Smitty’s Speed Drills2008 Code Drills

Health Care Facilities

(C) Copyright 2008 Ted "Smitty" Smith 1

InstructionsClick on the slide show ICON in the lower left hand

corner of this screen to start the slide show. A question will appear and stay on the screen for 2 minutes. The

question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes.

Do not worry about writing down the answers until after the timed portion of the program.

Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC.

(C) Copyright 2008 Ted "Smitty" Smith 2

• The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment.

(C) Copyright 2008 Ted "Smitty" Smith 3

• Entirely independent 517.30(C)(1)

(C) Copyright 2008 Ted "Smitty" Smith 4

• All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly.

(C) Copyright 2008 Ted "Smitty" Smith

5

• An effective ground-fault current path 517.13(A)

(C) Copyright 2008 Ted "Smitty" Smith 6

• The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason.

(C) Copyright 2008 Ted "Smitty" Smith 7

• Limited amount 517.25

(C) Copyright 2008 Ted "Smitty" Smith 8

• Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility?

• Generator located on the premises• Battery system• A second external utility service, separate from the

main external utility provided service• An external utility service when the normal source of

power consists of a generating unit located on premises.

(C) Copyright 2008 Ted "Smitty" Smith 9

• A second external utility service 517.35(A)

• An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises.

(C) Copyright 2008 Ted "Smitty" Smith 10

• The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________.

(C) Copyright 2008 Ted "Smitty" Smith 11

• X-ray control

• 517.72(B)

(C) Copyright 2008 Ted "Smitty" Smith 12

• The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source.

(C) Copyright 2008 Ted "Smitty" Smith 13

• Delayed automatic 517.43(A)

(C) Copyright 2008 Ted "Smitty" Smith 14

• The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation.

(C) Copyright 2008 Ted "Smitty" Smith 15

• Equipment 517.30(B)(3)

(C) Copyright 2008 Ted "Smitty" Smith 16

• Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment.

(C) Copyright 2008 Ted "Smitty" Smith 17

• Critical care 517.19(F)

(C) Copyright 2008 Ted "Smitty" Smith 18

• The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor.

(C) Copyright 2008 Ted "Smitty" Smith 19

• 100 517.13(B)

(C) Copyright 2008 Ted "Smitty" Smith 20

• In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current.

(C) Copyright 2008 Ted "Smitty" Smith 21

• Line isolation monitor 517.160(B)

(C) Copyright 2008 Ted "Smitty" Smith 22

• The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater.

(C) Copyright 2008 Ted "Smitty" Smith 23

• 50 percent 517.72(A)

(C) Copyright 2008 Ted "Smitty" Smith 24

• Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 25

• Life safety 517.32(A)

(C) Copyright 2008 Ted "Smitty" Smith 26

• Nurse call systems shall be provided power from the __________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 27

• Critical branch 517.33(A)(5)

(C) Copyright 2008 Ted "Smitty" Smith 28

• Each patient bed location shall be provided with a minimum of __________ receptacles.

(C) Copyright 2008 Ted "Smitty" Smith 29

• Four 517.18(B)

(C) Copyright 2008 Ted "Smitty" Smith 30

• The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG.

(C) Copyright 2008 Ted "Smitty" Smith 31

• 10 517.14

(C) Copyright 2008 Ted "Smitty" Smith 32

End of Drill

• This is the end of the timed portion of the drill.

• You can now click on each slide and take your time reviewing the questions and answers.

(C) Copyright 2008 Ted "Smitty" Smith 33

• The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment.

(C) Copyright 2008 Ted "Smitty" Smith 34

• Entirely independent 517.30(C)(1)

(C) Copyright 2008 Ted "Smitty" Smith 35

• All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly.

(C) Copyright 2008 Ted "Smitty" Smith

36

• An effective ground-fault current path 517.13(A)

(C) Copyright 2008 Ted "Smitty" Smith 37

• The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason.

(C) Copyright 2008 Ted "Smitty" Smith 38

• Limited amount 517.25

(C) Copyright 2008 Ted "Smitty" Smith 39

• Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility?

• Generator located on the premises• Battery system• A second external utility service, separate from the

main external utility provided service• An external utility service when the normal source of

power consists of a generating unit located on premises.

(C) Copyright 2008 Ted "Smitty" Smith 40

• A second external utility service 517.35(A)

• An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises.

(C) Copyright 2008 Ted "Smitty" Smith 41

• The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________.

(C) Copyright 2008 Ted "Smitty" Smith 42

• X-ray control

• 517.72(B)

(C) Copyright 2008 Ted "Smitty" Smith 43

• The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source.

(C) Copyright 2008 Ted "Smitty" Smith 44

• Delayed automatic 517.43(A)

(C) Copyright 2008 Ted "Smitty" Smith 45

• The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation.

(C) Copyright 2008 Ted "Smitty" Smith 46

• Equipment 517.30(B)(3)

(C) Copyright 2008 Ted "Smitty" Smith 47

• Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment.

(C) Copyright 2008 Ted "Smitty" Smith 48

• Critical care 517.19(F)

(C) Copyright 2008 Ted "Smitty" Smith 49

• The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor.

(C) Copyright 2008 Ted "Smitty" Smith 50

• 100 517.13(B)

(C) Copyright 2008 Ted "Smitty" Smith 51

• In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current.

(C) Copyright 2008 Ted "Smitty" Smith 52

• Line isolation monitor 517.160(B)

(C) Copyright 2008 Ted "Smitty" Smith 53

• The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater.

(C) Copyright 2008 Ted "Smitty" Smith 54

• 50 percent 517.72(A)

(C) Copyright 2008 Ted "Smitty" Smith 55

• Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 56

• Life safety 517.32(A)

(C) Copyright 2008 Ted "Smitty" Smith 57

• Nurse call systems shall be provided power from the __________ branch of the emergency system.

(C) Copyright 2008 Ted "Smitty" Smith 58

• Critical branch 517.33(A)(5)

(C) Copyright 2008 Ted "Smitty" Smith 59

• Each patient bed location shall be provided with a minimum of __________ receptacles.

(C) Copyright 2008 Ted "Smitty" Smith 60

• Four 517.18(B)

(C) Copyright 2008 Ted "Smitty" Smith 61

• The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG.

(C) Copyright 2008 Ted "Smitty" Smith 62

• 10 517.14

(C) Copyright 2008 Ted "Smitty" Smith 63