A Neutral-Point Clamped Converter System For

Embed Size (px)

Citation preview

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    1/12

    596 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 2, JUNE 2006

    A Neutral-Point Clamped Converter System forDirect-Drive Variable-Speed Wind Power Unit

    Amirnaser Yazdani,Member, IEEE,and Reza Iravani,Fellow, IEEE

    AbstractRecent and ongoing developments in wind turbinetechnology indicate a trend towards utilization of high capacity(e.g., up to 5 MW) wind power units in large wind farms. Highercapacity of the wind turbine necessitates operation of the corre-sponding electric machine and thestatic converter systemat highervoltages. This paper presents a neutral point diode clamped (NPC)converter system that inherently accommodates higher voltage andpower ratings of a high capacity wind power unit. The overall con-trol strategy of an NPC-based wind power unit and the detailsof the ac side and the dc side controls of the NPC converter sys-tem are also described. The generator-side NPC converter providestorque-speed control of the turbine-generator unit. The network-side NPC converter controls real and reactive power flow to the

    network and thus regulates the dc bus voltage and the ac sidepower-factor (or voltage) respectively. The paper also presents anew control approach to balance the dc capacitor voltages. TheNPC converter system is augmented with a dc chopper that con-trols the synchronous generator field current. The NPC-based con-verter system is used to interface a 3 MW, direct-drive (gearless),synchronous machine based wind power unit to the utility grid.Performance of the overall NPC-based wind power unit, under theproposed controls, is evaluated based on time domain simulationsin the power systems computer aided design (PSCAD) electromag-netic transient for DC (EMTDC) environment.

    IndexTermsCurrent control, dc-side voltage balancer, electro-magnetic transients, neutral-point diode clamped (NPC) converter,variable-speed wind-power system.

    I. INTRODUCTION

    WORLDWIDE, wind energy has been the fastest growing

    energy technology within the last several years, and all

    factors indicate that the growth will continue for many years in

    the future [1]. The technological trend of large wind turbines,

    for wind farm applications, is toward large capacity units. For

    example, a 5 MW prototype wind power unit was recently in-

    stalled and is currently being tested [2]. The high capacity of a

    wind turbine indicates that the corresponding electric machine

    and static power converter system must operate at higher voltage

    levels to achieve 1) maximum efficiency and 2) optimum size,

    volume, and form-factor.

    The back-to-back connected, two-level voltage-sourced con-verter (VSC) system is the most widely used static converter

    configuration for variable-speed wind power units [3], [4]. Op-

    eration of the two level converter system at high voltage levels

    requires valves with high voltage ratings. This can be achieved

    through either by using the state-of-the-art switches available at

    Manuscript received December 29, 2004, revised June 06, 2005. Paper no.TEC-00369-2004.

    The authors are with the Center for Applied Power Electronics (CAPE)at the Department of Electrical and Computer Engineering, University ofToronto, Toronto, ON M5S 3G4, Canada (e-mail: [email protected];[email protected]).

    Digital Object Identifier 10.1109/TEC.2005.860392

    high voltage ratings, or cascading switches with lower-voltage

    ratings. The former option imposes excessive switch cost which

    may render the converter unit economically unattractive or even

    unacceptable. The latter approach imposes its own technical

    challenges; e.g., equal voltage sharing and simultaneous gating

    requirements.

    Another approach that avoids the previously described

    problems is use of the multilevel VSC instead of the two-level

    VSC [5], [6]. This paper proposes the application of the

    three-level neutral point diode clamped (NPC) converter [7]

    for a high-power variable-speed wind power unit. Applications

    of the NPC converter for back-to-back HVDC links [8] and

    high-power drives [9] have been reported in the technical

    literature, but has neither been proposed nor investigated for

    wind power applications.

    This paper provides a detailed formulation and evaluation of

    the control system of a back-to-back NPC converter system for

    a direct-drive (gearless) variable-speed synchronous machine

    based wind-power system. The proposed direct drive, variable

    speed, NPC-based wind power configuration has the following

    salient features when compared with fixed-speed, squirrel-cage

    induction machine based and doubly-fed induction machine

    based wind power unit.

    1) Eliminationof the gearbox significantly reduces scheduledand unscheduled maintenance;

    2) Mechanical speed of the turbine-generator is controlled

    in a noticeably wider range and thus the captured wind

    energy is higher;

    3) The configuration can naturally accommodate low-speed

    (high-pole) permanent magnet synchronous machines,

    which translates in significant reduction in size, volume,

    and weight; and

    4) The converter systemacts as a buffer between theelectrical

    grid and the turbine-generator, and thus minimizes unde-

    sirable dynamic interactions between the two subsystems,

    e.g., due to wind speed fluctuations and electrical faults.The control model is developed based on a generalized state-

    space model of the NPC converter [10] and includes 1) torque-

    speed control of the synchronous machine, 2) grid-side power-

    factor (voltage) control, 3) net dc bus voltage control, and 4)

    dc capacitor voltage equalizer. The NPC converter system is

    augmented by a dc-dc chopper that is supplied from the dc-

    bus, and controls the synchronous machine field current. The

    chopper controls are also described in detail. This paper also

    presents the control strategy of the overall wind-power unit.

    Performance of the overall wind power unit, including the NPC

    converter system and the controllers, is evaluated based on time

    domain simulationstudies in the PSCAD/EMTDCenvironment.

