Moisture Migration ControlMoisture Migration Controlwith 100% Dedicatedwith 100% DedicatedOutdoor Air SystemsOutdoor Air Systems
ASHRAE 2005 Winter MeetingASHRAE 2005 Winter MeetingOrlando, FloridaOrlando, Florida
Presented byPresented byBoggarm S. Setty, P.E., FASHRAEBoggarm S. Setty, P.E., FASHRAE
Setty & Associates, Ltd.Setty & Associates, Ltd.
ASHRAE TC 9.8 SeminarASHRAE TC 9.8 Seminar
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
IntroductionIntroduction
Mold/Mildew Growth are Issues in SchoolsMold/Mildew Growth are Issues in Schools High Humidity Levels Encourage Fungi/Fungal GrowthHigh Humidity Levels Encourage Fungi/Fungal Growth Potential Health Effects Occur at Alarming RatePotential Health Effects Occur at Alarming Rate Claims and Litigation are CostlyClaims and Litigation are Costly Renew or Consider Property Insurance Policies Renew or Consider Property Insurance Policies Know How to Manage Mold Claims and LitigationKnow How to Manage Mold Claims and Litigation
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Design ConsiderationsDesign Considerations
Control of Moisture PenetrationControl of Moisture Penetration EnvelopeEnvelope
100 % Dedicated Outside Air Unit System (DOAS)100 % Dedicated Outside Air Unit System (DOAS)
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Design Considerations - EnvelopeDesign Considerations - Envelope
Heat Transfer CoefficientHeat Transfer Coefficient Permeability CoefficientPermeability Coefficient Envelope Dewpoint Design Envelope Dewpoint Design Outside Air Leakage ControlOutside Air Leakage Control Treat Exterior Water Penetration with Flashings and Treat Exterior Water Penetration with Flashings and
Weep HolesWeep Holes Design Windows, Doors, Roofing to Control Outside Air Design Windows, Doors, Roofing to Control Outside Air
LeakageLeakage
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
100% HVAC Dedicated System100% HVAC Dedicated System
Fresh Air to Every Breathing SpaceFresh Air to Every Breathing Space Discharge Air Temperature 50Discharge Air Temperature 50OOF DP and 70F DP and 70OOF DB – F DB –
ASHRAE 62nASHRAE 62n Positive Pressure up to 45Positive Pressure up to 45OOF DB Outside Air Temperature F DB Outside Air Temperature Neutral Pressure when Temperature falls below 45Neutral Pressure when Temperature falls below 45OOF DB.F DB. DOAS Units to Operate 24 hours, Positive PressureDOAS Units to Operate 24 hours, Positive Pressure DOAS Packaged Units or Builtup UnitsDOAS Packaged Units or Builtup Units
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Liberty High School, Bealeton, Virginia Liberty High School, Bealeton, Virginia
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Existing Envelope Conditions
Existing Air Handling UnitExisting Air Handling Unitand Zone Configurationand Zone Configuration
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Existing Unit Ventilator ConfigurationExisting Unit Ventilator Configuration
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Outside Air not Outside Air not Cooled to the Cooled to the Necessary Necessary DewpointDewpoint
Units Run Units Run ContinuouslyContinuously
Continuous 24 Continuous 24 Hour Draw of Hour Draw of Fresh Air Fresh Air
Potential Potential Condensation in Condensation in Ceiling and Ceiling and ClassroomsClassrooms
Excessive Air Excessive Air LeakageLeakage
Existing Typical Classroom Unit Ventilator
Existing Unit Ventilator Schematic Diagram
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Existing Typical Classroom System
Existing Passive Relief Air System
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Air Leakage Unconditioned Air Passive Outside Air
