480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

Embed Size (px)

Citation preview

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    1/21

    480V Metal-Enclosed SwitchgearSelection and Application Guide

    SGSA-3061C (Nov.1998)

    Contents

    General .......................................................................................................1

    Construction Details ................................................................................ 2-4

    LV Power Circuit Breakers ...................................................................... 5-9

    VT, CPT, CT Data ...................................................................................... 10

    LV Power Circuit Breakers Ratings ..................................................... 11-13

    Weights and Dimensions ................................................................... 14-15

    Floor Plans / Side Views ..................................................................... 16-17

    Guide Form Specifications .................................................................. 18-19

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    2/21

    Siemens low-voltage metal-enclosedswitchgear is used in electric power dis-tribution systems for the control and pro-tection of circuits and equipment. Theswitchgear employs drawout type lowvoltage power circuit breakers described

    on pages 5-13.LV switchgear is typically installed in:

    Industrial Plants for power andlighting networks and feeders, powergeneration and other auxiliaries, and toprovide power for machine tools andmaterial handling equipment drivers.

    Utility and Co-generation Facilities for motor control centers to protectand distribute power to electricaldevices such as blowers, compres-sors, fans, pumps, and motors.

    Commercial and ResidentialBuildings for protection and distri-

    bution of power for lighting, elevators,air conditioning, blowers, fans,motors, and pumps.

    Available Types:

    Type R indoor (NEMA 1)

    Type SR outdoor walk-in (NEMA3R)

    Low-voltage switchgear can be appliedon distribution systems with:

    3-phase, 3- or 4-wire feeders

    50 or 60Hz

    Voltages of 208, 240,480, or 600 volts

    Currents up to 5000 amperesCircuit breakers may be either manuallyor electrically operated, fused or unfused.The following designations are used:

    RL Standard Interrupting

    RLE Extended Interrupting

    RLI High Interrupting

    RLF Fused Type

    Siemens Static Trip III trip units are pro-vided on all low voltage power circuitbreakers, except non-automatic circuitbreakers. All circuit breakers are ULListed. See Tables 4.10 and 4.11 for cir-cuit breaker ratings.

    Industry Standards

    Types R and SR switchgear with powercircuit breakers are designed, tested andconstructed in accordance with:

    ANSI C37.20.1 Metal-EnclosedLow Voltage Power Circuit BreakerSwitchgear

    ANSI C37.50 Test Procedure forLow Voltage AC Power Circuit

    Breakers Used in Enclosures

    ANSI C37.51 Conformance Testingof Metal-Enclosed Low Voltage ACPower Circuit Breaker SwitchgearAssemblies

    Applicable standards of IEEE andNEMA

    Applicable requirements of theNational Electric Code (NEC)

    UL 1558 Metal-Enclosed LowVoltage Power Circuit BreakerSwitchgear

    Type RL drawout circuit breakers are in

    accordance with: ANSI C37.13 Low Voltage AC

    Power Circuit Breakers Used inEnclosures

    ANSI C37.16 Preferred Ratings,Related Requirements, andApplication for Low Voltage PowerCircuit Breakers and ACPower CircuitProtectors.

    ANSI C37.17 Trip Devices for ACand General Purpose DC Low- VoltagePower Circuit Breakers.

    UL 1066 Low Voltage AC and DCPower Circuit Breakers Used inEnclosures.

    Features and modifications required byNEC are incorporated when the assemblyis designated as Service (Entrance)

    Equipment.

    UL Listing (Optional)

    An Underwriters Laboratories listingmark (UL label) can be optionally suppliedfor each vertical section. The specificsection must contain only devices whichare UL Listed or are UL recognized com-ponents found suitable for the intendeduse. All circuit breaker drawout elementsare UL Listed.

    General

    1

    480 Volt Metal-Enclosed Switchgear

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    3/21

    480V Metal-Enclosed SwitchgearConstruction Details

    2

    General

    General

    The Siemens 480 volt switchgear assem-bly consists of one or more metal-enclosed, vertical sections. Normally theend sections are designed to allow forinstallation of future sections.

    Each vertical section consists of up tofour individually enclosed breaker or auxil-iary compartments which are sized toprovide uniform height.

    Included in each assembly are variouscomponents such as circuit breakers,instrumentation and control equipment,transformers, relays, three-phase buswork, and all internal wiring, connectors,and other supporting equipment.

    In accordance with ANSI C37.20.1, themaximum temperature for parts that arehandled is 50C. The main bus maximumtemperature rise is 65C above 40Cambient. The temperature rise of the airsurrounding the cable connection pointsis limited to 45C above 40C ambient.

    Finish

    During construction, the structural steelparts, panels, and compartments are allprepared for painting by a five-stagewash system. Standard finish color islight gray ANSI 61. If a different finish

    color is required, it is applied over thestandard finish with conventional sprayequipment and is allowed to air cure. Thecompleted finish has a nominal 2 mils dryfilm thickness.

    Assembly Construction

    Siemens metal-enclosed powerswitchgear is constructed of preformed,full-depth, 14-gauge steel sheets boltedtogether and reinforced with cross-mem-ber braces to form a rigid, self-supportingcompact assembly. The top and rearplates, and side sheets are all 14-gaugesteel. When two vertical sections aremounted together, two sheets of 14-gauge steel separate adjacent circuitbreaker compartments.

    Bolted steel / glass polyester compart-ments housing each power circuit break-er are mounted in the vertical section toform the switchgear assembly. This iso-lates the circuit breakers from the bus /cable section and from adjacent circuitbreaker compartments.

    The bus / cable section includes mainhorizontal bus, riser bus, connectionsfrom the main bus to each set of primarydisconnects, and load side copper run-back bus.

    Grounded metal barriers can be providedto isolate the main bus from cable con-nections. Barriers are also available toisolate the incoming line to the main cir-cuit breakers from the main load bus ofthe switchgear.

    Inter-Unit Wiring TroughMeter and Auxiliary Compartment Ventilation and Lifting StructureTelescoping Breaker Drawout Rails Ventilation Openings (RL-2000, RL-3200, RL-4000

    and RL-5000)

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    4/21

    480V Metal-Enclosed SwitchgearConstruction Details

    General

    3

    Main and Ground Bus

    The standard main bus is silver-platedcopper. Welded aluminum is also avail-able. Provisions for future extension ofaluminum main bus conductors includetin plated joints with high tensile strength

    steel hardware. Tin-plated copper bus isoptionally available.

    The main three-phase horizontal bus isarranged vertically one phase above theother with edge-to-edge alignment toprovide high, short circuit strength.Insulated main and vertical bus areoptional.

    Main bus ratings available are 1600,2000, 3200, 4000, or 5000 amperes con-tinuous current. A neutral bus is fur-nished when specified, and can be rated1600, 2000, 3200, 4000 or 5000 amperescontinuous current.

    A standard copper ground bus extendsthrough all sections. A cable lug can bemounted to the ground bus in eachsection.

