levels Encourage Fungi/Fungal Growth Potential Health Effects Occur at Alarming RatePotential Health Effects Occur at Alarming Rate Claims and Litigation are CostlyClaims and Litigation are Costly Renew or Consider Property Insurance Policies Renew or Consider Property Insurance Policies Know How to Manage Mold Claims and LitigationKnow How to Manage Mold Claims and Litigation

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Design ConsiderationsDesign Considerations

Control of Moisture PenetrationControl of Moisture Penetration EnvelopeEnvelope

100 % Dedicated Outside Air Unit System (DOAS)100 % Dedicated Outside Air Unit System (DOAS)

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Design Considerations - EnvelopeDesign Considerations - Envelope

Heat Transfer CoefficientHeat Transfer Coefficient Permeability CoefficientPermeability Coefficient Envelope Dewpoint Design Envelope Dewpoint Design Outside Air Leakage ControlOutside Air Leakage Control Treat Exterior Water Penetration with Flashings and Treat Exterior Water Penetration with Flashings and

Weep HolesWeep Holes Design Windows, Doors, Roofing to Control Outside Air Design Windows, Doors, Roofing to Control Outside Air

LeakageLeakage

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

100% HVAC Dedicated System100% HVAC Dedicated System

Fresh Air to Every Breathing SpaceFresh Air to Every Breathing Space Discharge Air Temperature 50Discharge Air Temperature 50OOF DP and 70F DP and 70OOF DB – F DB –

ASHRAE 62nASHRAE 62n Positive Pressure up to 45Positive Pressure up to 45OOF DB Outside Air Temperature F DB Outside Air Temperature Neutral Pressure when Temperature falls below 45Neutral Pressure when Temperature falls below 45OOF DB.F DB. DOAS Units to Operate 24 hours, Positive PressureDOAS Units to Operate 24 hours, Positive Pressure DOAS Packaged Units or Builtup UnitsDOAS Packaged Units or Builtup Units

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Liberty High School, Bealeton, Virginia Liberty High School, Bealeton, Virginia

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Existing Envelope Conditions

Existing Air Handling UnitExisting Air Handling Unitand Zone Configurationand Zone Configuration

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Existing Unit Ventilator ConfigurationExisting Unit Ventilator Configuration

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Outside Air not Outside Air not Cooled to the Cooled to the Necessary Necessary DewpointDewpoint

Units Run Units Run ContinuouslyContinuously

Continuous 24 Continuous 24 Hour Draw of Hour Draw of Fresh Air Fresh Air

Potential Potential Condensation in Condensation in Ceiling and Ceiling and ClassroomsClassrooms

Excessive Air Excessive Air LeakageLeakage

Existing Typical Classroom Unit Ventilator

Existing Unit Ventilator Schematic Diagram

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Existing Typical Classroom System

Existing Passive Relief Air System

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Air Leakage Unconditioned Air Passive Outside Air

Exhaust Gravity Ventilators Natural Flow through the Ceiling

During Unoccupied Hours

Typical Roof Exhauster

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Existing DX Hot Water AHU Flow Diagram

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Serves Administration AreaServes Administration Area Units Contain other DX SystemUnits Contain other DX System Not Capable of Cooling Supply Ducts Down Not Capable of Cooling Supply Ducts Down

to 50to 5000F DewpointF Dewpoint

Existing DX Hot Water AHU ConfigurationExisting DX Hot Water AHU Configuration

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

OptionsOptions

C-1C-1: Convert Existing Classroom Unit with Chilled Water and : Convert Existing Classroom Unit with Chilled Water and Electric Heating CoilElectric Heating Coil C-2C-2: Existing Unit Ventilator Chilled and Hot Water Coil: Existing Unit Ventilator Chilled and Hot Water Coil C-3C-3: Existing Unit Ventilator with Chilled Water and Electric: Existing Unit Ventilator with Chilled Water and Electric Heating Coil with DOA UnitHeating Coil with DOA Unit C-4C-4: Convert to Four-Pipe Fan Coil Units with a Separate DOAS: Convert to Four-Pipe Fan Coil Units with a Separate DOAS UnitUnit C-5C-5: New Four-Pipe Fan Coil Units with a Separate DOAS Unit: New Four-Pipe Fan Coil Units with a Separate DOAS Unit C-6C-6: New Four-Pipe Chilled and Hot Water Coil with Electric: New Four-Pipe Chilled and Hot Water Coil with Electric Heating Coil with DOAS UnitsHeating Coil with DOAS Units

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-1Option C-1

Existing Classroom Unit VentilatorExisting Classroom Unit Ventilator Convert to Two PipeConvert to Two Pipe

Chilled Water Coil/Chilled Water Coil/Electric Heating CoilElectric Heating Coil

New Duct to be Extended New Duct to be Extended for Proper Circulationfor Proper Circulation

Dehumidification Up toDehumidification Up to505000F Dewpoint not F Dewpoint not FeasibleFeasible

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-2Option C-2

Existing Classroom Unit Ventilators withExisting Classroom Unit Ventilators withChilled Water Cooling Coils and Hot Water Chilled Water Cooling Coils and Hot Water Heating CoilsHeating Coils Convert Existing Two PipeConvert Existing Two Pipe

