NETWORK ANALYZERS.A. DE CONSTRUCCIONES INDUSTRIALES
13 op st leio un dal o m
AH 3M
AHM3
ELECTRICAL PARAMETER UNIT L1 L2 L3 TOTAL MAX/MIN DEMAND
Voltage (Line-to-neutral) V, kV
Voltage (Line-to-Line) V, kV
Current A, kA
Neutral current A, kA
Active power (P) kW, MW, GW
Reactive power (Q) kvar, Mvar, Gvar
Apparent power (S) kVA
Power factor (Cos φ) PF
Frequency Hz
Import active energy (EP+) kWh, M Wh, G Wh
Export active energy (EP-) kWh, M Wh, G wh
Reactive energy (Q1, Q2, Q3, Q4) kvarh, M varh, G varh
Backup energy kWh
Hour meter h: min
THD Current and Voltage A, V
Harmonic RMS-U and I (1-63th) %
Unbalance-U and I %
NETWORK ANALYZER AHM3
Additional modules COMMUNICATION PROTOCOL
DM 10 Probus-DP VO
DM11 Ethernet: Mobus/TCP
DM 12 Wi: Modbus/TCP
DM 13 GPRS: Modbus/TCP, SMS
DIGITAL I/O
DM 6 2 digital inputs + 2 digital outputs
DM 7 4 digital inputs
DM 8 2 relay outputs
DM 9 1 AC digital input
ANALOG I/0
DM 2 2 analog inputs: mA
DM 5 2 analog outputs: mA
TEMPERATURE MEASUREMENT
DM 3 2 analog inputs: PT100
DM 4 2 analog inputs: TC (J, K or E)
DATA RECORDER
DM 1 Memory: 8MB, include RTC
COMMUNICATION PROTOCOL
DIGITAL I/O
ANALOG I/O
TEMPERATURE MEASUREMENT
DATA RECORDER
GENERAL FEATURES DIN SIZE 96 x 96 mm. 13 ADDITIONAL MODULES. 4 INTERFACES FOR MODULES. THD on V and I. HARMONIC RMS (1-63th) MAXIMUM DEMAND, A, kW, kVA, kvar. MAXIMUM AND MINIMUM VALUES. PROGRAMMABLE RATED V AND I 4 QUADRANT MEASUREMENT. WAVEFORM
SACI
Dimensions
The AHM3 is designed to be used for the measurement and calculation of electrical variables such as voltage, current, frequency, power, power factor, energy, harmonic components, etc. in low, medium and high voltage power distribution.
It is capable of single-phase, two-phase, or three-phase measurement and can be used in two-wire,three-wire,four-wire, TN,TT and IT systems. There are four interfaces on the meter for modules which are used to extend functions.
Up to ❹ modules combined at your choice
at the same time
INPUT
Rated voltage (Un) 3 x 400 / 690 V AC
Overload 1,2 Un
Impedance > 1MΩ
Rated Current (In) 1 A and 5 A
Overload Continuous 2 In
Overload Instantaneous 10 In/5s or 20 In/1s
Burden < 0,1 VA
Rated value < 2 0 mΩ
AUXILIARY VOLTAGE
Aux. V. AC/DC 80 - 270 V
Burden < 10 VA
OUTPUT
Relay output 250V/5A AC; 30V/5A DC
Isolation 2500 V AC
Energy pulse width 80 ± 20% ms
RS 485 port Modbus-RTU
Baud rate Up to 38400 bps programmable
GENERAL FEATURES
Case material ABS, UL94 V0
Dimensions DIN 96 x 96 mm
Terminals Pluggable
Max. wire section 2,5 mm²
Weight 0,4 Kg
ProtectionIP 65 - front panel
IP 20 - meter body
Operating t emperature -10 - 60 °C
Storage temperature -25 - 70 °C
Relative h umidity 5 - 9 5 %
AHM3
PARAMETER OPERATING RANGE ACCURACY
Voltage 2,5-120 % 0,2 %
Current 0,005-6 A 0,2 %
Active power 1-120 % 0,2 %*
Reactive power 1-120 % 0,2 %*
Apparent power 1-120 % 0,2 %*
Power factor ± 0,5 % 0,5 %
Frequency 45-65 Hz ± 0,01 Hz
Active energy 5-120 % Class 0,5 S
Reactive energy 5-120 % Class 2
Accuracy
* Class 0,2 (25ºC) and Class 0,5 (-10 - 60 ºC)
AHM3
Multifunction Power Meter
The AHM3 is designed to be used for the
measurement and calculation of electrical variables such as voltage, current, frequency, power, power factor, energy, harmonic components, etc. in low, medium and high voltage power distribution. It is capable of single-phase, two-phase, or three-phase measurement and can be used in two-wire, three-wire, four-wire, TN,TT and IT systems. There are four interfaces on the meter for modules which are used to extend functions.
The following list shows variables which can be measured by AHM3 including relative variables calculated from basic electrical parameters.
Dimensions
Signal Wiring Diagrams
ABC
3P3W,3CT,3PT
*
*
4 95 8I A I A I C I C* *
6 7I B I B*
*
1 1 1 4U
1 2 1 3 A U B U C U N
ABC
3P4W,3CT,3PT
4 95 8I A I A I C I C* *
6 7I B I B*
1 1 1 4U
1 2 1 3 A U B U C U N
N
*
**
ABC
Balanced 3P4W,3PT,1CT
4 95 8I A I A
*
6 7 1 1 1 4U
1 2 1 3 A U B U C U N
N
*
U A U C U B
AB
C
1 1 1 3 1 41 2
3P3W,2CT,no PT
A
BC
3P3W,2CT,2PT
U A U C U B
1 1 1 3 1 41 2
ABC
3P3W,2CT,3PT
1 1 1 4U
1 2 1 3 A U B U C U N
ABC
1 1 1 4U
1 2 1 3 A U B U C U N
N
*
*
4 95 8I A I A I C I C* *
6 7
*
*
4 95 8
I A I A I C I C* *
6 7
*
*
4 95 8I A I A I C I C* *
6 7
*
*
4 95 8I A I A I C I C* *
6 7
AN
*
U A U N1 1 1 3 1 44 95 8
I A I A*
6 7 1 2
1-Phase,1CT,1PT
U A U N
AN
*
1 1 1 3 1 44 95 8I A I A
*
6 7 1 2
1-Phase,1CT,no PT
U A U C U B
A
BC
*
*
1 1 1 3 1 44 95 8
I A I A I C I C* *
6 7 1 2
3P3W,3CT,no PT
I B I B*
*
U A
ABC
*
*
1 1 1 3 1 44 95 8I A I A I C I C* *
6 7 1 2
3P4W,3CT,no PT
I B I B*
*
N
U B U C U N
A
BC
3P3W,3CT,2PT
*
*
4 95 8
I A I A I C I C* *
6 7
I B I B*
*
U A U C U B
1 1 1 3 1 41 2
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9
1 3 4 6 7 9 1 3 4 6 7 9 1 3 4 6 7 9
2 5 8 11 2 5 8 11 2 5 8 11
2 5 8 11 2 5 8 11 2 5 8 11
2 5 8 11 2 5 8 11 2 5 8 11
2 5 8 11 2 5 8 11 2 5 8 11
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2 S1 S2
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
L1N
L1N
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
L1L2L3
Measurement variable Instant Max Min Demand sum unit
V1 V2 V3 √ √ √ [V,kV]
V12 V23 V31 √ √ √ [V,kV]
I1 I2 I3 √ √ √ √ [A,kA]
F √ √ √ [Hz]
P P1 P2 P3 √ √ √ √ [kW,MW,GW]
Q Q1 Q2 Q3 √ √ √ √ [kvar,Mvar,Gvar]
S S1 S2 S3 √ √ √ √ [kVA,MVA,GVA]
PF PF1 PF2 PF3 √ √ √ -
EP+ EP- √ [kWh,MWh, GWh]
EQ1 EQ2 EQ3 EQ4 √ [kvarh,Mvarh,Gvarh]
Backup Energy √
THDV1 THDV2 THDV3 √ [% ]
THDI1 THDI2 THDI3 √ [% ]
Harmonic RMS-U (1~63th) √ [% ]
Harmonic RMS-I (1~63th) √ [% ]
Unbalance-U √ [% ]
Unbalance-I √ [% ]
Hour meter √ h:min
Neutral current √ [A,kA]
AHM3
Multifunction Power Meter
Electric Characteristics
Accuracy
Voltage and current 0.2%
Power 0.5%
Frequency ±0.01Hz
Active energy IEC62053-22, class 0.5S
Reactive energy IEC62053-23, class 2
Data update rate 1s
Input
Wiring mode 1P2W, 3P3W, 3P4W
Voltage
Rated value 690 V AC Phase-phase
Overload 1.2Un
Impedance >1MΩ
Current
Rated value 1A or 5A
Overload
Continuous: 2In
Instantaneous: 10In/5s or 20In/1s
burden <0.1VA
Impedance <20mΩ
Grid frequency (45~65)Hz
Auxiliary
supply
Working range AC/DC(80~270)V
consumption ≤ 10VA
Energy pulse output 2 photocoupler outputs, pulse width (80±20%) ms
Digital input Dry contact input, isolation:2000VAC
Relay output Contact rated at AC 250V/5A or DC 30V/5A
Isolation: 2500VAC
Communications
RS485 port Modbus-RTU , 2-wire,up to 38400bps
Mechanical Characteristics
IP index IP65(front panel)and IP20(meter body)
Dimensions 96×96×55mm
Environmental Characteristics
Operating temperature (-10~60)ºC
Storage temperature (-25~70)ºC
Relative humidity (5~95)% (no gel)
Insulation IEC 61010-1
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
Program Example
E.g. select wiring mode as three phase three wire, set primary value of PT as 6kV, and set secondary value of PT as 100V.
EnergyInstant
Harmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
MENU
Enter Password
Admin
ENTER
User
EDIT
CT Primary
380 V
00038 V000005 A
3P3W
5 APT Primary
EDIT
CT Primary
380 V
000005 A
3P3W
5 APT Primary 006000 V
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X2Module X1
ENTER
Basic SetupSignal Inputs
Setup
COM1 Port
ESC
DemandRelay Outputs
Module X2Module X1
ENTER
Basic SetupSignal Inputs
→ENTER →ENTER →→ENTER
→ENTER →ENTER →→ENTER
→ →ENTER →→ENTER
→ ESC → ESC →ENTER
→
→ENTER
→ENTER
Signal Inputs
CT Secondary
ESC
PT SecondaryWiring
EDIT
CT Primary
380 V
000380 V000005 A
3P3W
5 APT Primary
Signal Inputs
CT Secondary
ESC
PT SecondaryWiring
Signal Inputs
CT Secondary
ESC
PT SecondaryWiring
Signal Inputs
CT Secondary
ESC
PT Secondary
PT Primary
EDIT
CT Primary
380 V
000380 V000005 A
3W
5 A
Wiring
Save Settings?YesNo
Signal Inputs
CT Secondary
ESC
PT Secondary
PT Primary
EDIT
CT Primary
380 V
000380 V000005 A
3P4W
5 A
Wiring
EnergyInstant
Harmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
000
Signal Inputs
CT Secondary
ESC
PT Secondary
PT Primary
EDIT
CT Primary
380 V
000380 V000005 A
3P3W
5 A
Wiring
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X2Module X1
ENTER
Basic Setup
Signal Inputs
CT Secondary
ESC
PT Secondary
PT Primary
EDIT
CT Primary
380 V
000380 V000005 A
5 A
Wiring 3P4W
Signal Inputs
CT Secondary
ESC
PT SecondaryWiring
EDIT
CT Primary
380 V
000005 A
3P3W
5 APT Primary 006000 V
0
1User
3P3W
>
Safety Precautions The manufacturer shall not be held responsible for failure to comply with the instructions in this
manual.
The equipment must be installed and serviced only by qualified personnel.
Prior to any work on or in the equipment, isolate the voltage inputs and auxiliary power
supplies,short the secondary of all CT, but never short the secondary of PT.
Always use a properly rated voltage sensing device to conform that all power is off.
Risk of damaging device
The voltage of the auxiliary power supply is beyond the rated range.
The frequency of the power distribution system is beyond the rated range.
The input polarity of the voltage or the current is wired improperly.
1
DM1 module
Módulo DM1
(Memory & RTC)
(Memoria y RTR)
User manual
Manual de Usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 Display
MENU
7.2Module X1
Module DM1
Saturday
14-09-2010:50:50
This module provides time information
and supports data storage function. Left
picture shows time information.
Este módulo proporciona información
del día y soporta el almacenamiento de
datos. La Imagen de la izquierda
muestra la información de día.
5 Setup / Configuración
Operating process: / Proceso de Programación:
→ → →
EnergyHarmoni c
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Inf o
MENU
ESC
Enter Passwo rd
Admin
ENTER
000
Setup
COM1 Po rt
ESC
Signal Inpu ts
DemandRelay Outpu ts
ENTER
Basic Set up
Module X2
Module X1-DM1
ESC
Time
EDIT
Monday
01 min14-09-2811:20:0 0
Measure .
Setup
1User
Module X1
Interva l
Module X1-DM1
ESC
Time
EDIT
Interval
Monday
01 min14-09-2811:20:00
Interval
Intervalo
Data record Interval
Intervalo de registro de
datos
0~99min
Time
Fecha
Setup real time clock::
Configurar reloj de
tiempo real
Year-month-day
Año-mes-día
Hour:min:sec
Hora:min:seg
Week / Semana
4
6 Technical specifications
Memory
Memoria
8M byte flash memory
Memoria flash de 8M bytes
Real time clock
Reloj de tiempo real
Accuracy: <0.5s/day
Precisión: <0.5s/días
1
DM2 module
Módulo DM2
( 2 Analog Inputs:0~20mA )
(2 Entradas Analógicas: 0 .. 20 mA)
User manual
Manual de Usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3
3 Installation / Instalación
4 wiring / Conexionado
5 Display
MENU
Module X1 7. 2
Analog Inputs DM2No.0102
Value07.60 mA18.20 mA
Left picture shows 2 measured value of
analogue input.
La imagen muestra dos lecturas de las
entradas analógicas.
No.1: 7.60mA;
No.2: 18.20mA.
4
6 Setup / Configuración
AHM3 can automatic identification module type, Don't need to setup.
El modulo no necesita ser configurado. El equipo AHM3 lo identifica
automáticamente. http://www.elso.sk/product.php?id_product=3367
7 Technical specifications / Especificaciones técnicas
maximum values
Valores maximos
0-24mA
Accuracy / Precisión 0.5%
1
DM3 module
Módulo DM3
( 2 Analog Inputs:PT100 )
2 entradas de sonda PT100
User manual
Manual de Usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3
3 Installation / Instalación
4 wiring / Cableado
4
5 Display
MENU
Module X4 7. 5
PT100 DM3No.0102
Value075.5 027.6
Left picture show measured value of
PT100 thermal resistor.
First temperature is 75.5 ºC;
Second temperature is 27.6 ºC.
La imagen muestra la lectura de
temperatura de dos sondas PT100.
Primera temperatura 75.5 ºC;
Segunda temperatura 27.6 ºC.
6 Setup / Configuración
AHM3 can automatic identification module type, Don't need to setup.
El modulo no necesita ser configurado. El equipo AHM3 lo identifica
automáticamente.
7 Technical specifications / Especificaciones técnicas
Update time / Tiempo de refresco 1 second / 1 segundo
Type of sensor / Tipo de sensor PT100( -200~600 ºC)
Accuracy / Precision ±1ºC
1
DM4 module
Módulo DM4
( 2 Analog Inputs:Thermocouple)
(2 Entradas analógicas: Termopar)
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 wiring / Conexionado
5 Display
MENU
Module X1 7. 2
Thermocouple-J DM4
0763
No.0102
Value0507
Left picture shows 2 measured value of
thermocouple J.
La imagen de la izquierda muestra 2
valores del termopar J
No.1 :507ºC;
No.2: 763ºC.
