Upload
vudien
View
215
Download
0
Embed Size (px)
Citation preview
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKETCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3018B1000NA
TAG: _________________________________
1.5 Ton Split SystemAir Conditioner - 1 Phase M4AC3018B1000NA
SUBMITTAL
M4AC3018B1000NA208/230/1/60
11.920
SCROLL1 - 1
208/230/1/609.0 - 39.0
NOPROPELLER17-3/4 - 1DIRECT - 1
16001 - 1/12
1075208/230/1/60
0.6PLATE FIN
2 - 198.899/32
ORIFICE
4 LBS. - 7 OZ.YES3/43/8
8º FW X H X D
22-9/10X26-1/4X22-9/10
130123
NONO
M4AC3018B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
633 (24-15/16) 554 (21-7/8) 554 (21-7/8) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKETCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3024B1000NA
TAG: _________________________________
2.0 Ton Split SystemAir Conditioner - 1 Phase M4AC3024B1000NA
SUBMITTAL
M4AC3024B1000NA208/230/1/60
14.425
SCROLL1 - 1
208/230/1/6010.9-53.0
NOPROPELLER17-3/4 - 1DIRECT - 1
18001 - 1/12
1075208/230/1/60
0.7PLATE FIN
2 - 1710.059/32
ORIFICE
4 LBS. - 13 OZ.YES3/43/8
8º FW X H X D
22-9/10x26-1/4x22-9/10
132126
NONO
M4AC3024B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
633 (24-15/16) 554 (21-7/8) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
554 (21-7/8)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLED
START COMPONENTS INSULATION/SOUND BLANKETCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3030B1000NA
TAG: _________________________________
2.5 Ton Split SystemAir Conditioner - 1 Phase M4AC3030B1000NA
SUBMITTAL
M4AC3030B1000NA208/230/1/60
15.225
SCROLL1 - 1
208/230/1/6011.6 - 59.0
NOPROPELLER
23-5/8 - 1DIRECT - 1
31001 - 1/81075
208/230/1/600.7
PLATE FIN2 - 1912.849/32
ORIFICE
4 LBS. - 7 OZ.YES3/43/8
8º FW X H X D
30-1/5x26-1/4x30-1/5
152143
NONO
M4AC3030B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
633 (24-15/16) 740 (29-1/8) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
740 (29-1/8)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLED
START COMPONENTS INSULATION/SOUND BLANKETCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3036B1000NA
TAG: _________________________________
3.0 Ton Split SystemAir Conditioner - 1 Phase M4AC3036B1000NA
SUBMITTAL
M4AC3036B1000NA208/230/1/60
19.935
SCROLL1 - 1
208/230/1/6015.3 - 70.0
NOPROPELLER
18-7/8 - 1DIRECT - 1
20501 - 1/81075
208/230/1/600.70
Microchannel1 - 219.74
-ORIFICE
4 LBS. - 5 OZ.YES3/43/8
8º FW X H X D
24-7/10x26-1/4x24-7/10
139132
NONO
M4AC3036B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
633 (24-15/16) 600 (23-5/8) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
600 (23-5/8)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3042B1000NA
TAG: _________________________________
3.5 Ton Split SystemAir Conditioner - 1 Phase M4AC3042B1000NA
SUBMITTAL
M4AC3042B1000NA208/230/1/60
28.245
SCROLL1 - 1
208/230/1/6021.2 - 90.0
NOPROPELLER
23-5/8 - 1DIRECT - 1
42501 - 1/31075
208/230/1/601.70
PLATE FIN2 - 1915.599/32
ORIFICE
6 LBS. - 2 OZ.YES3/43/8
8º FW X H X D
30-1/5x34-1/2x30-1/5
196185
NONO
M4AC3042B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
843 (33-3/16) 740 (29-1/8) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
740 (29-1/8)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKE TCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3043B1000NA
TAG: _________________________________
3.5 Ton Split SystemAir Conditioner - 1 Phase M4AC3043B1000NA
SUBMITTAL
M4AC3043B1000NA208/230/1/60
21.635
SCROLL1 - 1
208/230/1/6015.9 - 112.3
NOPROPELLER
23 - 1DIRECT-1
37001 - 1/31075
208/230/1/601.70
PLATE FIN2 - 21
173/16
ORIFICE
7 LBS. - 16OZ.YES3/43/8
8º FW X H X D29x34-1/2x29
201190
NONO
M4AC3043B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
843 (33-3/16) 710 (28) 3/8 3/4
Ameristar
NOTE: All dimensions are in mm/inches.
