Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

Embed Size (px)

Citation preview

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    1/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 1

    Analysis and Design of a Continuous Reinforced Concrete Raker

    Beam for Stadium Using Eurocode 2

    Ubani Obinna Uzodimma

    Works/Engineering Services Department

    Ritman University, PMB 1321, Ikot Ekpene, Akwa Ibom [email protected]

    Abstract

     A continuous intermediate raker beam in the first tier of a football stadium was analysed using elastic

    method and designed using Eurocode 2. The raker beam was analysed for permanent and variable

    actions due to crowd load and permanent loads only. Due to its inclination, it was subjected to

    significant bending, axial, and shear forces. However, design results show that the effect of axial

     force was not very significant in the quantity of shear reinforcement required. Asv/Sv ratio of 1.175

    (3Y10mm @ 200 c/c) was found to satisfy shear requirements. The greatest quantity of longitudinal

    reinforcement was provided at the intermediate support with a reinforcement ratio of 1.3404%. The

     provided reinforcement was found adequate to satisfy ultimate and serviceability requirements.

    1.0 Introduction

    The most common construction concept of sports stadiums today is a composite type where usually precast

    concrete terrace units (seating decks) span between inclined (raker) steel or reinforced concrete beams and rest

    on each other, thereby forming a grandstand (Karadelis, 2012). The raker beams are usually formed in-situ with

    the columns of the structure, or sometimes may be preferably precast depending on site/construction constraints.

    This arrangement usually forms the skeletal frame of a stadium structure.

    In this paper, a raker beam isolated from a double tiered reinforced concrete grandstand that wraps around a

    football pitch has been presented for the purpose of structural analysis and design. A repetitive pattern has been

    adopted in the design which utilizes a construction joint of 25mm gap between different frame units. By

    estimate, each frame unit is expected to carry a maximum of 3600 spectators, under full working conditions.

    With ten different frames units, the stadium capacity is about 35000 after all other reservations have been taken

    into account. Each grandstand frame has precast L-shaped seating terrace units that span in between reinforced

    concrete raker beams inclined at angles between 20° - 22° with the horizontal. Crowd load and other loads are

    transferred from the seating units to the raker beams, which then transfers them to the columns and then to the

    foundations. Load from the service areas and concourse areas are also transferred using the same method.

    Figure 1.1: 3D skeletal structure of each grandstand frame units (slabs and sitting areas removed) 

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    2/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 2

    The three dimensional view of the skeleton of the grandstand is shown in Figure 1.1, while a sectionthrough the grandstand is shown if Figure 1.2. Section through the L-shaped seating unit is shown inFigure 1.3.

    In simple horizontal beams, vertical forces will produce vertical reactions only. However, once a beam is

    statically indeterminate and inclined, vertical forces will produce both vertical and horizontal reactions and as a

    result, axial forces which may be compressive or tensile in nature will be induced in the beam. In the design of

    horizontal floor beams in normal framed structures, the effect of axial force in the shear force capacity of the

    section is usually neglected. This is largely due to the fact that these forces are usually compressive, and in

    effect tends to increase the concrete resistance shear stress (Vc) and (VRd,c) of the section in accordance with BS

    8110-1:1997 and EC2 respectively. It is a well known phenomenon that compressive axial force increases the

    concrete resistance shear stress of a section, while tensile axial force will reduce the concrete resistance shearstress. So this neglect can be justified in terms of it being a conservative design which can only err in economy. 

    However for inclined beams members in a frame (as in the case of a grandstand), axial force behaviour can vary

    greatly especially when the load is applied in the global direction (which is the prevalent scenario). In other

    words, based on the structural configuration of the structure and the   loading, it is even common to see the  

    nature of axial forces moving from positive (tensile) to negative (compressive) in the same span of an

    inclined member. If the load is however resolved and applied in the local direction of the inclined member, the

    axial forces will be absent. A good design will therefore require the use of less shear reinforcement in the axial

    compression zone, and more shear reinforcement in the axial tension zone. While the effect of axial forces may

     be neglected in horizontal floor beams under axial compression, it may be unsafe to neglect it in inclined beams

     because more often than not, some sections are usually under axial tension.