    0885-8969/$20.00 2006 IEEE

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    2/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 597

    Fig. 1. Single-line schematic diagram of a three-level VSC-based power conversion system.

    This paper is organized as follows: Section II introduces

    the wind power system. Section III deals with the models ofthe synchronous machine, the machine side NPC converter,

    and the machine torque-speed control. Section IV develops

    the models for the grid side NPC converter, the grid side

    current controllers, the net dc bus voltage controller, and the

    dc-side voltage equalizer. The wind power system control strat-

    egy is described in Section V. Section VI presents the sys-

    tem performance in response to the startup, a wind gust, and

    a line-to-neutral fault in the grid. Section VII concludes the

    paper.

    II. SYSTEMSTRUCTURE ANDMODEL

    Fig. 1 shows a schematic representation of a three-level NPC-

    based wind power system. The system is comprised of a wind

    turbine that is directly coupled to a high pole synchronous ma-

    chine. The synchronous machine is field-controlled. The ma-

    chine is vector-controlled by NPC1. The second three-level NPC

    converter, NPC2, interfaces the wind power system to the utility

    grid.

    The dc bus is composed of twonominally identicalcapacitors.

    The clamped points of the two NPC converters are connected to

    the capacitors at midpoint 0, Fig. 1. The midpoint is assumed to

    be the circuit voltage reference, but is not necessarily grounded.

    Grounding midpoint or any other node in the converter sys-

    tem must take into account protection requirements and other

    unit dependent factors; e.g., configuration of the interface trans-

    former.

    A current-controlled buck converter, supplied from the DC-

    bus, is used to regulate the machine field current if. The buck

    converter is a diode clamped converter and thus can withstand

    high dc bus voltages. Therefore, the clamped point of the buck

    converter is also connected to the midpoint 0. ResistorRp rep-

    resents the total switching losses of the NPC converters, and is

    not a physical component.

    NPC2 equalizes the voltages of the dc side capacitors and

    regulates the dc bus voltage, [10], [14]. The ac side terminals of

    NPC2 are connected to the utility grid through series connected

    TABLE ISYSTEMPARAMETERS

    inductors and a three-phase transformer. R represents the on-

    state loss of NPC2 switches and the internal resistance of series

    inductorL. Two three-phase shunt filters are installed at the low

    voltage side of the transformer as shown in Fig. 1. The shunt

    filters trap dominant switching harmonics and prevent voltage

    distortion at the point of common coupling (PCC).

    A sinusoidal PWM switching is adopted for the NPC con-

    verters. The PWM carrier signals of both NPC converters and

    the buck converter are synchronized to the grid voltage Vsabcat the low voltage side of the interface transformer, see Fig. 1.

    Therefore, the converters operate at constant switching frequen-cies, and high frequency jitters and EMI phenomenon are mini-

    mized.Pextdenotes the power delivered to the dc bus from the

    machine side through NPC1. The system parameters are given

    in Tables IIII.

    III. SYNCHRONOUSMACHINEVECTORCONTROL

    A. Machine Dynamic Model

    The machine model, in its rotordq-frame; is adopted from

    [11]. The voltage and current vectors of the machine stator in

    the dq-frame, i.e., Vstdqand Istdq, are related to the correspond-

    ing abc-frame values; i.e., the vector of fundamental voltage

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    3/12

    598 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 2, JUNE 2006

    TABLE IISYNCHRONOUSMACHINEPARAMETERS

    TABLE IIIWINDTURBINEPARAMETERS

    components at the machine-NPC1 terminalsVstabc(t), and thecurrent vectoristabc(t) (see Fig. 1) by the following transfor-mations

    Vstdqo= T(Pr )Vstabc(t) (1)

    Istdqo= T(Pr )istabc(t) (2)

    wherer andPare the rotor mechanical angle and the number

    of pole-pairs. The transformation matrixTis defined by

    T() = 2

    3

    cos() cos 2

    3

    cos

    4

    3

    sin() sin

    2

    3

    sin

    4

    3

    12

    12

    12

    .(3)

    Vstdqis related to the dcbusvoltageVdc through the amplitude

    and phase angle: i.e., m1 and 1, of the PWM modulation

    waveform of NPC1, as given by (4) and (5)

    Vstd=m1

    2 Vdc cos 1 (4)

    Vstq=m1

    2 Vdc sin 1. (5)

    Based on (4) and (5):

    1= tan1

    Vstq

    Vstd

    (6)

    m1=

    2

    V2std+ V

    2stq

    Vdc . (7)

    TABLE IVGLOSSARY OFTERMS

    The dynamic model of the machine, in thedq-frame is [11]

    Lfdif

    dt = Rfif + Vf + Lmd

    dIstd

    dt (8)

    LddIstd

    dt = RsIstd+ LqIstqPr Vstd+ Lmd

    dif

    dt (9)

    LqdIstq

    dt = RsIstq LdIstdPr Vstq+ Lmd ifPr

    (10)

    where r = d rdt

    , and the other terms are defined in Table IV.

    Vfis the average ofVfover one switching period.

    No damper winding is considered in the model. The reason is

    that the machine is current-controlled and the flux is regulated

    at a constant value. Thus, the impact of damper windings is in-

    significant [11], and practically, damper bars are removed from

    a vector-controlled machine. Similarly, the magnetic saturationis not included in the model, since the flux is tightly regulated

    in a vector-controlled machine.