6 Setup / Configuración
Operating process: Proceso de Programación:
Module X1-DM4
ESC
CJC
EDIT
ThermocoupleType J
ON
→ → →
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
0001User
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
Module X2
Measure.
4
Module X 1-DM4
ESC
CJC
EDIT
ThermocoupleType J
ON
Type J,K,E,N
CJC Cold junction Compensation:
Compensación de unión fría:
ON/OFF
7 Technical specifications / Especificaciones técnicas
Update time
Tiempo de actualización
1 second
1 segundo
Type of sensors
Tipo de sensor
J( 0~ 1200), K(0 ~1300 ), E( 0~1000 ),
N(0 ~ 1300)
Accuracy
Precisión
±2
1
DM5 module
Módulo DM5
(2 Analog outputs:0~20mA)
(2 Salidas Analógicas: 0 .. 20 mA)
User manual / Manual de Usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 wiring / Cableado
5 Display
Instantaneous electrical parameters are change into DC current signal output
through DM5 module. If this module is installed onto meter, relative interface
will be displayed. The current value shown in the interface is theoretical value
in present status.
Analogue output items and range are programmed through meter.
Las medidas instantáneas pueden ser convertidas en salidas analógicas de
corriente continua mediante este módulo DM5. Cuando el módulo se instala
en el medidor, una pantalla muestra los datos relativos al módulo. La
configuración de las salidas se puede realizar en el medidor.
MENU
Module X1 7.2
Analog Outputs-DM5No.0102
Value04.00 mA08.20 mA
Left picture shows 2 theoretical value of
analog output.
La pantalla muestra los valores de las
dos salidas analógicas.
No.1: 4.00mA
No.2: 8.20mA
6 Setup / Configuración
4
Operating process / Proceso de Programación:
→ → →
EnergyHarmonic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
0001User
Setu p
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
Module X2
→
Module X1-DM 5
ESC
No.
02
EDIT
Analog Output
01Measure.
02 Analog Outpu t
ESC
Mode
OK
Zero
Item4-20mA
---- W
P
kMid.0150 W
0000 W
SetupFull k
Module X1-DM5
ESC
No.
02
EDIT
Analog Output
01
DM5 have 2 analog outputs, you need to
select one of them.
El módulo DM5 tiene dos salidas
analógicas. Necesita seleccionar la
salida a parametrizar.
02 Analog Output
ESC
Mode
OK
Zero
Item4-20mA
---- W
P
kMid.0150 W
0000 W
Full k
02 Analog Output
ESC
Mode
OK
Zero
Item4-12-20mA
0000 W-0150 kW
P
kMid.0150 WFull k
Item / Var. See following list
Ver la lista de variables
Mode
Modo
4-12-20mA
Zero
Cero
Zero scale ( Primary )
Valor de inicio para 4 mA.
Mid.
Medio
Middle scale(Primary)
Valor medio para 12 mA
Full
Final
Full scale ( Primary )
Valor final para 20 mA
Mode(4-20):
4-20mA----------Zero-Full.
Mode(4-12-20):
4-12mA----------Zero-Mid;
12-20mA----------Mid-Full.
Analog output items are shown in following list:
Lower limit value and upper limit value of analog output are primary
5
values. Upper limit value should not be larger than two times of rated value.
4-12-20mA analog output mode is only valid for active power, reactive power,
apparent power and power factor.
A continuación se muestra la lista de variables disponibles:
Los valores de configuración se corresponden con valores en primario.
El valor final máximo no puede ser mayor de dos veces el nominal. El modo
4-12-20 mA solo está disponible para las variables de Potencia Activa,
Reactiva, Aparente y Factor de Potencia.
Item
Variable
Format
Format Instruction / Descripción
OFF Off / Apagado
V1
xxx.x __V Voltage / Tensión
V2
V3
V12
V23
V31
I1
x.xxx __A Current / Corriente I2
I3
I0
P1
x.xxx __W Active Power / Potencia Activa P2
P3
P
Q1 x.xxx __var Reactive Power / Potencia Reactiva
6
Q2
Q3
Q
S1
x.xxx __VA Apprent Power / Potencia Aparente S2
S3
S
PF1
x.xxx Power Factor / Factor de Potencia PF2
PF3
PF
F xx.xx Hz Frequency / Frecuencia
7 Technical specifications / Especificaciones técnicas
maximum values
Valor máximo
0-24mA
Load resistor
Impedancia de carga
0~600Ω
Response time
Tiempo de respuesta
1second / 1 segundo
Insulation / Aislamiento 2kV
Accuracy (Full scale)
Precisión (Fondo de
escala)
0.5%
1
DM6 module
Modulo DM6
( 2 Digital inputs and 2 Digital outputs )
(2 Entradas digitales y 2 salidas digitales)
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 Wiring / Conexionado
5 Display
MENU
Module X2 7.3
Digital Outputs-DM6No.0102
No.01
ModeAlarmRemote
ModePulse
Status
StatusDigital Inputs
02 State00000024
At left shows digital input and output
state.
La figura muestra un ejemplo de
configuración del módulo.
4
6 Setup / Configuración
Operating process: Proceso de programación
→ → →
EnergyHarmonic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
000
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
→
Module X2-DM6
ESC EDIT
Mode
Remote
Digital Outputs
AlarmNo.
02
01 Pulse02 State
Digital Inputs
Measure.
No.01 Alarm
ESC
Item
EDIT
V1 >0005*100msPulse
LockDelay 0020*100ms
020.0 V
OFF
Hys400.0 VkValue01
1
Module X2
User
Setup
→ → →
EnergyHarmon ic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.In fo
MENU
ESC
Enter Pass word
Admin
ENTER
0001User
Set up
COM1 P ort
ESC
Signal Inp uts
DemandRelay Outp uts
Module X1
ENTER
Basic Se tup
Module X2
Modul e X2-DM6
ESC EDIT
Mode
Remote
Digita l Outputs
Alarm No.
0201
Digital In puts
State02 01
Measur e.
Setup Pulse
Module X2-DM6
ESC EDIT
Mode
Remote
Digital Outputs
Alarm No.
02
01
01
Pulse02 Spare En
Digital Inputs
At left shows DM6 setting interface.
La imagen muestra la interface con los
datos de configuración
No.01 Alar m
ESC
Item
EDIT
V1 >0005*100msPulse
LockDelay 0020*100ms
020.0 V
OFF
Hys400.0 VValue k
Alarm output mode / Modo Alarma
Pulse
Pulso
Pulse width / Ancho del
pulso: (0~9999)×100ms
Item Var. See following list /Ver lista
Value
Valor
Limit value(Primary)/ Valor
de referencia (Primario)
Hys Hysteresis value(Primary)
Histéresis (Primario)
Delay
Retardo
Delay time / Tiempo
retardo: (0~9999)×100ms
Lock
Bloqueo
Interlock/Bloqueo: ON/OFF
5
No.02 Remote
ESC EDIT
0001*100msPulse
Remote control output mode
Salida en modo control remoto
Pulse
Pulso
Pulse width / Ancho Pulso:
0~9999*100ms
Alarm items are shown in following list
A continuación se muestra la lista de variables en modo alarma
Item
Var.
Format /
Formato Instruction / Instrucciones
OFF Off
DI 0-5
Digital input linkage of selected channel, the
relay output copy the state of the digital input
Unión con la entrada digital seleccionada. La
salida copia el estado de la entrada digital.
THDi <
xx.xx%
Current harmonic distortion rate low alarm
Tasa de distorsión de corriente armónica
alarma de baja
THDi >
Current harmonic distortion rate high alarm
Tasa de distorsión de corriente armónica
alarma de alta
THDu <
Voltage harmonic distortion rate low alarm
Tasa de distorsión de tensión armónica alarma
de baja
THDu > Voltage harmonic distortion rate high alarm
6
Tasa de distorsión de tensión armónica alarma
de alta
Iunb <
xxx.x %
Current unbalance low alarm
Corriente desequilibrada alarma de baja
Iunb > Current unbalance high alarm
Corriente desequilibrada alarma de alta
Uunb < Voltage unbalance low alarm
Tensión desequilibrada alarma de baja
Uunb > Voltage unbalance high alarm
Tensión desequilibrada alarma de alta
F <
xx.xx Hz
Grid frequency low alarm
Frecuencia de red alarma de baja
F > Grid frequency high alarm
Frecuencia de red alarma de alta
PF <
x.xxx
Total power factor low alarm
Factor de potencia total alarma de baja
PF > Total power factor high alarm
Factor de potencia total alarma de alta
S <
xxxx _VA
Total apparent power low alarm
Potencia aparente total alarma de alta
S > Total apparent power high alarm
Potencia aparente total alarma de baja
Q <
xxxx _var
Total reactive power low alarm
Potencia reactiva total alarma de baja
Q > Total reactive power high alarm
Potencia reactiva total alarma de alta
P <
xxxx _W
Total active power low alarm
Potencia activa total alarma de baja
P > Total active power high alarm
Potencia activa total alarma de alta
7
Io <
x.xxx _A
Zero-sequence current low alarm
Corriente de secuencia cero alarma de baja
Io > Zero-sequence current high alarm
Corriente de secuencia cero alarma de alta
Iavg > Current average value low alarm
Valor promedio de corriente alarma de baja
Iavg < Current average value high alarm
Valor promedio de corriente alarma de alta
I < One of three phases currents low alarm
1 de las 3 corrientes de fase alarma de baja
I > One of three phases currents high alarm
1 de las 3 corrientes de fase alarma de alta
I3 < I3 currents low alarm
Corriente I3 alarma de baja
I3 > I3 currents high alarm
Corriente I3 alarma de alta
I2 < I2 currents low alarm
Corriente I2 alarma de baja
I2 > I2 currents high alarm
Corriente I2 alarma de alta
I1 < I1 currents low alarm
Corriente I1 alarma de baja
I1 > I1 currents high alarm
Corriente I1 alarma de alta
Ulavg <
xxx.x _V
Line voltage average value low alarm
Valor promedio de tensión de línea alarma de
baja
Ulavg > Line voltage average value high alarm
Valor promedio de tensión de línea alarma de
alta
8
Unavg < Phase voltage average value low alarm
Valor promedio de tensión de fase alarma de
baja
Unavg > Phase voltage average value high alarm
Valor promedio de tensión de fase alarma de
alta
Ul < One of three line-voltages low alarm
1 de las 3 tensiones de línea alarma de baja
Ul > One of three line-voltages high alarm
1 de las 3 tensiones de línea alarma de alta
V31 < V31 voltages low alarm
Tensión V31 alarma de baja
V31 > V31 voltages high alarm
Tensión V31 alarma de alta
V23 < V23 voltages low alarm
Tensión V23 alarma de baja
V23 > V23 voltages high alarm
Tensión V23 alarma de alta
V12 < V12 voltages low alarm
Tensión V12 alarma de baja
V12 > V12 voltages high alarm
Tensión V12 alarma de alta
Un < One of three phases voltages low alarm
1 de las 3 tensiones de fase alarma de baja
Un > One of three phases voltages high alarm
1 de las 3 tensiones de fase alarma de alta
V3 < V3 voltages low alarm
Tensión V3 alarma de baja
V3 > V3 voltages high alarm
Tensión V3 alarma de alta
9
V2 < V2 voltages low alarm
Tensión V2 alarma de baja
V2 > V2 voltages high alarm
Tensión V2 alarma de alta
V1 < V1 voltages low alarm
Tensión V1 alarma de baja
V1 > V1 voltages high alarm
Tensión V1 alarma de alta
7 Technical specifications/ Especificaciones técnicas
Digital input
Type Dry contact input
isolation 2kV AC
Min. Pulse duration 5ms
Max. frequency of Pulse 100Hz
Max. Number of operations 99999999
Digital output
Max. Load rating AC/DC 400V/0.1A
Isolation 1.5kV AC
1
DM7 module
Módulo DM7
( 4 Digital Inputs )
( 4 Entradas digitales)
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 Wiring / Conexionado
5 Display
MENU
Module X1 7.2
Digital Inputs-DM7No.
04
Mode
State
PulseState
StatusTariffs
03
010000005602
Left picture shows state of four digital input.
No.1: Tariff energy;
No.2: pulse counter, number 56;
No.3: status OFF
No.4: status ON
Estado de los 4 entradas digitales:
No.1: Energía facturada
No.2: Pulsador de energía numero 56
No.3: estado apagado
No.4: estado encendido
6 Setup / Configuración
Operating process: Proceso de programación
→ → →
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
0001User
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
Module X2
Module X1-DM7
ESC EDIT
Mode
Pulse
Digital Inputs
Tariffs No.
02 03 04
01
StateState
Measure.
4
Module X1- DM7
ESC EDIT
Mode
Pulse
Digital Inputs
TariffsNo.
020304
01
StateSapre En
There are four working modes of digital
input.
1. Tariff energy (effective in DM7 module)
2. Pulse counter
3. Backup energy (effective in DM9 module)
4. Status monitoring
Hay 4 modos de trabajo de las entradas
digitales
1. Energía facturada ( Efectiva en el módulo
DM7
2. Pulsador de energía
3. Copia de seguridad de la energía
( efectiva en el módulo DM9)
4. Monitorización de estado
Module X1-DM7
ESC EDIT
Mode
Tou En
Digital Inputs
Tou En No.
02 03 04
01
StateTou En
DM7 module is used for setting tariffs from
its first digital input. There are four digital
inputs available. Tariff is judged by meter
according to digital input status. Status 0000
corresponds to T1, and Status 1111
corresponds to T16. See following list for
detailed information.
Módulo DM7 se utiliza para configurar las
tarifas desde su primera entrada digital. Hay
cuatro entradas digitales disponibles. El
estado 0000 corresponde a T1, y el estado
1111 corresponde a T16. Vea la siguiente
lista para obtener información detallada
5
Detailed corresponding relation is shown in following list. "0" indicates the
digital input is open, and "1" indicates the digital input is closed.
La relación se detalla en la siguiente lista la relación correspondiente. "0"
indica que la entrada digital está abierta, y "1" indica que la entrada digital
está cerrada.
DI4 DI3 DI2 DI1 Tariff / Tarifa
0 0 0 0 T1
0 0 0 1 T2
0 0 1 0 T3
0 0 1 1 T4
0 1 0 0 T5
0 1 0 1 T6
0 1 1 0 T7
0 1 1 1 T8
1 0 0 0 T9
1 0 0 1 T10
1 0 1 0 T11
1 0 1 1 T12
1 1 0 0 T13
1 1 0 1 T14
1 1 1 0 T15
1 1 1 1 T16
6
7 Technical specifications / Especificaciones técnicas
Type / Tipo Dry contacts
Scan time
Tiempo de escaneado
ms
Isolation / Aislamiento 2kV AC
Min. Pulse duration
Duración de pulso mín.
5ms
Max. frequency of Pulse
Máx. frecuencia de pulso
100Hz
Max. Number of operations
Máx. número de operaciones
99999999
1
DM8 module
Módulo DM8
( 2 Relay Outputs )
( 2 Relés de salida)
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 wiring / Conexionado
5 Display
MENU
Module X1 7. 2
Relay Outputs-DM8No.0102
ModeAlarmRemote
Status
FREE
Left picture shows working mode of relay
outputs.
La imagen de la derecha muestra el
modo de trabajo de los relés
No.1 :alarm OFF;
No.1 :alarma apagada;
No.2: remote control OFF.
No.2: Control remoto apagado.
6 Setup / Configuración
Operating process: / Proceso de programación
→ → →
EnergyHarmonic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
0001User
Setu p
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
Module X2
→
Measure.
No.01 Alar m
ESC
Item
EDIT
V1 >0005*100msPulse
LockDelay 0020*100ms
020.0 V
OFF
HysValue 400.0 kV
Module X1-D M8
ESC EDIT
Mode
Remote
Relay Outputs
AlarmNo.
0201
Setup
4
Module X1-DM8
ESC EDIT
Mode
Remote
Relay Outputs
AlarmNo.