    Figure 1.2: Section through the grandstand 

    Figure 1.3: Section of the precast seating unit 

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    3/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 3

    1.2 Materials, Model, and Loading

    Structural design of stadiums is critical and this becomes more obvious when EN 1990 (Eurocode  –  Basis for

    Structural Design) classified it under ‘Consequence Class 3’ which by description means high consequence for

    loss in terms of human life, economy, environmental considerations, and otherwise if failure should occur.

    Several codes of practice across different countries and bodies have provisions made in them for the design of

    structures subjected to crowd loading (for example stadiums), but the level of expertise often associated with the

     processes in terms of analysis, design and construction is often perceived to be something left to a limited few.

    The application of static crowd imposed loads according to both BS 6399-1:1997( Loading on buildings - Code

    of practice for dead and imposed loads) and EN 1991-1: ( Action on structures: General actions - Densities,

    self-weight, imposed  loads for buildings) are given in Table 1 below: 

    Table 1.1: Values of variable actions on grandstands from BS 6399 and EN 1991

    CODE CATEGORY(DESCRIPTION) IMPOSED

    LOAD/VARIABLE

    ACTION (KN/m2)

    CONCENTRATED

    LOAD (KN)

    BS 6399-1:1996 C5 (Areas susceptible to

    overcrowding e.g. grandstands)

    5 3.6

    EN 1991-1-1

    C5( Areas susceptible to large

    crowds, e.g

    sports halls including stands)5.0 –  7.5 *  3.5 –  4.5* 

    *Exact range of value to be set by various national annex  

    Raker beams in stadiums usually support precast seating terrace units which may be L-shaped, or extended into

    a more complex shape (see Figure 1.5). These seating terrace units are designed as simply supported elements

    spanning between the raker beams (Karadelis, 2012, Salyards et al 2005). The crowd loading is supported

    directly by these terrace units, which then transfer the load to the raker beams through the bearings. This

    construction concept has been adopted in the design of Cape Town Stadium (South Africa) for the 2010 FIFAworld Cup (Plate 1.5). The picture in (Figure 1.4) below shows the formwork and construction of in-situ raker

     beams at San Diego State University Student Activity Center (Steele and Larson 1996).

    In this design, each L-shaped seating unit is 7m long, which means that the raker beams are spaced at 7m centre

    to centre. The crowd loading is supported by the terrace seating units, which is then transferred to the raker

     beams through the end shears. The raker beams can be analysed as sub-frames or as full 3D structures in order

    to get the most realistic behaviour of the structure.

    Figure 1.4: Typical formwork and

    reinforcement for in-situ raker beam (Steele

    and Larson 1996). 

    Plate 1.5: Precast seating units being installed

    on raker beams at Cape Town Stadium (2010)

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    4/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 4

    1.2.1 Partial Factor for load

    The partial factor for all permanent actions (dead load) Gk is 1.35 while the partial factor for all variable actions

    (imposed load) Qk is 1.5. No reduction factor was applied in the analysis, and the effect of wind was neglected.

    1.2.2 Material Properties for the design

    Design compressive of concrete f ck  = 35 N/mm

    2

     Yield strength of steel f yk  = 460 N/mm2 

    Table 1.2: Values used in the computation of loading

    Load Value

    Density of concrete 25 KN/m3 

    Imposed load/variable action 5 KN/m2 

    Weight of finishes, rails, seats, stair units 2 KN/m2 

    1.2.3 Concrete cover

    Exposure class = XC1

    A concrete cover of 40mm is adopted for the section

    1.2.4 Design equations according EC2

    From EC2 singly reinforced concrete stress block;

    MRd  = FCz ------------ (1)

    FC =.

    .  0.8 ; z = d –  0.4x -------------- (2)Clause 5.6.3 of EC2 limits the depth of the neutral axis to 0.45d  for concrete class less than or equal to C50/60.