Exhaust Gravity Ventilators Natural Flow through the Ceiling
During Unoccupied Hours
Typical Roof Exhauster
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Existing DX Hot Water AHU Flow Diagram
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Serves Administration AreaServes Administration Area Units Contain other DX SystemUnits Contain other DX System Not Capable of Cooling Supply Ducts Down Not Capable of Cooling Supply Ducts Down
to 50to 5000F DewpointF Dewpoint
Existing DX Hot Water AHU ConfigurationExisting DX Hot Water AHU Configuration
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
OptionsOptions
C-1C-1: Convert Existing Classroom Unit with Chilled Water and : Convert Existing Classroom Unit with Chilled Water and Electric Heating CoilElectric Heating Coil C-2C-2: Existing Unit Ventilator Chilled and Hot Water Coil: Existing Unit Ventilator Chilled and Hot Water Coil C-3C-3: Existing Unit Ventilator with Chilled Water and Electric: Existing Unit Ventilator with Chilled Water and Electric Heating Coil with DOA UnitHeating Coil with DOA Unit C-4C-4: Convert to Four-Pipe Fan Coil Units with a Separate DOAS: Convert to Four-Pipe Fan Coil Units with a Separate DOAS UnitUnit C-5C-5: New Four-Pipe Fan Coil Units with a Separate DOAS Unit: New Four-Pipe Fan Coil Units with a Separate DOAS Unit C-6C-6: New Four-Pipe Chilled and Hot Water Coil with Electric: New Four-Pipe Chilled and Hot Water Coil with Electric Heating Coil with DOAS UnitsHeating Coil with DOAS Units
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-1Option C-1
Existing Classroom Unit VentilatorExisting Classroom Unit Ventilator Convert to Two PipeConvert to Two Pipe
Chilled Water Coil/Chilled Water Coil/Electric Heating CoilElectric Heating Coil
New Duct to be Extended New Duct to be Extended for Proper Circulationfor Proper Circulation
Dehumidification Up toDehumidification Up to505000F Dewpoint not F Dewpoint not FeasibleFeasible
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-2Option C-2
Existing Classroom Unit Ventilators withExisting Classroom Unit Ventilators withChilled Water Cooling Coils and Hot Water Chilled Water Cooling Coils and Hot Water Heating CoilsHeating Coils Convert Existing Two PipeConvert Existing Two Pipe
System to Chilled/Hot Water Coils System to Chilled/Hot Water Coils Keep the Unit Ventilation in PlaceKeep the Unit Ventilation in Place Modify DuctworkModify Ductwork Hot Water Coil Instead of Electric Hot Water Coil Instead of Electric
Heating Coil Heating Coil
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-3Option C-3
Existing Classroom UnitExisting Classroom UnitVentilators with Chilled WaterVentilators with Chilled WaterCooling/Electric Heating CoilsCooling/Electric Heating Coils Fresh Air is Supplied throughFresh Air is Supplied through
Dedicated Unit - DOASDedicated Unit - DOAS Dehumidified and Heated to Dehumidified and Heated to
707000F and 50F and 5000F Dewpoint F Dewpoint Existing Fresh Air is Shut DownExisting Fresh Air is Shut Down Passive Air is Disconnected Passive Air is Disconnected
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-4Option C-4
Existing Classroom UnitExisting Classroom UnitVentilators With ChilledVentilators With ChilledWater Cooling Coils andWater Cooling Coils andHot Water Heating CoilsHot Water Heating Coils
Difference: Hot Water Coil Difference: Hot Water Coil Instead of Electric CoilInstead of Electric Coil
Four-Pipe SystemFour-Pipe System
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-5Option C-5New Fan Coil Units withNew Fan Coil Units withChilled Water CoolingChilled Water CoolingCoils and Hot Water Coils and Hot Water Heating CoilsHeating Coils
