Notifier ONYX Fire Alarm SystemNotifier ONYX Fire Alarm System

2

AgendaAgenda

Company Profile Systems Construction NCS Network Control System NFS-3030 Fire Alarm System Family of Detectors & Modules Advantages features

3

A Company with an Outstanding Heritage and a Tradition of Leadership

1987

Founded 1851 Sold Honeywell

2003

Founded 1949 Sold to Pittway 1987

1984

Founded 1952

Sold to Pittway 1984

1998

Founded 1966

Sold to Pittway 1999

1999

Founded 1976 Sold to Pittway

1998

2003 Sold to Honeywell

Founded in 2003

2003

2000

History

1962

Founded

4

Seven Business Units

Worldwide

Worldwide Leading Commercial Fire Brands

MarketingOperationsEngineering

Customer OperationsCorporate

CommunicationsSix Sigma

Quality

5

EuropeNOTIFIER Burgess Hill, UKNOTIFIER Benelux, France NOTIFIER SwedenNOTIFIER Hilden, GermanyNOTIFIER Barcelona, SpainNOTIFIER Milan, ItalyNOTIFIER RussiaKAC Reddich, UKSSD Horsham, UKSSD Moscow, RussiaSSD Trieste, Italy

North AmericaNOTIFIER Vancouver NOTIFIER TorontoNOTIFIER QuebecNOTIFIER Northford, CTSSD TorontoSSD St. Charles, ILNESCO Atlanta, GAFire-Lite Northford, CTGamewell Northford, CTFCI Northford, CTSilent Knight Minneapolis, MN

Latin AmericaNOTIFIER Mexico

NOTIFER Brazil

NOTIFIER Chile

SSD Juarez, Mexico

Middle East/AfricaNOTIFIER Amman, JordanNOTIFIER South Africa

AustraliaNOTIFIER MelbourneNOTIFIER BrisbaneNOTIFIER Sydney

Far EastNOTIFIER BombayNOTIFIER BeijingNOTIFIER ShanghaiNOTIFIER Hong KongNOTIFIER SingaporeNOTIFIER TaiwanFCI ShanghaiSSD New DelhiSSD Xian, China

Worldwide Operations

6

Product Designed to Satisfy Local Requirements

Product Designed to Satisfy Local Requirements

UL, FM

ULC

CNTC

SSL

EN54, LPC, VDS… GOST

IRAM

KIS

CNS

Worldwide OperationsWorldwide Operations

7

Fire Contractor

User

Notifier

MainContractor

NotifierEngineered

SystemDistributors

O.E.M.Johnson Controls, Viking,

Chemetron, Ansual

Fire Contractor

MainContractor

User

8

NOTI•FIRE•NET V.5NOTI•FIRE•NET V.5

Support 103 Network Nodes

Nodes could be: - NFS-3030 NFS-640 NCA NCS And legacy product

Support 201,960 Addressable Points

9

NOTI•FIRE•NET V.5NOTI•FIRE•NET V.5

ARCNET Topology Token Passing Non-

collision Protocol Peer to Peer Network

Operation Communication

Speed 312.5 Kbps CCBE – Cooperative

Control by Event

10

NOTI•FIRE•NET V.5NOTI•FIRE•NET V.5

Support NFPA Network Style 4 and Style 7

Support wire, fiber and mixed wire and fiber communication

Node to node distance By Wire 914.4 m By Fiber 8 db loss (~2.2

km) Distance can be

extended by repeater RPT-W, -F, W/F

11

NCS Network Control SystemNCS Network Control System The Onyx SeriesThe Onyx Series

NCS Intelligent Fire Workstation Run on Windows 2000 operating

systems Traditional Chinese options 30,000+ floor plans graphics Key map Auto-vectoring

12

The Onyx SeriesThe Onyx Series

Full system information access

Operate systems devices, e.g. disable/enable devices, on/off devices

Upload and download panel database 5 panels each time

13

The Onyx SeriesThe Onyx Series

100 operators login, each with unique password and access level

History file filter Built in graphics icon Support Event printer

and graphic printer Support voice files

14

NFS-3030 Fire Alarm System NFS-3030 Fire Alarm System

NFS-3030 NFS-3030

Support 1 to 10 loops 159 intelligent detector

points & 159 module points per loop

Total 3180 points per panel

15

Software ZonesSoftware Zones

1000 General zones Simplified linking of inputs to outputs.

1000 Logic zones Allows conditional I/O linking such as

AND, OR, NOT, ANYx. 10 Releasing zones 100 Trouble zones

16

Traditional Chinese LCD DisplayTraditional Chinese LCD Display

Notifier Advantages Chinese operator interface Chinese event display (120

Chinese characters) Chinese printing direct

from panel Chinese custom action

message (100 messages)

17

LCD 中文顯示幕LCD 中文顯示幕

18

Active Event CountersActive Event CountersActive Event CountersActive Event Counters

確認火災警報二樓無塵室 A 區FAB棟 Z005 探測器 ( 光電 ) 9:55:24A FRI SEP 06, 2002 L01D126 9:56:25A FRI SEP 06, 2002 火警 :001 預警 :000 故障 :005 監視 :000 保安 :000 禁能 :000

其它資訊編程 / 狀態改變 主選單 Determine priorities and number of events at

a glance.