0201
Relay Output have two modes:
Alarm mode and remote control.
Los relés de salida tienen dos modos de
trabajo.
Modo alarma y control remoto
No.01 Alar m
ESC
Item
EDIT
V1 >0005*100msPulse
LockDelay 0020*100ms
020.0 V
OFF
Hys400.0 VValue k
Alarm output mode/ Modo alarma
Pulse
Pulso
Pulse width: (0~9999)×100ms
Item
Var.
See following list
Ver lista siguiente
Value
Valor
Limit value(Primary)
Valor limite(Primario)
Hys Hysteresis value(Primary)
Valor histéresis (primario)
Delay
Ret.
Delay time: (0~9999)×100ms
Tiempo de retardo:
Lock
Bloq.
Interlock: ON/OFF
Bloqueo: ON/OFF
No.02 Remote
ESC EDIT
0001*100msPulse
Remote control output mode
Modo control remoto
Pulse / Pulso
Pulse width:
Ancho de pulso:
0~9999*100ms
5
Alarm items are shown in following list.
Las variables de alarma se muestran en la siguiente lista.
Item
Var.
Format
Formato Instruction / Instrucciones
OFF Off
DI 0-5
Digital input linkage of selected channel, the
relay output copy the state of the digital input
Unión con la entrada digital seleccionada. La
salida copia el estado de la entrada digital.
THDi <
xx.xx%
Current harmonic distortion rate low alarm
Tasa de distorsión de corriente armónica
alarma de baja
THDi >
Current harmonic distortion rate high alarm
Tasa de distorsión de corriente armónica
alarma de alta
THDu <
Voltage harmonic distortion rate low alarm
Tasa de distorsión de tensión armónica alarma
de baja
THDu >
Voltage harmonic distortion rate high alarm
Tasa de distorsión de tensión armónica alarma
de alta
Iunb <
xxx.x %
Current unbalance low alarm
Corriente desequilibrada alarma de baja
Iunb > Current unbalance high alarm
Corriente desequilibrada alarma de alta
Uunb < Voltage unbalance low alarm
Tensión desequilibrada alarma de baja
Uunb > Voltage unbalance high alarm
Tensión desequilibrada alarma de alta
6
F <
xx.xx Hz
Grid frequency low alarm
Frecuencia de red alarma de baja
F > Grid frequency high alarm
Frecuencia de red alarma de alta
PF <
x.xxx
Total power factor low alarm
Factor de potencia total alarma de baja
PF > Total power factor high alarm
Factor de potencia total alarma de alta
S <
xxxx _VA
Total apparent power low alarm
Potencia aparente total alarma de alta
S > Total apparent power high alarm
Potencia aparente total alarma de baja
Q <
xxxx _var
Total reactive power low alarm
Potencia reactiva total alarma de baja
Q > Total reactive power high alarm
Potencia reactiva total alarma de alta
P <
xxxx _W
Total active power low alarm
Potencia activa total alarma de baja
P > Total active power high alarm
Potencia activa total alarma de alta
Io <
x.xxx _A
Zero-sequence current low alarm
Corriente de secuencia cero alarma de baja
Io > Zero-sequence current high alarm
Corriente de secuencia cero alarma de alta
Iavg > Current average value low alarm
Valor promedio de corriente alarma de baja
Iavg < Current average value high alarm
Valor promedio de corriente alarma de alta
I < One of three phases currents low alarm
1 de las 3 corrientes de fase alarma de baja
7
I > One of three phases currents high alarm
1 de las 3 corrientes de fase alarma de alta
I3 < I3 currents low alarm
Corriente I3 alarma de baja
I3 > I3 currents high alarm
Corriente I3 alarma de alta
I2 < I2 currents low alarm
Corriente I2 alarma de baja
I2 > I2 currents high alarm
Corriente I2 alarma de alta
I1 < I1 currents low alarm
Corriente I1 alarma de baja
I1 > I1 currents high alarm
Corriente I1 alarma de alta
Ulavg <
xxx.x _V
Line voltage average value low alarm
Valor promedio de tensión de línea alarma de
baja
Ulavg > Line voltage average value high alarm
Valor promedio de tensión de línea alarma de
alta
Unavg < Phase voltage average value low alarm
Valor promedio de tensión de fase alarma de
baja
Unavg > Phase voltage average value high alarm
Valor promedio de tensión de fase alarma de
alta
Ul < One of three line-voltages low alarm
1 de las 3 tensiones de línea alarma de baja
Ul > One of three line-voltages high alarm
1 de las 3 tensiones de línea alarma de alta
8
V31 < V31 voltages low alarm
Tensión V31 alarma de baja
V31 > V31 voltages high alarm
Tensión V31 alarma de alta
V23 < V23 voltages low alarm
Tensión V23 alarma de baja
V23 > V23 voltages high alarm
Tensión V23 alarma de alta
V12 < V12 voltages low alarm
Tensión V12 alarma de baja
V12 > V12 voltages high alarm
Tensión V12 alarma de alta
Un < One of three phases voltages low alarm
1 de las 3 tensiones de fase alarma de baja
Un > One of three phases voltages high alarm
1 de las 3 tensiones de fase alarma de alta
V3 < V3 voltages low alarm
Tensión V3 alarma de baja
V3 > V3 voltages high alarm
Tensión V3 alarma de alta
V2 < V2 voltages low alarm
Tensión V2 alarma de baja
V2 > V2 voltages high alarm
Tensión V2 alarma de alta
V1 < V1 voltages low alarm
Tensión V1 alarma de baja
V1 > V1 voltages high alarm
Tensión V1 alarma de alta
9
7 Technical specifications / Especificaciones técnicas
Contact rating
Contacto nominal
AC 250V/5A or DC 30V/5A
C.A. 250V/5A ó C.C. 30V/5A
Isolation
Aislamiento
2kV AC
1
DM9 module
Módulo DM9
(AC digital input)
(Entrada digital C.A. )
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 Dimensions / Dimensiones
3 Installation / Instalación
3
4 wiring / Conexionado
5 Display
MENU
Module X1 7.2
Analog AC Input -DM9No. Mode Status
State01
Status : OFF
Estado: Apagado
4
6 Setup / Configuración
Operating process: / Proceso de programación
→ → →
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Pass word
Admin
ENTER
0001User
Setup
COM1 Port
ESC
Signal Inp uts
DemandRelay Outp uts
Module X1
ENTER
Basic Setup
Module X2
Measure.
Module X1-DM9
ESC EDIT
ModeAnalag AC Input
State No.
01
Module X1-DM9
ESC EDIT
ModeAnalag AC Input
State No.
01
There are two working modes of digital input.
1. State(State monitoring)
2. Spare En(enable spare energy)
Hay 2 modos de trabajo de la entrada digital
1. Estado (monitorización del estado)
2. Ahorro energía habilitado (activación del
modo ahorro de energía)
7 Technical specifications / Especificaciones técnicas
Type / Tipo Wet contact / Contacto húmedo @ 240V AC
Input voltage scale
Escala de la tensión
de entrada
ON:200~270V AC, OFF: <100V AC
Insulation
Aislamiento
2kV AC
1
DM10 module
Módulo DM10
( Profibus-DP)
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
It is recommended to use this module as a reference to the following content.
《AHM3 user manual》
《AHM3 Modbus-RTU user manual》
《Modbus protocol implementation guide over TCP/IP》
Se recomienda el uso de este módulo como referencia al siguiente contenido.
"Manual de usuario AHM3"
"Manual de usuario AHM3 Modbus-RTU"
"Guía de implementación del protocolo Modbus TCP / IP"
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 General
DM10 can extend the communication function of AHM3.
Make AHM3 access PROFIBUS network
Communication based on master-slave principle
Function: P ROFIBUS DP slave
Cyclic data transfer
Automatic detection of baud rate
DM10 aumenta el sistema de comunicaciones del AHM3.
Hacer el acceso a red PROFIBUS para el AHM3
Comunicación basada en el principio maestro-esclavo
Función: PROFIBUS DP esclavo
Transferencia de datos cíclica
Detección automática de la velocidad de transmisión
3
3 Dimensions / Dimensions
4 Installations / Instalación
5 Parameter assignments
Every information frame transfers fixed quantity of user’s data in cyclic
data exchange which is especially suitable for transferring information fast
and continuously.
Cada frame de información transfiere cantidades fijas de los datos de
usuario en intercambio de datos cíclicos que es especialmente adecuado
para la transferencia de información rápida y continua.
4
Effective data types which can be transferred by PROFIBUS are defined
in the GSD file of DM10. Input data contains 224 bytes at most, and output
data contains 2 bytes at most. Three basic data types are pre-defined for
user’s convenience. User also can define other transmission variables
according to practical requirements.
Los tipos de datos eficaces que pueden ser transferidas por PROFIBUS
se definen en el archivo GSD del DM10. Los datos de entrada contiene 224
bytes como máximo, y los datos de salida contiene 2 bytes como máximo.
Tres tipos de datos básicos están predefinidos para la conveniencia del
usuario. El usuario también puede definir otras variables de transmisión de
acuerdo con los requisitos prácticos.
5.1 Basic type 1:/ Básico tipo 1:
Data structure of basic type 1 is fixed and composed of 20-byte input
data and 2-byte output data. The definition of input data is shown in the
following list.
La estructura de datos del tipo básico 1 es fija y compuesta por datos de
entrada de 20 bytes y datos de salida de 2 bytes. La definición de los datos
de entrada se muestra en la siguiente lista.
Byte Data value /Valor Format / Formato Unit /Unidad
0 ~ 3 Status information
Información
Unsigned long
Largo sin signo
4 ~ 7 I1 Float / Flotante A
8 ~ 11 I2 Float / Flotante A
12 ~ 15 I3 Float / Flotante A
16 ~ 19 P Float / Flotante kW
5
5.2 Basic type 2:/ Básico tipo 2:
Basic type 2 is an expansion of basic type 1. The data structure of basic
type 2 is fixed which is composed of 24-byte input data and no output data.
The definition of input data is shown in the following list.
El tipo básico 2 es una expansión de tipo básico 1. La estructura de
datos del tipo básico 2 está fija y se compone de datos de entrada de 24
bytes y no hay datos de salida. La definición de los datos de entrada se
muestra en la siguiente lista.
Byte Data value /Valor Format / Formato Unit /Unidad
0 ~ 3 V12 Float / Flotante V
4 ~ 7 V23 Float / Flotante V
8 ~ 11 V31 Float / Flotante V
12 ~ 15 F Float / Flotante Hz
16 ~ 19 PF Float / Flotante
20 ~ 23 EP+ Float / Flotante kWh
5.3 Basic type 3:/ Tipo básico 3:
The data structure of basic type 3 is fixed which is composed of
128-byte input data and 2-byte output data. The definition of input data is
shown in the following list.
La estructura de datos del tipo básico 3 está fija y se compone de datos
de entrada de 128 bytes y datos de salida de 2 bytes. La definición de los
datos de entrada se muestra en la siguiente lista.
Byte Data value /Valor Format / Formato Unit /Unidad
0 ~ 3 V1 Float / Flotante V
4 ~ 7 V2 Float / Flotante V
8 ~ 11 V3 Float / Flotante V
12 ~ 15 V12 Float / Flotante V
16 ~ 19 V23 Float / Flotante V
20 ~ 23 V31 Float / Flotante V
6
24 ~ 27 I1 Float / Flotante A
28 ~ 31 I2 Float / Flotante A
32 ~ 35 I3 Float / Flotante A
36 ~ 39 In Float / Flotante A
40 ~ 43 P1 Float / Flotante kW
44 ~ 47 P2 Float / Flotante kW
48 ~ 51 P3 Float / Flotante kW
52 ~ 55 PF1 Float / Flotante -
56 ~ 59 PF2 Float / Flotante -
60 ~ 63 PF3 Float / Flotante -
64 ~ 67 F Float / Flotante Hz
68 ~ 71 P Float / Flotante kW
72 ~ 75 Q Float / Flotante kvar
76 ~ 79 S Float / Flotante kVA
80 ~ 83 PF Float / Flotante
84 ~ 87 EP+ Float / Flotante kWh
88 ~ 91 EP- Float / Flotante kWh
92 ~ 95 EQ+ Float / Flotante kvarh
96 ~ 99 EQ- Float / Flotante kvarh
100~103 ES(Apparent Energy) Float / Flotante kVAh
104~107 THD-V1 Float / Flotante 0.01%
108~111 THD-V2 Float / Flotante 0.01%
112~115 THD-V3 Float / Flotante 0.01%
116~119 THD-I1 Float / Flotante 0.01%
120~123 THD-I1 Float / Flotante 0.01%
124~127 THD-I1 Float / Flotante 0.01%
5.4 Custom type: / Tipo personalizado
User can specify single measurement variable for transferring via
7
custom type. Please notice that the data length contains 224 bytes at most
and the data structure should be as follows.
El usuario puede especificar la variable de medida única para la
transferencia a través de tipo personalizado. Tenga en cuenta que la longitud
de datos contiene 224 bytes como máximo y la estructura de datos debe ser
la siguiente.
Byte Data value /Valor Format / Formato Unit /Unidad
0 ~ 3 ··· ··· ···
·
·
·
···
··· ···
220 ~ 223 ··· ··· ···
Please refer to Appendix A for measurement variables which can be selected
by user.
Por favor, consulte el Apéndice A para las variables de medición que pueden
ser seleccionadas por el usuario.
5.5 Operation status information / Información del estado de
funcionamiento
Operation status information which contains four bytes is processed as
static diagnostic data of meter. Operation status information is included in the
data structure of basic type 1. This information is optional in basic type 2 and
basic type 3. User can add this information in configuration.
Data structure of operation status information is shown in the following list.
La información de estado de funcionamiento que contiene cuatro bytes
se procesa como datos de diagnóstico estáticas del medidor. La información
sobre el estado de operación se incluye en la estructura de datos básicos
Tipo 1. Esta información es opcional en básicos Tipo 2 y básicos Tipo 3. El
usuario puede añadir esta información en la configuración.
8
La estructura de datos de información de estado de funcionamiento se
muestra en la siguiente lista.
Byte Bit Description / Descripción
Byte 0
0 0:Import power 1:Export power / 0:E Consumida1: E Generada
1 Reserved / Reservado
2 0:- 1:Over voltage / 0:- 1:Sobretensión
3 0:- 1:Over current / 0:- 1:Sobrecorriente
4 Reserved / Reservado
5 Reserved / Reservado
6 Reserved / Reservado
7 Reserved / Reservado
Byte 1
8 Status of X1 / Estado de X1
9 Status of X2 / Estado de X2
10 Status of X3 / Estado de X3
11 Status of X4 / Estado de X4
12 Reserved / Reservado
13 Reserved / Reservado
14 0:- 1:Built-in relay 1 in remote control / Relé 1 en control remoto
15 0:- 1:Built-in relay 2 in remote control / Relé 1 en control remoto
Byte 2
16 Reserved / Reservado
17 Reserved / Reservado
18 Reserved / Reservado
19 Reserved / Reservado
20 Reserved / Reservado
21 Reserved / Reservado
22 Reserved / Reservado
23 Reserved / Reservado
Byte 3
24 Reserved / Reservado
25 Reserved / Reservado
26 Reserved / Reservado
27 Reserved / Reservado
28 Reserved / Reservado
29 Reserved / Reservado
30 Reserved / Reservado
31 Reserved / Reservado
9
5.6 Control byte / byte de control
Control bytes are used to delete some content of register or remote control
relays.
Control bytes are included in basic type 1 and basic type 3. User can add
control bytes in configuration.
Los Bytes de control se utilizan para eliminar parte del contenido de relés de
registro o control remoto.
Los Bytes de control se incluyen en el básico tipo 1 y tipo 3. El usuario puede
agregar bytes de control de configuración.