Hot Water Coil Provides Hot Water Coil Provides Necessary ReheatNecessary Reheat
Ducted Air DistributionDucted Air Distribution DOAS Fresh Air SupplyDOAS Fresh Air Supply
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Option C-6Option C-6New Fan Coil Units withNew Fan Coil Units withChilled Water Cooling Coils Chilled Water Cooling Coils and Electric Heating Coilsand Electric Heating Coils Existing Piping will be Existing Piping will be
Converted into Two-Pipe Converted into Two-Pipe Chilled Water and Electric Chilled Water and Electric Reheat CoilReheat Coil
Ducted Air DistributionDucted Air Distribution DOAS Fresh Air SupplyDOAS Fresh Air Supply
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New Chilled/Hot Water AHU ConfigurationNew Chilled/Hot Water AHU Configuration
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New DX and Hot Water Reheat AHUNew DX and Hot Water Reheat AHU
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New 100% Dedicated Outdoor Air System (DOAS) Options
Option 1:
Variable Speed Makeup Air Handling Unit DX Coil, Hot Water Reheat Coil
Option 2:
Constant Volume Air Handling Unit Chilled Water and Hot Water Heating Coils Desiccant Wheels for Dehumidification Units
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
DOAS – Option 1DOAS – Option 1
100% Fresh Air Heat Reclaim Make-Up Air Handling Units
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
DOAS - Option 2DOAS - Option 2
100% Fresh Air New Desiccant Dehumidification – DOAS Unit
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New 100% Dedicated Outside Air Units LocationsNew 100% Dedicated Outside Air Units Locations
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New Integrated DOAS and FCU SystemsNew Integrated DOAS and FCU Systems
New Fan Coil Units Toilet Exhaust System
DOA Units New Reheat Coil
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
New DX and Hot Water Reheat AHU ConfigurationNew DX and Hot Water Reheat AHU Configuration
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
XXX (1)Unit Ventilators, Dual Temp
Second Floor ClassroomsUnit Ventilators19
XAHU: DX, HWGymnasium, WestAHU-1818
XAHU: DX, HWGymnasium, CenterAHU-1717
XAHU: Dual TempTeam RoomsAHU-1616
XAHU: DX, HWBoys Lockers, Wrestling, Weights
AHU-1515
XAHU: DX, HWGymnasium, EastAHU-1414
XAHU: Dual TempGirls Lockers/Aux GymAHU-1313
XAHU: Dual TempGirls LockersAHU-1212
XAHU: Dual TempMusicAHU-1111
XAHU: Dual TempArtAHU-1010
XAHU: DX, HWStageAHU-99
XAHU: DX, HWAuditoriumAHU-7, 8 & 198
XAHU: Dual TempHealth, Athletic OfficesAHU-67
XAHU: DX, HWDining/KitchenAHU-56
XAHU: DX, HWLibraryAHU-45
XAHU: DX, HWOffice/AdminAHU-34
XAHU: DX, HWOffice/AdminAHU-23
XAHU: Dual TempSupport, VocationalAHU-12
XXX (1)Unit Ventilators, Dual Temp
First Floor ClassroomsUnit Ventilators1
Add New Make-up Air Units
Convert DT Coil To Chilled
Water
Add Reheat Coil
RecommendationsSystem TypeSpace TypeSystemZone No
Options SummaryOptions Summary
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
SummarySummary
MU-1CH-1DX-1C-6
MU-1CH-1DX-1C-5
MU-1CH-1DX-1C-4
MU-1CH-1DX-1C-3
--CH-1DX-1C-2
--CH-1DX-1C-1
Makeup Air Unit Option
AHU Heating/Cooling
Option
ClassroomOption
RecommendationsRecommendations
Two-Pipe Fancoil Unit with Electric Heating Coil with DOAS.Two-Pipe Fancoil Unit with Electric Heating Coil with DOAS.
MU-1CH-1DX-1
C-6
Moisture Migration Control with 100% Dedicated Outdoor Air SystemsMoisture Migration Control with 100% Dedicated Outdoor Air Systems
Makeup Air Unit Option
AHU Heating/Cooling
Option
ClassroomOption