    Therefore for an under reinforced section (ductile);

     x = 0.45d  ----------------- (3)

    Combining equation (1), (2) and (3), we obtain the ultimate moment of resistance (MRd )

    MRd  = 0.167

      ---------------------- (4)

    Also from the reinforced concrete stress block;

    MEd  = FSz ------------------ (5)

    FS =.  ------------------ (6) 

    Substituting equ (6) into (5) and making   the subject of the formular;

      = . -------------------- (7)The lever arm z in EC2 is given ;

     z = d [0.5  (0.25 0.882) ] ---------------------- (8)where K =

      ---------------- (9) 

    1.2.4.1 For doubly reinforced sections;

    Area of compression reinforcement AS2 =−

    .(− ) ----------------------- (10) 

    Area of tension reinforcement  = . + AS2 -------------------- (11)

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    5/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 5

    Where z = d [0.5  (0.250.882 ′) ] where K’   = 0.1671.2.4.2 Check for deflection (Clause 7.4.2)

    The limiting basic span/ effective depth ratio is given by;

    L/d = K 111.5   3.2   1 ⁄  if  ≤  --------------------------- (12)

    L/d = K 111.5   −    ⁄  if  >  ---------------------- (13)

    Where;

    L/d is the limiting span/depth ratio

    K = Factor to take into account different structural systems

     = reference reinforcement ratio = 10−   

     = Tension reinforcement ratio to resist moment due to design load

    ′ = Compression reinforcement ratio

    1.2.4.3 Shear design

    In EC2, the concrete resistance shear stress without shear reinforcement is given by;

    VRd,c = [CRd,c.k. (100 ) + k 1. ]bw.d ≥ (Vmin + k 1. ) ----------------------- (14)CRd,c = 0.18/; k = 1+    < 0.02 (d in mm);  =  < 0.02 (In which   is the area of tensile reinforcementwhich extends ≥ ( ) beyond the section considered; Vmin = 0.035  K 1 = 0.15;

     = NEd /Ac < 0.2fcd (Where NEd  is the axial force at the section, Ac = cross sectional area of the

    concrete), fcd = design compressive strength of the concrete.

    1.2.5 Load Analysis

    1.2.5.1 Loading on precast seating unit

    Permanent Actions

    Self weight of the 7m precast seating deck (see Figure 1.4)

    (GK1) = (25 × 0.25 × 0.15 × 7) + (25 × 0.95 × 0.15 × 7) = 31.5 KNWeight of finishes, rails, seats (G

    K2) = (2

    × 0.95

    × 7) = 13.3 KN

    Variable Actions

    Imposed load for structural class C5 (QK ) = (5 × 0.95 × 7) = 33.25 KNTotal action on L-shaped seating terrace unit at ultimate limit state by Eurocode 2

    (FE) = 1.35∑(GKi) + 1.5QK   = 1.35(44.8) + 1.5(33.25) = 110.355 KN

    1.2.5.2 Loading on the raker beams

    Height of beam = 1200mm

    Width of beam = 400mm

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    6/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 6

    Self weight of raker beam

    Concrete own weight (waist area) = 1.2m × 0.4m × 25 KN/m3 = 12.00 KN/m (normal to the inclination i.e. inthe local direction)

    Height of riser in the raker beam = 0.4m; Width of tread in the raker beam = 0.8m; Angle of inclination (

    )=

    20.556°

    Stepped area (risers) = 1 2⁄  × 0.4 × 25 = 5 KN/m (in the global direction)For purely vertical load in the global y-direction, we convert the load from the waist of the beam by;

    UDL from waist of the beam = (12.00  × cos 20.556°) = 11.236 KN/m Total self weight (Gk) = 11.236 + 5 = 16.235 KN/m