19

Custom Action MessageCustom Action MessageCustom Action MessageCustom Action Message

火警時請速連絡勤務中心 :2298-1234 消防隊 :2256-1119

Each device can be linked to 1 of 100 messages Each message allows up to 45 characters (3 rows x

15 characters) to provide clear instruction related to the event

20

Programming OptionsProgramming Options

Veri-Fire Tools. Create and

backup programs in the comfort of the office.

Test and compare programs.

Communicate with all network panels from any network location.

21

Advanced TechnologyAdvanced Technology

Flash memory...no need to change EPROM's. Customers can receive upgrades via

modem or web. Reduces cost of labor and parts.

Database signature protection. Prevents accidental data loss.

22

Family of Detectors & ModulesFamily of Detectors & Modules Advanced Detectors Advanced Detectors

Photoelectric Smoke Detector (FSP-851) Ionization Smoke Detector (FSI-851) Heat Detector (FST-851 / FST-851R / FST-851H) Acclimate PLUS TM Multi-sensor Detector (FAPT-851) High Sensitivity Laser Detector (FSL-751) HARSH Detector (FSH-751) Intrinsically Safe Smoke and Heat Detector (1151EIS and 5451EIS) Beam Detector (FSB-200)

23

Detector BaseDetector Base

B501 Detector Base 4” B501PB Detector Base 4”X 10 pcs B710LP Detector Base 6” B710LPPB Detector Base 6”X 10 pcs B224BI Isolator Base B224BH Sounder Base B224RB Relay Base B710HD Base for HARSH B401 Base for 1151EIS, 5451EIS

24

FlashScan™ SpeedFlashScan™ Speed

FlashScan Protocol Groups and Scans 10 Devices at a Time Significantly Improves Response

Time Reports an Alarm within 1 Second Turns on All Outputs within 2

Seconds

FlashScan Request D1 D2 D3 D5D4 D6 D7 D8 D9 D10

Analog data from 10 devices at a time

25

Includes FlashScan™Includes FlashScan™

26

Acclimate Plus Acclimate Plus TMTM

Microprocessor based Analog intelligent

design Dual bi-color LEDs

Flashes green when normal

Steady red on alarm Separate head and

base Multiple base options

(ISO / Relay / Sounder )

27

HARSH™ HARSH™

Standard commercial photoelectric sensor.

Integral fan to draw air into the sensing chamber.

Two 32 micron filters to filter out dust, lint, grime and steam.

Filters are supervised for loading and replaceable.

28

HarshHarshTMTM

29

30

VIEW™ Very Early Warning VIEW™ Very Early Warning DetectionDetection

Uses an extremely bright, controlled laser

Obscuration to .02%/ Ft. Light is transmitted

through the chamber When the light is

scattered (smoke) the light reflects

off the mirror to the photo diode

Application: Critical Environments

31

What are the best locations for the What are the best locations for the Beam?Beam?

Areas with high ceilings Atria Churches

Large open areas Warehouses Manufacturing

facilities Garages

Mount detector on stable mounting surface

32

Operating AdvantagesOperating Advantages

16 to 328 ft. protection range Accommodates both short- and

long-range applications Long-range reflector kit

available

12 & 24 V operating range

-22°F to 131°F operating temperature range Ideal for garages, warehouses,

barns, etc.

33

Intrinsically Safe DetectorIntrinsically Safe Detector

5451 EIS is UL approved as a heat detector 1451 EIS is UL approved as a smoke detector FM approved for use in

Class A,B,C,D hazardous (classified) locations BASEEFA approved for use in EEX ia IIC T5

hazardous locations Two LEDs provide 360o visibility Build-in tamper-resistant feature SEMS screws for easy wiring Low standby current