    The machine electrical torque is given by [11]

    Te =

    3

    2

    P(LmdifIstq LdIstdIstq+ LqIstdIstq). (11)

    B. Machine Vector Control

    Te is a nonlinear function of machine currents. Based on a

    vector control strategy, the nonlinearity can be avoided and the

    current coupling minimized. One optimal approach is to impose

    Istd= 0[11] and [12]. This reduces (11) to

    Te =

    3

    2

    PLmd ifIstq. (12)

    Equation (12) shows that Teis a linear function ofIstq, provided

    that field currentif is regulated at a constant value; e.g., at the

    rated field current. Moreover, imposing Istd= 0 ensures that thestator currents are minimum for a pre specified torque and, thus,

    the machine efficiency is enhanced [12]. Furthermore, regulat-

    ingIstd at zero eliminates the transient impact of the machine

    damper windings (if they exist) on the torque [11]. The struc-

    tures of the machine current regulators, based on the availability

    of the rotor angle r and speed r via either measurement or

    estimation [13], is as follows:

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    4/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 599

    1) Rotor Current Regulator: In (8),if is the state variable,

    Vfis the control input, and LmddIstddt

    is the coupling term be-

    tween if andIstd. Istd is to be regulated at zero. Thus, if the

    closed loop system is stable, LmddIstddt

    becomes zero after tran-

    sients. Hence, (8) can be approximated as

    Lf

    dif

    dt =

    Rfif+ Vf. (13)The output voltage of the buck converter is

    Vf =d.Vdc (14)

    wheredis the duty ratio.dis provided by the following control

    law

    d= 1

    Vdc

    Kf pef + Kf i

    t0

    efdt

    (15)

    where, ef =ifref ifand ifrefis set at the rated value. Choos-

    ing Kf p = L ff

    and Kf i = Rff

    , we deduce the closed loop trans-

    fer function as

    if(s)

    ifref(s) =

    1

    fs + 1, (16)

    wherefis the time constant of the closed loop response.

    2) Stator Current Regulators: In (9), Istd is the state vari-

    able,Vstdis the control input, and Lmddi fdt

    is the coupling term

    between Istdand if. If the closed loop system is stable, Lmddi fdt

    becomes zero after transients and (9) can be approximated as

    LddIstd

    dt = RsIstd+ LqIstqPr Vstd. (17)

    Let us define the following change of variable

    Vstd= ustd+ LqIstqPr (18)

    where ustdis the control variable. ustdis given by the following

    PI controller

    ustd= Kdp estd+ Kdi

    t0

    estddt (19)

    whereestd= IstdrefIstd, and referenceIstdrefis set to zero.Istdand Istqare filtered Istdand Istq, respectively. The filteringis to reduce the impact of current harmonics on the closed loop

    system. The transfer function of each filter is

    Fi(s) =IstdIstd

    =IstqIstq

    = 1is + 1

    . (20)

    To provide adequate attenuation of harmonics, i must be large,

    but considerably smaller than the smallest desired time-constant

    of the closed loop system. These constraints can be readily

    satisfied, since the PWM generated harmonics are of high order.

    Substituting forVstdfrom (18) into (17), we obtain

    LddIstd

    dt = RsIstd+ LqPr (Istq Istq) + ustd. (21)

    Based on (21), Istdcannot be decoupled fromIstq, since (Istq

    Istq)is not zero during transients. However, since the filter time

    constanti is small,(Istq Istq)rapidly approaches zero, and

    Fig. 2. Block diagram of machine current controllers.

    the coupling is weakened. Consequently, the following SISO

    model is obtained for the machined-axis current dynamics

    LddI

    stddt = R

    sIstd+ ustd. (22)

    Similarly, theq-axis stator current controller is defined by

    ustq = Kqp estq+ Kq i

    t0

    estqdt (23)

    Vstq = ustq LdIstdPr + Lmd ifPr (24)

    where, estq= Istqref Istq. Istqrefis the q-axis reference value,which is determined based on the desired torque. Substituting

    forVstq from (24) into (10) and ignoring the transient impact

    of(Istd Istd), we deduce the following SISO model for themachineq-axis current dynamics

    LqdIstq

    dt = RsIstq+ ustq. (25)

    The PI-controller gains Kdp , Kdi ,Kqp , and Kqi can be deter-

    mined from pole placement, based on the desired performance.

    Fig. 2 shows block representations of the machined-andq-axis

    current controllers.

    IV. CONTROL OFGRID-SIDECONVERTER, NPC2

    A. Dq-Frame Synchronization

    The dynamic model of NPC2 is developed in the grid syn-

    chronously rotating dq-frame. The dq quantities are related tothe correspondingabcquantities through

    fdqo= T(t)fab c(t) (26)

    where is the grid frequency, and the transformation matrix T

    is given by (3). The dq-frame is synchronized to the three-phase

    ac side voltagesVsabc , (see Fig. 1) such thatVsq = 0. Thus,

    Vsa (t) =Vsd cos(t) (27)

    Vsb (t) =Vsd cos

    t

    2

    3

    (28)

    Vsc

    (t) =Vsd

    cost 43 . (29)

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    5/12

    600 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 2, JUNE 2006

    Fig. 3. Block representation of (a) three-phase space-vector PLL, (b)dq-frame current controllers.