    Self weight of raker beam at ultimate limit state;

    n = 1.35∑(GKi) = 1.35 × 16.235 = 21.917 KN/mLoad from precast seating units

    End shear from precast seating unit = FE/2 = 110.355 = 55.1775 KN

    Total number of the precast seating units on the beam = 24/0.8 = 30 unitsFor an intermediate beam supporting seating units on both sides;

    Total number of precast seating units = 2 × 30 = 60 unitsTherefore, total shear force transferred from the seating units to the raker beam = 55.1775 × 60 = 3310.65 KNEquivalent uniformly distributed load in the global direction at ultimate limit state =

    .  = 137.94 KN/m

    Total load on intermediate raker beams at ultimate limit state in the global direction = 137.94 + 21.917 =

    159.857 KN/m

    1.3 Structural Analysis

    A full 3D elastic analysis of the whole stadium was performed using Staad Pro with all elements

    loaded at ultimate limit state. Also, the raker beam is isolated as a subframe and also analysed. Theresults from the two models are very comparable. 

    Figure 1.6: 3D Modelling of the grandstand on Staad Pro

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    7/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 7

    The internal stresses on the intermediate raker beams from the analysis of the frame at ultimate limit

    state are shown in Figures 1.7 to 1.9.

    Figure 1.7: Bending Moment Diagram 

    Figure 1.8: Shear Force Diagram 

    Figure 1.9: Axial Force Diagram 

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    8/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 8

    1.3.1 Summary of Analysis Results 

    The summary of the analysis result of the raker beams is shown in Table 1.3.

    Section  Moment

    (KN.m) 

    Section  Shear Force

    (KN) 

    Section Axial Force

    (KN)

    MA  1967.54 QAB  934.62 NAB  380.061(C)

    MABspan 948.078 QBA  983.88 NBA  339.376(T)

    MB  2283.18 QBC  999.52 NBC  510.767(C)

    MBCspan 1249.787 QCB  918.98 NCB  208.670(T)

    MC  1565.63

    1.4 Structural Design

    The structural design of the of the raker beam using EN 1992-1-1has been carried out and all the

     parameters used in the, and steps followed are shown below in the subsequent sections.

    Design compressive of concrete f ck  = 35 N/mm2 

    Yield strength of steel f yk  = 460 N/mm2 

     bw = 400mm; h = 1200mm; Cc = 40mm

    1.4.1 Flexural Design of span AB (MABspan)

    MABspan = 948.078 KNm

    d = h –  Cc –  ϕ/2 –  ϕlink

    d = 1200 –  40 –  16 –  10 = 1134mm

    k =

      =. ×

    × ×   = 0.0527 Since k < 0.167 No compression reinforcement required

     z = d [0.5  (0.25 0.882) ] = z = d [0.5  (0.25 0.882(0.0527) ] = 0.95d  

      = . =. ×

    . × × . ×  = 2199 mm2 Provide 5Y25mm BOT (ASprov = 2450 mm2)

    To calculate the minimum area of steel required; (TABLE 3.1 EC2) 

    fctm = 0.3 × ⁄  = 0.3 × 35 ⁄  = 3.2099 N/mm2ASmin = 0.26 × mFyk   × bw × d = 0.26 × 3.2099   ×400 ×1134 = 822.962 mm2 Check if ASmin < 0.0013 × bw × d (589.68 mm2)Therefore, ASmin = 822.962 mm2 

    Check for deflection;

    K = 1.5 for beam fixed at both ends

    L/d = K 111.5   3.2   1

     if  ≤  

    Table 1.3: Analysis Results of the Raker Beam 

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    9/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016)  Page 9

    L/d = K 111.5   −   

    ⁄  if  >  

     =  = ×  = 0.00540 < 10−√ 35 

    L/d = 1.5 111.5√ 35 × .. 3.2√ 35 .. 1 ⁄  = 1.5(20.695 + 0.5333) = 31.842 Modification factor  =   =  = × × ×  = 278.241 N/mm2 = . =1.11 Since the span is greater than 7m, allowable span/depth ratio =  × 31.842 ×  = 1.11 × 31.842×  = 19.374Actual deflection L/d =

     = 11.301

    Since 11.301 < 19.374, deflection is ok.