Structure of the control bytes: / Estructura de los bytes de control
Byte Bit Activation Description
Byte 0 0 - Reserved
1 Level sensitive 0:Big-endian mode
1:Little-endian mode(Float format)
2 Rising edge
transition
Reset the maximum values
3 Rising edge
transition
Reset the minimum values
4 - Reserved
5 - Reserved
6 Level sensitive 0:OFF 1: ON (Built-in relay output 1)
7 Level sensitive 0:OFF 1: ON (Built-in relay output 2)
Byte 1 8 Level sensitive 0:OFF 1:ON (X1-RO1)
9 Level sensitive 0:OFF 1:ON (X1-RO2)
10 Level sensitive 0:OFF 1:ON (X2-RO1)
11 Level sensitive 0:OFF 1:ON (X2-RO2)
12 Level sensitive 0:OFF 1:ON (X3-RO1)
13 Level sensitive 0:OFF 1:ON (X3-RO2)
14 Level sensitive 0:OFF 1:ON (X4-RO1)
15 Level sensitive 0:OFF 1:ON (X4-RO2)
10
Byte Bit Activación Descripción
Byte 0 0 - Reservado
1 Nivel de sensibilidad 0:Big-endian modo
1:Little-endian modo( flotante)
2 Flanco ascendente Resetear los valores máximos
3 Flanco ascendente Resetear los valores mínimos
4 - Reservado
5 - Reservado
6 Nivel de sensibilidad
0:OFF 1: ON (Salida de relé
incorporado 1)
7 Nivel de sensibilidad 0:OFF 1: ON (Salida de relé
incorporado 2)
Byte 1 8 Nivel de sensibilidad 0:OFF 1:ON (X1-RO1)
9 Nivel de sensibilidad 0:OFF 1:ON (X1-RO2)
10 Nivel de sensibilidad 0:OFF 1:ON (X2-RO1)
11 Nivel de sensibilidad 0:OFF 1:ON (X2-RO2)
12 Nivel de sensibilidad 0:OFF 1:ON (X3-RO1)
13 Nivel de sensibilidad 0:OFF 1:ON (X3-RO2)
14 Nivel de sensibilidad 0:OFF 1:ON (X4-RO1)
15 Nivel de sensibilidad 0:OFF 1:ON (X4-RO2)
6. Operation / Funcionamiento
6.1 AHM3
Disconnect the power supply of AHM3, and then connect DM10 module
to slot X2 (take slot X2 as example).
Connect AHM3 to power supply, and then enter module interface of AHM3 to
check the information of slot X2. If the connection between meter and module
is correct, parameters of DM10 will be shown. Detailed operation process is
shown in the following pictures.
11
Desconecte la fuente de alimentación del AHM3, y luego conectar el
módulo DM10 a la ranura X2 (tomar la ranura X2 como ejemplo).
Conecte el AHM3 a la fuente de alimentación, y luego acceder a la interfaz
del módulo del AHM3 para comprobar la información de la ranura X2 . Si la
conexión entre el medidor y el módulo es correcta, se mostrarán los
parámetros del DM10. El proceso de operación detallada se muestra en las
siguientes imágenes.
→
MENU
7.1Relay Ou tput s
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
→
MENU
7. 3Module X2
Profibus-DP DM10Address 004
→
MENU
7.2Module X1
No ModuleMeasure.
6.2 DP address setup / Configuración de la dirección DP
Every DP instrument needs an only communication address. Please
modify the address of DM10 via the panel of AHM3 transferring data. Detailed
operation process is shown in the following pictures.
Cada instrumento DP necesita una única dirección de comunicación.
Modifique la dirección del DM10 a través del panel de transferencia de datos
del AHM3. El proceso de operación detallada se muestra en las siguientes
imágenes.
→ → →
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
ESC
Enter Password
Admin
ENTER
0001User
Set up
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic Setup
Module X2
Modul e X2-DM10
ESC EDIT
Profibus-DPAddress 004Measure.
After the address is modified, DM10 will re-start, and then new address
will become effective. Please use new address to do the re-configuration of
PROFIBUS DP master.
Después de que la dirección se modifique, El DM10 volverá a iniciarse,
y entonces la nueva dirección comenzará a efectuarse. Por favor, utilice la
nueva dirección para hacer la reconfiguración del PROFIBUS DP.
12
6.3 Configuration / Configuración
Communication model / Modelo de comunicación
A PROFIBUS network model is composed of PC, PLC and AHM3 with
DM10 module. PLC which is DP master accesses AHM3 which is DP slave to
realize data exchange and control output. The model is shown in the following
picture.
Un modelo de red PROFIBUS se compone del PC, PLC y el AHM3 con
su módulo DM10. El PLC tiene acceso a AHM3 que es el esclavo DP para
realizar el intercambio y el control de la salida de datos. El modelo se
muestra en la siguiente imagen.
Configuration PROFIBUS network through STEP 7 and GSD file is
shown as follows. User also can make configuration by using modules and
software from other factories.
La configuración de red PROFIBUS a través del STEP 7 y el archivo
GSD se muestra a continuación. El usuario también puede realizar la
configuración mediante módulos y software de otras fábricas.
Step 1: install GSD file
·Start HW config in SIMATIC Manager.
Paso 1: Instale el archivo GSD
· Iniciar HW config en el administrador SIMATIC.
13
·Select 【Option】 and choose 【Install GSD File】.
·Seleccionar 【Option】 and clickear en 【Install GSD File】.
14
·Select the storage directory of GSD file and Install.
·Seleccionar el directorio de almacenamiento del fichero GSD e
instalarlo.
15
Step 2: Configuration of network.
·Create a PROFIBUS master station
Paso 2: Configuración de la red.
· Crear una estación maestra PROFIBUS
·Add instrument to PROFIBUS master station system 1 from hardware list.
· Añadir el dispositivo al sistema 1 de la estación maestra PROFIBUS de la
lista de hardware.
16
·Select an instrument and input the parameters of instrument to slot.
Seleccione un dispositivo y introduce los parámetros del instrumento a la
ranura.
Download configuration file to PLC after finishing the configuration.
Descargar el archivo de configuración al PLC después de terminar la
configuración.
17
Step 3: Test
· Test data exchanging status in 【OPC Scout】 window.
Paso 3: Test
· El estado del intercambio de los datos en la ventana【OPC Scout】.
7. Technical parameters / Parámetros técnicos
Network interface PROFIBUS
Transmission protocol DP V0
Baud rate 9.6/19.2/45.45/93.73/187.75/500/
1500/3000 (k bps)
Address 1 ~ 127
Insulation voltage 1.5 kV
Working temperature -40 ~ 85
Storage temperature -40 ~ 85 / 0 ~ 95%RH
18
Interfaz de red PROFIBUS
Protocolo de transmisión DP V0
Velocidad de transmisión 9.6/19.2/45.45/93.73/187.75/500/
1500/3000 (k bps)
Dirección 1 ~ 127
Tensión de aislamiento 1.5 kV
Temperatura de trabajo -40 ~ 85
Temperatura de almacenamiento -40 ~ 85 / 0 ~ 95%RH
Appendix A: Measurement variables which can be selected by user are
shown in the following list.
Apéndice A: Las variables de medición que pueden ser seleccionadas por el
usuario se muestran en la siguiente lista.
Data value / Valor Format / Formato Unit / Unidad Description
V1 Float / Flotante V Note 1 / Nota 1
V2 Float / Flotante V
V3 Float / Flotante V
V12 Float / Flotante V
V23 Float / Flotante V
V31 Float / Flotante V
I1 Float / Flotante A
I2 Float / Flotante A
I3 Float / Flotante A
In Float / Flotante A
P1 Float / Flotante kW
P2 Float / Flotante kW
P3 Float / Flotante kW
P Float / Flotante kW
Q1 Float / Flotante kvar
19
Q2 Float / Flotante kvar
Q3 Float / Flotante kvar
Q Float / Flotante kvar
S1 Float / Flotante kVA
S2 Float / Flotante kVA
S3 Float / Flotante kVA
S Float / Flotante kVA
PF1 Float / Flotante
PF2 Float / Flotante
PF3 Float / Flotante
PF Float / Flotante
F Float / Flotante
Average value of Vph-n Float / Flotante V
Average value of Vph-ph Float / Flotante V
Average current Float / Flotante A
Import Active Energy Float / Flotante kWh
Export Active Energy Float / Flotante kWh
Import Reactive Energy Float / Flotante kvarh
Export Reactive Energy Float / Flotante kvarh
Apparent Energy Float / Flotante kVAh
1st Quadrant Reactive
Energy - EQL+
Float / Flotante kvarh
2nd Quadrant Reactive
Energy - EQC+
Float / Flotante kvarh
3rd Quadrant Reactive
Energy - EQL-
Float / Flotante kvarh
4th Quadrant Reactive
Energy - EQC-
Float / Flotante kvarh
Hour meter-EP+ Float / Flotante s
Hour meter-EP- Float / Flotante s
Spare Import Active
Energy
Float / Flotante kWh
Spare Export Active
Energy
Float / Flotante kWh
20
Spare Import Reactive
Energy
Float / Flotante kvarh
Spare Export Reactive
Energy
Float / Flotante kvarh
Spare Apparent Energy Float / Flotante kVAh
Spare Energy - EQL+ Float / Flotante kvarh
Spare Energy - EQC+ Float / Flotante kvarh
Spare Energy - EQL- Float / Flotante kvarh
Spare Energy - EQC- Float / Flotante kvarh
Hour meter - Spare EP+ Float / Flotante s
Hour meter - Spare EP- Float / Flotante s
Total tariff import energy Float / Flotante kWh
Tariff #1 import energy Float / Flotante kWh
Tariff #2 import energy Float / Flotante kWh
Tariff #3 import energy Float / Flotante kWh
Tariff #4 import energy Float / Flotante kWh
Tariff #5 import energy Float / Flotante kWh
Tariff #6 import energy Float / Flotante kWh
Tariff #7 import energy Float / Flotante kWh
Tariff #8 import energy Float / Flotante kWh
Tariff #9 import energy Float / Flotante kWh
Tariff #10 import energy Float / Flotante kWh
Tariff #11 import energy Float / Flotante kWh
Tariff #12 import energy Float / Flotante kWh
Tariff #13 import energy Float / Flotante kWh
Tariff #14 import energy Float / Flotante kWh
Tariff #15 import energy Float / Flotante kWh
Tariff #16 import energy Float / Flotante kWh
Total tariff export energy Float / Flotante kWh
Tariff #1 export energy Float / Flotante kWh
21
Tariff #2 export energy Float / Flotante kWh
Tariff #3 export energy Float / Flotante kWh
Tariff #4 export energy Float / Flotante kWh
Tariff #5 export energy Float / Flotante kWh
Tariff #6 export energy Float / Flotante kWh
Tariff #7 export energy Float / Flotante kWh
Tariff #8 export energy Float / Flotante kWh
Tariff #9 export energy Float / Flotante kWh
Tariff #10 export energy Float / Flotante kWh
Tariff #11 export energy Float / Flotante kWh
Tariff #12 export energy Float / Flotante kWh
Tariff #13 export energy Float / Flotante kWh
Tariff #14 export energy Float / Flotante kWh
Tariff #15 export energy Float / Flotante kWh
Tariff #16 export energy Float / Flotante kWh
Max. value-V1 Float / Flotante V
Max. value-V2 Float / Flotante V
Max. value-V3 Float / Flotante V
Max. value-V12 Float / Flotante V
Max. value-V23 Float / Flotante V
Max. value-V31 Float / Flotante V
Max. value-I1 Float / Flotante A
Max. value-I2 Float / Flotante A
Max. value-I3 Float / Flotante A
Max. value-In Float / Flotante A
Max. value-P1 Float / Flotante kW
Max. value-P2 Float / Flotante kW
Max. value-P3 Float / Flotante kW
22
Max. value-P Float / Flotante kW
Max. value-Q1 Float / Flotante kvar
Max. value-Q2 Float / Flotante kvar
Max. value-Q3 Float / Flotante kvar
Max. value-Q Float / Flotante kvar
Max. value-S1 Float / Flotante kVA
Max. value-S2 Float / Flotante kVA
Max. value-S3 Float / Flotante kVA
Max. value-S Float / Flotante kVA
Max. value-PF Float / Flotante
Max. value-F Float / Flotante
Max. value-Average
Vph-n
Float / Flotante V
Max. value-Average
Vph-ph
Float / Flotante V
Max. value-Average I Float / Flotante V
Min. value-V1 Float / Flotante V
Min. value-V2 Float / Flotante V
Min. value-V3 Float / Flotante V
Min. value-V12 Float / Flotante V
Min. value-V23 Float / Flotante V
Min. value-V31 Float / Flotante V
Min. value-I1 Float / Flotante A
Min. value-I2 Float / Flotante A
Min. value-I3 Float / Flotante A
Min. value-In Float / Flotante A
Min. value-P1 Float / Flotante kW
Min. value-P2 Float / Flotante kW
Min. value-P3 Float / Flotante kW
Min. value-P Float / Flotante kW
23
Min. value-Q1 Float / Flotante kvar
Min. value-Q2 Float / Flotante kvar
Min. value-Q3 Float / Flotante kvar
Min. value-Q Float / Flotante kvar
Min. value-S1 Float / Flotante kVA
Min. value-S2 Float / Flotante kVA
Min. value-S3 Float / Flotante kVA
Min. value-S Float / Flotante kVA
Min. value-PF Float / Flotante
Min. value-F Float / Flotante
Min. value-Average Vph-n Float / Flotante V
Min. value-Average
Vph-ph
Float / Flotante V
Min. value-Average I Float / Flotante V
Max. demand value -I1 Float / Flotante A
Max. demand value -I2 Float / Flotante A
Max. demand value -I3 Float / Flotante A
Max. demand value -P Float / Flotante kW
Max. demand value -Q Float / Flotante kvar
Max. demand value -S Float / Flotante kVA
Present demand value -I1 Float / Flotante A
Present demand value -I2 Float / Flotante A
Present demand value -I3 Float / Flotante A
Present demand value -P Float / Flotante kW
Present demand value -Q Float / Flotante kvar
Present demand value -S Float / Flotante kVA
Previous demand value
-I1
Float / Flotante A
Previous demand value
-I2
Float / Flotante A
Previous demand value
-I3
Float / Flotante A
24
Previous demand value -P Float / Flotante kW
Previous demand value -Q Float / Flotante kvar
Previous demand value -S Float / Flotante kVA
Running status
information Byte[4]
See Data structure
of operation status
list.