    Minimum bus bracing is 65,000 amperesRMS symmetrical. Higher symmetricalbracings are available based on the low-est breaker short circuit rating in thegroup.

    Load side runbacks for feeder circuits areone-piece copper construction, are insu-lated with sleeve tubing in the main busarea, and are supported by high-strength,glass polyester moldings.

    Control Wiring

    Standard secondary and control wiring is#14 AWG extra-flexible, stranded coppertype SIS. Terminations are made withcompression-type, insulated terminals.

    For devices not having screw-type termi-

    nals, tab-type disconnects are used.

    Insulation

    The insulation used is Pyro-Shield, a fiber-glass-reinforced polyester material thathas high impact strength and low mois-ture absorption. Other features includehigh flame retardance, high resistance tochemical fumes, and long life at hightemperatures.

    Circuit Breaker Compartments

    Typical circuit breaker compartmentsinclude primary disconnects, ground dis-connect, drawout rails, and associatedinterlocks, and secondary disconnects, ifappropriate. Telescoping drawout rails

    allow the breaker to be withdrawn fromthe compartment without additionalextensions or adapters. Compartmentsfor electrically-operated circuit breakersinclude secondary disconnects and con-trol circuit fuses. Up to three currenttransformers for metering or relaying canbe mounted in each compartment.

    Circuit breaker compartment front panelscan be used to hold a variety of auxiliarydevices such as breaker control switch-es, ammeters, and test blocks.

    Control Circuit Fuses Ground Disconnect

    Secondary Disconnect Front Panel Devices Primary Disconnect

    TOC Switch Operator Interference Interlock

    MOC Switch Operator Space Heater Drawout Rails

    Circuit Breaker Cell Interior

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    5/21

    Options

    Switchgear Mounted Hoist

    The hoist, optional on type R indoorswitchgear, and standard on type SRoutdoor switchgear, travels along rails ontop of the switchgear to ease breaker

    handling.

    TOC and MOC Switches

    The Truck Operated Cell (TOC) Switchprovides interlocking control or remoteindication of the breaker racking position.The cubicle mounted auxiliary switch orMechanism Operated Cell (MOC) switchprovides interlocking control or remoteindication based on the main contactposition (open or closed).

    The switches have field adjustable con-tacts for simple conversion of contactsfrom normally open (a type) to normal-ly closed (b type). Each contact may be

    adjusted individually without disassemblyor removal of wiring.

    Shutters

    These provide protection against acciden-tal contact with primary disconnects in a

    compartment when the breaker isremoved.

    Wire Trough Covers

    Secondary wiring is enclosed within eachvertical section in the primary bus andoutgoing cable areas.

    Key Interlock

    This provides a mechanical means foroperating circuit breakers and otherdevices only when predescribed condi-tions are met.

    PTS4 Test Set

    Set allows testing of the full range of pro-tective settings of Static Trip III trip units.

    Metering and Auxiliary Compartments

    Compartments are available to housedevices such as voltage transformers,metering, control power transformers,and supervisory devices.

    Instrument and Control Transformers

    Voltage transformers and control powertransformers are mounted in auxiliarycompartments. These transformers areprotected by primary pull-out type cur-rent-limiting fuses and secondary fuses.Current transformers are normally mount-ed on the compartment primary discon-nect studs where they are readily acces-sible. See Tables 4.10, 4.11, 4.12, and4.13 for available ratings.

    Outdoor Switchgear

    Type SR outdoor switchgear, available upto 5000amp, is enclosed in a weatherresistant (NEMA 3R) steel housing. All

    exterior doors extend below the floor lineand are gasket sealed.

    For protection from snow, rain, and dust,the switchgear rests on a six-inch,formed steel base which provides rigidsupport and a tight bottom seal. A heavyduty, coal tar emulsion protective under-coating is applied to the underside forprotection against moisture and corro-sion. Shielded ventilation housings permitproper air circulation while excludingdust, dirt, and foreign matter.

    A lighted, unobstructed service aisle isprovided at the front of the switchgearallowing inspection and maintenancewithout exposure to the elements, Anaccess door equipped with an emer-gency bar release is located at each endof the aisle. A GFI convenience outlet isincluded.

    Accessories

    Each switchgear assembly includes the

    following standard accessories: Crank for circuit breaker racking

    Lifting bar assembly for all circuitbreaker types

    Spring charging handle for electricallyoperated circuit breakers

    As an optional accessory, a test cabinetis available for indoor use that is wallmounted with necessary equipment fortesting electrically-operated breakers thathave been removed from the breakercompartments.

    480V Metal-Enclosed SwitchgearConstruction Details

    4

    General

    Typical Outdoor Installation with Liquid Filled Transformer

    MOC and TOC Switches. TOC Shownwith Cover Removed.

    Portable PTS4 Test Set

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    6/21

    General

    5

    The Siemens RL series circuit breakersare designed for up to 600 volt servicewith current carrying capacities of up to5000 amperes and interrupting capacitiesof up to 130,000 amperes unfused or200,000 amperes fused.

    These compact, fast operating circuitbreakers incorporate a stored energyclosing mechanism, either manually orelectrically charged, for fast, positiveclosing.

    A quick-make closing mechanism releas-es the stored energy for high speed clos-ing of the primary contacts. This positive,controlled closing prevents unnecessaryarcing between the movable and station-ary breaker contacts and thus lengthenscontact and breaker life.

    Manual tripping is performed with thepush lever on the front of the breaker. Upto three padlocks can be used to lock thebreaker contacts in the open position.

    Typical Breaker Features

    Arc Quenchers

    Main and Arcing Contact Structures

    Inductive Tripping Sensors

    Control Wiring

    Interlocks

    Position Indicators

    Interpole Barriers

    Mechanical Trip Bar

    Auxiliary Switches (option)

    Each circuit breaker is a complete 3-pole,single-throw element that is mechanicallyand electrically trip-free, with a Static TripIII overcurrent trip unit.

    Tables 4.16 and 4.17 show circuit breakeroperating and control data.

    Circuit Breaker Racking

    Racking is accomplished by turning aracking screw on the front of the breakerand may be done with the compartmentdoor open or closed. The racking screwturns U-shaped brackets on each side ofthe breaker which rack the breaker framein or out of the compartment.

    As the racking screw is turned counter-clockwise, the breaker frame moves outof the compartment and disconnects theprimary contacts, followed by the sec-ondary contacts. With only the secondarycontacts connected (test position), thebreaker may be closed and opened fortesting without energizing the load. Anindicator located on the front of thebreaker identifies the position of thebreaker in the compartment.

    Primary Disconnects

    Primary current is applied to the circuitbreaker through silver plated disconnects.The stationary contacts are mountedthrough solid Pyro-Shield insulationsheets in the back of the compartments.The movable contacts are mounted onthe back of the breaker. Stainless steelsprings provide pressure to the fingercontacts in the connected position. Lowcontact resistance is maintained by theseself-aligning contacts. The primary con-tacts are positioned so that current canflow only in the connected position. Inthe test position the contacts are separat-ed a safe distance.