34

FMM-1 Class A/B Monitor Module

FMM-101 Class B Mini Monitor Module

FDM-1 Dual Monitor Module

FZM-1 Smoke Detector Interface Module

FCM-1 Class A/B Control Module

FRM-1 Relay Module ISO-X Isolator Module

FlashscanFlashscan®® Modules Modules

35

New Multi-I/O ModulesNew Multi-I/O Modules

XP10-M Ten Class B circuits

36

New Multi-I/O ModulesNew Multi-I/O Modules

XP6-C Six Class B or three

Class A circuits

37

New Multi-I/O ModulesNew Multi-I/O Modules

XP6-R Six SPDT relays

2A @ 30Vdc

38

Advantages featuresAdvantages features

Flash Scan ModeFlash Scan Mode

Twice the Information LED Color Control Blink control and pattern generation

Walk Test indicates Device Address Address 23 = 2 Blinks, Pause, Three Blinks

Reverse Compatible Mix Previous Technology Sensors with

FlashScan Devices Entire Loop must be FlashScan to Benefit

from Protocol Advantages

39

AWACS™ ApplicationAWACS™ Application

Drift Compensation Maintenance Warning – Three Levels Detector Sensitivity Settings Cooperative Multi-Detector Sensing

40

AWACS™ Software Algorithms AWACS™ Software Algorithms Drift CompensationDrift Compensation

AnalogAnalogReadinReadingg

Time (Months)Time (Months)

with compensationwith compensation

without compensationwithout compensation

Alarm LevelAlarm Level

41

Three Maintenance AlertsThree Maintenance Alerts

0

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

0.045

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27

Adjustment Periods

Ch

am

be

r V

alu

e

Upper Chamber Threshold

Lower Chamber Threshold

Maintenance Alert

Low Chamber Value

Maintenance Urgent

42

AWACS™ Sensitivity LevelsAWACS™ Sensitivity Levels

0.0%

0.5%

1.0%

1.5%

2.0%

2.5%

3.0%

3.5%

1 - (Hospital)2 - (Schools)

4 - (Office)

6 - (Mercantile)7 - (Industrial)

5 - (Residential)

8 - (Laundry)9 - (Process Plant)

3 - (Theater)CLEAN

DIRTY

Alarm Too Quickly

Alarm Too Slowly

“Clean” vs. “Dirty” Environments

43

AWACS™ AlgorithmsAWACS™ Algorithms

Self-Optimizing Pre-alarm. Reduces false pre-alarms due to

spikes. Patented Drift Compensation

algorithm (US patent 5,764,142). Meets the individual sensor

calibration testing requirements of NFPA-72.

44

AWACS™ AlgorithmsAWACS™ Algorithms

Exclusive cooperative multi-sensor. Allows the signals from up to three

sensors to be combined to make the fire decision.

Adds “distance” to the equation.Smoke acts like a gas and will evenly

disperse. Increased response to uniformly

distributed smoke.Sampling over a wider area is more

stable.Reject isolated sources of false signals.

45

Application ChallengeApplication Challenge

An Elevator Lobby

D001 D002 D003D004D005

Group 1Group 1

Group 2

Very stable against spurious single source smoke, but reacts

almost twice as fast to uniform smoke from a real fire!

Group 1 Sensitivity = (D12+D22+D32)1/2 / 3

46

80% Alarm Level

Cooperative Sensor DetectionCooperative Sensor Detection

Photo Sees Smoke, but the IonsDo Not Due to the

Critical Element of Distance! The Spurious Alarm Is Avoided.

Ion Photo Ion

Cooperating Sensors

47

Incipient SmokeIncipient Smoke

Because Each Sensor Sees Uniform Distributionof Smoke an Alarm Is Generated, Even Though

There Is Not Enough Smoke to Set off Any Individual Sensor on its own!

Ion Photo Ion

Cooperating Sensors

58% Smoke

48

49

AWACS™ AlgorithmsAWACS™ Algorithms

Alarm Verification. Prevents false alarms by ignoring

momentary peak or spurious values. Insures the presence of a “real”

alarm by rechecking the chamber values.

50

Weekly Occupancy ScheduleWeekly Occupancy Schedule

Permits detector sensitivity change by time of day, day of week and/or preset holiday schedule. Enhances ability to avoid false

alarms based on occupancy. Provides ability to increase

sensitivity when building is not occupied.

51

Example: A Restaurant / BarExample: A Restaurant / Bar

0.0%

0.5%

1.0%

1.5%

2.0%

2.5%

12:0

0 A

M

1:00

AM

2:00

AM

3:00

AM

4:00

AM

5:00

AM

6:00

AM

7:00

AM

8:00

AM

9:00

AM

10:0

0 A

M

11:0

0 A

M

12:0

0 P

M

1:00

PM

2:00

PM

3:00

PM

4:00

PM

5:00

PM

6:00

PM

7:00

PM

8:00

PM

9:00

PM

10:0

0 P

M

11:0

0 P

M

Time of Day

Bac

k-G

rou

nd

Ob

scu

rati

on

The solution is to adjust the sensitivity based on occupancy

Recommended