A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar 1 , Former Graduate Student Dr. Sudhir Misra 1 , Professor Dr. Naveen Tiwari 2 , Associate Professor 1 Department of Civil Engineering, Indian Institute of Technology Kanpur 2 Department of Chemical Engineering, Indian Institute of Technology Kanpur July 21 st , 2017 1

A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

A Case Study of Energy Demand in

Housing Units

Contributors:

Niket Kumar1, Former Graduate Student

Dr. Sudhir Misra1, Professor

Dr. Naveen Tiwari2, Associate Professor

1 Department of Civil Engineering, Indian Institute of Technology Kanpur

2 Department of Chemical Engineering, Indian Institute of Technology Kanpur

July 21st, 20171

Page 2: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Outline

Motivation

Introduction

◦ Whole Building Approach

◦ Thermal Energy Performance Evaluation

◦ Calibrating Building Energy Simulation Model (BESM)

Objective

Simulation Tool

Methodology

Results and Discussion

Conclusions and Scope of Future Work

2

Page 3: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Motivation

45%

20%

20%10%

5%

World Energy Trend

by Sector

Building Services Industry

Transport Other

Building Construction

Source: IEA 2014

33%

67%

India Building energy

consumption trends

Building Sector Other Sectors

Source: ECBC 2007

• With Current Policies IEA predicts the global energy demand of buildings

to grow by 30% in 2035 in comparison to 2010

• Complying buildings with ECBC guidelines can lead to 40 - 60% less

energy usage than conventional buildings3

Page 4: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Whole Building Approach

Whole Building Approach = Building Envelope + Passive Design Strategies + Heating, Ventilation and Air-Conditioning (HVAC) strategies

Source : CLEAR (Comfort and Low Energy ARchitecture)

4Introduction

Page 5: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Introduction: Thermal Energy Evaluation

5

Actual house

3D Modelling

Input Parameters : Weather, House orientation, Envelope properties,

Indoor air properties as per actual conditions

Simulation Outputs

Collected Actual Output Data

Compare

Input parameters values are

established for given period and

condition

Thermal Energy Performance Evaluation

Simulation

Tune input parameters

Building Energy Efficiency and

thermal comfort outputs

Introduction

Page 6: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Calibrating Building Energy Model

6

Model

• 3D geometry information

• Other input information (building orientation, indoor and outdoor conditions)

Data Collection

• Indoor air temperature and surface temperature

• Heating / Cooling Energy Demand

Calibration

• Vary input parameters iteratively to model

• Arrive at max match with the simulation outputs (Calibrated)

Introduction

Page 7: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Objective

Thermal energy performance evaluation of a prefabricated

housing unit in New Delhi

Calibration of whole building energy model using measured

indoor temperature and hourly heating energy demand

Parametric study by varying parameters relating to weather,

material, indoor and surrounding environment of unit

Aimed at achieving optimized energy consumption and

thermal comfort for the unit

7

Page 8: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Simulation Tool : TRNSYS 17

8Simulation Tool

3D Modelling of building in

Google Sketchup Type – 56 Multizonebuilding

Input parameters

Simulation outputs

Building description

Page 9: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Methodology of this study

9

Identification and calibration of measuring instruments

Case study of LGS unit with modelling and simulation

Validation of building energy model (BEM) using collected data

Parametric Study of Calibrated Model

Methodology

Page 10: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Instrumentation

10Methodology

Laptop (Terminal)

Data Acquisition System

Digital Temperature

Measurement

Thermocouple Wires

Page 11: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Instrumentation

11Methodology

Digital electricity meter

Attached thermocouple on north

facing wall

Attached thermocouple

on inside wall surface

Attached HF sensor

on inside wall surface

Page 12: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Case Study

Location

Weather

Geometry and surrounding description

Sketch-up Model Implementation

Envelope Parameters

Simulation conditions

12Methodology

Page 13: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Location

13

Location of Light Gauge Steel Building in Housing Park (Shown in red circle)

Methodology

Page 14: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Weather

14

A suspended thermocouple sensor employed at outside of room for ambient temperature

measurement

Details of measured ambient temperature connection to type 56 multi-zone building

Methodology

Page 15: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Geometry

15

Perspective view of top floor of LGS housing unit under study

Plan of LGS housing unit top floor under study

Methodology

Page 16: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Sketchup Model Implementation