Digital input status Byte[4] Note 2
Relay output status Byte[4] Note 3
Phase angle of V1(default
0°)
Float / Flotante °
Phase angle of V2 Float / Flotante °
Phase angle of V3 Float / Flotante °
Phase angle of I1 Float / Flotante °
Phase angle of I2 Float / Flotante °
Phase angle of I3 Float / Flotante °
Positive-sequence
component of voltage
Float / Flotante V
Negative-sequence
component of voltage
Float / Flotante V
Zero-sequence
component of voltage
Float / Flotante V
Unbalance factor of
voltage
Float / Flotante %
Positive-sequence
component of current
Float / Flotante A
Negative-sequence
component of current
Float / Flotante A
Zero-sequence
component of current
Float / Flotante A
Unbalance factor of
current
Float / Flotante
Fundamental value -V1 Float / Flotante %
Fundamental value -V2 Float / Flotante %
Fundamental value -V3 Float / Flotante %
Fundamental value -I1 Float / Flotante %
Fundamental value -I2 Float / Flotante %
Fundamental value -I3 Float / Flotante %
25
Harmonic content -V1 Float / Flotante V
Harmonic content -V2 Float / Flotante V
Harmonic content -V3 Float / Flotante V
Harmonic content -I1 Float / Flotante A
Harmonic content -I2 Float / Flotante A
Harmonic content -I3 Float / Flotante A
Fundamental value -V1 Float / Flotante V
Fundamental value -V2 Float / Flotante V
Fundamental value -V3 Float / Flotante V
Fundamental value -I1 Float / Flotante A
Fundamental value -I2 Float / Flotante A
Fundamental value -I3 Float / Flotante A
2ND harmonic ratio-V1 Float / Flotante %
3rd harmonic ratio-V1 Float / Flotante %
4th harmonic ratio-V1 Float / Flotante %
5th harmonic ratio-V1 Float / Flotante %
6th harmonic ratio-V1 Float / Flotante %
7th harmonic ratio-V1 Float / Flotante %
8th harmonic ratio-V1 Float / Flotante %
9th harmonic ratio-V1 Float / Flotante %
10th harmonic ratio-V1 Float / Flotante %
11th harmonic ratio-V1 Float / Flotante %
12th harmonic ratio-V1 Float / Flotante %
13th harmonic ratio-V1 Float / Flotante %
14th harmonic ratio-V1 Float / Flotante %
15th harmonic ratio-V1 Float / Flotante %
16th harmonic ratio-V1 Float / Flotante %
17th harmonic ratio-V1 Float / Flotante %
26
18th harmonic ratio-V1 Float / Flotante %
19th harmonic ratio-V1 Float / Flotante %
20th harmonic ratio-V1 Float / Flotante %
21th harmonic ratio-V1 Float / Flotante %
22th harmonic ratio-V1 Float / Flotante %
23th harmonic ratio-V1 Float / Flotante %
24th harmonic ratio-V1 Float / Flotante %
25th harmonic ratio-V1 Float / Flotante %
26th harmonic ratio-V1 Float / Flotante %
27th harmonic ratio-V1 Float / Flotante %
28th harmonic ratio-V1 Float / Flotante %
29th harmonic ratio-V1 Float / Flotante %
30th harmonic ratio-V1 Float / Flotante %
31th harmonic ratio-V1 Float / Flotante %
32th harmonic ratio-V1 Float / Flotante %
33th harmonic ratio-V1 Float / Flotante %
34th harmonic ratio-V1 Float / Flotante %
35th harmonic ratio-V1 Float / Flotante %
36th harmonic ratio-V1 Float / Flotante %
37th harmonic ratio-V1 Float / Flotante %
38th harmonic ratio-V1 Float / Flotante %
39th harmonic ratio-V1 Float / Flotante %
40th harmonic ratio-V1 Float / Flotante %
41th harmonic ratio-V1 Float / Flotante %
42th harmonic ratio-V1 Float / Flotante %
43th harmonic ratio-V1 Float / Flotante %
44th harmonic ratio-V1 Float / Flotante %
45th harmonic ratio-V1 Float / Flotante %
27
46th harmonic ratio-V1 Float / Flotante %
47th harmonic ratio-V1 Float / Flotante %
48th harmonic ratio-V1 Float / Flotante %
49th harmonic ratio-V1 Float / Flotante %
50th harmonic ratio-V1 Float / Flotante %
51th harmonic ratio-V1 Float / Flotante %
52th harmonic ratio-V1 Float / Flotante %
53th harmonic ratio-V1 Float / Flotante %
54th harmonic ratio-V1 Float / Flotante %
55th harmonic ratio-V1 Float / Flotante %
56th harmonic ratio-V1 Float / Flotante %
57th harmonic ratio-V1 Float / Flotante %
58th harmonic ratio-V1 Float / Flotante %
59th harmonic ratio-V1 Float / Flotante %
60th harmonic ratio-V1 Float / Flotante %
61th harmonic ratio-V1 Float / Flotante %
62th harmonic ratio-V1 Float / Flotante %
63th harmonic ratio-V1 Float / Flotante %
2nd harmonic ratio-V2 Float / Flotante %
3rd harmonic ratio-V2 Float / Flotante %
4th harmonic ratio-V2 Float / Flotante %
5th harmonic ratio-V2 Float / Flotante %
6th harmonic ratio-V2 Float / Flotante %
7th harmonic ratio-V2 Float / Flotante %
8th harmonic ratio-V2 Float / Flotante %
9th harmonic ratio-V2 Float / Flotante %
10th harmonic ratio-V2 Float / Flotante %
11th harmonic ratio-V2 Float / Flotante %
28
12th harmonic ratio-V2 Float / Flotante %
13th harmonic ratio-V2 Float / Flotante %
14th harmonic ratio-V2 Float / Flotante %
15th harmonic ratio-V2 Float / Flotante %
16th harmonic ratio-V2 Float / Flotante %
17th harmonic ratio-V2 Float / Flotante %
18th harmonic ratio-V2 Float / Flotante %
19th harmonic ratio-V2 Float / Flotante %
20th harmonic ratio-V2 Float / Flotante %
21th harmonic ratio-V2 Float / Flotante %
22th harmonic ratio-V2 Float / Flotante %
23th harmonic ratio-V2 Float / Flotante %
24th harmonic ratio-V2 Float / Flotante %
25th harmonic ratio-V2 Float / Flotante %
26th harmonic ratio-V2 Float / Flotante %
27th harmonic ratio-V2 Float / Flotante %
28th harmonic ratio-V2 Float / Flotante %
29th harmonic ratio-V2 Float / Flotante %
30th harmonic ratio-V2 Float / Flotante %
31th harmonic ratio-V2 Float / Flotante %
32th harmonic ratio-V2 Float / Flotante %
33th harmonic ratio-V2 Float / Flotante %
34th harmonic ratio-V2 Float / Flotante %
35th harmonic ratio-V2 Float / Flotante %
36th harmonic ratio-V2 Float / Flotante %
37th harmonic ratio-V2 Float / Flotante %
38th harmonic ratio-V2 Float / Flotante %
39th harmonic ratio-V2 Float / Flotante %
29
40th harmonic ratio-V2 Float / Flotante %
41th harmonic ratio-V2 Float / Flotante %
42th harmonic ratio-V2 Float / Flotante %
43th harmonic ratio-V2 Float / Flotante %
44th harmonic ratio-V2 Float / Flotante %
45th harmonic ratio-V2 Float / Flotante %
46th harmonic ratio-V2 Float / Flotante %
47th harmonic ratio-V2 Float / Flotante %
48th harmonic ratio-V2 Float / Flotante %
49th harmonic ratio-V2 Float / Flotante %
50th harmonic ratio-V2 Float / Flotante %
51th harmonic ratio-V2 Float / Flotante %
52th harmonic ratio-V2 Float / Flotante %
53th harmonic ratio-V2 Float / Flotante %
54th harmonic ratio-V2 Float / Flotante %
55th harmonic ratio-V2 Float / Flotante %
56th harmonic ratio-V2 Float / Flotante %
57th harmonic ratio-V2 Float / Flotante %
58th harmonic ratio-V2 Float / Flotante %
59th harmonic ratio-V2 Float / Flotante %
60th harmonic ratio-V2 Float / Flotante %
61th harmonic ratio-V2 Float / Flotante %
62th harmonic ratio-V2 Float / Flotante %
63th harmonic ratio-V2 Float / Flotante %
2nd harmonic ratio-V3 Float / Flotante %
3rd harmonic ratio-V3 Float / Flotante %
4th harmonic ratio-V3 Float / Flotante %
5th harmonic ratio-V3 Float / Flotante %
30
6th harmonic ratio-V3 Float / Flotante %
7th harmonic ratio-V3 Float / Flotante %
8th harmonic ratio-V3 Float / Flotante %
9th harmonic ratio-V3 Float / Flotante %
10th harmonic ratio-V3 Float / Flotante %
11th harmonic ratio-V3 Float / Flotante %
12th harmonic ratio-V3 Float / Flotante %
13th harmonic ratio-V3 Float / Flotante %
14th harmonic ratio-V3 Float / Flotante %
15th harmonic ratio-V3 Float / Flotante %
16th harmonic ratio-V3 Float / Flotante %
17th harmonic ratio-V3 Float / Flotante %
18th harmonic ratio-V3 Float / Flotante %
19th harmonic ratio-V3 Float / Flotante %
20th harmonic ratio-V3 Float / Flotante %
21th harmonic ratio-V3 Float / Flotante %
22th harmonic ratio-V3 Float / Flotante %
23th harmonic ratio-V3 Float / Flotante %
24th harmonic ratio-V3 Float / Flotante %
25th harmonic ratio-V3 Float / Flotante %
26th harmonic ratio-V3 Float / Flotante %
27th harmonic ratio-V3 Float / Flotante %
28th harmonic ratio-V3 Float / Flotante %
29th harmonic ratio-V3 Float / Flotante %
30th harmonic ratio-V3 Float / Flotante %
31th harmonic ratio-V3 Float / Flotante %
32th harmonic ratio-V3 Float / Flotante %
33th harmonic ratio-V3 Float / Flotante %
31
34th harmonic ratio-V3 Float / Flotante %
35th harmonic ratio-V3 Float / Flotante %
36th harmonic ratio-V3 Float / Flotante %
37th harmonic ratio-V3 Float / Flotante %
38th harmonic ratio-V3 Float / Flotante %
39th harmonic ratio-V3 Float / Flotante %
40th harmonic ratio-V3 Float / Flotante %
41th harmonic ratio-V3 Float / Flotante %
42th harmonic ratio-V3 Float / Flotante %
43th harmonic ratio-V3 Float / Flotante %
44th harmonic ratio-V3 Float / Flotante %
45th harmonic ratio-V3 Float / Flotante %
46th harmonic ratio-V3 Float / Flotante %
47th harmonic ratio-V3 Float / Flotante %
48th harmonic ratio-V3 Float / Flotante %
49th harmonic ratio-V3 Float / Flotante %
50th harmonic ratio-V3 Float / Flotante %
51th harmonic ratio-V3 Float / Flotante %
52th harmonic ratio-V3 Float / Flotante %
53th harmonic ratio-V3 Float / Flotante %
54th harmonic ratio-V3 Float / Flotante %
55th harmonic ratio-V3 Float / Flotante %
56th harmonic ratio-V3 Float / Flotante %
57th harmonic ratio-V3 Float / Flotante %
58th harmonic ratio-V3 Float / Flotante %
59th harmonic ratio-V3 Float / Flotante %
60th harmonic ratio-V3 Float / Flotante %
61th harmonic ratio-V3 Float / Flotante %
32
62th harmonic ratio-V3 Float / Flotante %
63th harmonic ratio-V3 Float / Flotante %
2nd harmonic ratio-I1 Float / Flotante %
3rd harmonic ratio-I1 Float / Flotante %
4th harmonic ratio-I1 Float / Flotante %
5th harmonic ratio-I1 Float / Flotante %
6th harmonic ratio-I1 Float / Flotante %
7th harmonic ratio-I1 Float / Flotante %
8th harmonic ratio-I1 Float / Flotante %
9th harmonic ratio-I1 Float / Flotante %
10th harmonic ratio-I1 Float / Flotante %
11th harmonic ratio-I1 Float / Flotante %
12th harmonic ratio-I1 Float / Flotante %
13th harmonic ratio-I1 Float / Flotante %
14th harmonic ratio-I1 Float / Flotante %
15th harmonic ratio-I1 Float / Flotante %
16th harmonic ratio-I1 Float / Flotante %
17th harmonic ratio-I1 Float / Flotante %
18th harmonic ratio-I1 Float / Flotante %
19th harmonic ratio-I1 Float / Flotante %
20th harmonic ratio-I1 Float / Flotante %
21th harmonic ratio-I1 Float / Flotante %
22th harmonic ratio-I1 Float / Flotante %
23th harmonic ratio-I1 Float / Flotante %
24th harmonic ratio-I1 Float / Flotante %
25th harmonic ratio-I1 Float / Flotante %
26th harmonic ratio-I1 Float / Flotante %
27th harmonic ratio-I1 Float / Flotante %
33
28th harmonic ratio-I1 Float / Flotante %
29th harmonic ratio-I1 Float / Flotante %
30th harmonic ratio-I1 Float / Flotante %
31th harmonic ratio-I1 Float / Flotante %
32th harmonic ratio-I1 Float / Flotante %
33th harmonic ratio-I1 Float / Flotante %
34th harmonic ratio-I1 Float / Flotante %
35th harmonic ratio-I1 Float / Flotante %
36th harmonic ratio-I1 Float / Flotante %
37th harmonic ratio-I1 Float / Flotante %
38th harmonic ratio-I1 Float / Flotante %
39th harmonic ratio-I1 Float / Flotante %
40th harmonic ratio-I1 Float / Flotante %
41th harmonic ratio-I1 Float / Flotante %
42th harmonic ratio-I1 Float / Flotante %
43th harmonic ratio-I1 Float / Flotante %
44th harmonic ratio-I1 Float / Flotante %
45th harmonic ratio-I1 Float / Flotante %
46th harmonic ratio-I1 Float / Flotante %
47th harmonic ratio-I1 Float / Flotante %
48th harmonic ratio-I1 Float / Flotante %
49th harmonic ratio-I1 Float / Flotante %
50th harmonic ratio-I1 Float / Flotante %
51th harmonic ratio-I1 Float / Flotante %
52th harmonic ratio-I1 Float / Flotante %
53th harmonic ratio-I1 Float / Flotante %
54th harmonic ratio-I1 Float / Flotante %
55th harmonic ratio-I1 Float / Flotante %
34
56th harmonic ratio-I1 Float / Flotante %
57th harmonic ratio-I1 Float / Flotante %
58th harmonic ratio-I1 Float / Flotante %
59th harmonic ratio-I1 Float / Flotante %
60th harmonic ratio-I1 Float / Flotante %
61th harmonic ratio-I1 Float / Flotante %
62th harmonic ratio-I1 Float / Flotante %
63th harmonic ratio-I1 Float / Flotante %
2nd harmonic ratio-I2 Float / Flotante %
3rd harmonic ratio-I2 Float / Flotante %
4th harmonic ratio-I2 Float / Flotante %
5th harmonic ratio-I2 Float / Flotante %
6th harmonic ratio-I2 Float / Flotante %
7th harmonic ratio-I2 Float / Flotante %
8th harmonic ratio-I2 Float / Flotante %
9th harmonic ratio-I2 Float / Flotante %
10th harmonic ratio-I2 Float / Flotante %
11th harmonic ratio-I2 Float / Flotante %
12th harmonic ratio-I2 Float / Flotante %
13th harmonic ratio-I2 Float / Flotante %
14th harmonic ratio-I2 Float / Flotante %
15th harmonic ratio-I2 Float / Flotante %
16th harmonic ratio-I2 Float / Flotante %
17th harmonic ratio-I2 Float / Flotante %
18th harmonic ratio-I2 Float / Flotante %
19th harmonic ratio-I2 Float / Flotante %
20th harmonic ratio-I2 Float / Flotante %
21th harmonic ratio-I2 Float / Flotante %
35
22th harmonic ratio-I2 Float / Flotante %
23th harmonic ratio-I2 Float / Flotante %
24th harmonic ratio-I2 Float / Flotante %
25th harmonic ratio-I2 Float / Flotante %
26th harmonic ratio-I2 Float / Flotante %
27th harmonic ratio-I2 Float / Flotante %
28th harmonic ratio-I2 Float / Flotante %
29th harmonic ratio-I2 Float / Flotante %
30th harmonic ratio-I2 Float / Flotante %
31th harmonic ratio-I2 Float / Flotante %
32th harmonic ratio-I2 Float / Flotante %
33th harmonic ratio-I2 Float / Flotante %
34th harmonic ratio-I2 Float / Flotante %
35th harmonic ratio-I2 Float / Flotante %
36th harmonic ratio-I2 Float / Flotante %
37th harmonic ratio-I2 Float / Flotante %
38th harmonic ratio-I2 Float / Flotante %
39th harmonic ratio-I2 Float / Flotante %
40th harmonic ratio-I2 Float / Flotante %
41th harmonic ratio-I2 Float / Flotante %
