Upload
chatsworth-products
View
230
Download
0
Embed Size (px)
Citation preview
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Early Containment Planning in the Data Center
Samuel Rodriguez, RCDDSenior Product Manager – Cabinet and Thermal Management Systems
Chatsworth Products Inc.
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Average power allocation for 12 benchmarked data centers (LBNL 2007a).
Average Data Center Power Allocation
Thermal Trends in the Data Center
How Can You Dramatically ReduceYour Costs Starting Today?
800-834-4969 | www.chatsworth.com An Employee-Owned Company
• Many data centers use 20 – 50% of the total electrical supply just for cooling
• Looking at technology and components, cooling is becoming more critical as densities continue to increase
• Typical data centers operate in the range of 50 – 200 watts per sq ft (0.09 m); industry trends show that these values could DOUBLE in the future!
• What can we do given current carbon footprint concerns and potential costs associated with implementing an efficient energy efficient system?
Current Status
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Cooling Methods
Traditional Hot/Cold AisleDesigned around TIA-942 and ASHRAE
standards
Close Coupled Cooling (In-Row, Overhead)
Cooling is moved to heat, producing equipment shortening delivery and return air paths
Hot Aisle Containment (HAC) Hot aisle is enclosed, usually at the rear edge of the cabinets and sides
Cold Aisle Containment (CAC)Similar to HAC, except containment is usually at the front edge of the cabinet and includes a
roof across the cabinet rows
Passive Cooling Containment Similar to HAC/CAC but dramatically different
800-834-4969 | www.chatsworth.com An Employee-Owned Company
• What design elements of my facility impacts containment?• Overhead cabling and power distribution• Overhead return air plenum• Raised floor vs. concrete floor
• Fire suppression considerations• Wet sprinkler vs. gas • Ability to expand existing system
• Performance goals• Mitigate hot spots• Increase density • Add economization • Maximize thermal efficiency• Maximize long-term return on investment
Major Considerations for Efficient Data Center Cooling
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Traditional Hot Aisle/Cold Aisle
UPS
• Oversupply required• No airflow strategy• Hot / chilled air mixing occurs • No economization options• Lowest thermal performance
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Close-Coupled Cooling
• Cooling placed in the rows• Reduces airflow delivery and return paths• Reduces cabinet count per row• Requires fire suppression changes with aisle roof• Smallest volume of ride through air capacity
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Hot Aisle Containment
UPS
• Requires clear path from cabinet to ceiling• High temperature in hot aisle during servicing• Complete isolation prevents mixing• Facilitates all economization techniques• High ride through air capacity
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Cold Aisle Containment
UPS
• Complete isolation prevents mixing• Aisle roof reduces interference with room structures• Fire suppression must be added to aisle • Facilitates all economization techniques• Smaller ride through air capacity
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Passive Cooling
UPS
• Complete isolation prevents mixing• Facilitates all economization techniques• Least cost to deploy (1 cabinet at a time)• High ROI• Comfortable work environment
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Limitations of Various Systems
Isolation Strategy Major LimitationsTraditional Hot/Cold Aisle • No air management
• Economization options limited as return air temperatures are too low
Close Coupled Cooling • Only allows water side economization• Reduces aisle space for equipment• Reduces ride-through air capacity
Hot Aisle Containment • Requires unobstructed path to plenum• Hot work environment during service• Deploy by complete POD
Cold Aisle Containment • Requires fire suppression changes• Smallest ride through air capacity• Deploy by complete POD
Passive Cooling • Requires overhead return plenum• Requires clear path for vertical duct
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Containment Comparison Summary
Traditional HA/CA
Close Coupled Cooling
Cold Aisle Containment
Hot Aisle Containment
Passive Cooling Vertical Exhaust
Ducted End of Row Doors
Initial Cost * * High Efficiency * * * * Highest ROI * * * Facilitates Economization * * * * Ride Through Air Reserve * * Fire Suppression * * * * Flexibility to Deploy * * Allows Increased Chilled Water Setpoint * * * * Reduces Overall Cooling Requirements * * * Room Comfort * * * Quantity Cabinets/Row * * * * *
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Conclusions Summary
Cold Aisle Containment
Hot Aisle Containment
Passive Cooling Vertical Exhaust
Ducted
Initial Cost * High Efficiency * * * Highest ROI * * * Facilitates Economization * * * Ride Through Air Reserve * * Fire Suppression * * Flexibility to Deploy * Allows Increased Chilled Water Setpoint * * * Reduces Overall Cooling Requirements * * * Room Comfort * Quantity Cabinets/Row * * *
Good
Better
Best
• A range of data center architectures were studied to determine thermal performance/cooling cost impact
– Hot Aisle/Cold Aisle (no containment strategy)– End of row doors– Complete Hot Aisle Containment with Vertical Exhaust Ducted Return
• Six 45U high-performance cabinets in a 3x3 configuration were used for all tests
• For all test cases, the loading conditions were constant– 72kW total IT load via TTV load banks– 12kW IT load per cabinet– 1200 CFM of airflow per cabinet
• All energy exchanges were measured to determine total system efficiency and airflow leakage
– Chilled water to CRAH– CRAH to Cabinet Supply– Cabinet Exhaust to CRAH
• Various airflow return conditions were also tested– Room return – Ceiling return– Airflow supply vs.demand was balanced (positive room pressure)
Containment Strategy Lab TestingContainment Strategy Lab Testing
800-834-4969 | www.chatsworth.com An Employee-Owned Company 15
Legacy Chiller Plant and CRAH Conditioned Air Delivery
Containment Strategy Yearly Cooling Cost per Cabinet ($/Cab)
Hot Aisle Containment with Vertical Exhaust Duct
$1,579
End of Row Doors Ceiling Return $1,786
End of Row Doors Room Return $2,246
Legacy HA/CA Ceiling Return $2,251
Legacy HA/CA Room Return $2,257
Cost Per Containment Strategy
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Data Center Solutions
800-834-4969 | www.chatsworth.com An Employee-Owned Company
Contact Information
Sam RodriguezRCDD
Senior Product Manager for Cabinets and Thermal Management Products
Content support provided by:
Steven R. BornfieldSenior Data Center ConsultantChatsworth Products Inc.
800-834-4969 | www.chatsworth.com An Employee-Owned Company