    Secondary Disconnects

    Secondary circuits are connected to thecircuit breaker through silver-plated, slide-type contacts which are located below

    the arc quenching area to avoid contami-nation from arc product gases. The posi-tion of these contacts is visible with thepanel door open. The stationary contactsare silver-plated copper strips mountedon a Pyro-Shield molded base. The con-tacts are recessed to guide the movable,self-aligning contacts and to prevent acci-dental short circuiting. Secondary connec-tions are made automatically in both theconnected and test positions.

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    Type RL Circuit Breaker With Static Trip III Trip Unit And Optional Breaker Display Unit (BDU)

    Secondary Disconnects in CellLeft =CommunicationsRight =Breaker Control

    Main and Arcing Contacts SimilarDesign for all Ratings

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    7/21

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    6

    General

    Ground Connection

    A ground contact is located on the circuitbreaker to connect with the ground cir-cuit. The breaker is grounded in both theconnected and test positions.

    Drawout Interlocks

    All circuit breakers have drawout inter-locks to:

    prevent racking a closed breaker

    prevent closing breaker until racked toconnected or test position

    prevent inserting or withdrawingbreaker from compartment while clos-ing springs are charged

    Arc Interruption

    When a fault occurs, the main contactsopen first, transferring the fault current tothe arcing contacts. As the arcing con-tacts open, the thermal and electromag-netic characteristics force the arc into the

    arc chute, where the metal plates length-en, constrict, and cool the arc.

    Current Limiting Fuses

    The 800,1600 and 2000 ampere circuitbreakers are available with integrallymounted current limiting fuses toincrease interrupting rating and / or tolimit short circuit (let-through) current.The fuses are bolted in series with theupper set of primary disconnects. Thebreakers meet all required standards andare UL Listed based on current limitingfuses.

    An open fuse tripping device is wired in

    parallel with the main fuses to insure thatthe circuit breaker opens if a main fuseinterrupts, thus preventing single phasing.This device holds the circuit breaker trip-free until it is reset and also indicateswhich main fuse has interrupted.

    The higher ratedcircuit breakers, 3200,4000 and 5000 ampere, are availablewith current limiting fuses mounted on aseparate drawout carriage, which is keyinterlocked with the circuit breaker. Thisallows racking of the fuse carriage onlywiththe associated circuit breaker in the

    open position. The carriage mounts in thesame vertical section as the circuit break-er element.

    Current Sensors

    The tripping system of the RL breaker isself-powered from the current sensorsmounted on the primary contacts of thebreaker element (four-wire ground applica-tions include a fourth sensor mounted inthe cable compartment). A signal from thecurrent sensors, proportional to primarycurrent, is applied to the trip device whichthen operates the actuator to trip thebreaker based on a pre-set time delayversus current magnitude relationship.

    Ground shoe contact Mounting rails Racking position detent Stored energy mechanism position

    indicator Contact position indicator Arc chutes Handle for manually charging stored

    energy closing springs (optional onelectrically operated breakers)

    Inter-phase barriers Racking mechanism shutter (with

    packlocking provisions) Racking position indicator Contact closing release lever

    (behind charging handle)

    Clevis attached to racking drivescrew.

    Circuit breaker rating nameplate Racking interlock bar Static Trip III trip unit test points Static Trip III overcurrent device Tripping lever (with padlocking

    provisions) with guard. Breaker Display Unit (optional) Power switch for spring charging

    motor (electrically operating break-er only)

    Spring charging motor (electricallyoperated breaker only)Auxiliary switch (optional on man-ually operated breakers)

    Integrally Fused RLF-800 Circuit Breaker

    RL Circuit Breaker Features (Electrically Operated Breaker Shown)

    Sensor RatingsFrame Size andMax Amp Rating

    800 150, 200, 300,400, 600, 800

    1600

    2000

    150, 200, 300, 400,600, 800, 1200, 1600

    150, 200, 300, 400,600, 800, 1200, 1600, 2000

    4000

    3200 1200, 1600, 2000, 3200

    1600, 2000,3200 , 4000

    5000 5000

    Table 4.1 Available Sensor Ratings

    Optionally available with integral 2000A ground sensorwinding to meet NEC 239-95 requirements.

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    8/21

    Static Trip III Trip UnitStatic overcurrent tripping devices havebeen standard on Siemens circuit break-ers for over thirty years. The Static Trip Illtrip unit features microprocessor-con-trolled tripping, while providing RMS

    sensing for standard overcurrent protec-tion, and optional metering and communi-cations functions. Located in the lowerright side of the breaker, the trip unit isreadily accessible for simple reading andadjustment of all settings and indicators.Static Trip III trip units are interchange-able on all ratings of low voltage circuitbreakers.

    The time / current characteristics of theStatic Trip III trip unit are shown on page13.

    All communicating StaticTrip III trip units includea local communication

    port that supports thebreaker-mounted displayunit or BDU. The BDUfeatures a high-visibility

    alpha-numeric display. Real-time meteredvalues, min/max values, event log dataand setpoint data can be read on theBDU in straightforward engineering units.Alarm and relay setpoint can be config-ured using the BDU keypad.

    This data can also be communicated toother devices or computers for controlmonitoring via Siemens ACCESS sys-tem. See Section 1 of this guide for athorough description of ACCESS.

    General

    7

    480V Metal-Enclosed SwitchgearLV Power Circuit Breaker Trip Unit

    Static Trip Ill Trip Unit (right) and Breaker Display Unit (left)

    Harmonics distort the current wave shapeand can increase its peak value. Normal

    peak-sensing units may trip, causing nui-sance shutdowns.

    Siemens RMS sensing samples the entirecurrent wave shape and calculates theeffective heating value of the current.Static Trip Ill trip units provide accurateprotection and avoid unnecessary trips.

    T: Long Time

    S: Short Time

    I: Instantaneous

    G: Ground Fault

    20, 30, 40, 50, 60 .10, .25, .40

    Delay(Seconds @ 6X Setting)

    Setting

    DelayPickup

    (X Sensor Rating)

    3.5, 6, 1017, 30

    .5, .55, .6, .65, .7, .75,

    .8, .85, .9, .95, 1.0

    (Seconds)

    (Seconds)

    (X LT Setting)

    0.8, .15, .22

    .30, .40

    2, 3, 4, 5,

    6, 7, 8, 12

    DelayPickup(X Sensor Rating)

    (Seconds)DelayPickup

    (% Ground Sensor)

    No IntentionalDelay

    2, 4, 6, 8,12, 15

    Table 4.2 Static Trip III Settings

    Pickup is fixed at 1.1 times long time setting.