    1.4.2 Flexural Design of support A (MA);

    MA = 1967.54 KNm

    k = 0.1093; la = 0.8919; AS1 = 4861 mm2; ASmin = 822.9785 mm2 

    Provide 4Y32mm + 4Y25mm TOP (ASprov = 5180 mm2)

    1.4.3 Flexural Design of support B (MB);

    MA = 2283.18KNmk = 0.1268; la = 0.8717; AS1 = 5772 mm2; ASmin = 822.9785 mm2 

    Provide 6Y32mm + 4Y20mm TOP (ASprov = 6080 mm2)

    1.4.3 Flexural Design of span BC (MBCspan)

    MBCSpan = 1249.787 kNm

    k = 0.0694; la = 0.9345; AS1 = 2947mm2; ASmin = 822.9785 mm2 

    Provide 5Y25mm + 2Y20mm BOT (ASprov = 3083 mm2)

    Check for deflection

     =  = ×  = 0.00679 > 10−√ 35 

    L/d = K 111.5   −   

    ⁄  if  >  

    L/d = 1.5 111.5√ 35 × .. − 0  = 28.066Modification factor  =  

     =  = × × ×  = 299.039 N/mm2

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    10/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016) Page 10

     = . = 1.0366Since the span is greater than 7m, allowable span/depth ratio =  × 28.066 ×  = 1.0366 × 28.066 ×  = 15.89Actual deflection L/d =  = 11.301Since 11.301 < 15.89, deflection is ok.

    1.4.4 Flexural Design of support C (MC);

    MC = 1565.63 KNm

    k = 0.0870; la = 0.9163; AS1 = 3765 mm2; ASmin = 822.9785 mm2 

    Provide 5Y32mm TOP (ASprov = 4020 mm2)

    Provide Y16 @ 200mm c/c on both faces as longitudinal side bars

    1.4.5 Shear Design

    1.4.5.1 Support A

    VEd  = 934.62 KN; N = 380.061 KN (Compression)

    Taking shear at the centreline of support; VEd = 934.62 KN

    VRd,c = [CRd,c.k. (100 ) + k 1. ]bw.d  ≥ (Vmin + k 1. ) bw.d  CRd,c = 0.18/ = 0.18/1.5 = 0.12k = 1+   = 1+  = 1.4199 < 2.0Vmin = 0.035  = Vmin = 0.035 ×(1.4199) ×(35) = 0.3504 N/mm2 

     =  = ×  = 0.011419 < 0.02; K 1 = 0.15 = NEd /Ac < 0.2fcd (Where NEd  is the axial force at the section, Ac = cross sectional area of the concrete),fcd = design compressive strength of the concrete.)

     = . × × = 0.7917 N/mm2 

    VRd,c = [0.12 × 1.4199 (100×0.011419 ×35 ) + 0.15 ×0.7917 ]400 ×1134 = 318111.948 N = 318.11 KNSince VRd,c < VEd , shear reinforcement is required.

    Assume strut angle  = 21.8°Let us now investigate the compression capacity of the strut;v1 = 0.61  = 0.61  = 0.516f cd  =

     Taking  = 0.85; fcd = . × .  = 19.833 N/mm2; z = 0.9d

    VRd,max =( + ) = × . × × . × .(. + .) 10− = 1440.64 KN > VEd  

    Since VEd  < VRd,max 

    VEd,s = cot = 934620 N

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    11/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016) Page 11

     =

    (. × ×. × × .) = 0.9153

    Trying 3Y10mm @ 200mm c/c (235/200 = 1.175)

    1.175 > 0.9153 Hence shear reinforcement is ok.

    Following the steps described above;

    1.4.5.2 Support B; Shear at VBA 

    VEd  = 983.88 KN; N = KN 339.376 (Tension)

     Note that due to the tensile axial force in the section, the second term of VRd  equation assumes a negative value.