    The synchronization is achieved by a space-vector PLL[15]. The block diagram of the space-vector PLL is shown in

    Fig. 3(a). The feedback loop with compensatorH(s)adjust an-gle such that Vsq is forced to zero. The PLL compensator

    H(s)must include an integral term for zero steady state error.Moreover, H(s) should include a band-stop characteristic toeliminate distortions ofVsq, and provide a distortion free angle.

    Similarly, notch filters Fn (s) are required for conditioningVsd andVsq.

    B. Dynamic Model

    A dynamic model of NPC2 in thedq-frame is [10]

    dId

    dt =

    R

    LId + Iq

    1

    LVsd +

    1

    LVtd (30)

    dIq

    dt = Id

    R

    LIq

    1

    LVsq+

    1

    LVtq (31)

    d

    dt(V1 V2) =

    3

    C(Idcos2+ Iqsin2)(0 0) (32)

    dVdc

    dt =

    2

    Ciext

    3

    2Cm2(Idcos 2+ Iqsin 2)

    3

    C(0+ 0)(Idcos 2+ Iqsin 2) (33)

    where

    Vtd =

    V1

    m2

    2 +

    20

    + V2

    m2

    2 +

    20

    cos2 (34)

    Vtq =

    V1

    m2

    2 +

    20

    + V2

    m2

    2 +

    20

    sin 2. (35)

    m2 and 2 are the amplitude and phase angle of the PWM

    modulation signals, V1 and V2 are the dc components of the dcside voltagesV1 and V2, and0 and 0 are small offsets added

    to the PWM modulating waveforms, in consecutive half-cycles,

    to equalize V1and V2[10]. Since0and 0are small, (34) and

    (35) can be approximated as

    Vtd m2

    2 Vdc cos 2 (36)

    Vtq m2

    2 Vdc sin 2. (37)

    m2and 2are calculated from (34) and (35) as

    2= tan1

    Vtq

    Vtd

    (38)

    m2=2

    V2td + V2tq

    4(0V1+ 0V2)

    Vdc

    2V2td + V2tqVdc

    . (39)

    Equations (30) and (31) are used for the ac side current control,

    (32) is used for the dc side voltage equalization, and (33) is used

    for the net dc bus voltage control.

    C. AC Side Current Control

    The objectives of the ac side current controls are 1) dc bus

    voltage control and 2) reactive power control. Principles of

    current control are given in detail in [10]. Fig. 3(b) shows a

    block representations of the d- and q-axis current controllers.

    As shown in Fig. 3(b),Id andIqare passed through the corre-

    sponding notch filters to eliminate distortions.

    The transfer function of each notch filter is:

    Fn (s) =fdq

    fdq=

    1 + s2

    21 +

    m=2m=1 ams

    m. (40)

    Then, the closed loop current dynamics are expressed by

    Gi(s) = Id(s)

    Idref(s) =

    Iq(s)

    Iqref(s)

    1 +

    k i ps

    k i i 1 +

    m=2m=1 ams

    m

    1 + n=4n=1 bnsn (41)

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    6/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 601

    where kip and kii are the proportional and the integral gains

    of the current controllers, respectively. The poles of the notch

    filters, Fn (s), given by 1 +m=2

    m=1 amsm = 0, appear as the ze-

    ros ofGi(s). Based on the adopted control strategy, the reactiveand real power components supplied by NPC2 to the grid can

    be expressed as

    Qg = 3

    2Vsd Iq (42)

    Pg = 3

    2Vsd Id . (43)

    In Fig. 3(b),Iqrefis set at zero for operation at unity power-

    factor. Based on the power balance principle, Idrefis determined

    by the dc bus voltage controller to keep the dc bus voltage

    regulated, as discussed in the following section.

    D. DC-Bus Voltage Dynamics and Control

    The dynamics of the dc bus voltage are described by (33).Since (33) contains m2Idcos2and m2Iqsin 2, which includemultiplications of the state variables and the control inputs, con-

    trol ofVdc based on (33) is not straightforward. A modified form

    of (33), based on the principle of power balance, is presented

    in [14]; (33) can be rewritten as:

    dV2dcdt

    = 2

    RpCeqV2dc +

    2

    CeqPext

    3L

    2Ceq

    dI2ddt

    +dI2q

    dt

    3

    CeqVsd Id . (44)

    In (44),V2dc is the output variable, Id is the input signal,Iqand

    Pex t are the disturbance signals. Equation (44) is linear with

    respect to V2dc and Pext, but nonlinear with respect to Id and

    Iq. Based on (44),Id andPextaffectV2dc during transients, and

    the steady state.Iqhas an insignificant transient impact on V2dc .