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    9/21

    8

    General

    RL BreakerAccessories/Modifications

    Type RL circuit breakers feature severaloptions, including:

    Shunt Trip, (for MO breakers)

    Operation Counter

    Undervoltage Trip Device

    Electrically Operated Interlock

    Automatic Trip Alarm Contact (with orwithout Lockout Bell Alarm)

    Tripping Actuator

    The tripping actuator is a low energy,flux-shifting device that allows fast actiontripping of the breaker.

    Shunt Trip

    The shunt trip is used to electrically tripthe circuit breaker from a remote device,such as pushbutton, switch, or relay. Theshunt trip is standard on all electricallyoperated breakers, optional on manuallyoperated breakers. The shunt trip coil isdesigned for a momentary duty cycle.Thus, an a type auxiliary contact switchis used to interrupt the shunt trip circuitimmediately after the breaker is tripped.

    When the coil is energized, the armaturepicks up and rotates the trip latch, there-by tripping the breaker. A compressionspring returns the armature to the normalposition.

    480V Metal-Enclosed SwitchgearLV Power Circuit Breaker Trip Unit

    Function

    Model

    III

    Table 4.3 Static Trip III Trip Unit Functions

    Self-Powered Overcurrent Protection

    IIIC IIICP IIICPX

    Requires additional compartment mounted devicesand wiring to meet specific application.

    Supports optional Breaker Display Unit accessory.Open command uses alarm relay output and restricts

    use for other alarm functions. Close commandrequires electrically operated breaker.

    Included when ground fault protection specified.Requires N option and neutral current sensor.Only displayed for four wire systems.

    RMS Sensing Switchable Thermal Memory

    Ground Fault Protection opt opt opt opt

    opt opt opt opt

    LCD Target Protective Microprocessor Watchdog Pickup LEDs

    Zone Interlocking (For Short Time and Ground Fault)

    opt opt opt optRetrofit Universal Mounting Package

    opt opt optAlarm Relay Output

    RS-485 Communications Port

    Breaker Display Unit Port Communications Microprocessor Watchdog Comm Watch LED Backup Shadow Protection

    opt opt opt

    opt opt opt

    Communication Open/Close/Trip

    Trip Log

    Trip Unit Status Indication Breaker Position Indication

    Breaker Operation Counter

    Event Log Phase Current Metering Ground Current Metering Neutral Current Metering

    Min/Max Current Log Power Metering Functions

    Min/Max Power Log Extended Protective Relaying Extended Trip Log

    Function

    Model

    Table 4.5Functions

    Static Trip III Metering

    Phase Currents

    IIIC IIICP

    Avg Phase Currents

    Neutral Current opt opt

    Phase Voltage Avg Phase Voltage Line Voltages

    Avg Line Voltages

    Ground Current

    kW

    Power Factor

    kW Demand

    kW Hours kW Hours Reverse kVA kVAR

    kVAR Hours

    Frequency

    Protective FunctionSettingRange

    Typical Applications

    Motors

    Table 4.4 Static Trip IIICPX Protective Relay Functions

    Current Unbalance 550%

    550%

    60660V

    60660V

    102000kW

    50.070.0 Hz

    45.060.0 Hz

    Generators Mains

    Voltage Unbalance

    Overvoltage Undervoltage

    Reverse Power Overfrequency Underfrequency

    Shunt Trip(Amperes)Seal-In/Inrush

    OperatingVoltageRange

    Nominal ControlVoltage

    60 HzAC

    104127120 1.65/7.7208254240 0.71/3.4

    DC

    2856 5.45

    70140

    48

    125 2.76

    140280250 1.85

    Table 4.6 Shunt Trip Coil Ratings

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    10/21

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    General

    9

    RL Breaker Accessories /Modifications (contd)

    Operation Counter

    A mechanically-operated, 5-digit non-resetable counter can be mountedbeneath the breaker auxiliary switch.The counter is incremented by theaction of the auxiliary switch operatingmechanism.

    Undervoltage Trip Device

    The undervoltage trip device protectsagainst a drop in normal bus voltage andfunctions to directly trip the breaker.Pickup occurs at 85 percent or less ofrated value and dropout between 30 and60 percent of rated value. Pickup anddropout are individually adjustable.Instantaneous or time-delayed operationcan be provided. The static timing unit isadjustable from 0.04 to 4 seconds for

    time delay. This allows the system todistinguish between undervoltageconditions and momentary voltage dips.

    Electrically Operated InterlockThis can be added to interlock two break-ers, preventing both from being closed atthe same time. These electromechanicaldevices add an additional solenoid thatmust be energized before the breakercan be closed. When the interlock is de-energized, the breaker is held trip-freeand cannot be closed electrically ormanually. The interlock has a mechanicallink that goes to the main shaft of thebreaker. The interlock is held in thepicked-up position when the breaker isclosed. Once closed the interlock can bede-energized without tripping the breaker.

    There are no adjustments for pickup ordropout voltages. The interlocks arecontinuously energized.

    Automatic Trip Alarm Contact (with orwithout Lockout) (Bell Alarm)

    The bell alarm contact is operated whenthe trip actuator operates in response tothe Static Trip III trip unit. It indicateswhen the circuit breaker has tripped as aresult of the static trip unit. The contactcan control a local or remote auxiliaryalarm for indication of an automatic tripor, by wiring in series with a breaker clos-ing coil, for interlocking to prevent circuitbreaker closure until the circuit is reset.The contact must be reset manually orelectrically (optional). The manually resetswitch is available with a single-poledouble-throw contact, or two single-polesingle-throw contacts. The electricallyreset switch is available with a single-pole single-throw contact.

    If desired, a mechanical lockout optionmay be provided. This substitutes amanual reset for the automatically resettripping actuator. In this case the breakeris held trip free until the lockout ismanually reset.

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    DropoutVoltage

    PickupVoltage

    Nominal ControlVoltage

    60 Hz AC

    100120

    240 or

    480

    60

    DC 40 24

    105

    48

    125 62

    Table 4.7 Undervoltage TripRatings

    Not available. Use 120 VAC undervoltage device withappropriate 240/120V or voltage transformer in cubicle.

