Upload
earthsafe-systems-inc
View
138
Download
2
Embed Size (px)
DESCRIPTION
Technician Training: Wiring Basics
Citation preview
Technician Training: Wiring Basics
o Conduit – Materials & Junction Boxes
o Wire & Cable – Material & Types
o Color Conventions
o Number Conventions
o Termination – Methods
o Organization & Protection – Reasoning & Methods
o Pumps, Motors & Valves – Instructions
o Sensors & Data Communication – Standards & Instructions
Wiring Basics
Wiring Basics – Conduit
o Common Conduit Types:
PVC - Plastic for underground use
EMT - Metal tube conduit for standard commercial use
RGS - Rigid Conduit for industrial, exterior, & hazardous area use
FMC - Flexible metal conduit typically with plastic waterproof jacket (seal tight), usually maximum of 3-5 feet runs
o Conduit accessories and junction boxes may be plastic, light duty metal, or cast aluminum
May be standard/waterproof or UL listed for hazardous area
o Jobsite project standards determine conduit/box type
Wiring Basics – Wire & Cable
o Power & Signal wires are standard THHN stranded copper wire rated at 600VAC
THHN is oil and gasoline resistant and the stranded is important for terminating in panel terminal blocks
o Cable should also consist of stranded copper conductors within an oil and gas resistant jacket (Kynar)
o Ethernet cables for data communication should be CAT 5/6 with a PVC jacket suitable for industrial use
Wiring Basics – Color Conventions
o Color standards for wiring:
Green Ground White Neutral Black/Red 120 VAC Power and Signal Blue 24 VDC Power and Signal Brown/Yellow/Orange 480 VAC Power Other Colors Signal Wires
o Wires within a conduit should be numbered consecutively at each end –Temporary wire markers are commonly used for this purpose
o Wires should be permanently labeled with adhesive labels at each end –The numbering convention is the number of the terminal block in the panel
Wiring Basics – Number Conventions
Wiring Basics – Terminations
o Wires should be stripped and secured in the panel terminal blocks with no exposed copper conductors
Ground conductors may be exposed at lug connection
o Wire termination fittings are not typically needed for panel terminations
Crimp style spade and ring terminals are often needed for wire terminations at sensors and devices
o Standard wire nuts are used at motors and other devices as needed
Waterproof connectors or gel packs should be considered where wires could be exposed to water
o Wire installation should be inspected to assure protection at conduit entries with plastic bushings
o Wires within panels and junction boxes should be secured in logical bundles with tie wraps, while removing all electrical tape
o Install wiring within plastic wiring ducts where provided
o Cable troughs are used at a series of control panels
These are used for separate instrumentation and communication wiring from power wiring
Wiring Basics – Organization & Protection
o Pump motors wiring schematic
Attached to the body of the motor and indicate the termination of the power wires (ground wires attached to a bolt secured to the motor body)
o Motors for positive displacement and centrifugal pumps are usually supplied as dual voltage
1 Phase motors can be wired as: 120VAC (low voltage) or 208-230 VAC (high voltage)
3 Phase motors can be wired as: 240VAC (low voltage) or 480 VAC (high voltage)
o Motor / Pump Rotation
Our std. motors allow for rotation in either direction to suit the pump req.
For 1 Phase interchange wires 5 & 8, for 3 Phase interchange any 2 power leads
Wiring Basics – Pump Motors
Wiring Basics – Actuated Valves
o Wiring includes: 6 Wires plus ground & #14 AWG wire
o Wiring schematic inside the housing of the actuator Important to check this schematic because it may differ from generic
valve data sheets
o Limit Switch Feedback Wiring 1 Neutral 2 120 or other power to close 3 120 or other power to open 4 COM wire for limit switches unless internal line power used 5 Close limit switch signal 6 Open limit switch signal G Ground
Wiring Basics – Solenoid Valves
o Basics – Normally Open or Close, require 2 wires and sometimes a ground (for 120VAC the wires are 120VAC power and neutral)
o Mechanics – Panel operates a relay to send power to the panel to energize the valve and change state
When De-energized the valve return to its normal position
Continuous operation is advised against due to the vibration and heat generated during usage
o Relays isolate the solenoid from the PLC
Power to solenoid is typically fused, so shorts will not effect the PLC
Wiring Basics – On/Off Sensors
o Example of On/Off Sensors:
Level Switches, Leak Sensors, Flow Switches, Pressure Switches, Current Sensors, & Low-High Outputs from other panels
o Mechanics – The control panel sends out voltage to the sensor, the sensor changes states, which changes the status of the PLC input (used in logic)
o Many On/Off sensors (level-leak-flow) are reed switches
Thin metal elements which are drawn into contact with a magnet to complete a circuit
Reed switches are sensitive to over-current damage
Ground fault because of wire damage/bad connections/water
o Analog Sensors: transmitters for level, pressure, temperature & flow
0-10VDC or 4-20mA output, input is typically 24VDC
o Loop Power
2 wires (+ and -) power the device and provide a signal
Other sensors require 3 wires for power( +,-,signal)
o Wired with stranded THHN or more commonly jacketed cable
Twisted wires and shielding increase signal integrity
Wiring Basics – Analog Sensors
o RS-232 & RS-485 Circuit require twisted and shielded cables, 18-22 AWG conductors
o Ethernet CAT5 or CAT6 with industrial outer jacket Ethernet cables require special RJ-45 connectors on each end
1 Orange/White 2 Orange 3 Green/White 4 Blue 5 Blue/White 6 Green 7 Brown/White 8 Brown
o Data Cables should be in a separate conduit than power/signal
Wiring Basics – Data Communications