     = 0.0134;  =  0.7070 N/mm2; vmin = 0.3504 N/mm2; VRd = 230.6532 KNSince VRd,c < VEd , shear reinforcement is required

    Assuming that the strut angle  = 21.8° v1 = 0.5160; f cd  = 19.8450 N/mm

    2

    ; z = 0.9d = 1020.6 mm; VRDmax =1440.64 KNSince VRDmax > VEd  

     = 0.9635

    Trying 3Y10mm @ 200mm c/c (235/200 = 1.175)

    1.175 > 0.9153 Hence shear reinforcement is ok.

    1.4.5.3 Support B; Shear at VBC 

    VEd  = 999.52 KN; N = KN 510.767 (Compression)

     Note that due to the tensile axial force in the section, the second term of VRd  equation assumes a negative value. = 0.0134;  = 1.0641 N/mm2; vmin = 0.3504 N/mm2; VRd  = 351.161 KNSince VRd,c < VEd , shear reinforcement is required

    Assuming that the strut angle  = 21.8° v1 = 0.5160; f cd  = 19.8450 N/mm2; z = 0.9d = 1020.6 mm; VRDmax =1440.64 KN

    Since VRDmax > VEd  

     = 0.9789

    Trying 3Y10mm @ 200mm c/c (235/200 = 1.175)

    1.175 > 0.9153 Hence shear reinforcement is ok.

    1.4.5.4 Support C; Shear at VCB 

    VEd  = 918.98 KN; N = KN 208.670 (Tension)

     Note that due to the tensile axial force in the section, the second term of VRd  equation assumes a negative value.

     = 0.0089;  = 0.4347 N/mm2; vmin = 0.3504 N/mm2; VRd  = 213.2707 KNSince VRd,c < VEd , shear reinforcement is required

    Assuming that the strut angle  = 21.8° v1 = 0.5160; f cd  = 19.8450 N/mm2; z = 0.9d = 1020.6 mm; VRDmax =1440.64 KN

    Since VRDmax > VEd  

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    12/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016) Page 12

     = 0.9000

    Trying 3Y10mm @ 200mm c/c (235/200 = 1.175)

    1.175 > 0.9153 Hence shear reinforcement is ok.

    1.5 Discussion and Conclusion

    It is very easy to see that the influence of axial force was not very pronounced in the results produced. It would

    have been very significant using BS 8110. The maximum reinforcement was seen at support B due the high

    magnitude of moment at that section. This phenomenon is consistent with horizontal continuous beams. See

    detailing sketches in Figure 2.0.

    Figure 2.0: Reinforcement detailing sketches (not to scale) 

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/

  • 8/17/2019 Analysis and Design of a Continuous R. C. Raker Beam using Eurocode 2

    13/13

     Analysis and Design of Stadium Raker Beam Using EC2 Ubani Obinna U. (2016)

     Downloaded from www.structville.blogspot.com   Ranks Michael Enterprises (2016) Page 13

    References

    [1]  BS 6399 part 1: 1996: Loading for Building code of practice for dead and imposed loads.British Standards Institution.

    [2]  BS 8110  –   1:1997: Structural use of concrete Part1: Code of practice for design andconstruction. British Standard Institutions.

    [3] 

    EN 1991-1-1 (2002): General Actions- Densities, self weight, imposed loads for buildings

    [4]  EN 1992-1-1 (2004): Design of concrete structures: General Rules and rules for building

    [5]  Jeff Steele, Mark Larsen (1996): Raker-Beam Construction Requires Rugged Steel Forms.

    Publication #C960738 The Aberdeen Group 

    [6]  Karadelis J (2009): Concrete Grandstands. Part 1: Experimental investigations. Proceedingsto the Institution of Civil Engineers  –  Engineering and Computational mechanics. Volume162,Issue 1 ISSN 1755-0777

    [7]  Salyards K.A., Honagan L.M (2005): Evaluation of a finite element model for dynamiccharacteristic prediction of stadium facility.

    http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/http://www.structville.blogspot.com/