System to Chilled/Hot Water Coils System to Chilled/Hot Water Coils Keep the Unit Ventilation in PlaceKeep the Unit Ventilation in Place Modify DuctworkModify Ductwork Hot Water Coil Instead of Electric Hot Water Coil Instead of Electric

Heating Coil Heating Coil

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-3Option C-3

Existing Classroom UnitExisting Classroom UnitVentilators with Chilled WaterVentilators with Chilled WaterCooling/Electric Heating CoilsCooling/Electric Heating Coils Fresh Air is Supplied throughFresh Air is Supplied through

Dedicated Unit - DOASDedicated Unit - DOAS Dehumidified and Heated to Dehumidified and Heated to

707000F and 50F and 5000F Dewpoint F Dewpoint Existing Fresh Air is Shut DownExisting Fresh Air is Shut Down Passive Air is Disconnected Passive Air is Disconnected

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-4Option C-4

Existing Classroom UnitExisting Classroom UnitVentilators With ChilledVentilators With ChilledWater Cooling Coils andWater Cooling Coils andHot Water Heating CoilsHot Water Heating Coils

Difference: Hot Water Coil Difference: Hot Water Coil Instead of Electric CoilInstead of Electric Coil

Four-Pipe SystemFour-Pipe System

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-5Option C-5New Fan Coil Units withNew Fan Coil Units withChilled Water CoolingChilled Water CoolingCoils and Hot Water Coils and Hot Water Heating CoilsHeating Coils

Hot Water Coil Provides Hot Water Coil Provides Necessary ReheatNecessary Reheat

Ducted Air DistributionDucted Air Distribution DOAS Fresh Air SupplyDOAS Fresh Air Supply

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Option C-6Option C-6New Fan Coil Units withNew Fan Coil Units withChilled Water Cooling Coils Chilled Water Cooling Coils and Electric Heating Coilsand Electric Heating Coils Existing Piping will be Existing Piping will be

Converted into Two-Pipe Converted into Two-Pipe Chilled Water and Electric Chilled Water and Electric Reheat CoilReheat Coil

Ducted Air DistributionDucted Air Distribution DOAS Fresh Air SupplyDOAS Fresh Air Supply

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New Chilled/Hot Water AHU ConfigurationNew Chilled/Hot Water AHU Configuration

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New DX and Hot Water Reheat AHUNew DX and Hot Water Reheat AHU

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New 100% Dedicated Outdoor Air System (DOAS) Options

Option 1:

Variable Speed Makeup Air Handling Unit DX Coil, Hot Water Reheat Coil

Option 2:

Constant Volume Air Handling Unit Chilled Water and Hot Water Heating Coils Desiccant Wheels for Dehumidification Units

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

DOAS – Option 1DOAS – Option 1

100% Fresh Air Heat Reclaim Make-Up Air Handling Units

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

DOAS - Option 2DOAS - Option 2

100% Fresh Air New Desiccant Dehumidification – DOAS Unit

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New 100% Dedicated Outside Air Units LocationsNew 100% Dedicated Outside Air Units Locations

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New Integrated DOAS and FCU SystemsNew Integrated DOAS and FCU Systems

New Fan Coil Units Toilet Exhaust System

DOA Units New Reheat Coil

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

New DX and Hot Water Reheat AHU ConfigurationNew DX and Hot Water Reheat AHU Configuration

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

XXX (1)Unit Ventilators, Dual Temp

Second Floor ClassroomsUnit Ventilators19

XAHU: DX, HWGymnasium, WestAHU-1818

XAHU: DX, HWGymnasium, CenterAHU-1717

XAHU: Dual TempTeam RoomsAHU-1616

XAHU: DX, HWBoys Lockers, Wrestling, Weights

AHU-1515

XAHU: DX, HWGymnasium, EastAHU-1414

XAHU: Dual TempGirls Lockers/Aux GymAHU-1313

XAHU: Dual TempGirls LockersAHU-1212

XAHU: Dual TempMusicAHU-1111

XAHU: Dual TempArtAHU-1010

XAHU: DX, HWStageAHU-99

XAHU: DX, HWAuditoriumAHU-7, 8 & 198

XAHU: Dual TempHealth, Athletic OfficesAHU-67

XAHU: DX, HWDining/KitchenAHU-56

XAHU: DX, HWLibraryAHU-45

XAHU: DX, HWOffice/AdminAHU-34

XAHU: DX, HWOffice/AdminAHU-23

XAHU: Dual TempSupport, VocationalAHU-12

XXX (1)Unit Ventilators, Dual Temp

First Floor ClassroomsUnit Ventilators1

Add New Make-up Air Units

Convert DT Coil To Chilled

Water

Add Reheat Coil

RecommendationsSystem TypeSpace TypeSystemZone No

Options SummaryOptions Summary

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

SummarySummary

MU-1CH-1DX-1C-6

MU-1CH-1DX-1C-5

MU-1CH-1DX-1C-4

MU-1CH-1DX-1C-3

--CH-1DX-1C-2

--CH-1DX-1C-1

Makeup Air Unit Option

AHU Heating/Cooling

Option

ClassroomOption

RecommendationsRecommendations

Two-Pipe Fancoil Unit with Electric Heating Coil with DOAS.Two-Pipe Fancoil Unit with Electric Heating Coil with DOAS.

MU-1CH-1DX-1

C-6

Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems

Makeup Air Unit Option

AHU Heating/Cooling

Option

ClassroomOption