    Hence, in the following analysis, for simplicity and without the

    loss of generality, we do not consider the impact ofIq. Equation

    (44) is linearized as

    dV2dcdt

    = 2

    RpCeqV2dc

    + 2Ceq

    Pext 3LIdssCeq

    dIddt

    + VsdLIdss

    Id . (45)where ss and represent the steady state value and the

    small signal perturbation of a variable, respectively. Since Rp is

    large, the following equality holds

    Pextss 3

    2Vsd Idss. (46)

    Expressing (45) in the Laplace domain and substituting forIdssfrom (46), we deduce

    V2dc (s) =Gv (s)Id+ Gp(s)Pext (47)

    Fig. 4. Block representation of the dc bus voltage controller.

    where transfer functionsGv (s)and Gp(s)are

    Gv (s) =V2dc (s)

    Id(s)=

    2LPextssVsdCeq

    s + 1.5V 2s dLPextss

    s + 2

    RpCe q (48)

    Gp(s) =Vdc (s)

    Pext(s)= 2Ceq

    1s + 2

    RpCe q

    . (49)Equation (48) shows that transfer functionGv (s)has a pole at

    P = 2RpCe q

    and a zero at Z= 1.5V 2

    s d

    LPextss. Since Rp is large,

    the pole is constant and fairly close to the origin. However, the

    location of zero is highly dependent onPextssand can vary from

    to + depending on the mode of operation and the amountof steady state real power flowPextss. IfPextss is negative, the

    system is nonminimum-phase. This is the case when the wind

    power system is in the standby mode of operation and a smallamount of power is drawn from the grid to compensate for the

    losses. However, in this case, the nonminimum-phase zero is

    far from the origin and has no significant impact on the system

    stability.

    Fig. 4 shows a block representation of the dc bus voltage

    control system. The dc bus voltage is controlled by Id ; the

    controller is designed based on (48) and at the rated power.

    To mitigate the transient impact of the disturbance signal Pext,

    a feed-forward action is included in the control scheme. The

    following methods can be considered to obtain Pext for the

    feed-forward:

    1) Direct measurement of iext, and calculation of power

    based onPext= iextVdc ;2) Torque estimation based on (12), and calculation of power

    based onPext Pm Ter .

    Method 1) needs an instantaneous Hall effect current sen-

    sor for the dc current measurement. Moreover, since iext is a

    switched waveform, additional low pass filtering is necessary

    to provide a smooth measurement ofPext. This results in a

    slow feed-forward process. Method 2) utilizes the machine pa-

    rameters andIstq, which is available from the machine vector

    control. Therefore, Method 2) is adopted in this study.Pextis a

    few percent less than the machine mechanical powerPm , due to

    the machine and converter losses. Thus, the feed-forward action

    is less accurate at lower power levels.

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    7/12

    602 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 2, JUNE 2006

    E. DC-Side Voltage Equalization

    The dc side voltage balancer maintains the dc components of

    voltagesV1 and V2 (see Fig. 1) equal at a pre-specified value

    [10]. In view of (32), we define

    0= sgn() (50)

    0= sgn() (51)

    e= V1 V2 (52)

    where the sign functionsgn( )is unity for a positive argument,and zero otherwise. Substituting for0from (50), 0from (51),

    ande from (52), in (32) we obtain

    de

    dt =

    3

    C(Idcos 2+ Iqsin 2). (53)

    Based on (53), can be adjusted to equalize the voltages of

    the two dc side capacitors. The plant modeled by (53) is re-

    garded as an integrator with a variable gain. The integral gain,3

    C(Idcos 2+ Iqsin 2), is a function of the system operatingpoint. To optimize the control design, the range of gain varia-tions should be known. The ranges over which Id and Iqchange

    are known from the operational specifications. However, angle

    2and consequently cos2and sin 2are functions of the oper-ating point. Therefore, the range of2cannot be predetermined

    from the converter specifications, and must be deduced based

    on intermediate calculations. Thus, we manipulate (53) to tailor

    it for control design.

    Multiplying and dividing the right hand side of (53) by

    m2Vd c2

    , and substituting form2cos2and m2sin 2from (36)and (37) in the resultant, we obtain

    dedt

    = 6Cm2Vdc

    (Vtd Id+ VtqIq). (54)

    Since in the steady state, Vtd Id + VtqIq Vsd Id , (54) can berewritten as

    de

    dt =

    6

    C

    Vsd

    Vdc

    Id

    m2

    . (55)

    m2 typically assumes values from 0.5 to 0.9 over the whole

    operating range. Therefore, (54) can be approximated as

    de

    dt =

    6

    C

    Vsd

    Vdc

    Idss

    mtyp.

    . (56)

    In (56),Vsd is a constant value, Vdc is regulated at its nominalvalue, and the rated value ofIdss is known from the converter

    specifications. In (56), is thecontrol variableand e is theoutput

    to be regulated at zero. SinceV1and V2contain high amplitude

    triple line frequency components, a low pass or a notch filter is

    required in the loop, to provide V1 and V2 as required by (52).Fig. 5 shows a block diagram of the dc side voltage balancer.

    V. CONTROLSTRATEGY OFWIND-POWERSYSTEM

    The wind turbine is characterized by its mechanical power,

    which is given by [16], [17]

    Ptur= 0.5r2

    Cp(, )V3w (57)

    Fig. 5. Block diagram of the dc side voltage balancer.

    where is the air mass density, r is theblade length, andVw isthe

    wind velocity.Cp(, ) is called Power Performance Coefficientand varies within the range of zero to 0.59 (Betz limit) [17].

    Cp(, )is a static nonlinear function of the blade pitch angleand tip speed ratio . The analytical formula forCp(, )areavailable in [16] and [18]. The blade tip speed ratio is given as

    = VtipVw

    = rrVw

    (58)

    where Vtip is the blade tip speed and is the turbine speed.

    Based on (57), the turbine power is a nonlinear function of

    the wind speed and the turbine speed. The maximum power is

    captured at an optimum turbine speed and the corresponding

    optimum turbine torque.