42th harmonic ratio-I2 Float / Flotante %
43th harmonic ratio-I2 Float / Flotante %
44th harmonic ratio-I2 Float / Flotante %
45th harmonic ratio-I2 Float / Flotante %
46th harmonic ratio-I2 Float / Flotante %
47th harmonic ratio-I2 Float / Flotante %
48th harmonic ratio-I2 Float / Flotante %
49th harmonic ratio-I2 Float / Flotante %
36
50th harmonic ratio-I2 Float / Flotante %
51th harmonic ratio-I2 Float / Flotante %
52th harmonic ratio-I2 Float / Flotante %
53th harmonic ratio-I2 Float / Flotante %
54th harmonic ratio-I2 Float / Flotante %
55th harmonic ratio-I2 Float / Flotante %
56th harmonic ratio-I2 Float / Flotante %
57th harmonic ratio-I2 Float / Flotante %
58th harmonic ratio-I2 Float / Flotante %
59th harmonic ratio-I2 Float / Flotante %
60th harmonic ratio-I2 Float / Flotante %
61th harmonic ratio-I2 Float / Flotante %
62th harmonic ratio-I2 Float / Flotante %
63th harmonic ratio-I2 Float / Flotante %
2nd harmonic ratio-I3 Float / Flotante %
3rd harmonic ratio-I3 Float / Flotante %
4th harmonic ratio-I3 Float / Flotante %
5th harmonic ratio-I3 Float / Flotante %
6th harmonic ratio-I3 Float / Flotante %
7th harmonic ratio-I3 Float / Flotante %
8th harmonic ratio-I3 Float / Flotante %
9th harmonic ratio-I3 Float / Flotante %
10th harmonic ratio-I3 Float / Flotante %
11th harmonic ratio-I3 Float / Flotante %
12th harmonic ratio-I3 Float / Flotante %
13th harmonic ratio-I3 Float / Flotante %
14th harmonic ratio-I3 Float / Flotante %
15th harmonic ratio-I3 Float / Flotante %
37
16th harmonic ratio-I3 Float / Flotante %
17th harmonic ratio-I3 Float / Flotante %
18th harmonic ratio-I3 Float / Flotante %
19th harmonic ratio-I3 Float / Flotante %
20th harmonic ratio-I3 Float / Flotante %
21th harmonic ratio-I3 Float / Flotante %
22th harmonic ratio-I3 Float / Flotante %
23th harmonic ratio-I3 Float / Flotante %
24th harmonic ratio-I3 Float / Flotante %
25th harmonic ratio-I3 Float / Flotante %
26th harmonic ratio-I3 Float / Flotante %
27th harmonic ratio-I3 Float / Flotante %
28th harmonic ratio-I3 Float / Flotante %
29th harmonic ratio-I3 Float / Flotante %
30th harmonic ratio-I3 Float / Flotante %
31th harmonic ratio-I3 Float / Flotante %
32th harmonic ratio-I3 Float / Flotante %
33th harmonic ratio-I3 Float / Flotante %
34th harmonic ratio-I3 Float / Flotante %
35th harmonic ratio-I3 Float / Flotante %
36th harmonic ratio-I3 Float / Flotante %
37th harmonic ratio-I3 Float / Flotante %
38th harmonic ratio-I3 Float / Flotante %
39th harmonic ratio-I3 Float / Flotante %
40th harmonic ratio-I3 Float / Flotante %
41th harmonic ratio-I3 Float / Flotante %
42th harmonic ratio-I3 Float / Flotante %
43th harmonic ratio-I3 Float / Flotante %
38
44th harmonic ratio-I3 Float / Flotante %
45th harmonic ratio-I3 Float / Flotante %
46th harmonic ratio-I3 Float / Flotante %
47th harmonic ratio-I3 Float / Flotante %
48th harmonic ratio-I3 Float / Flotante %
49th harmonic ratio-I3 Float / Flotante %
50th harmonic ratio-I3 Float / Flotante %
51th harmonic ratio-I3 Float / Flotante %
52th harmonic ratio-I3 Float / Flotante %
53th harmonic ratio-I3 Float / Flotante %
54th harmonic ratio-I3 Float / Flotante %
55th harmonic ratio-I3 Float / Flotante %
56th harmonic ratio-I3 Float / Flotante %
57th harmonic ratio-I3 Float / Flotante %
58th harmonic ratio-I3 Float / Flotante %
59th harmonic ratio-I3 Float / Flotante %
60th harmonic ratio-I3 Float / Flotante %
61th harmonic ratio-I3 Float / Flotante %
62th harmonic ratio-I3 Float / Flotante %
63th harmonic ratio-I3 Float / Flotante %
Pulse counter:X1-DI1 Long Note 4
Pulse counter:X1-DI2 Long
Pulse counter:X1-DI3 Long
Pulse counter:X1-DI4 Long
Pulse counter:X2-DI1 Long
Pulse counter:X2-DI2 Long
Pulse counter:X2-DI3 Long
Pulse counter:X2-DI4 Long
39
Pulse counter:X3-DI1 Long
Pulse counter:X3-DI2 Long
Pulse counter:X3-DI3 Long
Pulse counter:X3-DI4 Long
Pulse counter:X4-DI1 Long
Pulse counter:X4-DI2 Long
Pulse counter:X4-DI3 Long
Pulse counter:X4-DI4 Long
Note 1: float type data format
Float type data format is defined by the first bit of control byte with two options which
are big-endian mode and little-endian mode. It is defaulted as big-endian mode.
E.g.
Storage Phase voltage value V1 in the internal memories of PLC which are PIB260,
PIB261,PIB262 and PIB263,
V1 = 222.7, V=0x435EB333
For big-endian mode, PIB260=0x43,PIB261=0x5E,PIB262=0xB3,PIB263=0x33;
For little-endian mode, PIB260=0x33,PIB261=0xB3,PIB262=0x5E,PIB263=0x43;
Note 1: Formato de datos tipo flotante
El formato de datos tipo flotante está definido por el primer bit del byte de control
con dos opciones, que son el modo big-endian y el modo little-endian. Por defecto está el
modo biig-endian.
E.g.
Almacenar el valor de la tensión de fase V1 en la memoria interna del PLC que son
PIB260,PIB261,PIB262 y PIB263,
V1 = 222.7, V=0x435EB333
Para el modo big-endian, PIB260=0x43 , PIB261=0x5E , PIB262=0xB3 ,
PIB263=0x33;
Para el modo little-endian, PIB260=0x33 , PIB261=0xB3 , PIB262=0x5E ,
PIB263=0x43;
40
Note 2: Structure of the digital input status (0:OFF,1:ON)
Nota 2: Estructura del estado de la entrada digital (0:OFF,1:ON)
Byte Bit Description / Descrición
Byte 0
0 X1-DI1
1 X1-DI2
2 X1-DI3
3 X1-DI4
4 X2-DI1
5 X2-DI2
6 X2-DI3
7 X2-DI4
Byte 1
8 X3-DI2
9 X3-DI3
10 X3-DI4
11 X3-DI2
12 X4-DI2
13 X4-DI3
14 X4-DI4
15 X4-DI2
Byte 2
16 Reserved / Reservado
17 Reserved / Reservado
18 Reserved / Reservado
19 Reserved / Reservado
20 Reserved / Reservado
21 Reserved / Reservado
22 Reserved / Reservado
23 Reserved / Reservado
Byte 3
24 Reserved / Reservado
25 Reserved / Reservado
26 Reserved / Reservado
27 Reserved / Reservado
28 Reserved / Reservado
29 Reserved / Reservado
30 Reserved / Reservado
41
31 Reserved / Reservado
Note 3: Structure of the relay output status(0:OFF,1:ON)
Nota 3: Estructura del estado del relé (0:OFF,1:ON)
Byte Bit Description / Descripción
Byte 0
0 Built-in relay output 1
1 Built-in relay output 2
2 X1-RO1
3 X1-RO2
4 X2-RO1
5 X2-RO2
6 X3-RO1
7 X3-RO2
Byte 1
8 X4-RO1
9 X4-RO2
10 Reserved
11 Reserved / Reservado
12 Reserved / Reservado
13 Reserved / Reservado
14 Reserved / Reservado
15 Reserved / Reservado
Byte 2
16 Reserved / Reservado
17 Reserved / Reservado
18 Reserved / Reservado
19 Reserved / Reservado
20 Reserved / Reservado
21 Reserved / Reservado
22 Reserved / Reservado
23 Reserved / Reservado
Byte 3
24 Reserved / Reservado
25 Reserved / Reservado
26 Reserved / Reservado
27 Reserved / Reservado
28 Reserved / Reservado
29 Reserved / Reservado
30 Reserved / Reservado
42
31 Reserved / Reservado
Note 4: 32-bit unsigned long type data format
Unsigned long type data format is defined by the first bit of control byte with two
options which are big-endian mode and little-endian mode.
E.g.
Storage X1 which is the first pulse counting value in the internal memories of PLC
which are PIB264,PIB265,PIB266 and PIB267.
Pulse counting value = 32580000 = 0x01F121A0
For big-endian mode, PIB264=0x01,PIB265=0xF1,PIB266=0x21,PIB267=0xA0;
For little-endian mode, PIB264=0xA0,PIB265=0x21,PIB266=0xF1,PIB267=0x01;
Nota 4: Formato de datos de 32-bit long sin signo
Formato de datos de 32-bit long sin signo está definido por el primer bit del byte de control
con las dos opciones que son el modo big-endian y el modo little-endian .
E.g.
Almacenar X1 que es el primer valor de pulso en la memoria interna del PLC que son
PIB264,PIB265,PIB266 y PIB267.
Valor del pulso = 32580000 = 0x01F121A0
Para el modo big-endian, PIB264=0x01 , PIB265=0xF1 , PIB266=0x21 ,
PIB267=0xA0;
Para el modo little-endian, PIB264=0xA0 , PIB265=0x21 , PIB266=0xF1 ,
PIB267=0x01;
1
DM11module
Módulo DM11
( Ethernet )
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
It is recommended to use this module as a reference to the following content.
《AHM3 user manual》
《AHM3 Modbus-RTU user manual》
《Modbus protocol implementation guide over TCP/IP》
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 General
DM11 can extend the communication function of AHM3.
. A 10M to 100M RJ45 network interface
.Support 802.3 standard Ethernet frame format
.Working mode:TCP Server
.Support DHCP automatically obtain IP
.Pre-programmed Globally Unique, Node MAC Address
.Support standard Modbus-TCP protocol
.Network anomalies automatically disconnect ensure reliable TCP connection
DM11 puede extender la función de comunicación del AHM3.
. De 10M a 100M RJ45 interfaz de red
.Soporte 802.3 estándar Ethernet con formato de marco
.Modo de trabajo: servidor TCP
.Soporte de DHCP obtiene automáticamente la IP
.Pre-programado único global: dirección MAC del nodo
.Soporte estándar protocol Modbus-TCP
.Las anomalías de red producen la desconexión automática, asegurarse de
una conexión TDP fiable.
3
3 Dimensions / Dimensiones
4 Installation / Instalación
5 Operation / Operación
5.1 Connect to AHM3 / Conexión al AHM3
Disconnect the power supply of AHM3, and then connect DM11 module
to slot X2 (take slot X2 as example).
Connect AHM3 to power supply, and then enter module interface of
AHM3 to check the information of slot X2. If the connection between meter
4
and module is correct, parameters of DM11 will be shown. Detailed operation
process is shown in the following pictures.
→
MENU
7.3Module X2
TCP/IP DM11DHCP OFFPort 00502IP 010.002.00 4.239MASK 255.255.255.000GW 010.002.00 4.001MAC 00.04.A3.E6 .80.4F
MENU
7.1Relay Outputs
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
MENU
7.2Module X1No Module
→ →
Measure.
Following parameters are used in this manual for ease of presentation.
Port = “502”
Local IP = “10.2.4.239”
Subnet mask = “255.255.255.0”
Gateway = “10.2.4.1”
Desconecte la fuente de alimentación de AHM3 y después conectar el
módulo DM11 a la ranura X2 (tomar la ranura X2 como un ejemplo).
Conectar el AHM3 a la fuente de alimentación y luego entrar en la
interfaz del módulo del AHM3 para comprobar la información de la ranura X2.
Si la conexión entre el medidor y el módulo es correcta, se mostrarán
parámetros en el DM11. El proceso de operación detallado se muestras en
las siguientes imágenes.
→
MENU
7.3Module X2
TCP/IP DM11DHCP OFFPort 00502IP 010.002.00 4.239MASK 255.255.255.000GW 010.002.00 4.001MAC 00.04.A3.E6 .80.4F
MENU
7.1Relay Outputs
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
MENU
7.2Module X1No Module
→ →
Measure.
Los siguientes parámetros se usan en este manual para facilitar la
presentación.
Puerto = “502”
Dirección local IP = “10.2.4.239”
Máscara de subred = “255.255.255.0”
Entrada = “10.2.4.1”
5
5.2 Parameters configuration / Configuración de parámetros
5.2.1 Communication model / Modelo de comunicación
AHM3 equipped with DM11 module is used as server in a LAN built on
switch or router. PC or other equipment with Ethernet is used as client to
access server to realize data exchanging and relative control output. The
model is shown in the following picture.
El AHM3 equipado con un módulo DM11 es usado como servidor en una
LAN basada en un interruptor o router. Un PC u otro equipo con Ethernet se
usa como cliente para acceder al servidor y realizar el intercambio de datos y
la salida de control relativo. Este modelo es el mostrado en la imagen.
5.2.2 Module configuration through the panel of AHM3 /
Configuración del módulo a través del panel AHM3
Communication parameters of DM11 such as DHCP, Port, Local IP, Subnet
mask and Gateway are configured through the panel of AHM3. The operation
process is shown in the following picture.
→ → →
EnergyHarmonic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Info
MENU
t ESC
Enter Password
Admin
ENTER
000
MENU
7.3Module X2TCP/IP DM11
OFFPort 00502IP 010.002.004.239MASK 255.255.255.000GW 010.002.004.001MAC 00.04.A3.E6.80.4F
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic SetupMeasure.
Setup
User 1
Module X2
DHCP
DM11 will re-start after the configuration is finished. It is suggested to
6
wait for three seconds and return to module display interface and check
whether the configuration is correct, see 5.1 operation.
DHCP
If switch or router is equipped with DHCP function, the DHCP of DM11
can be set as Enable to realize automatic address assignment. The operation
process is shown in the following picture.
→ →
t ESC
Enter Passwo rd
Admin
ENTER
000
MENU
7.3Module X2
TCP/IP DM1 1ON
Port 00502IP 010.002.003.1 01MASK 255.255.000.0 00GW 010.002.003.0 04MAC 00.04.A3.E6.80. 4F
Setup
COM1 Por t
ESC
Signal Inpu ts
DemandRelay Outpu ts
Module X 1
ENTER
Basic Setu p
User 1
Module X 2
DHCP
→
EnergyHarmoni c
ENTER
Qualit yDemand
ModuleMax/Mi n
EventsDev.Inf o
MENU
Setup
Measure .
If IP address is automatically assigned through DHCP, the parameters of
Local IP, Subnet mask and Gateway can not be set by manual.
After the configuration is finished, return to module display interface to
check dynamic assignment address. See operation process 4.1.
Los parámetros de comunicación del DM11 tales como el DHCP, el Puerto, la
dirección local IP, la máscara de subred y la entrada se configuran a través
del panel del AHM3. El proceso de operación se muestra en la siguiente
figura.
→ → →
EnergyHarmonic
ENTER
QualityDemand
ModuleMax/Min
EventsDev.Info
MENU
t ESC
Enter Password
Admin
ENTER
000
MENU
7.3Module X2TCP/IP DM11
OFFPort 00502IP 010.002.004.239MASK 255.255.255.000GW 010.002.004.001MAC 00.04.A3.E6.80.4F
Setup
COM1 Port
ESC
Signal Inputs
DemandRelay Outputs
Module X1
ENTER
Basic SetupMeasure.
Setup
User 1
Module X2
DHCP
DM11 se reiniciará después de terminar la configuración. Se recomienda
esperar tres segundos y luego volver a la interfaz del módulo para comprobar
si la configuración es correcta, véase el proceso 5.1.