16

3D Model of LGS unit developed in Google Sketch-up to generate *.idf file

Methodology

Page 17: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Envelope and Surrounding Parameters

17

Cross section of wall made of multilayered structure

Cross section of roof made of multilayered structure

Surrounding Description around housing unit

Page 18: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Calibration by Tuning

18

Do sensitivity analysis to find parameters to be tuned

Find the value of parameters with maximum match to simulation results

Iterate to find the best possible value of input parameters

Calibrated Model (CM)

Initial Model (IM)

Methodology

Page 19: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Parametric Study

19

Surrounding

Conditions

Building Material

Indoor

Environment

Weather

U-value

Albedo

Window material

Internal Gain

Set temperature

Terminology:

1. Thermal Transmittance (U-Value): Measure of how effective a material is an

insulator. Lower U-value means better heat insulator.

2. Albedo: Proportion of the incident light or radiation reflected by a surface

3. Internal Gain: The sensible and latent heat emitted within an internal space

4. Set Temperature: The desired indoor air temperature (achieved through heating

or cooling system Methodology

Page 20: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Results and Discussion

Calibration by tuning

Validation of surface temperature

Cross validation using measured heating energy

demand

Parametric Study

20Results and Discussion

Page 21: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Ambient Temperature

21

0

5

10

15

20

25

30

35

0 1 2 3 4 5 6 7

Tem

pera

ture

C)

Time (days)

Ambient Measured Indoor Air Measured

Measured ambient and indoor air temperature through thermocouple (Starting 19th Nov 2016 12:07PM)

Results and Discussion

Page 22: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Calibration through Indoor air temperature

22

Measured vs Simulated indoor air temperature for 7 days period

Results and Discussion

Page 23: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Calibration Indices

23

Parameter Value

Measured Average 18.36°C

Simulated Average 18.92°C

Mean Biased Error, MBE (Minute Interval) -3.03 %

Mean Absolute Error, MAE (Minute Interval) 3.63 %

Root Mean Square Error, RMSE (Minute

Interval)

0.95°C

Coefficient of Variation of Root Mean Square

Error, CVRMSE (Minute Interval)

5.17 %

Results and Discussion

Page 24: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Validation of Surface Temperature

24

Wall Measured

Average

Simulated

Average

MBE (%) MAE (%) RMSE

(°C)

CVRMSE

(%)

A

(East)

18.50 19.07 -3.12 4.48 1.17 6.32

B

(South)

18.42 19.08 -3.58 4.24 0.99 5.35

C

(West)

18.17 18.83 -3.66 4.17 0.98 5.40

D (North) 18.10 18.71 -3.36 3.79 0.88 4.87

Measured vs Simulated inside surface temperature for 7 days period

Calibration indices for 24 days periodResults and Discussion

Page 25: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Heating energy demand

25

Measured set temperature of indoor air due to heating system in case 1 (winter season,

Starting 30th Jan, 12:35:29 hrs.)

Power output versus temperature, Source: (TRNSYS 17 Doc.Vol. 5 2012)

Results and Discussion

Page 26: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Cross Validation through Heating Energy

Demand

26

0

1000

2000

3000

4000

5000

6000

7000

0.00 10.00 20.00 30.00 40.00 50.00 60.00

Hea

tin

g En

ergy

Dem

and

(K

J/h

)

Time (h)

Simulated Measured

Cross validation of model 1 through measured hourly heating energy demand

(winter season, Starting 30th Jan, 12:35:29 hrs.)

-2000

-1000

0

1000

2000

3000

4000

5000

6000

7000

0 10 20 30 40 50 60 70

Heat

ing

Energ

y D

em

and (

KJ/h)

Time (h)

Simulated Measured Residual

Cross Validation of model 2 (Starting 14th

Feb 2017, 16:47:57 hrs.)