    BreakMakeContinuous

    Bell Alarm Contact Ratings(Amperes)

    NominalControlVoltage

    60 HzAC

    10.0 10.0

    10.0

    10.0

    10.0

    10.0

    10.0

    120

    240

    DC

    0.5

    0.5

    48

    125

    0.25

    10.0

    10.0

    0.5

    0.5

    0.25250

    Table 4.9Ratings

    Bell Alarm Contact

    RL Circuit Breaker Rear View

    Current Sensors PT Module (Optional)

    Ground Shoe Contact Primary Disconnects

    Secondary Disconnects

    DropoutVoltage

    PickupVoltage

    Voltage Range

    Nominal ControlVoltage

    60 Hz AC104

    208

    120

    240

    36

    72

    DC

    38 15

    100

    48

    125 38

    200250 75

    Table 4.8 Interlock Coil Ratings

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    11/21

    10

    480V Metal-Enclosed SwitchgearVT, CPT, CT Data

    Technical

    Ratio

    600:120 0.6

    480:120 0.6

    288:120 0.6

    0.6

    0.6

    0.6

    1.2

    1.2

    1.2

    100

    100

    100

    W X Y

    Burden

    Accuracy Class at 60 Hz

    Volt-AmpRating

    150

    150

    150

    ThermalRatingVA

    50/60

    50/60

    50/60

    Hertz

    Table 4.10 Voltage Transformers

    Ratio

    100:5 1.2

    150:5 1.2

    200:5 1.2

    2.4

    2.4

    1.2

    B-0.1 B-0.2 B-0.5

    Accuracy at 60 Hz Metering Burden (ohms)

    B-1.0

    B-2.0

    C5

    C5

    C10

    250:5 0.6 1.2 C10

    300:5 0.6 0.6 C10

    400:5 0.6 0.6 C5

    500:5 0.6 0.6 C10

    600:5 0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.6 C10

    800:5 C15

    1000:5 C20

    1200:5 C20

    1500:5 C30

    1600:5 C30

    2000:5 C5

    2500:5 0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    1.2

    1.2

    0.6

    0.6

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.6

    1.2

    0.3

    0.3

    0.3

    0.3

    0.6

    0.6

    0.3

    0.6

    0.6

    0.6

    1.2

    1.2

    0.6

    C10

    RelayClass

    Table 4.12 Current Transformers for RL-800, RLE-800, RLI-800, RL-1600, RLE-1600, RL-2000, or RLE-2000 Applications

    kVA Phase

    Single

    PrimaryVoltage

    240/480

    SecondaryVoltage

    120/240

    Table 4.11 Control Power Transformers115C Rise

    35

    1015

    Requires complete compartment.

    Breaker compartment will accept 3 CTs in-line on lower disconnects.

    Ratio

    1000:5

    1200:5

    1500:5

    B-0.1 B-0.2 B-0.5

    Accuracy at 60 Hz Metering Burden (ohms)

    B-1.0 B-2.0

    C20

    C25

    C35

    2000:5 C25

    2500:5 C30

    3000:5 C15

    3200:5 C20

    4000:5

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    C10

    5000:5 C10

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3 0.6

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.6

    0.6

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3

    0.3 0.6

    1.2

    1.2

    RelayClass

    Table 4.13 Current Transformers for RL-3200, RLE-3200, RL-4000, RLE-4000, or RL-5000Applications

    Breaker compartment will accept 3 CTs in line on lower disconnects.Breaker compartment will accept 6 CTs, 3 on lower and 3 on upper disconnects.

    Breaker compartment will accept 3 CTs in staggered arrangement, 2 on lower and 1 on upper disconnects.

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    12/21

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    11

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers Ratings

    Technical

    FrameSizeAmperes

    800

    1600

    2000

    RL-800

    600 635 2200

    BreakerType

    RatedVolts

    Rated Max.Volts

    Voltage Ratings

    WithoutInstantaneousTrip Amperes

    WithInstantaneousTrip Amperes

    Short Circuit RatingSymmetrical CurrentShort Time

    RatingSymmetricalAmperes

    InsulationLevelDielectricWithstandVolts

    30,00030,00030,000

    ContinuousCurrentRatingAmperes

    75800

    RLE-800 42,00065,00042,000 75800

    RLI-800 22,00042,00022,000 75800

    RL-1600

    RLE-1600

    RL-2000

    RLE-2000

    3200RL-3200

    RLE-3200

    4000RL-4000

    RLE-4000

    RL-50005000

    50,00065,00050,000 751600

    65,00065,00065,000 751600

    65,00065,00065,000 752000

    85,00085,00085,000 752000

    65,00085,00065,000 6003200

    85,00085,00085,000 6003200

    85,000100,00085,000 8004000

    100,000100,000100,000 8004000

    85,000100,00085,000 25005000

    800

    1600

    2000

    RL-800

    480 508 2200

    30,00030,00030,000 75800

    RLE-800 42,00065,00042,000 75800

    RLI-800 22,000100,00022,000 75800

    RL-1600

    RLE-1600

    RL-2000

    RLE-2000

    3200RL-3200

    RLE-3200

    4000RL-4000

    RLE-4000

    RL-50005000

    50,00065,00050,000 751600

    65,00065,00065,000 751600

    65,00065,00065,000 752000

    85,000100,00085,000 752000

    65,00085,00065,000 6003200

    85,00085,00085,000 6003200

    85,000100,00085,000 8004000

    100,000100,000100,000 8004000

    85,000100,00085,000 25005000

    800

    1600

    2000

    RL-800

    240and208

    254 2200

    30,00042,00030,000 75800

    RLE-800 42,00065,00042,000 75800

    RLI-800 22,000100,00022,000 75800

    RL-1600

    RLE-1600

    RL-2000

    RLE-2000

    3200RL-3200

    RLE-3200

    4000RL-4000

    RLE-4000

    RL-50005000

    50,00065,00050,000 751600

    65,00065,00065,000 751600

    65,00065,00065,000 752000

    85,000100,00085,000 752000

    65,00085,00065,000 6003200

    85,00085,00085,000 6003200

    85,000130,00085,000 8004000

    100,000130,000100,000 8004000

    85,000100,00085,000 25005000

    Table 4.14 Type RL Low-Voltage Power Circuit Breaker Ratings At 50 / 60 Hertz

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    13/21

    12

    Description

    Time from EnergizingShunt Trip Coil Unit (Cycles):

    Contacts Part Open

    RL-800RLE-800

    RLI-800RLF-800

    RL-1600 & 2000

    RLE-1600 & 2000RLF-1600 & 2000

    RL-4000 & 5000

    RLE-4000RLF-4000 & 5000

    RL-3200

    RLE-3200RLF-3200

    Type

    2.03.01.03.01.253.01.53.0

    3.04.02.23.52.23.52.23.7Contacts Fully Open

    Time from EnergizingClosing Control Relay Until (Cycles):

    Contacts Touch 2.5 5.52.25.02.05.02.55.0

    Minimum Voltage 22191715

    2.5 5.72.55.72.35.32.85.3Contacts Fully Close

    Length of Break,Inches (mm)

    Between Main Contacts 1.00 (25 mm)1.00 (25 mm)1.00 (25 mm)1.00 (25 mm)

    1.10 (28 mm)1.10 (28 mm)1.10 (28 mm)1.10 (28 mm)Between Arcing Contacts

    Average SpringCharging Time (Seconds): Nominal Voltage 15131210

    10888Maximum Voltage

    Table 4.16 Type RL Circuit Breaker Operating Data (60 Hertz Basis)