DHCP
Si el interruptor o el router están equipados con la función DHCP, el
DHCP del DM11 puede ser configurado como Enable para realizer la
7
asignación automática de direcciones. El proceso de operación se muestra
en la siguiente figura.
→ →
t ESC
Enter Passwo rd
Admin
ENTER
000
MENU
7.3Module X2
TCP/IP DM1 1ON
Port 00502IP 010.002.003.1 01MASK 255.255.000.0 00GW 010.002.003.0 04MAC 00.04.A3.E6.80. 4F
Setup
COM1 Por t
ESC
Signal Inpu ts
DemandRelay Outpu ts
Module X 1
ENTER
Basic Setu p
User 1
Module X 2
DHCP
→
EnergyHarmoni c
ENTER
Qualit yDemand
ModuleMax/Mi n
EventsDev.Inf o
MENU
Setup
Measure .
Si la dirección IP es asignada automáticamente a través del DHCP, los
parámetros de la dirección local IP, la máscara de subred y la entrada no
pueden configurarse de manera manual.
Después de terminar la configuración, hay que volver a la interfaz de
visualización del módulo para comprobar la asignación dinámica de
direcciones. véase el proceso 4.1.
5.2.3 Configure parameters of DM11 module through special software
/ Configuración de parámetros del DM11 a través de un software
especial.
Configure the parameters of DM11 module through special software for
AHM3. AHM3 is equipped with a RS485 interface. It is connected to PC
through RS232 (or USB)/RS485 conversion device. See the following picture.
Step1: Set serial communication
Click Setting menu and select Serial Port Setup
8
Step2: Connection test
Set communication address of AHM3 in Address item on the upper right
part of PC window.
Select Basic Setup item, and then click Upload button on the lower right
part of PC window. If Succeed in upload appears, that means serial
communication is normal. In this condition, DM11 module appears in X2 slot.
Step3: Change parameters
Click Communication item, and then select TCP/IP item to change
relative parameters. At last, click Download button on the lower right part of
PC window.
9
DM11 will re-start after the setting is finished. It is suggested to operate
AHM3 after three seconds and return to module display interface and verify
the setting. See operation process 5.1.
Configuración de los parámetros del módulo DM11 a través de un
software especial para el AHM3. El AHM3 está equipado con una interfaz
RS485. Este va conectado a un PC a través de un dispositivo de conversión
RS232 (o USB)/RS485. Véase la siguiente imagen.
Paso 1: Establecer comunicación de serie
Cliquear en setting menu y seleccionar Serial Port Setup
10
Paso 2: Test de conexión.
Establecer la dirección de comunicación del AHM3 en la pestaña
Address situada en la parte derecha superior de la ventana del PC.
Seleccionar Basic Setup, y cliquear en el botón Upload en la parte
derecho inferior de la ventana. Si aparece la palabra Succeed, la
comunicación es normal Bajo esta condición, el módulo DM11 aparece en la
ranura X2.
11
Paso 3: Cambio de parámetros.
Cliquear en Communication y después seleccionar TCP/IP para cambiar
los parámetros reelativos. Para terminar, cliquear en el botón Download en la
parte inferior derecho de la pantalla.
DM11 se reiniciará después de que termine el ajuste. Se recomienda
operar el AHM3 después de tres segundos y volver a la interfaz de
visualización del módulo y verificar el ajuste. Véase el proceso de operación
5.1.
5.2.3 Test / Test
. Ping
In communication model, PC executes ping command to check whether
AHM3 is connected to LAN correctly and verify the configuration parameters.
The operation process is shown in the following picture.
12
. Modbus/TCP
In communication model, the correctness and reliability of
communication are checked by PC through Modbus/TCP test software such
as Modbus-Poll.
Open Modbus-Poll, click Connection, and then set relative parameters of
AHM3. Click Setup, and set Modbus/TCP command, address and number of
register.
Please refer to AHM3 user manual for communication register address
list.
13
14
. Ping
En el modelo de comunicación, el ordenador ejecuta el comando ping
para comprobar si el AHM3 está conectado a LAN correctamente y verificar
los parámetros de configuración. El proceso de operación se muestra en la
siguiente imagen.
15
. Modbus/TCP
En el modelo de comunicación la exactitude y fiabilidad de la
comunicación son controlados por el PC a través del software de prueba
Modbus/TCP como Modbus-Poll.
Para abrir Modbus-Poll, cliquear en Connection, y después configure los
parámetros relativos de AHM3. Cliquear en Setup, y configurar los
commandos, dirección y número de registro del Modbus..
Por favor consulte el manual de usuario AHM3 para el registro de la lista
de direcciones de comunicación.
16
17
6 Technical specifications / Especificaciones
técnicas
Interface RJ45 (10M to 100M)
Frame format IEEE 802.3
Working mode Server
MAC IEEE certification,Globally Unique
IP Static set or DHCP
Protocol Modbus-TCP
Insulation 1.5 kV
Working temperature -10 ~ 60ºC
Storage environment -25 ~ 70ºC, ≤95%RH
18
Interfaz RJ45 (10M a 100M)
Formato de frame IEEE 802.3
Modo de trabajo Servidor
MAC IEEE certification,Globally Unique
IP Static set or DHCP
Protocolo Modbus-TCP
Aislamiento 1.5 kV
Temperatura de trabajo -10 ~ 60ºC
Temperatura de
almacenamiento -25 ~ 70ºC, ≤95%RH
1
DM12 module
Módulo DM12
( WiFi )
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
It is recommended to use this module as a reference to the following content.
《AHM3 user manual》
《AHM3 Modbus-RTU user manual》
《Modbus protocol implementation guide over TCP/IP》
Se recomienda el uso de este módulo como referencia para el siguiente
contenido.
(AHM3 manual de usuario)
(AHM3 Modbus-RTU manual de usuario)
(Guía Modbusde protocol de implementación a través de TCP/IP)
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 General / General
DM12 can extend the communication function of AHM3.
. Support 802.11 b/g/n
. working mode :TCP Server
. Support DHCP automatically obtain IP
. Pre-programmed Globally Unique, Node MAC Address
.Support standard Modbus-TCP protocol
.Network anomalies automatically disconnect,ensure reliable TCP connection
DM12 extiende la función de comunicación del AHM3.
.Soporte 802.11 b/g/n
.Modo de trabajo:servidor TCP
.Soporte de DHCP obtiene automáticamente la IP
3
.Pre-programado único global: dirección MAC del nodo
.Soporte estándar protocolo Modbus-TCP
.Las anomalías de red producen la desconexión automática, asegurarse de
una conexión TDP fiable.
3 Dimensions / Dimensiones
4 Installation / Instalación
5 Operation / Operación
Connect to AHM3 / Conexión a AHM3
Disconnect the power supply of AHM3, and then connect DM12 module
to slot X2 (take slot X2 as example).
4
Connect AHM3 to power supply, and then enter module interface of
AHM3 to check the information of slot X2. If the connection between meter
and module is correct, parameters of DM12 will be shown. Detailed operation
process is shown in the following pictures.
→
MENU
7.1Relay Outputs
Relay Outpu tsNo.0102
ModeE Puls eAlarm
Status
FREE
EnergyHarmoni c
ENTER
SetupQualit yDemand
Max/Mi n
EventsDev.Inf o
MENU
→
MENU
7.3Module X2WiFi DM1 2
DHCP OFFPort 00502IP 192.168.1.1 00MASK 255.255.255 .0GW 192.168.1. 1MAC C8.93.46.43.CE. 15
→
MENU
7.2Module X1No Modul e
Measure .Module
Following parameters are used in this manual for ease of presentation.
Port = “502”
Local IP = “192.168.1.100”
Subnet mask = “255.255.255.0”
Gateway = “192.168.1.1”
Desconecte la fuente de alimentación de AHM3 y después conectar el
módulo DM12 a la ranura X2 (tomar la ranura X2 como un ejemplo).
Conectar el AHM3 a la fuente de alimentación y luego entrar en la
interfaz del módulo del AHM3 para comprobar la información dela ranura X2.
Si la conexión entre el Contador y el módulo es correcta, se mostrarán
parámetros en el DM12. El proceso de operación detallado se muestras en
las siguientes imágenes.
→
MENU
7.3Module X2
TCP/IP DM11DHCP OFFPort 00502IP 010.002.00 4.239MASK 255.255.255.000GW 010.002.00 4.001MAC 00.04.A3.E6 .80.4F
MENU
7.1Relay Outputs
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
MENU
7.2Module X1No Module
→ →
Measure.
Los siguientes parámetros se usan en este manual para facilitar la
presentación.
Puerto = “502”
Dirección local IP = “192.168.1.100”
Máscara de subred = “255.255.255.0”
5
Entrada = “192.168.1.1”
6 Setup / Configuración
AHM3 equipped with DM12 module is used as server in a LAN built on
wireless router. PC or other equipment is used as client to access server to
realize data exchanging and relative control output. The model is shown in
the following picture.
Configure parameters of DM12 module through special software
Configure the parameters of DM12 module through special software for
AHM3. AHM3 is equipped with a RS485 interface. It is connected to PC
through RS232 (or USB)/RS485 conversion device. See the following picture.
AHM3 equipado con un módulo DM12 es usado como servidor en una
LAN basada en un interruptor o router. PC u otro equipo se usa como cliente
para acceder al servidor y realizar el intercambio de datos y la salida de
control relativo. Este modelo se muestra en la imagen.
6
Configuración de parámetros del módulo DM12 a través de un software
especial
La configuración de parámetros del módulo DM12 a través de un
software especial para AHM3. AHM3 está equipado con una interfaz RS485.
Se conecta a un PC a través de un dispositivo de conversión RS232 (o
USB)/RS485. Véase la siguiente imagen.
Step1: Set serial communication
Click Setting menu and select Serial Port Setup
7
Step2: Connection test
Set communication address of AHM3 in Address item on the upper right
part of PC window.
Select Basic Setup item, and then click Upload button on the lower right
part of PC window. If Succeed in upload appears, that means serial
communication is normal. In this condition, DM12 module appears in X2 slot.
Step3: Change parameters
Click Communication item, and then select WiFi item to change relative
parameters. At last, click Download button on the lower right part of PC
window.
8
DM12 will re-start after the setting is finished. It is suggested to operate
AHM3 after three seconds and return to module display interface and verify
the setting. See operation process 5.
Paso 1: Establecer comunicación de serie
Cliquear en setting menu y seleccionar Serial Port Setup
9
Paso 2: Test de conexión.
Establecer la dirección de comunicación del AHM3 en la pestaña
Address situada en la parte derecha superior de la ventana del PC.
Seleccionar Basic Setup, y cliquear en el botón Upload en la parte
derecho inferior de la ventana. Si aparece la palabra Succeed, la
comunicación es normal Bajo esta condición, el módulo DM12 aparece en la
ranura X2.
Paso 3: Cambio de parámetros.
Cliquear en Communication y después seleccionar Wifi para cambiar los
parámetros reelativos. Para terminar, cliquear en el botón Download en la
parte inferior derecho de la pantalla.
10
DM12 se reiniciará después de que termine el ajuste. Se recomienda
operar el AHM3 después de tres segundos y volver a la interfaz de
visualización del módulo y verificar el ajuste. Véase el proceso de operación
5.
DM12 parameters list:
Function Default setup
DHCP Use DHCP service to get local
IP address
Disable
Connecting mode TCP work in Server mode Server (Read only)
Port Modbus-TCP Port Number 502
Local IP Module's static IP address Example:192.168.1.20
Remote IP not use not use
Subnet mask Example:255.255.255.0
Gateway Example:192.168.1.1
MAC address ( Read only )
11
WiFi mode WIFI work mode Station ( Read only )
SSID WIFI network name Example: AHM3TEST
Security mode 0: WEP
1: WPA / WPA2 PSK
2: null
WPA / WPA2 PSK
WEP key length 13 ASCII
IO1 not use NULL
WEP key Example: 123456
WAP/WAP2 key Example: 123456
Firmware version Module's firmware version ( Read only )
Lista de parámetros del DM12:
Función Configuración por defecto
DHCP Uso del servicio DHCP para
obtener la dirección local IP
Inhabilitado
Modo de conexión TCP trabaja en modo servidor Servidor (solo lectura)
Puerto Modbus-TCP Número de
puerto
502
IP Local Dirección IP del Módulo
estático
Ejemplo:192.168.1.20
IP Remota Sin uso Sin uso
Máscara de subred Ejemplo:255.255.255.0
Entrada Ejemplo:192.168.1.1
Dirección MAC (Solo lectura )
Modo WiFi Modo de trabajo WIFI Estación (solo lectura)
SSID Red de trabajo WIFI Ejemplo: AHM3TEST
Modo de seguridad 0: WEP
1: WPA / WPA2 PSK
2: nulo
WPA / WPA2 PSK
12
Longitud de la
clave WEP
13 ASCII
IO1 Sin uso NULO
Clave WEP Ejemplo: 123456
Clave WAP/WAP2 Ejemplo: 123456
Versión Firmware Módulo de la versión firmware ( Solo lectura )
DHCP
If wireless router is equipped with DHCP function, the DHCP of DM12 is
set as Enable to realize automatic address assignment. The operation
process is shown in the following picture.
If IP address is automatically assigned through DHCP, the parameters of
Local IP, Subnet mask and Gateway can not be set by manual.
After the configuration is finished, return to module display interface to
check dynamic assignment address. See operation process 5.
DHCP
Si el router de conexión inalámbrica está equipado con la función DHCP,
la DHCP del DM12 se establece como Enable para realizar la asignación
automática de la dirección. El proceso de operación se muestra en la
siguiente figura.
Si la dirección IP se asigna de manera automática a través del DHCP, los
parámetros del IP local, la máscara de subred y la entrada no pueden ser
configuradas de manera manual..
Después de que se termine la configuración, se debe volver a la interfaz
de visualización del módulo para comprobar la asignación dinámica de
direcciones. Véase el proceso de operación 5.
13
Test
. Ping
In communication model, PC executes ping command to check whether
AHM3 is connected to LAN correctly and verify the configuration of
parameters. The operation process is shown in the following picture.
. Ping
En el modelo de comunicación, el ordenador ejecuta el comando
ping para comprobar si el AHM3 está conectado a LAN correctamente y
verificar los parámetros de configuración. El proceso de operación se
muestra en la siguiente imagen.
14
Modbus/TCP
In communication model, the correctness and reliability of
communication are checked by PC through Modbus/TCP test software such
as Modbus-Poll.
Open Modbus-Poll, click Connection, and then set relative parameters of
AHM3.
Click Setup, and set Modbus/TCP command, address and number of register.
Please refer to AHM3 user manual for communication register address
list.
En el modelo de comunicación la exactitud y fiabilidad de la
comunicación son controlados por el PC a través del software de prueba
Modbus/TCP como Modbus-Poll.
Para abrir Modbus-Poll, cliquear en Connection, y después configure los
parámetros relativos de AHM3. Cliquear en Setup, y configurar los comandos,
dirección y número de registro del Modbus..
Por favor consulte el manual de usuario AHM3 para el registro de la lista
de direcciones de comunicación.
15
16
7 Technical specifications / Especificaciones técnicas
Interface WiFi
Frame format 802.11 b/g/n
Transmission power 18dBm@11b, 15dBm@11g, 15dBm@11n
Baud rate 11Mbps@11b,54Mbps@11g,72Mbps@11n
Working mode Server
MAC IEEE certification,Globally Unique
IP Static setting or DHCP
Protocol Modbus-TCP
Working temperature -10 ~ 60
Storge environment -25 ~ 70 ,≤ 95%RH
Interfaz WiFi
Formato de pantalla 802.11 b/g/n
Potencia de transmisión 18dBm@11b, 15dBm@11g, 15dBm@11n
Velocidad de transmisión 11Mbps@11b,54Mbps@11g,72Mbps@11n
Modo de trabajo Servidor
MAC IEEE Certificación Global Única
IP Configuración estática o DHCP
Protocolo Modbus-TCP
Temperatura de trabajo -10 ~ 60
Temperatura de
almacenamiento -25 ~ 70 ,≤ 95%RH
1
DM13 module
Modulo DM13
( GPRS )
User manual
Manual de usuario
VER:V15A
S. A. DE CONSTRUCCIONES INDUSTRIALES (SACI)
15, Aragoneses St 28108 Alcobendas, Madrid Spain Tel.: +34 91 519 02 45 Fax.: +34 91 416 96 46
www.saci.es e-mail : [email protected]
2
It is recommended to use this module as a reference to the following content.