710 (28)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
P rod u c t S pe c i f i c a t i o n s O U T D O O R U N I T PO W E R C O N N S . — V / P H / H Z M I N . B R C H . C I R . A M P A C I T Y B R . C I R . P R O T . R TG . - M AX . ( A M P S ) C O M P R E S S O R N O . U S E D - N O . SP E E D S V O L T S / P H / H Z R . L . A M P S - L . R . A M P S F A C T O R Y I N S T A L L E D
S T A R T C O M P O N E N T S I N S U L A T I O N / S O U N D B L A N K E T C O M P R ES S O R H E A T
O U T D O O R F A N D I A . ( I N . ) - N O . U S E D TYP E D R IV E - N O. SP E E D S C F M @ 0 . 0 I N . W . G . N O . M O T O R S - H P M O T O R SP E E D R . P . M . V O L T S / P H / H Z F . L . A M P S O U T D O O R C O I L — T Y P E R OW S - F . P . I . F A C E A R E A ( S Q . F T . ) T U B E S I Z E ( I N . ) R E F R I G E R A N T C O N T R O L R E F R I G E R A N T
L B S . — R- 4 1 0 ( O . D . U N I T ) F A C T O R Y S U P P L I E D L I N E S I Z E - I N . O . D . G A S L I N E S I Z E - I N . O . D . L I Q . C H A R G I N G S P E C I F I C A T I O N S U B C O O L I N G D I M E N S I O N S C R A T E D ( I N . ) WE I G H T S H IP P I N G ( L B S . ) N E T ( L B S . )
M4AC3048B1000NA
TAG: _____________________________ _ _ _ _
4.0 T o n S p l i t S y s te m A i r Conditioner - 1 Phase M4AC3048B1000NA
S U B M I T T A L
M4AC3048B1000NA2 0 8 / 2 3 0 / 1 / 6 0
32.050
S C R O L L 1 - 1
2 0 8 / 2 3 0 / 1 / 6 0 24.2 - 100.0
N O PROPELLER
23 - 1 D I R E C T - 1
40001 - 1 / 3 1075
2 0 8 / 2 3 0 / 1 / 6 0 1.70
PLATE FIN 2 - 19 17.42 9/32
O R I F I C E
8 L B S . - 1 O Z . Y E S 7 / 8 3 / 8
8 º F W X H X D 29x31-1/5x29
216 200
N O N O
M4AC3048B1000NA
Mo d e l H W L L I Q U I D V A L VE S I Z E GAS V A L VE S I Z E
759 (29-7/8) 710 (28) 3 / 8 7 / 8
A m e r i s t a r
NOTE: All dimensions are in mm/inches.
710 (28)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.
Product Specifications OUTDOOR UNIT
POWER CONNS. — V/PH/HZ MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS)
COMPRESSOR NO. USED - NO. SPEEDS VOLTS/PH/HZ R.L. AMPS - L.R. AMPS FACTORY INSTALLEDSTART COMPONENTS INSULATION/SOUND BLANKETCOMPRESSOR HEAT
OUTDOOR FAN DIA. (IN.) - NO. USED TYPE DRIVE - NO. SPEEDS CFM @ 0.0 IN. W.G. NO. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I. FACE AREA (SQ. FT.) TUBE SIZE (IN.) REFRIGERANT CONTROL
REFRIGERANT
LBS. — R-410 (O.D. UNIT) FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS LINE SIZE - IN. O.D. LIQ.
CHARGING SPECIFICATION SUBCOOLING
DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.)
M4AC3060B1000NA
TAG: _________________________________
5.0 Ton Split SystemAir Conditioner - 1 Phase M4AC3060B1000NA
SUBMITTAL
M4AC3060B1000NA208/230/1/60
31.150
SCROLL1 - 1
208/230/1/6023.5 - 125.0
NOPROPELLER23-5/8 - 1DIRECT - 1
42501 - 1/31075
208/230/1/601.70
PLATE FIN3 - 1918.459/32
ORIFICE
9 LBS. - 1 OZ.YES7/83/8
8º FW X H X D
30-1/5x34-1/2x30-1/5
246231
NONO
M4AC3060B1000NA
Model H W L LIQUID VALVE SIZE GAS VALVE SIZE
843 (33-3/16) 740 (29-1/8) 3/8 7/8
Ameristar
NOTE: All dimensions are in mm/inches.
740 (29-1/8)
SUCTION LINE CONNECTION
CONTROL WIRING 7/8” (22.2mm)
KNOCKOUT 1-11/32” (34.5mm)
LIQUID LINE CONNECTION
SERVICE FITTING
SERVICE FITTING
POWER WIRING SEE DETAIL A
DETAIL A
HOLE 1-3/32” (27.8mm)
NOTE: GRILL APPEARANCE MAY VARY.
SERVICE ACCESS ALLOW 24” CLEARANCE
AIR INLETS LOUVERED PANELS ALLOW 12” MINIMUM CLEARANCE
W
ACCESS VALVLEFOR LOW PRESSURENOTE: ONLY ADOPTED BY HEAT PUMP, CAN BE USED FOR MEASURING PRESSURE AFTER SWITCHOVER VALVE-SUCTION TO COMPRESSOR ORREFRIGERANT CHARGE.
Literature Order Numbe r SS-PRC007-EN
File Numbe r —
Supersede s SS-PRC007-EN 2/0 2
Stocking Locatio n PI Louisville & Webb/Mason Houston
Ameristar has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
MechanicalSpecification Options
General
Casing
Refrigerant Controls
Scroll Compressor
Condenser Coil
Optional accessories
Liquid line drier
—
Ameristar
The M4AC30 is fully charged from the factory. This unit is designed to operateat outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with air handlers and furnace coils that are AHRI certified. The unit is certified to ETL. Exterior is designed for outdoor application.
Unit casing is constructed of heavy gauge, Galvanized steel and painted with a weather-resistant powder paint on all grilles, panels, pre-paint on all other panels. And had 500-hours salt spray tested.
Refrigeration system controls include condenserfan, compressor contactor.
Features include low vibration and noise.
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by grille panels.
It is used to filter out impurities and water in the system, ensures system clean and dry.