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers Ratings

    Technical

    FrameSizeAmperes

    800

    1600

    2000

    3200

    RLF-800

    208to600

    600

    TypeRatedVolts

    Rated Max.Volts

    Voltage Ratings

    Rangeof FuseRating Amperes

    Short CircuitRatingsSymmetrical Amps

    InsulationLevel DielectricWithstand Volts

    2501600

    ContinuousCurrentRating Amperes

    75800

    RLF-1600

    RLF-2000

    8003000

    20005000

    200,0002200

    2200

    751600

    4000 752000

    6003200RLF-3200 &RFC-3200Fuse Carriage

    200,000

    400060002200 8004000200,000RLF-4000 &RFC-4000Fuse Carriage

    4000

    500060002200 25005000200,000RLF-5000 &RFC-5000Fuse Carriage

    5000

    Table 4.15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz

    Description

    Nominal Control Voltage

    Spring Charge Motor Voltage Range

    Voltage Rating

    120 VAC 240 VAC 48 VDC 125 VDC 250 VDC

    Table 4.17 Type RL Circuit Breaker Control Data

    104127 100140 200280208254 3856

    Shunt Trip and Closing Coil Voltage Range (at Coil) 104127 70140 140280208254 2856

    Tripping Coil Current (Seal-in / Inrush) Amperes 1.65/7.7 2.76 1.850.71/3.4 5.45

    Closing Coil Current (Seal-in / Inrush) Amperes

    Y-Relay Current (Max. Value Amperes)

    1.65/7.7 2.76 1.850.71/3.4 5.45

    Current of Spring Charge Motor: Cutoff Value Amperes

    Inrush Value Amperes

    0.48 0.45 0.210.36 1.16

    0.026 0.02 0.010.015 0.15

    3.3 3.97 1.921.75 7.5

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    14/21

    480V Metal-Enclosed SwitchgearLV Power Circuit Breakers

    13

    Technical

    Time/Current Characteristics of Static Trip III Trip Unit

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    15/21

    14

    Siemens 480 volt switchgear can beconfigured in many ways by combiningdifferent section types. Up to five verticalsections plus a transition section can beshipped together as a unit. If all verticalsections are not to be shipped as a unit,specifications need to be provided thatdescribe the limiting factors (e.g., lowdoor or narrow hallway).

    Normal indoor vertical sections are 101in. (2565 mm) high and 60 in. (1524 mm)deep. A top-mounted hoist, which isshipped as an accessory in a separatecontainer, adds 2 in. (51 mm) for a totalinstalled height of 103 in. (2616 mm).

    The outdoor switchgear assemblycontains the indoor assembly in an out-door housing. The overall height is 113in. (2870 mm) and the depth is 119.40 in.(3033 mm).

    The major assembly sections include:

    Transition Sections used as transi-tion to liquid filled transformer or tooutdoor dry type transformers.

    Auxiliary Sections used as incom-ing bus duct or cable entrance when a

    main breaker is not used. Main Sections used to contain

    main breaker and may house meteringand feeder breakers.

    Feeder Sections used to containfeeder breakers and other equipmentsuch as instrumentation.

    Tie Sections used to contain tiebreaker and other equipment such asfeeder breakers.

    480V Metal-Enclosed SwitchgearWeights and Dimensions

    Dimensions

    Transition Section For Liquid Filled andOutdoor Dry Type Transformers

    RL-800

    150 (68)

    45 (20)

    140 (64)

    RLE-800

    180 (82)

    45 (20)

    170 (64)

    RLI-800

    185 (84)

    45 (20)

    175 (80)

    RL-1600

    190 (86)

    45 (20)

    180 (82)

    RLE-1600

    195 (89)

    45 (20)

    185 (84)

    RL-2000

    220 (100)

    45 (20)

    210 (95)

    RL-3200

    300 (136)

    50 (23)

    290 (132)

    RL-4000

    360 (164)

    50 (23)

    350 (159)

    RL-5000

    445 (202)

    55 (25)

    425 (193)

    RLE-2000

    225 (102)

    45 (20)

    215 (98)

    RLE-3200

    305 (139)

    50 (23)

    295 (134)

    RLE-4000

    365 (166)

    50 (23)

    355 (161)

    Operation

    Manual

    Electrical

    AdditionalWeight forShipping

    Element Type

    Table 4.19 Breaker Element Weight in lbs. (kg)

    RLF-800

    205 (93)

    45 (20)

    195 (89)

    RLF-1600

    320 (145)

    45 (20)

    310 (141)

    RLF-2000

    335 (152)

    45 (20)

    325 (148)

    RLF-3200

    330(150)

    50 (23)

    290(132)

    RFC-3200

    50 (23)

    390

    (177)

    450

    (205)

    475 (217)

    55 (25)

    RLF-4000

    360(100)

    45 (20)

    350(95)

    RLF-5000

    445(202)

    55 (25)

    425(193)

    RFC-4000

    50 (23)

    RFC-5000Operation

    Manual

    Electrical

    AdditionalWeight forShipping

    Element Type

    Table 4.20 Fused Element Weight in lbs. (kg)

    For use with RLF-3200 breaker.For use with RLF-4000 breaker.

    For use with RLF-5000 breaker.

    Fuses mounted on separate drawout carriage and locatedin separate compartment. For total weight, add weight ofbreaker element and separate fuse carriage.

    550 (250)

    500 (227)

    61 (1549)

    55 (1397)Outdoor

    Indoor

    Dimension Ain Inches (mm)

    Weightin lbs. (kg)

    Table 4.18

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    16/21

    15

    Tie Breaker Sections and Combinations Front Views

    480V Metal-Enclosed SwitchgearAuxiliary / Breaker Section Dimensions

    Dimensions

    R30R22

    Indoor

    Outdoor

    1000 (455) 1200 (545)

    2000 (909) 2400 (1091)

    Table 4.21Weight in lbs. (kg)

    Auxiliary Section

    Auxiliary Sections Front Views

    R30R22

    Indoor

    Outdoor

    1400 (636 ) 1900 (864)

    2400 (1091) 3100 (1409)

    R36

    2210 (1005)

    Table 4.22Connection Weights in lbs. (kg)

    Breaker Section and

    Weights shown do not include weight of circuit breakerremoveable elements. All weights are approximatebased on aluminum bus. For outdoor lineup, add

    1200 lb (545 kg) to total weight of individual sections forend walls and hoist.

    Main Breaker Sections Front Views

    Feeder Breaker Sections and Combinations Front Views

    Breaker Designations

    A =RL- 800 / 1600 / 2000,RLF- 800 / 1600 / 2000,RLE- 800 / 2000, RLI-800

    B =RL- 3200C = RLF- 3200 in one cell, with

    fuse drawout (RFC-3200)in other cell

    D =RLF- 4000 in one cell, withfuse drawout (RFC-4000)in other cell

    E = RL- 4000, RLE-4000F = RLF- 5000 in one cell with

    fuse drawout (RFC-5000)in other cell

    G =RL- 5000

    22 in. (559 mm) compartment only.

    Feeder breakers located above tie breaker must beelectrically on opposite side of tie breaker fromfeeder breaker which is located below the breaker.