    To obtain the maximum power at wind speeds below a cer-

    tain wind speed, the pitch angle is set to a small value; e.g.,

    5, andCp(, )is maximized. Since the pitch angle is a con-stant value in this mode, Cp(, )is a single-valued function of; i.e., Cp(). The peak ofCp() corresponds to = op t .

    Therefore, the turbine speed must be changed according tothe wind speed to keep at opt. This is achieved through

    the machine torque control. The optimum operating point can

    be reached if the following reference is commanded to the ma-

    chine torque controller [3]

    Teref=Kopt2r . (59)

    Based on Teref, the corresponding Istqref is determined from

    (12), and commanded to the machineq-axis current controller.

    Koptis given by

    Kopt= 0.5r5Cp(opt)

    3opt. (60)

    Koptcan be calculated based on the turbine manufacturer data

    or measurements.

    VI. CASESTUDIES ANDSIMULATIONRESULTS

    A detailed switching model of the wind power system of

    Fig. 1 and the controllers are developed in the PSCAD/EMTDC

    [19] environment. Based on the system parameters in

    Tables IIII, the designed controllers are given in the Appendix.

    The following case studies illustrate typical time responses of

    the proposed wind power unit from the startup to t= 30 s.To simulate more realistic operating conditions, actual mea-

    sured wind speed [20] is imposed on the turbine. However, to

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    8/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 603

    Fig. 6. dc bus voltage during startup.

    demonstrate the performance of the wind power unit under the

    most severe operating conditions, we add a 2.5 m/s step change

    to the wind speed waveform at t= 11 s; and at t= 21 s, weremove the step function.

    A. System StartUp

    Initially, the pitch angle is set at 5, and the turbine speed

    is zero. Figs. 68 illustrate the system behavior during startup.Until t= 0.05s, gating signals of NPC1 and NPC2 are blockedand the dc bus capacitors are charged to about 1000 V through

    the antiparallel diodes of NPC2, see the Fig. 6. At t = 0.05s,gating signals of NPC2 are released, the reference of the dc

    bus voltage is ramped up, and the dc bus voltage reaches its

    prespecified value of 2000 V. At t= 0.4 s, gating signals ofNPC1 are also released, and the machine vector controller takes

    over; the dc bus voltage experiences a transient disturbance as

    shown in Fig. 6.

    Fig. 7(a) and (b) shows that the field current and Istdare regu-

    lated at 1.0 p.u. and zero, respectively. Since the turbine speed is

    low (less than 3.5 rpm), the turbine torque is very small. Hence,the control system sets Istqat 3.55kA, corresponding to 1.0p.u., to accelerate the turbine Fig. 7(c). During acceleration,

    power is drawn from the grid. Fig. 7(a)(c) illustrates that, ifis well decoupled from Istd and Istq. However, Istd and Istqare not entirely decoupled during transients. This is due to the

    effect of current measurement filters.

    Fig. 7(d) indicates that, corresponding to a change in Istq, the

    dc bus voltage controller with its feed-forward action changes

    thed-axis current component of NPC2, Id . The change ofId is

    to ensure the balance of power. Fig. 7(d) and (e) shows that due

    to the notch filters,Id andIqare not entirely decoupled.

    Fig. 7(f) shows that duringthe time interval that themachine is

    supplied from the system and is accelerating, capacitor voltages

    V1 and V2 significantly deviate from their nominal values of

    1000 V. The reason is that during this time interval, the machine

    speed (and its stator frequency) is very low while the machine

    currents are large; and the midpoint current of NPC1, inp 1, has

    a dominant third harmonic component [21] with an amplitude

    proportional to the amplitude of machine current. Therefore,

    inp1 has a large magnitude at a fairly low frequency. At this

    low frequency, the impedances of the dc capacitors are large

    and therefore, the third harmonic ofinp 1 imposes large ripple

    components on V1 and V2. Fig. 7(g) shows that despite large

    deviations ofV1 and V2, the net dc bus voltage Vdc is tightly

    regulated at its nominal value. Fig. 7. System response during startup.

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    9/12

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    10/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 605

    Fig. 10. System response to a sudden wind speed increase.

    However, a step change in the wind speed is artificially in-

    troduced to subject the system to the most severe conditions

    and evaluate the system performance under the worst case

    scenario.

    Fig. 9(b) and (d) shows that the turbine torque Ttur andpower Ptur increase rapidly due to the wind speed change.

    However, the machine torque Te and power Pm do not in-

    stantly react to the disturbance. The reason is that Te is

    proportional to the square of the turbine speed, and due to

    the turbine inertia, the turbine speed cannot have a sudden

    change.

    Fig. 9(b) indicates that due to the change in the wind speed,

    the turbine torque becomes higher than that of the machine.

    Consequently, the turbine accelerates (Fig. 9(c)). Fig. 9(d) and

    (e) shows thatPm andPg smoothly followPtur.

    Att = 18.5s, phase (c) of the PCC is subjected to a line-to-ground fault. Therefore, the grid power is disturbed (Fig. 9(e)).

    The fault is self-cleared after 1.0 second. Fig. 9(b) and (c) shows

    that during the fault, the machine torque and the turbine speed

    are not affected. This is because of the decoupling property of

    the back-to-back converter configuration via the dc link.