Results and Discussion

Page 27: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Cross Validation : ASHRAE Standards

27

Measure M1 (30th Jan) M2 (14th Feb) M3 (20th Feb)

Measured Heating Energy

Demand (KJ/h)

3143.4 2747.5 2089.5

Simulated Heating Energy

Demand (KJ/h)

3389.3 2620.0 2066.3

MBE Magnitude (%) 7.82 4.64 1.11

CVRMSE (%) 24.59 19.20 21.33

Standard / Guideline Monthly Criteria (%) Hourly Criteria (%)

MBE CVRMSE MBE CVRMSE

ASHRAE Guideline 14 5 15 10 30

ASHRAE Guidelines for considering a model to be calibrated; based on measured and simulated heating energy demand

Measures to cross validate model at 3 different time periods represented by M1, M2 and M3 (Set Temperature 25°C)

Results and Discussion

Page 28: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Parametric Study

28

Region New Delhi Dras Guwahati Chennai Goa Bikaner

% Reduction 0 -183.90 30.82 13.44 35.02 -13.71

Percentage reduction in total annual energy demand of heating and cooling systems for different climate zone cities

Albedo Percentage reduction (heating)

Percentage reduction (cooling)

Percentage reduction (Total)

0.4 (Base Case) 0.00 0.00 0.00

0.6 -3.88 5.36 2.40

0.8 -8.08 10.64 4.65

Percentage reduction in total annual energy demand of heating and cooling systems for different albedo values applied on the walls of same building

Results and Discussion

Page 29: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Parametric Study: Internal Gain (Occupants)

29

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

0 2 4 6

An

nu

al

en

erg

y d

em

an

d (

KW

h)

No. of occupants

Heating (KWh) Cooling (KWh)

No. of

occupants

Heating load

reductions (%)

Cooling load

reductions (%)

0 (Base case) 0.00 0.00

2 11.86 -11.10

4 22.87 -22.62

6 33.02 -34.58

Comparison of variation in heating and cooling energy demand with increasing number of

occupants

Annual heating and cooling energy demand for different number of occupants

Results and Discussion

Page 30: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Parametric Study: Set Temperature

30

Set Temperature

(°C)

25 28 30 22 20

Percentage

reduction

0 37.01 57.66 -43.11 -75.23

Set Temperature

(°C)

25 28 30 22 20

Percentage

reduction

0 -52.96 -97.19 41.05 62.23

Percentage annual energy savings with changing set temperature of

cooling system

Percentage annual energy savings with changing set temperature of

heating system

Results and Discussion

Page 31: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Conclusions

Calibrated as per ASHRAE standards with MBE and CVRMSE

values 1.11% to 7.82% and 19.20% to 24.59%

Weather variation showed the same building construction in Goa,

Chennai and Guwahati with reduced energy demands

Higher reflectance (0.4 to 0.8) can increase total number of yearly

comfort hours from 1037 to 1080 hrs as per ASHRAE standards

Internal gain analysis showed that increasing number of occupants

from 0 to 6 can lead to upto 33% savings in annual heating energy

demand

Increase in set temperature of cooling from 25°C to 30°C leads to

57.7% of energy savings while a decrease in set temperature of

heating from 25°C to 20°C leads to 62.2% of energy savings 31

Page 32: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Scope of Future Work

Doing a cooling system energy demand measurement and

validation for the same LGS unit, which is more relevant to Indian

warm and humid climate condition

Efforts can be made to measure other relevant weather

parameters, like humidity, solar irradiation, infiltration etc. to have a

closer understanding of actual phenomena

Doing a comparative study of more prefabricated units to identify

best performing unit as per given climate, structural, architectural,

ecological and resource constraints

Validate any design and retrofit strategy by either constructing new

buildings or making changes in the existing ones

Do a subjective assessment of thermal comfort which is based on

questionnaire based survey of occupants’ perception of thermal

comfort 32

Page 33: A Case Study of Energy Demand in Housing Units Case Study of Energy De… · A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar1, Former Graduate Student Dr

Acknowledgement

1. Dr. K.K. Bajpayi, Senior Scientific Officer, Structural Engineering

Laboratory, IIT Kanpur

2. Mr. Mohit Dwivedi, Jr. Technical Superintendent, Structural

Engineering Laboratory, IIT Kanpur

3. Mr. S.K. Jain, General Manager, M/s Hindustan Prefab Limited

4. Mr. N.K. Sharma, Project Manager, M/s Hindustan Prefab Limited

5. Mr. Nitin Kumar, Mr. Tarun Kumar and Mr. Priyesh Pandey, Engineer,

M/s Hindustan Prefab Limited

33