    Dimensions in Inches (mm)

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    17/21

    16

    480V Metal-Enclosed SwitchgearIndoor Floor Plan, Side View

    Dimensions

    This transition required for liquid filled and outdoor dry type transformers only. Cable space is 13.2 in. (335 mm) in depth for bottom entry with circuit breaker in bottom compartment. (Refer to side view.)

    Switchgear (5000A) Dimensions in Inches (mm)

    Bolting Arrangement

    Dimensions in Inches (mm)

    Switchgear (Up to 4000A)

    Indoor Side View

    Indoor Floor Plan

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    18/21

    17

    Outdoor Floor Plan

    480V Metal-Enclosed SwitchgearOutdoor Floor Plan, Side View

    Dimensions

    Dimensions in inches (mm)

    Dimensions in inches (mm)

    Cable space is 22.4 in. (569 mm) depth forbottom entry with circuit breaker in bottomcompartment.

    Bolting Arrangement

    Outdoor Bolting ArrangementType SR

    (Side View)

    30.0 (762 mm) Door

    Hinges on Extension

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    19/21

    18

    This equipment specification guideprovides information for describing atypical metal enclosed low voltage powercircuit breaker switchgear assembly.Items or features that are non-standardbut required for a specific application arepreceded by (option). Items preceded orfollowed by a blank (__) require thatadditional data be provided in order tocomplete the specification.

    General

    The equipment to be supplied shall bemetal enclosed low-voltage power circuitbreaker switchgear with drawout circuitbreaker elements. All power circuitbreakers and assemblies shall beproduced by a single manufacturer andshall be designed, tested and manufac-tured in accordance with the standardsreferenced in this specification.

    Codes and StandardsThe switchgear assemblies and power cir-cuit breakers shall comply with the codesand standards as indicated. Copies of cer-tified design tests shall be furnished ifrequested to confirm compliance.

    ANSI / IEEE C37.13 Low-Voltage AC Power Circuit BreakersUsed in Enclosures

    ANSI C37.16 Low-Voltage PowerCircuit Breakers and AC PowerCircuit Protectors PreferredRatings, Related Requirements, andApplication Recommendations

    ANSI C37.17 Trip Devices for ACand General Purpose DC Low-Voltage Power Circuit Breakers

    ANSI / IEEE C37.20.1 Metal-Enclosed Low-Voltage PowerCircuit-Breaker Switchgear

    ANSI / IEEE C37.27 ApplicationGuide for Low-Voltage ACNonintegrally Fused Power CircuitBreakers (Using Separately MountedCurrent Limiting Fuses)

    ANSI C37.50 Standard TestProcedures for Low-Voltage ACPower Circuit Breakers Used in

    Enclosures. ANSI C37.51 Standard

    Conformance Test Procedures forMetal Enclosed Low-Voltage ACPower Circuit-Breaker SwitchgearAssemblies

    ANSI / NEMA 250 Enclosures forElectrical Equipment (1000 VoltsMaximum)

    NEMA SG 3 Low-Voltage PowerCircuit Breakers

    NEMA SG 5 Power SwitchgearAssemblies

    (option) NEMA 210 SecondaryUnit Substations

    UL 1066 Low-Voltage AC and DCPower Circuit Breakers Used in

    Enclosures (Option) UL 1558 Metal-Enclosed

    Low-Voltage Power Circuit BreakerSwitchgear

    Assembly

    The switchgear assembly shall be SiemensType R and is to be located indoors, with aNEMA 1 enclosure, (option) outdoor,NEMA 3R per specifications below andconstructed of multiple, metal-enclosed,ventilated sections. The front of each verti-cal section is to contain three or four com-partments with 14 gauge steel side sheetsand compartment barriers of 11 gauge

    steel. A double thickness of 14 gauge steelis to be provided between vertical sec-tions. The side sheets shall be full heightand depth to provide a full metal barrierseparating the rear cable compartmentsbetween sections. End sections shallinclude provisions for main bus extensionand installation of future vertical sections.The design shall incorporate preformedsteel channels, angles, and side sheetsbolted together and reinforced to form arigid, self-supporting, compact assembly.

    Horizontal barriers are to be provided to formindividual circuit breaker or metering com-partments. Circuit breaker compartmentsare to be barriered from the bus compart-ment through a primary disconnect assem-bly. Each circuit breaker or metering com-partment shall be provided with a hingedfront door secured with rotary latches requir-ing no tools to operate.

    Circuit breaker compartments shall includestationary primary contact disconnects.The primary disconnects shall be copper,silver-plated at connection points and shallbe of one piece construction. The upperset of disconnects shall bolt directly to themain bus and, for feeder circuit breakers,the lower set shall extend to the rear cable

    area and shall be insulated where theypass through the main bus compartment.Primary disconnects shall be sized for themaximum continuous current of the circuitbreaker which will be located in the com-partment. Interlocks shall be providedwhich will prevent a circuit breaker ele-ment of the incorrect frame size or inter-rupting rating from being inserted into thecompartment. A stationary circuit breakerframe grounding contact shall be providedwhich shall be visible with the circuitbreaker installed in any position.

    Secondary control contacts, whenrequired, shall be located in the circuitbreaker compartment and shall be of thesliding contact, silver-plated copperdesign. Barriers shall be providedbetween terminal points. The secondarycontrol contacts shall engage thedrawout circuit breaker element in theconnected and test positions.

    Control circuit fuses for electrically oper-ated circuit breakers shall be located onthe side of the circuit breaker compart-ment and shall be contained in a dead-front, pull-out fuse block with a clearcover. Withdrawing the cover from thefuse block shall automatically remove thecontrol circuit fuses and hold them cap-tive. The fuse block cover shall includeprovisions for being installed in thereverse position in order to maintain theopen control circuit for testing or mainte-

    nance purposes while continuing to holdthe fuses captive.

    All control wiring within the assemblyshall be continuous and shall terminateon each end at a suitable terminal block.Control wiring shall be 14 gauge, strand-ed, type SIS, and shall be labeled at eachend with sleeve type wire markers. Wiremarkers shall be machine imprinted withthe wire name as indicated on the wiringdiagrams. Wrap on wire markers will notbe accepted. Terminals shall be insulatedlocking fork or ring tongue type exceptwhere connecting to components that donot accept these terminations. Control

    wiring for external connections shall beterminated in the rear cable area for easeof access. (Option) Metal covers shall beprovided over control wiring troughswhere they pass through the powercable termination area. (Option) Metalcovers shall be provided over terminalblocks located in the power cable termi-nation area.