    When the ground fault occurs, the amplitude of the positive-

    sequence component of Vsabc becomes 0.67 times its rated

    value. Therefore, the dc bus voltage controller increases Id by

    1.5 times, to maintain the balance of power and the dc bus volt-

    age (Fig. 10(a)). Fig. 10(b) shows that Iq is fairly decoupled

    fromId , despite the fault.

    Fig. 10(c) illustrates that during the fault, the system is stable

    and the average of the dc bus voltage remains tightly regulated.

    However, a 120 Hz ripple component is experienced by the dc

    Fig. 11. System response to line-to-ground fault.

    bus voltage. This is a result of the ac side voltage and current

    imbalance due to the fault.

    Fig. 11(a) and (c) provides a closeup of the NPC2 currents,

    the DC-bus voltage, and the capacitors voltages, during thefault. Fig. 11(a) shows the unbalanced NPC2 line currents.

    Fig. 11(b) shows that the dc bus voltage is polluted with the

    120 Hz ripple component. However, the dc bus voltage is well

    regulated within 2.5% of its rated value. Fig. 11(c) indicatesthat the dc side voltage balancer maintainsV1and V2despite the

    fault.

    C. Sudden Wind Speed Drop

    Fig. 12 shows the system response to an artificial step change

    of2.5 m/s in the wind speed at the pitch angle of 5 . Priorto the step change, the wind speed, the turbine speed, and

    the grid power are at 9.5 m/s, 17 rpm, and 1250 kW, respec-

    tively. Att = 21the wind speed drops by 2.5 m/s (Fig. 12(a)).Fig. 12(b) and (d) shows that the turbine torque Tturand power

    Ptur drop rapidly due to the wind speed drop. However, the

    machine torque Te and power Pm do not instantly react to

    the disturbance, since the turbine speed cannot have a sudden

    change.

    Fig. 12(b) indicates that due to the change in the wind speed,

    the turbine torque becomes smaller than that of the machine.

    Consequently, the turbine decelerates and its speed reduces

    (Fig. 12(c)). Fig. 12(d) and (e) shows thatPm andPg smoothly

    follow Ptur. Fig. 12(f) shows that the dc bus voltage is regulated

    at the rated voltage of 2 kV.

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    11/12

    606 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 21, NO. 2, JUNE 2006

    Fig. 12. System response to a sudden wind speed drop.

    VII. CONCLUSION

    This paper presents a new application of a back-to-back con-

    nected, three-level NPC converter as the conversion system for

    a gearless, synchronous-machine based wind power unit. The

    NPC converter provides an economically attractive and techni-

    cally viable alternative to the two-level VSC, where operation

    at higher voltage levels is desired to meet the requirements for

    higher efficiency.

    This paper introduces detailed models of the ac side and dc

    side controls of the NPC-based back-to-back converter system.

    The machine-side NPC converter provides torque-speed control

    of the synchronous generator, based on a vector-control strat-egy. The generator field current is regulated by a dc-dc chopper

    which is supplied from the dc bus of the back-to-back NPC con-

    verter system. The grid-side NPC converter controls real- and

    reactive-power flow to the network, and regulates the DC-bus

    voltage and ac side power-factor, respectively. The paper also

    adopts a newly introduced control approach for dc side partial

    voltage equalization. Performance of the overall wind power

    unit, including the NPC converter system and its controllers,

    is evaluated based on time domain simulation studies in the

    PSCAD/EMTDC environment. Time domain responses of the

    system under startup, variations in the wind speed, and grid

    faults, show sound operation of the proposed converter system

    and controls.

    APPENDIX

    WINDPOWERUNITCONTROLLERS

    Fn (s) =fdq(s)

    fdq(s) =

    s2 + (754)2

    s2 + 602s + (754)2

    Ki(s) =udq(s)

    edq=

    0.09s + 1.05

    s

    H(s) = 16.4 s2 + (754)2s2 + 452s + (444)2

    s + 92.4s

    Kv (s) =

    uv (s)

    ev (s) = 5.2

    s + 314

    s + 2600

    s + 50

    s

    F(s) =

    s2 + (2 180)2

    s + 600s + (300)2

    K(s) = 4.5

    s + 300

    Fi(s) = 500

    s + 500

    Kd(s) = ustd(s)estd(s)

    = 0.406s + 0.652s

    Kq(s) =ustq(s)

    estq(s) =

    0.308s + 0.652

    s

    Kf(s) =uf(s)

    ef(s) =

    0.414s + 0.199

    s .

    REFERENCES

    [1] R.Swisher,C. R.De Azua,and J.Clendenin,Strongwinds onthe horizon:Wind Power comes of age,Proc. IEEE, vol. 89, no. 12, pp. 17541764,Dec. 2001.

    [2] E. De Vries, Moving on up, the 5M prototype is installed, Renewable

    Energy World, vol. 7, no. 6, pp. 94103, Nov./Dec. 2004.

    Authorized licensed use limited to: INDIAN INSTITUTE OF TECHNOLOGY MADRAS. Downloaded on May 28, 2009 at 07:19 from IEEE Xplore. Restrictions apply.

  • 8/11/2019 A Neutral-Point Clamped Converter System For

    12/12

    YAZDANI AND IRAVANI: A NEUTRAL-POINT CLAMPED CONVERTER SYSTEM FOR DIRECT-DRIVE VARIABLE-SPEED WIND POWER UNIT 607

    [3] G. Poddar, A. Joseph, and A. K. Unnikrishnan, Sensorless variable-speedcontroller for existingfixed-speedwind power generatorwith unity-power-factor operation, IEEE Trans. Ind. Electron., vol. 50, no. 5, pp. 10071015, Oct. 2003.