《AHM3 user manual》
《AHM3 Modbus-RTU user manual》
《Modbus protocol implementation guide over TCP/IP》
Se recomienda el uso de este módulo como referencia para el siguiente
contenido.
《AHM3 manual de usuario》
《AHM3 Modbus-RTU manual de usuario》
《Guía Modbusde protocol de implementación a través de TCP/IP》
1 Safety Precautions / Precauciones de Seguridad
The manufacturer shall not be held responsible for failure to comply with the
instructions in this manual.
The equipment must be installed and serviced only by qualified personnel.
El fabricante no se hace responsable de los fallos originados en los módulos
si no se cumplen las instrucciones de éste manual.
El equipo debe ser instalado y puesto en marcha por personal cualificado.
2 General
DM13 can extend the communication function of AHM3.
.Spectrum: 850/900/1800/1900
.Working mode:GPRS (TCP), SMS
.Support standard Modbus-TCP protocol
. Interface: SIM card
.Network anomalies automatically disconnect,ensure reliable TCP connection
El DM12 incrementa la función de comunicación del AHM3.
.Espectro: 850/900/1800/1900
.Modo de trabajo: GPRS (TCP), SMS
.Protocolo de soporte estándar Modbus-TCP
.Interfaz: Tarjeta SIM
.Las anomalías de red producen la desconexión automática, asegurarse de
una conexión TDP fiable.
3
3 Dimensions / Dimensiones
4 Installation / Instalación
Module installation / Módulo de Instalación
SIM card installation / Instalación de la tarjeta SIM
4
5 Operation / Operación
5.1 Connect to AHM3 / Conexión a AHM3
Disconnect the power supply of AHM3, and then connect DM13 module
to slot X2 (take slot X2 as example).
Connect AHM3 to power supply, and then enter module interface of
AHM3 to check the information of slot X2. If the connection between meter
and module is correct, parameters of DM13 will be shown. Detailed operation
process is shown in the following pictures.
→
MENU
7.1Relay Outputs
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyMeasure.
Harmonic
ENTER
SetupQualityDemand
Max/Min
EventsDev.Info
MENU
→
MENU
7.3Module X2GPRS DM13
Port 00502IP 192.168.1.100
→
MENU
7.2Module X1No Module
Module
Following parameters are used in this manual for ease of presentation.
Port = “3000”
IP = “222.191.243.130”
Desconecte la fuente de alimentación del AHM3 y después conectar el
5
módulo DM13 a la ranura X2 (tomar la ranura X2 como un ejemplo).
Conectar el AHM3 a la fuente de alimentación y luego entrar en la
interfaz del módulo del AHM3 para comprobar la información de la ranura X2.
Si la conexión entre el medidor y el modulo es correcta, se mostrarán
parámetros en el DM13. El proceso de operación detallado se muestra en las
siguientes imágenes.
→
MENU
7.3Module X2
TCP/IP DM11DHCP OFFPort 00502IP 010.002.00 4.239MASK 255.255.255.000GW 010.002.00 4.001MAC 00.04.A3.E6 .80.4F
MENU
7.1Relay Outputs
Relay OutputsNo.0102
ModeE PulseAlarm
Status
FREE
EnergyHarmonic
ENTER
SetupQualityDemand
ModuleMax/Min
EventsDev.Info
MENU
MENU
7.2Module X1No Module
→ →
Measure.
Los siguientes parámetros se usan en este manual para facilitar la
presentación.
Puerto = “3000”
Dirección IP = “222.191.243.130”
5.2 Parameters configuration
5.2.1 Communication model
In GPRS and Internet network, cell phone user can read the real-time
data of AHM3 which is equipped with DM13 module through short message
mode, and PC user can built TCP connection with AHM3 to realize data
exchanging and relative control output by creating server mode. The model is
shown in the following picture.
En el GPRS y a través de Internet, el usuario del teléfono puede leer los
datos del AHM3 en tiempo real, el cual está equipado con un módulo DM13 a
través del modo de mensajes cortos, y el usuario del PC puede generar una
conexión TCP con el AHM3 y realizar intercambio de datos y el control
relativo de la salida mediante la creación de un modo de servidor. El modelo
se muestra en la siguiente figura.
6
5.2.2 Configure parameters of DM13 module through special
software
Configure the parameters of DM13 module through special software for
AHM3. AHM3 is equipped with a RS485 interface. It is connected to PC
through RS232 (or USB)/RS485 conversion device. See the following picture.
Configura los parámetros del módulo DM13 a través de un software
especial para el AHM3. El AHM3 está equipado con una interfaz RS485. Se
conecta a un PC a través de un dispositivo de conversión RS232 (o
USB)/RS485. Véase la siguiente imagen.
7
Step1: Set serial communication
Click Setting menu and select Serial Port Setup
Paso 1: Establecer comunicación de serie
Cliquear en setting menu y seleccionar Serial Port Setup
Step2: Connection test
Set communication address of AHM3 in Address item on the upper right
part of PC window.
Select Basic Setup item, and then click Upload button on the lower right
part of PC window. If Succeed in upload appears, that means serial
communication is normal. In this condition, DM13 module appears in X2 slot.
Paso 2: Test de conexión.
Establecer la dirección de comunicación del AHM3 en la pestaña
Address situada en la parte derecha superior de la ventana del PC.
Seleccionar Basic Setup, y cliquear en el botón Upload en la parte
derecho inferior de la ventana. Si aparece la palabra Succeed, la
comunicación es normal Bajo esta condición, el módulo DM13 aparece en la
ranura X2.
8
Step3: Change parameters
Click Communication item, and then select GPRS item to change relative
parameters. At last, click Download button on the lower right part of PC
window.
Paso 3: Cambio de parámetros.
Cliquear en Communication y después seleccionar Wifi para cambiar los
parámetros reelativos. Para terminar, cliquear en el botón Download en la
parte inferior derecho de la pantalla.
9
DM13 will re-start after the setting is finished. It is suggested to operate
AHM3 after three seconds and return to module display interface and verify
the setting. See operation process 5.1.
DM13 se reiniciará después de que termine el ajuste. Se recomienda
operar el AHM3 después de tres segundos y volver a la interfaz de
visualización del módulo y verificar el ajuste. Véase el proceso de operación
5.1
10
DM13 parameters list:
GPRS Power 1: On
Working Mode 0: GPRS only 1: SMS only 2:GPRS+SMS
GPRS Setting ( TCP )
Port 0 ~ 60000 the Source Port number
Connect mode 0: IP Link 1: Domain name Link
IP Fixed public IP,don't set when using domain name
methods
Domain name Don't set when using IP
APN By the local GSM network
APN User name By the local GSM network
APN Password By the local GSM network
Send keep Interval 300 ~ 60000 s
SMS Setting
Short Message Center
Number
not use
User's cell phone number 1 Need set
User's cell phone number 2 Need set
User's cell phone number 3 Need set
User's cell phone number 4 Need set
Lista de parámetros DM13:
Potencia GPRS 1: Encendido
Modelo de trabajo 0:Solo GPRS 1: Solo SMS 2:GPRS+SMS
Ajuste GPRS ( TCP )
Puertp 0 ~ 60000 Número de Fuente de Puerto
11
Modo de conexión 0: IP Link 1: Link del nombre del dominio
IP IP pública fija , no la coloque al utilizar métodos de
nombres de dominio
Nombre del dominio No introducirlo cuando se este usando el IP
APN Por la red local GSM
Nombre de usuario APN Por la red local GSM
Contraseña APN Por la red local GSM
Mantener el interval de
envio
300 ~ 60000 s
Ajuste SMS
Número de centro de
mensaje corto
Sin uso
Número de teléfono del
usuario 1
Necesita ajuste
Número de teléfono del
usuario 2
Necesita ajuste
Número de teléfono del
usuario 3
Necesita ajuste
Número de teléfono del
usuario 4
Necesita ajuste
12
5.2.3 GPRS(TCP)test example
PC is used as server to build TCP connection with AHM3 which is client.
Data exchanging, AHM3 real-time measured data reading and configuration
of AHM3 parameters are realized through standard Modbus-TCP data
transmission protocol.
Note:
1. If it is fixed IP access network, please select IP Access Mode; If it is
dynamic IP access network, please select Domain Name Access Mode.
2. In fixed IP access network, if PC is in a LAN built on router, it is
necessary to set port mapping in router which means to set a port to
allow communication between LAN and external network in router. The
port number of DM13 should be the same as that in router.
El PC se usa como servidor para generar una conexión TCP con AHM3
como cliente. El intercambio de datos, datos medidos en tiempo real de
AHM3, su lectura y configuración de los parámetros del AHM3 se realizan a
través del protocol de transmisión de datos estándar Modbus-TCP.
Nota:
1. Si el acceso a la red IP es fijo, por favor seleccionar el modo de
acceso IP, si el acceso a la red IP es dinámico, por favor seleccionar el
modo de acceso de dominio.
2. En la red de acceso IP fijada, si el PC está en una LAN en el router,
es necesario establecer la asignación de puertos en router lo que
significa establecer un puerto para permitir la comunicación entre LAN y
la red externa en el router. El número de puerto de DM13 debe ser el
mismo que en el router.
Step1: DM13 setting
In communication example model, fixed IP is 222.191.243.130, set port
13
mapping in router with port number 3000.
Paso 1: Ajuste del DM13
En modelo de ejemplo de comunicación, IP fija es 222.191.243.130,
configurar el mapeo de puerto en el router con el número 3000.
DM13 parameters are as follows:
Los parámetros del DM13 son los siguientes:
GPRS Power 1: On
Work Mode /Modo de trabajo 0: GPRS only / 0: Solo GPRS
GPRS Setting ( TCP ) / Configuración GPRS ( TCP )
Port / Puerto 3000
Connect mode
Modo de conexión
0: IP Link
IP 222.191.243.130
Domain name / Nombre dominio
APN
APN User name /Usuario
APN Password / Contraseña
Send keep Interval /Intervalo de
envio
600 s
Step2: PC user create TCP server mode
Server mode can be created through relative TCP test software on PC.
Take TCP Monitor Modbus, test software of our company, as example.
·Open software
Step2: Crear modo de servidor TCP por usuario de PC
El modo de servidor puede ser creado mediante el software de pruebas
TCP en un PC. Prueba el software TCP Modbus de su compañía como
ejemplo.
·Open software / Abre el software
14
·Set port as 3000, click button Start Monitor, and then start to monitor
client.
· Configurar puerto como 3000, haz clic en el botón Start Monitor, y luego
comenzar a monitorear al cliente.
·If the configuration of network and DM13 is correct, new client will
15
appear, which means the connection succeeds.
· Si es correcta la configuración de red y el DM13, el nuevo cliente aparecerá,
significando que la conexión funciona.
Step3: Modbus-TCP test
Write test data frame which is to be sent by server in Request area. For
example, read eight float type data starting from register 0x0006 by using
command 03, click button Send, response data frame will appear in
Response area. If user set Interval and select Auto, this software will execute
data exchanging automatically at regular time to test the reliability of
communication.
Paso 3: Prueba de Modbus-TCP
Por ejemplo, leer los ocho datos de tipo flotante a partir del registro
0x0006 mediante el comando 03, haz clic en el botón Enviar, la respuesta de
datos aparecerá en el área de respuesta. Si el usuario establece el intervalo y
selecciona Auto, este software ejecutará el intercambio de datos
automáticamente en tiempo regular para probar la fiabilidad de la
comunicación.
16
Please refer to AHM3 Modbus-RTU Communication User Manual for
communication register address list.
Por favor consulte Manual de usuario de comunicación de Modbus-RTU
de AHM3 para la lista de direcciones de registro de comunicación.
5.2.4 SMS test example / Ejemplo de prueba
Cell phone user can read the real-time measured data of AHM3 through
SMS mode. Please set correct working mode and user’s short message
number in the configuration of DM13.
In the following example, SIM number equipped in DM13 is
(+34)137712455, SIM numbers of test software are (+86)156578890 and
(+86)702890912.
DM13 parameters are as follows:
Un usuario de teléfono móvil puede leer los datos medidos en tiempo real del
AHM3 a través de la modalidad SMS. Configure el modo correcto de trabajo y
número de mensajes cortos del usuario en la configuración de DM13.
En el ejemplo siguiente, el número SIM equipado en el DM13 es (34)
137712455, número SIM del test son (86) 156578890 y (86) 702890912.
Response area
Request area
17
Los parámetros del DM13 son los siguientes:
GPRS Power 1: On
Work Mode
Modo de trabajo
1: SMS only ( or 2:GPRS+SMS )
SMS Setting / Configuración GPRS
User's cell phone number 1
Teléfono movil de usuario 1
+34156578890
User's cell phone number 2
Teléfono movil de usuario 2
+34702890912
User's cell phone number 3
Teléfono movil de usuario 3
User's cell phone number 4
Teléfono movil de usuario 4
Cell phone user can send message READ01 ~ READ10 to get the
real-time measured data of AHM3. Letters in the message are not case
sensitive. For example, READ01 also can be written as rEad01.
El usuario de teléfono móvil puede enviar mensaje READ01 ~ READ10
para obtener en tiempo real los datos medidos del AHM3. No distingue
mayúsculas y minúsculas. Por ejemplo, READ01 también puede ser escrito
como rEad01
18
Energy Information:
Información de energía
IAE: Import Active Energy
EAE: Export Active Energy
IRE: Import Reactive Energy
ERE: Export Reactive Energy
AE: Apparent Energy
Tariff Information:
Información de consumo
TEpA: Total tariff import energy
TEp1: Tariff #1 import energy
TEp2: Tariff #2 import energy
TEp3: Tariff #3 import energy
TEp4: Tariff #4 import energy
19
Limit Information:
Información de límites
LmUN: Max. value-Average Vph-n
LmUL: Max. value-Average Vph-ph
LmIv: Max. value-Average I
LmP: Max. value-P
LmQ: Max. value-Q
LmS: Max. value-S
LmPF: Max. value-PF
LmF: Max. value-F
Demand Information:
Información de la demanda
DI1: Present demand value -I1
DI2: Present demand value -I2
DI3: Present demand value -I3
DP: Present demand value -P
MDI1: Max. demand value -I1
MDI2: Max. demand value -I2
MDI3: Max. demand value -I3
MDP: Max. demand value -P
Quality Information:
Información de calidad
SqIP:Positive-sequence component of current
SqIN:Negative-sequence component of current
SqIZ:Zero-sequence component of current
unbI:Unbalance factor of current
SqUP:Positive-sequence component of voltage
SqUN:Negative-sequence component of voltage
SqUZ:Zero-sequence component of voltage
unbU:Unbalance factor of voltage
20
6 Technical specifications / Especificaciones técnicas
Interface GPRS
Spectrum 850/900/1800/1900 MHz
Working mode GPRS,SMS
Protocol Modbus-TCP
SMS format Text
Antenna External connect
Working temperature -10 ~ 60
Storge environment -25 ~ 70,≤ 95%RH
Interfaz GPRS
Espectro 850/900/1800/1900 MHz
Modo de trabajo GPRS,SMS
Protocolo Modbus-TCP
Format SMS Text
Antenna External connect
Temp. de trabajo -10 ~ 60
Temp. de almacenam. -25 ~ 70,≤ 95%RH
Harmonic Information:
Información de armónicos
HmU1: THD-V1
HmU2: THD-V2
HmU3: THD-V3
HmI1: THD-I1
HmI2: THD-I2
HmI3: THD-I3