    Bus

    Main bus shall be three-phase, ___ wire___ ampere copper with silver-platedconnection joints (option) aluminum withwelded connection points (option) copper

    with tin-plated connection points.(Option) Neutral bus rating shall be ___%of the main bus current rating and shallbe located centrally in the structure forease of terminating cables whetherentering from above or below. 600 voltclearances shall be maintained in all hori-zontal and vertical buses such that insula-tion is not required. The main horizontalbus shall be run in a vertical, edge-to-edge arrangement for high short circuitstrength. Access to the rear cable termi-nation area shall be possible without

    480V Metal-Enclosed SwitchgearGuide Form Specifications

    Specifications

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    20/21

    reaching over the main and vertical bus.Bus bracing shall be equal to the shortcircuit interrupting rating of the lowestrated non-fused circuit breaker applied inthe assembly. A 0.25 in. (6 mm) by 2.00 in.(51 mm) copper ground bus will be provid-ed. Barriers shall be provided which isolate

    the rear cable termination compartmentfrom the adjacent vertical section. (Option)Barriers shall be provided to isolate therear cable area from the main bus area.(Option) Barriers shall be provided to sepa-rate the incoming line connections fromthe main horizontal and vertical bus.

    Circuit Breakers

    Circuit breakers shall be Siemens Type RLand shall be either electrically or manuallyoperated as indicated on the data sheets(or drawings). Minimum interrupting rat-ings will be as defined on the data sheets(or drawings) and shall meet or exceed the

    interrupting ratings as defined by ANSIstandards. (Option) Fused circuit breakersare to be the integrally fused type throughthe 2000 ampere frame size. 3200 through5000ampere frame sizes are to be sup-plied with separate drawout fuse carriageswhich are mounted in the same verticalsection as the circuit breaker element andare to be key interlocked with the circuitbreaker element such that the fusecarriage cannot be withdrawn unless thecircuit breaker is locked in the openposition. All fused circuit breakers are to beequipped with blown fuse lockout devicesto prevent single phasing. The application

    of fused circuit breakers shall not reducethe amount of rear cable termination spacewhich would have been provided with non-fused circuit breakers.

    Circuit breakers are to be 600 volt classwith nominal ratings as dictated by thesystem voltage. Circuit breakers shall bethree-pole, single-throw, operated by astored energy mechanism, with arcquenchers, main and arcing contact struc-ture, a three-phase solid state trip overcur-rent trip unit, trip actuator, three single ratiotripping sensors, and primary disconnect-ing devices. In addition, the circuit breakerelement shall have connected, test, and

    disconnected position indicators, springcharged/discharged indicators, and circuitbreaker open or closed indicators all ofwhich shall be visible to the operator withthe compartment door closed. It shall bepossible to rack the circuit breaker elementfrom the disconnect to the connected posi-tion with the compartment door closed.Interlocks will be provided that preventracking a circuit breaker unless the circuitbreaker is open and that prevent closing acircuit breaker unless it is in the connectedor test position.

    Solid State Trip Units

    Solid state trip units shall be Siemens

    Static Trip III (basic device)

    (Option) Static Trip IIIC (addscommunications capability)

    (Option) Static Trip IIICP (adds

    communications and power metering)

    (Option) Static Trip IIICPX (addscommunications, power metering,and relaying functions)

    Trip units shall be interchangeable so thatany trip unit can be used with any framesize circuit breaker. The basic trip unit shallbe a self powered, micro-processor baseddevice that measures true RMS currents.Long time, short circuit or ground fault tripindication shall be maintained for a mini-mum of 48 hours without the need for aseparate battery or relay. Peak sensingdevices will not be accepted. All adjust-

    ment setting switches shall be digitallyencoded type with gold contacts. (Note:Refer to catalog section SGBR-3169B forspecifications on the Siemens Static Trip IIItrip unit family and all associated options).

    Instrumentation and Metering

    A wide variety of user defined meteringand instrumentation options are available.They include Siemens 4720, 4700 & 4300power meters, Siemens Static Trip III tripunits, and traditional analog devices. Formore detailed specification information onSiemens devices refer to bulletins SGFL3181B, 3161A, and 3151B for 4720, 4700,and 4300 power meters, respectively; andSGBR-3169B Static Trip III Micro-processorBased Tripping System. If one of theoptions selected requires separate voltageand current transformers, such as theSiemens 4700 power meter, the followingmay be used to define these devices.

    Current transformers shall have standardaccuracy class ratings as defined by ANSIC37.20.1 and shall be mounted directly onthe stationary primary disconnects in thecircuit breaker compartment. Voltage trans-formers shall have a minimum 150VAthermal rating and shall be located in ametal enclosed metering compartment

    and shall be protected on the primary sidewith current limiting fuses.

    Outdoor

    (Option) Outdoor, NEMA 3R, walk-in,weatherproof construction is to be provided.The complete assembly is to rest on aformed steel base provided under eachvertical section and running perpendicularto the depth of the switchgear. The under-side of the enclosure and base structure isto be undercoated with coal tar emulsionmaterial.

    Front and rear doors are to be gasketedand hinged. Front doors, located at eachend, are to include panic release door hard-ware, three point latches, and provision forpadlocking. Rear doors shall be bolted. Allexterior hardware shall be stainless steel.

    An indoor access aisle approximately 42 in.(1067 mm) deep and accessible fromeither door is to be provided at the front ofthe switchgear line-up for inspection andtesting of the circuit breakers and associat-ed equipment. A hand-operated travelinghoist, mounted above the switchgear is tobe provided for changeout of circuit break-ers. The aisle is to have an extension oneach end to accommodate end unit doorsthat have instrumentation and metering,and to provide additional space for circuitbreaker handling.

    The switchgear is to include space heatersto prevent condensation of moisture. The

    aisle shall be provided with incandescentlights, convenience receptacle, and an ON/ OFF switch at each end to control thelights.

    Finish

    During construction, the structural steelparts, panels, and compartments shall beprepared for painting by a five-stage washsystem consisting of an alkaline cleaner,fresh water rinse, iron phosphate treat-ment, fresh water rinse, and non-chromatesealer. After cleaning and stabilization, thesteel parts shall be coated with a ther-mosetting polyester powder applied withelectrostatic equipment at a nominal 2 milsdry film thickness and then cured at 425degrees Fahrenheit for 20 minutes. Paintcolor shall be ANSI 61 light gray. The paintfinish shall have a pencil hardness of 2H, agloss as defined by ANSI D523-78 of 45-55%, a salt spray rating per ASTM B-117-73 of 600 hours, and shall be outdoor ratedper UL1332.

    Accessories

    The following accessories are to beprovided:

    crank for racking circuit breakers

    lifting yoke for circuit breakers

    container of touch-up paint (optional) portable test set, type PTS4

    overhead hoist for indoor switchgear

    (optional) test cabinet

    Testing

    Production tests in accordance with ANSIC37.20.1, ANSI C37.50, ANSI C37.51 andNEMA SG 5 shall be performed on thecompleted assembly. Certified copies ofthese tests shall be furnished uponrequest.

    19

    480V Metal-Enclosed SwitchgearGuide Form Specifications

    Specifications

  • 7/27/2019 480V_ Metal-Enclosed_Switchgear_ Selection _and_ Application_ Guide_ 3061C.pdf

    21/21

    Siemens Energy & Automation, Inc.

    P.O. Box 29503

    Raleigh, NC 27626-0503