    [4] R. Pena, J. C. Clare, and G. M. Asher, A doubly fed induction generatorusing back-to-back PWM converters supplying an isolated load from avariable speed wind turbine, in IEE Proc. Power Applications, vol. 143,Sep. 1996, pp. 380387.

    [5] C. Newton, M. Sumner, and T. Alexander, Multi-level converters: A realsolution to high voltage drives?,IEE New Power Electronic Techniques,London, UK, pp. 3/13/5, May. 1997.

    [6] J. S. Lai and F. Z. Peng, Multilevel convertersA new breed of powerconverters, IEEE Trans. Ind. Appl., vol. 32, no. 3, pp. 509517, May/Jun.1996.

    [7] A. Nabae, I. Takahashi, and H. Akagi, A New Neutral-Point-ClampedPWM Inverter,IEEE Trans. Ind. Appl., vol. IA-17, no. 5, pp. 518523,Sep./Oct. 1981.

    [8] T. Larsson, A. Edris, D. Kidd, and F. Aboytes, Eagle pass back-to-backtie: a dual purpose application of voltage source converter technology, inIEEE PES Summer Meeting, Jul. 2001, pp. 16861691.

    [9] J. Rodriguez, J. Pontt, G. Alzamora, N. Becker, O. Einenkel, andA. Weinstein, Novel 20-MW downhill conveyor system using three-levelconverters, IEEE Trans. Ind. Electron., vol. 49, no. 10, pp. 10931100,Oct. 2002.

    [10] A. Yazdani and R. Iravani, A generalized state-space averaged model

    of the three-level NPC converter for systematic dc-voltage-balancer andcurrent-controller design, IEEE Trans. Power Del., vol. 20, no. 4,pp. 11051114, Apr. 2005.

    [11] D. W. Novotny andT.A. Lipo, VectorControl and Dynamicsof ACDrives.London, U.K.: Oxford Univ. Press, 1996.

    [12] W. Leonhard, Control of Electrical Drives, 3rd ed. New York:Springer-Verlag, 2001.

    [13] A. B. Plunkett and F. G. Turnbull, Load-commutated in-verter/synchronous motor drive without a shaft position sensor, IEEETrans. Ind. Appl., vol. IA-15, no. 1, pp. 6371, Jan./Feb. 1979.

    [14] A. Yazdani and R. Iravani, An accurate model for the DC-side voltagecontrol of the neutral point diode clamped converter,IEEE Trans. PowerDel., vol. 21, no. 1, pp. 185193, Jan. 2006.

    [15] S. Chung, A phase tracking system for three phase utility interface in-verters, IEEE Trans. Power Electron., vol. 15, no. 5, pp. 431438, May2000.

    [16] P. M. Anderson and A. Bose, Stability simulations of wind turbine sys-tems, IEEE Trans. Power App. Syst., vol. PAS-102, no. 12, pp. 37913795, Dec. 1983.

    [17] M. P. Kazmierkowski, R. Krishnan, and F. Blaabjerg, Control in PowerElectronics, Selected Problems. New York: Academic, 2002.

    [18] J. G. Slootweg, H. Polinder, and W. L. Kling, Representing wind tur-bine electrical generating systems in fundamental frequencysimulations,IEEE Trans. Energy Convers., vol. 18, no. 4, pp. 516524, Dec. 2003.

    [19] PSCAD/EMTDC Power Systems Simulation Software Manual., Version4.0, MB, Manitoba, Canada, 2003.

    [20] B. G. Rawn Wind Energy Conversion Systems as Power Filters: AControl Methodology, M.A.Sc. thesis, Dept. Elect. Comp. Eng., Univ.Toronto, ON, Canada, 2004.

    [21] M. Mohaddes, D. P. Brandt, and K. Sadek, Analysis and elimination ofthird harmonic oscillations in capacitor voltages of 3-level voltage sourceconverters, in IEEE PES Summer Meeting, Seattle, Washington, USA,Jul. 2000, pp. 737741.

    Amirnaser Yazdani (M05) received the B.Sc. de-gree in 1995,(with honors) from Sharif University ofTechnology, Tehran, Iran, the M.Sc. degree in 2001,from the University of Tehran, and the Ph.D. degreein 2005, fromthe University of Toronto, Toronto, ON,Canada, all in electrical engineering.

    From 1995 to 2002, he was with Maharan Engi-neering Corporation, Tehran, Iran, where he workedon the design of switching power supplies and UPS

    systems. His research interests include design, dy-namic modelling and control of switching powerconverters.

    Currently, he is with Digital Predictive Systems (DPS) Inc., Mississauga,Ontario, Canada, as an Industrial Research and Development Post-DoctoralFellow.

    Reza Iravani (M85SM00F03) received theB.Sc. degree from Tehran Polytechnic University,Tehran, Iran, in 1976, and the M.Sc. and the Ph.D.degrees from the University of Manitoba, Winnipeg,MB, Canada, in 1981 and 1985, respectively, all inelectrical engineering.

    He is currently a Professor at the University ofToronto, Toronto, ON, Canada. His research interestsinclude power electronics and power system dynam-ics and control.